Liebert Emerson Air Conditioning
Liebert Emerson Air Conditioning
Liebert® DS™
Designed To A Higher Standard Of Performance And Reliability
Emerson Network Power Understands The Need For
Precision And Reliability...
And Why This Is So Important To You
Sensitive electronics must be maintained in a Liebert Precision Cooling Systems are used
stable environment of 64.4°F to 80.6°F (18°C to in the most demanding, critical applications
27°C) with moisture between 41.9°F (5.5°C) dew in the world. From banking to government
point and 60% relative humidity with 59°F (15°C) to corporate computer and communications
dew point. Computers and communications centers, when it has to be the best—this is
equipment generate six to ten times the the brand of choice.
heat density of normal office space, the air
conditioning system must have more than just
enough cooling capacity.
INFRASTRUCTURE
ECO AVAILABILITY FLEX CAPACITY HIGH DENSITY
MANAGEMENT
Balancing high levels of Adapting to IT changes for Delivering architectures
Improving performance
availability and efficiency continuous optimization from 10–60 kW/Rack to
of the IT infrastructure
and design flexibility minimize space and cost
and environment
2
The Liebert DS is Designed and Built
Like No Other
3
Engineered For Precision, Efficiency And Strength
The Liebert DS is designed to fit room applications Designed For Energy Efficiency
requiring high level precision control of the room Liebert DS provides maximum energy efficiency
environment, including temperature, humidity, without compromising the accuracy and reliability
filtration and airflow. demanded by sensitive electronics. All enhancements
to energy efficiency are designed to reduce operating
Precise Temperature And Humidity Control time of key components and increase the Mean
The environmental control system must be able to sense Time Between Failure. This is accomplished by
and react to temperature and humidity fluctuations far too taking advantage of alternate sources of cooling by
small for building HVAC systems to control. The Liebert minimizing compressor operation when heat loads in
DS is capable of control to within ±1°F (°C) and ±1% RH. By the conditioned space are lower. Energy savings is also
analyzing the rate of change in temperature or the moisture gained through the use of high efficiency components
content in the environment, the control system anticipates such as advanced digital scroll and 4-step semi-
what is going to happen in the room, not simply responding hermetic compressors.
to what has happened.
Quality, Rugged Construction
The durable design of the Liebert DS provides a stable,
virtually vibrationless platform for compressor and fan
operation:
4
Front Access And Serviceability Save
Valuable Floor Space
Total front access provides space and
serviceability benefits not found on
previous models or competitive units.
5
Flexible Cooling Configurations
6
The Widest Variety Of Air Supply Choices
Downflow Supply
7
Air Delivery System Designed For Optimized Air
Distribution And Long Service Life
Centrifugal blowers
Flexibility for high enable performance
filtration or external over a wide range of
static pressures up to air volume and static
2.5”(625 Pa). pressure ranges.
Computers and other sensitive electronics require greater air Pentadrive™ Blower System
volumes than comfort air conditioning can provide. The high Large capacity fans are dynamically balanced
density heat load in the relatively small space of a data center to minimize vibration and provide even air
requires more air changes to remove heat properly. A key to distribution. The low velocity fans use less fan
the outstanding performance of the Liebert DS is its optimized motor energy and operate more quietly than
air delivery design. It combines high efficiency and effective forced air blowers. Filtered air at the right
air handling to deliver reliable, constant cooling under the temperature and humidity is fed positively and
most demanding conditions. evenly into the room.
Motors
The Liebert DS features fan motors that are optimized for reliability and energy efficiency.
High-efficiency open drip-proof motor meets National Electrical Manufacturers Association (NEMA) Premium
motor standard.
Motor Options
Optional TEFC (Totally Enclosed Fan-Cooled) motors—for rugged industrial environments.
Optional larger horsepower motors available—for higher air volume or higher static pressures.
8
Energy Efficient Fan Selections
9
Dependable, Effective Cooling System
At the heart of the Liebert DS are its cooling system components, each designed to provide maximum reliability.
