JEMStar II IEC High Accuracy Revenue Meter
For Generation, Transmission and Industrial Power
Measurement
These meters are your cash register. Fractions
of a percent accuracy can mean the difference FEATURES AND BENEFITS
of hundreds of thousands of dollars. Our
precision design provides high accuracy
with long term stability, making it easy to
guarantee a 0.05% accuracy for 10 years. Low
current accuracy is better than 0.2% RDG at
1 High accuracy – 0.05% guaranteed for 10
years
50 mA.
NERC CIPS, WELMEC Compliant - Secure
Ease of Use
The JEMStar II is easy to configure with
2 access and audit logs for all access
attempts
AMETEK’s intuitive JEMWARE II software. It
can be used off-line or on-line so you can
build configurations without having the meter
connected. We designed our software with 3 Graphic color display, totalization via
digital inputs and remote test mode
metering personnel in mind and most can
learn the basics of configuring a meter in
one hour. All meter setup is done with the
JEMWARE II Software, eliminating the need 4 Advanced communications and alarms
to open up the meter and set jumpers or
switches. Operating the meter is simplified
with the graphic color display that has a
user menu for viewing or editing the meter 5 Power Quality to IEC 61000-4-30 Class A
configuration.
Utilizing the JEMWARE II software, the meter
can be switched to a remote test mode. Test
mode is always available through the meter
display or users can be given access to this
option based on user rights that are
controllable within the software.
The JEMStar II also offers totalization via digital
inputs which allows the user to sum the
measurements of several different meters. This
process is completed through the connection
of digital I/Os of the meters. The user is then
allowed to combine the load profile, registers
and measurement log of up to 16 meters in
any combination.
The color display makes it easy to view power
measurements, phasor displays and meter diagnostics.
Meter Security and Data Integrity
The JEMStar II includes security features that satisfy
NERC CIPS and WELMEC requirements. Username
and password combinations are required to access
your secure data and configuration details. The meter
communications are password protected to prevent
unauthorized access. The audit logs store all access
attempts; including meter connection, configuration,
firmware changes and data access with username
and time/date for each occurrence.
Additionally, JEMStar II includes DLMS protocol,
which not only requires a client ID and password for
access to the meter, but also includes three different
account levels that enable the user the following Operating the JEMStar II is simplified with the
options: color display, which provides a user menu for
• Read only viewing and editing the meter configurations.
•R ead and set the date and time with approved password
• Read all DLMS objects and logos with approved password
Communications
Communication ports support various metering
protocols including DLMS, IEC-61860, DNP, Modbus
and JEM Binary. They can operate simultaneously
and independently. Tracking the status and protocol
selections is simplified with the meter's graphical
'heads-up-display'; displaying what ports are
installed and configured, which are in use and which
require attention. The JEMStar II can be supplied
with up to six communication ports including:
• Optical port • Analog modem port
• (2) Serial ports: • (2) Ethernet ports
RS-232 and RS-485
The independent Ethernet ports have separate IP
Our communications ‘heads-up display’ simplifies
addresses so the end users can allow access to third
parties without breaching their secure network. tracking the port status and protocol selections.
Each Ethernet port can be addressed for multiple
users and protocols operating simultaneously with
permissions given to specified functions.
Alarm Notification
The meter can provide alarm notifications using web
based JSON messages, contact outputs,
communication protocols and third-party software.
The alarms can be initiated from an alarm trigger to
indicate outages and other power quality conditions.
Meter wiring connections can be checked at the
meter via a color phasor diagram and alert you when
wiring is mis-connected or phase angles exceed
preset limits. The Phasor display can also be viewed
remotely through the JEMWARE II software.
Within the meter software, email notifications can be
sent for events such as triggers, battery status, time Wiring connections can be checked through the
synchronizations and more. These are fully color phasor diagram.
configurable, with options to send periodically or in
live time.
