Fire Damper

The FK-EU fire dampers are tested to EN 1366-2 and designed to prevent fire and smoke spread in ductwork during a fire. They can be installed in various locations, including solid walls, ceiling slabs, and lightweight partitions, and are equipped with features for easy installation and operation. The dampers are available with different release mechanisms and comply with relevant European standards for fire resistance and performance.

Uploaded by

Adedayo Adebimpe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views56 pages

Fire Damper

The FK-EU fire dampers are tested to EN 1366-2 and designed to prevent fire and smoke spread in ductwork during a fire. They can be installed in various locations, including solid walls, ceiling slabs, and lightweight partitions, and are equipped with features for easy installation and operation. The dampers are available with different release mechanisms and comply with relevant European standards for fire resistance and performance.

Uploaded by

Adedayo Adebimpe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 56

FK-EU/DE/DE/en

Fire dampers
Type FK-EU
tested to EN 1366-2
according to Declaration of Performance

DoP / FK-EU / DE / 2013 / 001

The art of handling air


Contents · Description

Description__________________________________ 2 Quick selection_______________________________ 30


Correct use__________________________________ 4 Aerodynamic selection:
Construction · Dimensions_______________________ 6 Differential pressure__________________________ 31
Accessories 1: Sound power levels__________________________ 32
Dry mortarless installation______________________ 10 Free cross sectional area, resistance coefficient and
Accessories 2: correction values_____________________________ 33
Cover grille_________________________________ 16 Installation details:
Circular spigot plate__________________________ 17 Solid walls and ceiling slabs____________________ 34
Flexible connectors___________________________ 18 On the face of solid walls and ceiling slabs________ 40
Extension piece_____________________________ 19 Adjacent to solid walls and ceiling slabs___________ 41
Attachments: Remote from solid walls and ceiling slabs_________ 42
Limit switches_______________________________ 20 Lightweight partition walls______________________ 43
Spring return actuator_________________________ 22 Fire walls___________________________________ 48
Spring return actuator and smoke detector_________ 24 Shaft walls_________________________________ 50
Spring return actuator (Ex)_____________________ 26 Suspension systems__________________________ 52
TROXNETCOM_____________________________ 27 Order details_________________________________ 54
Smoke detectors_____________________________ 29

FK-EU with fusible link FK-EU with spring return actuator

In case of a fire, fire dampers shut automatically to prevent Special features


the propagation of fire and smoke through ductwork to adjacent – Complies with the requirements of EN 15650
designated fire compartments. Type FK-EU fire dampers are
tested to EN 1366-2 and comply with EN 15650. – Tested for fire resistance properties according to EN 1366-2
– Classified according to EN 13501-3
Correct approved installation locations are in solid walls and
ceiling slabs, on the face of solid walls, adjacent to and remote - Low differential pressure and sound power level
from solid walls, upright on solid ceiling slabs, in lightweight – Equipped with optional accessories approved for potentially
partition walls, in lightweight fire walls, and in shaft walls. explosive atmospheres
Installation in horizontal and vertical ducts. Airflow direction is – Easy dry mortarless installation with installation kit
not critical. When installed in walls or ceiling slabs combustible – Integration into the central BMS with TROXNETCOM
ventilation ducting may be connected directly to the fire damper.
In the case of fire, the damper is triggered at 72° C or 95° C Declaration of Performance
(for use in warm air ventilation systems) either by a fusible link DoP / FK-EU / DE / 2013 / 001
or thermoelectrically with a spring return actuator. The release For further and up-to-date information, including the operating
mechanism is accessible and can be tested from the outside. and installation manual, please refer to our website.
The fire dampers have two inspection accesses.
For a more detailed selection and design of our fire dampers
The class of performance of FK-EU fire dampers depends on please refer to the Easy Product Finder design programme on
the application, see table on pages 4 and 5. our website.
This technical leaflet is only valid in Germany.

2
Description

FK-EU as air transfer application FK-EU with spring return actuator (Ex)

FK-EU as air transfer application FK-EU with spring return actuator (Ex)
The fire damper with general building inspectorate licence The fire damper can be used in supply and extract air systems
Z-6.50-2031 can be used to close air transfer flow openings in areas with potentially explosive atmospheres.
in fire-resistant internal walls and ceiling slabs. According to the declaration of conformity
For the air transfer application, the FK-EU fire damper TÜV 11 ATEX 085420 X suitable for
is combined with: – II 2G c IIC T 6
– Smoke detector type RM-O-3-D with general building – II 2D c T80 °C
inspectorate licence Z-78.6-125 and technical leaflet For the operation of the fire damper, the operating and
no. 4/6.3/EN/..., installation manual and the additional operating manual must
– Spring return actuator 24 V AC/DC or 230 V AC with two be observed.
integrated limit switches and For the construction version with fusible link, see page 21.
– Cover grilles on both ends
For the air transfer application, the operating and installation
manual and the general building inspectorate licences
Z-6.50-2031 and Z-78.6-125 must be observed.