10
Hybrid Designs Deliver Maximum Energy Efficiency
Optional 70/30 Cu/Ni free-cooling Provides redundancy Optional econo-coil rests on an Dual Cooling coil increases availability
coil must be specified to prevent tube and energy savings for A-frame coil to minimize air pressure by using building chilled water as
corrosion when used with a cooling increased ROI. drop and increase efficiency. primary, compressor as back-up.
tower loop or other open water system.
For even greater efficiency and reduced operating costs, source of cooling for the room. This coil is sufficiently sized
Liebert DS offers energy saving alternatives such as our to offer the identical cooling capacity as is obtained during
GLYCOOL and Dual Cool options. Used where the climate the refrigeration cycle of both compressors.
permits, a conventional air or water cooled direct
expansion system adds a second cooling coil which Dual Cool
utilizes a building chiller supply to reduce compressor Utilizing this option, a conventional air cooled Liebert DS is
operation. converted to a dual source cooling system by the addition
of a second coil that utilizes a central building chiller supply.
GLYCOOL™ System Using a modulating control valve and a comparative
The Liebert GLYCOOL freecooling system incorporates a temperature sensor, the unit can function either as a
conventional glycol cooled unit along with the addition chilled water system, as a compressorized system—or a
of a second cooling coil, control valves and a comparative combination of both.
temperature monitor. This allows the system to take
advantage of cooler outdoor temperatures to reduce or During times when the chiller supply is available,
eliminate compressor runtime. compressor operation is eliminated, reducing energy costs.
Switchover between the two cooling modes is performed
During colder months, the glycol solution returning from automatically by a microprocessor control and temperature
the outdoor drycooler is routed to the second coil by a sensor. In addition to energy efficiency, this option can
pre-piped modulating three-way valve. Located upstream provide increased redundancy and flexibility to the
of the evaporator coil, the second coil becomes the primary environmental control system.
11
Air Delivery System Designed For Optimized Air
Distribution And Long Service Life
capability is provided through the use Infrared valve controls flow vapor provides quality. High-intensity
of integrated humidification systems to Humidifier of water to the most effective quartz lamps shine on water
humidifier pan. humidification. creating instantaneous
provide the necessary level of moisture
moisture using almost any
control, higher air supply capacity
water quality.
and larger coil size.
Humidity Control
Maintaining the correct humidity level in the room is just as important as
maintaining proper temperature. Inadequate humidity control can cause
static electricity if it’s too dry—or condensation that can corrode circuitry
if the air is too moist. The Liebert DS utilizes an integrated humidification
system to provide the necessary level of moisture control.
Dehumidification Control
The compressors operate at full capacity during dehumidification. The
precision control of the Liebert DS saves energy by tightly regulating
compressor operation and avoiding over dehumidification that causes the
humidifier to come on when not needed.
12
Natural air-gap. No
need for back-flow
prevention.
Autoflush system High water float Bypass air slots Cleanable stainless
Reheat Function
reduces build-up switch shuts down ensure that moisture steel humidifier
The reheat function of the Liebert DS is
of mineral deposits humidifier upon can be introduced pan. Removable
primarily used to keep the temperature
and impurities in the high water. into air stream. from front.
from going too low during the
water pan.
dehumidification cycle.
Standard Reheat
Three-stage electric reheat—low watt-
density, 304 stainless-steel fin-tubular
reheat, location maximizes airflow to
maximize element life and improve
reliability.
13
A Choice Of Compressors Offers Higher Efficiency, Adaptability
And Reliable Operation
100000
A standard fixed-capacity scroll compressor. Two Compressors
80000
Digital Compressor
Efficient 0
The standard scroll compressor offers efficient, reliable Year 1 Year 2 Year 3 Year 4
performance with a robust design that contains only Increasing compressor cycling takes a toll on compressor
a few moving parts. Quiet operation is accomplished life. Liebert Four-Step Semi-Hermetic compressors and
through a continual, smooth compression process. Digital Scroll compressors automatically adjust to yearly
Discharge gas and vibration are kept at a low level. increases in heat load, providing significantly greater
component life than other compressor technologies.