Power Quality Power Quality Recordings
The JEMStar II comes equipped with Sag/Swell/
Sag/Swell/Outage (Standard) • Record event time, date,
Outage recordings that store the time, date, duration
duration and site conditions. For advanced power • Record Phase that triggered
quality (PQ) analysis, there is an option to record • Record Min/Max/Avg V, A,
Pf, THD
high speed RMS measurements and waveform
data from pre-selected triggers. Triggers are High Speed RMS (Optional) •R ecord voltage and current per
provided for any instantaneous measurement, phase
• 1 20 Hz recording rate
sub cycle transients, outages, rapid voltage •C onfigurable trigger: pre and
changes, loss of phase and more. Waveform data post event recording, max 60
is selectable from one kHz to 32 kHz recording second recording per event
rates with durations lasting up to 16 seconds. Waveform Capture (Optional) • Record voltage and current per
Power quality data resides in the meter via PQDIF phase
file format and can be automatically exported for • 16 samples/cycle recording
rate: max 960 cycle recording
easy analysis with our analysis software or third- per event
party applications. Meters can be equipped with • 128 samples/cycle recording r
a 'PQ Ready' option that provides all necessary ate: max 240 cycles recording
per event
hardware for a future upgrade to one of our • 512 samples/cycle recording
advanced PQ options. Upgrading your meter can rate: max 30 cycles recording
be done locally or remotely through upgrade per event
• Configurable trigger: pre and
codes for a seamless transition. post event recording
Measurement Logging: Harmonic Recording (Optional) •R
ecord individual voltage and
current harmonic per phase
To assist with your power quality continuous up to 64th
monitoring, the meter can be provided with •R
ecord magnitude and phase
a 400 channel measurement log that has angle
selectable recording intervals from 150/180 cycles
Flicker Measurement (Optional) •P
st and Plt
to 120 minutes. Logs can be used for short or •P
inst (instantaneous
long-term trending of energy values, minimum/
maximum/average power measurements and Measurement Log (Optional) • 8 logs of 50 measurements
individual harmonics up to the 64th. There is each
• Recording intervals: 150/180
enough memory to store more than six months cycles to 120 minutes
of measurements from 400 channels using 10 • Min/Max/Avg measurements
minute recording intervals.
Trigger Selections (used for alarm • Sag/Swell
logging and PQ recording) •T ransient trigger
Metering Features and Functions •R apid voltage change
The meter can display 50 normal and 50 alternate • Interruptions
registers on the graphical display, listing one to •T HD, TDD, Flicker
•P hase loss, Phase rotation
four measurements per screen. It can be provided •A ny instantaneous
with two independent load profile groups, each measurement (over/under)
with 16 channels at intervals of one to 60 minutes, •D igital inputs
daily, weekly and monthly. The meter supports bi-
directional, four quadrant metering with up to eight
Tariff rates. To improve the accuracy even further, the Power Quality complies
Transformer Correction function allows you to enter to IEC 61000-4-30 Class A
up to eight correction factors for your external CT's
so the CT is matched to the meter. The meter comes
with one GB of non-volatile memory for storing Load
Profile, Measurement Logs and Power Quality data,
providing ample space for all.
Input/Output Capability
We can equip your meter with an internal eight-
channel digital I/O module. Each digital I/O channel
can be selected as either an input or output through
the JEMWARE II software and the I/O module has a
built-in isolated supply to provide power for inputs.
Time Synchronization
The meter clock can be synchronized from its own
high accuracy temperature compensated internal
crystal or externally synchronized to the AC frequency
and NTP inputs depending on your application’s
requirements.
SPECIFICATIONS
METER CIRCUIT CONNECTIONS LOAD PROFILE MECHANICAL
• 3 Phase: 4 wire Wye, 3 wire Delta • 16 channels storage CASE STYLE
• 1 – 60-minute intervals • IEC
INPUTS •V
alues stored in scalable counts
or 32-bit engineering units SIZE AND WEIGHT
VOLTAGE • IEC: 7.5 pounds (3.4 kg)
• 45 to 300 VAC (L-N), 78 to 520 VAC (L-L) • O
ptional second independent
• Frequency range: 45 - 55 Hz, 55 - 65 Hz 16 channel LP Group
• M
ax 365 days storage of 32 channels ENVIRONMENT
CURRENT @ 15-minute recording intervals OPERATING TEMPERATURE
• 1 amp nominal, 2 amp max •-22° to 185°F (-30° to 85°C)
• 5 amps nominal, 10 amps max TIME SYNC STORAGE TEMPERATURE
• 10 amps nominal, 20 amps max • Internal clock: 0.5 second/day accuracy • -40° to 185°F (-40° to 85°C)
• Burden: 0.5 VA maximum • 50/60 Hz line frequency
• Overload: 1.5x rated max current • External time sync options: NTP
ELECTRICAL STANDARDS
continuous
INTERNAL I/O • IEC61000-4-2, 61000-4-3, 61000-4-4,
• Starting current: 0.001 A (2 amp meter) 61000-4-5, 61000-4-6, 61000-4-12
• Starting current: 0.002 A (10 and 20 • Digital I/O: 8-channel selectable as input
or output. Isolated power supply for • IEEE C37.90.1
amp meter)
digital inputs
METERING STANDARDS
AUXILIARY POWER • IEC 62052-11, IEC 62052-21
• Self powered via all three phases: 45 - DIGITAL INPUT RATING
• Form A or KYZ • IEC 62053-22 Active Energy (Class 0.2S)
300 VAC (L-N)
• Maximum voltage 40 VDC • IEC 62053-24 Reactive Energy
• External Aux power option: 45 - 300 (Class 0.5S)
VAC (L-N) or 90 - 300 VDC • EN 50470-1, EN 50470-3
• Auto switching between Self and Aux
DIGITAL OUTPUT RATING
• Form A or KYZ • IEC 61000-4-30 Class A Ed 3.0
power
• Maximum open-circuit voltage: 200 V
AUXILIARY POWER BURDEN DC or peak AC AGENCY STANDARDS
• 25 VA maximum • Maximum switching current, 50 mA • MID
ACCURACY COMMUNICATIONS
WATT HOUR (6 ports available)
• 0.05% reading (0.02% typical) PORT 1: Optical (Standard) JEMStar IEC Dimensions Drawing
• IEC 1107: 19,200 baud Height: 330.9 mm (13.03 in)
VOLTS, AMPS PORTS 3 and 4: RS-232/485 Serial Width: 182.0 mm (7.17 in)
• 0.04% reading (Optional) Depth: 105.4 mm (4.15 in)
FREQUENCY • User selectable: RS-232/485
• 0.001 Hz • User configurable: 300 to 38,400 baud
PORT 5: Internal Analog Modem
MEASUREMENTS (Optional)
• Bi-directional, 4 quadrant • 56,000 baud
• Energy, instantaneous, per phase values PORTS 6 and 7: Ethernet (Optional)
• Min/Max/Avg values • 100 BaseT, unshielded twisted pair
• Demand: peak, present, past, thermal • DHCP or fixed IP address
and coincident • Up to 12 simultaneous connections
• TOU: 8 rates/day, 4 season • WEB server
• TLC, LLC: per phase, delivered and
received, transformer factors or % loss COMMUNICATION PROTOCOLS
• Modbus RTU
• Modbus TCP/IP
MEASUREMENT LOGGING • DNP 3.0
(Optional) • ANSI Tables
• 8 groups x 50 channels • IEC 61850 (Optional)
• Recording interval: 150/180 cycle • JEM Binary
to 120 minutes • DLMS
• Max 203 days of storage of 400
channels @ 10-minute recording
METER DISPLAY
interval
• 4.3” (109.2 mm) color graphic LCD
• Registers, phasor diagram, diagnostics
REGISTERS • User menu configuration
• 50 normal, 50 alternate, 50 test
1
Doesn’t include auxiliary power requirements
WORLD HEADQUARTERS EUROPEAN ASIA PACIFIC AMETEK INSTRUMENTS WEBSITE
255 North Union Street HEADQUARTERS HEADQUARTERS INDIA PVT. LTD. www.ametekpower.com
Rochester, NY 14605 UK Singapore Bengaluru
Toll Free: +1.800.950.6686 +44.770.280.9377 +65.6484.2388 EMAIL
+91.80.6782.3252
Tel: +585.263.7700
[email protected] [email protected] [email protected] [email protected]Fax: +585.454.7805
REV 11/2023