The Digital Scroll Compressor: A New Standard For
Performance and Reliability
The exclusive digital scroll compressor option on
the Liebert DS utilizes the latest control technology
to deliver precise operation and significantly higher
energy efficiency. In addition to the advantages of the
dependable scroll design, Digital Scroll technology
provides infinitely variable capacity modulation that
enables the output to precisely match the changing
cooling demands of the room. This approach is as
much as 30 percent more efficient than traditional hot-
gas bypass. Benefits include:
100%
7.5 secs capacity
50% Load
0% Future Load 100%
Digital Scroll 7.5 secs capacity
Capacity Control Digital Scroll Capacity
15 secs Initial Load
Diagram 5 secs adapts as load changes
33% Load
10 secs 10%
Capacity
Load
14
Four-Step Semi-Hermetic Compressors: New Refrigerants To Meet Government Regulations
Proven Performance Without the ability to utilize newer environmentally-
The Liebert DS Four-Step system achieves high levels of friendly refrigerants, your cooling equipment could
energy efficiency through the integration of two high- become obsolete and “out of compliance.” The Montreal
efficiency semi-hermetic compressors with capacity Protocol and EPA Clean Air Act require cooling equipment
control valves, an advanced microprocessor control manufacturers to switch to environmentally-friendly
system and a computer-optimized cooling coil. refrigerants by 2010.
The Four-Step system reduces compressor cooling R-407C environmentally-friendly refrigerant is the
capacity and energy consumption during periods of standard in the Liebert DS.
low room load conditions. As a result, four distinct
stages of cooling are activated to more closely respond
to changing room conditions. Reliability is enhanced by
fewer and less stressful compressor starts for
reduced wear.
Energy Savings
100% 100%
88%
75% 76%
50%
38%
25%
105°F 22.4
Saturated Condensing Temperature
110°F
115°F
120°F
125°F
Semi-Hermetic Compressors
130°F 11.7 12.8 14.0
15
Liebert iCOM®
Small Graphic Display
The Liebert iCOM control system The standard Small Graphic Display features a 128x64 dot matrix backlit
featured on the Liebert DS brings screen. Advanced monitoring can be achieved with the addition of the
high-level supervision to multiple Optional Wall Mounted Display.
units allowing them to work together
as a single system to optimize room
performance. The Liebert iCOM
control system offers a variety of
advantages.
16
Maintenance /
Large Graphic Display Wellness Setup
17
Easy Component and Control Option Access
Electric Panel
The electric panel of the Liebert DS is designed for easy access to critical electrical and control components.
IntelliSlot™ for
easy plug-in
of optional
communication
cards.
Low voltage
terminal strip
provides
connection
flexibility.
Control interface
board for easy
access.
Optional Location for Deadfront panel Optional solidstate Individually-fused components
disconnect switch optional secondary folds down for easy contactors used high-rated fuses for maximum
available as non- disconnect switch for viewing of electrical on SCR reheat for reliability, high interrupt rating,
locking or locking. non-critical loads. schematic. tight temperature and cooler operating fuses for
applications. maximum reliability.
Unit Monitoring And Control Options alarm. Dry contacts are available for a remote customer
Dual float condensate pump—installed in unit, with alarm. This smoke sensor is not intended to function as,
secondary float to shut down unit and trigger alarm if or replace, any room smoke detection system that may
high water detected. be required by local or national codes.
Optional low voltage terminal package—two extra n/o Analog input wiring—includes four customer-accessible
common alarm contacts, two extra remote shutdown analog inputs for sensors provided by others. The
terminals, one main fan auxiliary contact. When analog inputs accept a 4 to 20 mA signal. Gains
connected to an optional water sensor, shuts down unit Calibration for each input are programmable from the
and provides dry contact closure. front panel.
High temperature sensor—alerts users to any high Compressor overload—activates an audible and visual
temperature situations within the system. Senses alarm in the event of a compressor overload.
return air temperature and shuts down unit if Main Fan Overload—activates an audible and visual
temperature exceeds 125°F (51.7°C). alarm in the event of a motor overload.
Smoke sensor—senses the return air, shuts down the
unit upon detection, and sends visual and audible
18
Paradenser™ Cleanable Condenser Provides Liebert DS
With Longer Service Life
19
Liebert Heat Rejection Systems—Flexible
ConfigurationsTo Meet Application Requirements
20
The Liebert DS Has A Solution Water Cooled
Glycol circulating
pump
A-frame
coil Condenser
with optional
Liebert Lee-Temp
drycooler Package
Compressors
Centrifugal
Blower
Paradenser
Tubes
Compressors
Centrifugal
Blower
Glycol-cooled
condensers Coil
21
Stand-Alone Monitoring And Leak Detection Solutions
22
Maximizing Your Investment Through Adaptive Monitoring
Distributed Management With Centralized Management With Enterprise Management with Liebert
Liebert IntelliSlot® Interface Cards Liebert Nform™ Software SiteScan® Web Software
For enchanced remote communications As business grows, your critical For customers who require extensive
and control of your Liebert units, the equipment infrastructure will management of critical system equipment
Liebert IntelliSlot Web and 485 Cards expand, thus the need for centralized that may span multiple locations in an
deliver the communication capabilities management of this equipment will ever-moving global enterprise, Liebert
you require. be key to your business success. SiteScan Web will centrally manage your
Connecting to equipment in the critical equipment and give you the power
Monitoring and control through your distributed critical space is only part of to move beyond the event-responsive
existing Network with no additional the monitoring challenge. service paradigm.
software required.
Liebert Nform leverages the SiteScan Web does it all—
Each Liebert system equipped with an network connectivity capabilities of
Liebert IntelliSlot Web Card takes full your Liebert equipment to provide a Real-Time Monitoring and Control
advantage of your Ethernet network, centralized monitoring view of your Event Management and Reporting
allowing remote monitoring from your distributed equipment. Data Analysis and Trending
computer desktop, network operations
Building Management Integration
center or wherever network access is Utilizing the SNMP and Web
permitted, without the need for front- technologies built into each of the Liebert SiteScanWeb is a comprehensive
end software. Liebert IntelliSlot communication critical systems management solution
cards, Nform will centrally manage dedicated to ensuring reliability through
Monitoring integration with your alarm notifications to provide you graphics, event management and data
existing Building Management with an easy interface to access critical extrapolation. The standard Web interface
System. status information. allows users easy access from anywhere at
anytime.
A Liebert system equipped with an Liebert Nform puts critical systems
IntelliSlot 485 Card can be seamlessly information at the fingertips of Single- and multi-site applications.
integrated with your existing Building support personnel—wherever they Event management and unit control.
Management System. are—increasing responsiveness to Trend and historical data captures and
alarm-event conditions, thus allowing reporting.
IT organizations to maximize their
Full ASHRAE BACnet compatibility.
system availability.
Java based.
Windows 2000, XP and 2003
compatible.
23
Emerson Network Power, a business of Emerson (NYSE:EMR), delivers software, hardware and Emerson Network Power
Liebert Corporation World Headquarters
services that maximize availability, capacity and efficiency for data centers, healthcare and 1050 Dearborn Drive
P.O. Box 29186
industrial facilities. A trusted industry leader in smart infrastructure technologies, Emerson Columbus, Ohio 43229
United States Of America
Network Power provides innovative data center infrastructure management solutions that 800 877 9222 Phone (U.S. & Canada Only)
614 888 0246 Phone (Outside U.S.)
bridge the gap between IT and facility management and deliver efficiency and uncompromised 614 841 6022 FAX
[email protected]
availability regardless of capacity demands. Our solutions are supported globally by local
Emerson Network Power
Emerson Network Power service technicians. Learn more about Emerson Network Power Caribbean and Latin America
Office – United States of America
products and services at www.EmersonNetworkPower.com +1-954-984-3452 Phone
[email protected]
Emerson Network Power
European Headquarters
Office – Italy
+39 049 9719 111 Phone
+39 049 5841 257 FAX
[email protected]
Emerson Network Power
Asia Pacific
Office – Phillipines
+63 2 687 6615
+63 2 730 9572 FAX
[email protected]
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)