3
Correct use

To ensure complete functioning of the fire damper it is essential Design information


to read the operating and installation manual and to comply with – The class of performance of FK-EU fire dampers depends
it. In addition, the national guidelines must be complied with. on the application, see table.
The general guidelines of DIN 31051 and EN 13306 are also – Installation in solid walls and ceiling slabs, in lightweight
applicable. partition walls with metal support structure and cladding on
The functional reliability of fire dampers must be tested at least both sides, and in shaft walls whose class of performance
every six months. is lower than EI 90 is approved. In this case the class of per-
If two consecutive tests are successful, the next test can be formance of the wall or ceiling slab applies also to the FK-EU.
conducted one year later. – For use in ventilation systems, ducts must be connected
In general, it is sufficient to release and re-open the fire damper; to both ends of the FK-EU fire damper or one duct on one end
for a fire damper with spring return actuator this can be done by and a cover grille on the other.
remote control. – Installation of fire dampers must be carried out in compliance
Fire dampers must be included in the regular cleaning schedule with provisions of federal state law and the generally
of the ventilation system. recognised codes of practice.
– Ducting must be installed in such a manner that it does not
impose any loads on the fire damper in case of a fire.
– For information on how to limit such loads please refer to the
guideline regarding fire protection requirements on ventilation
systems (Lüftungsanlagen-Richtlinie, LüAR).
– It is recommended to use flexible connectors to connect rigid
ducting to the fire damper for particular applications.

Installation location Construction Minimum Class Mortar-based Dry mortarless Installa-


and building material thickness of performance installation installation tion
[mm] EI TT (ve–ho, i ↔ o) S Casing length Casing length details
[mm] [mm] on page

L = 375 L = 500 L = 375 L = 500

Solid walls and ceiling slabs Solid walls, gross density EI 90 S N N – E 34 to 37


≥ 500 kg/m³
100
EI 120 S – – – W 38 to 39

Solid ceiling slabs, gross density 125 EI 90 S N N – – 34


≥ 600 kg/m³

150 EI 120 S – – – W 38 to 39

On the face of solid walls and Solid walls, gross density


ceiling slabs ≥ 500 kg/m³
100 EI 90 S – – – E 40

Solid ceiling slabs, gross density


≥ 600 kg/m³
125 EI 90 S N N – – 40

Adjacent to solid walls and Solid walls, gross density


ceiling slabs 1 ≥ 500 kg/m³
100 EI 90 S – – – E 41

Solid ceiling slabs, gross density


≥ 600 kg/m³
125 EI 90 S N N – – 41

Remote from solid walls and Solid walls, gross density


ceiling slabs 1 ≥ 500 kg/m³
100 EI 90 S – – – E 42

Solid ceiling slabs, gross density


≥ 600 kg/m³
125 EI 90 S N N – – 42

1 Not permitted for air transfer applications N = mortar-based installation, E = installation kit, W = fire batt (Hilti system)

4
Correct use

Installation location Construction Minimum Class Mortar-based Dry mortarless Installa-


and building material thickness of performance installation installation tion
[mm] EI TT (ve–ho, i ↔ o) S Casing length Casing length details
[mm] [mm] on page

L = 375 L = 500 L = 375 L = 500

Lightweight partition walls with metal Lightweight partition walls


support structure and cladding on both
sides EI 90 S N N – E 43 to 44

100

EI 120 S2 – – – W 45 to 46

Lightweight partition walls with metal Lightweight partition walls


support structure, cladding on both
sides and flexible ceiling joint

1003 EI 90 S – – – E 47

Fire walls with metal support structure Fire walls


and cladding on both sides

115 EI 90 S N N – E 48 to 49

Lightweight partition walls with metal Shaft walls


support structure and cladding on
one side

90 EI 90 S – – – E 50

Lightweight partition walls without Shaft walls


metal support structure but with
cladding on one side

40 EI 90 S – – – E 51

2 For lightweight partition walls ≥ EI 120 N = mortar-based installation, E = installation kit, W = fire batt (Hilti system)
3 Wall thickness ≤ 225 mm and 175 mm width of metal support structure

5
Construction · Dimensions

Characteristics Approved installation positions for horizontal ducts


– Classified according to EN 13501-3
– For classes of performance see the tables on pages 4 and 5
– Airflow in either direction
– Release temperature 72 °C or 95 °C (for use in warm air
ventilation systems) Release mechanism

Construction features
– Two casing lengths to allow for wall and ceiling slabs
of various thicknesses
– Rectangular construction, rigid frame
– Flanges with pre-drilled holes on both sides
– Two inspection panels
– Intermediate dimensions in 1 mm increments for both width
and height are available
– Closed blade air leakage according to EN 1751, class 2
– Casing air leakage to EN 1751, class C;
(B + H) ≤ 700, class B

FK-EU with fusible link


311

260  35 B 35

35

 


H


35


L = 375 or 500 x ≈ 70

≈ 175
FK-EU with spring return actuator

311 x 94 mm for B < 251 mm


115 mm for all other dimensions
260 

Keep clear to provide access to release mechanism


or spring return actuator

 Casing
 Damper blade
  Release mechanism
 Handle
 Interlock
 Fusible link
 Thermoelectric release mechanism

 Spring return actuator
 Inspection access
 Travel stop

L = 375 or 500

6
Construction · Dimensions
FK-EU as air transfer application

Characteristics Approved installation positions for horizontal ducts


– Classified according to EN 13501-3 Smoke detector
– For classes of performance see the tables on pages 4 and 5
– Airflow in either direction
– Release temperature 72 °C
Construction features Spring return actuator

– Rectangular construction, rigid frame


– Two inspection access openings; the smoke detector
RM-O-3-D is inserted into the top inspection access
– Intermediate dimensions in 1 mm increments for both width
and height are available
– Closed blade air leakage according to EN 1751, class 2
For additional details, see pages 24 and 25.

FK-EU as air transfer application


120 260 120 or 35 B 35
   260  

≈ 150
35


H
35

x ≈ 70
        
L = 500 ≈ 175

 Casing x 94 mm for B < 251 mm


 Damper blade 115 mm for all other dimensions
 Thermoelectric release mechanism
 Spring return actuator
 Inspection access
 Travel stop Keep clear to provide access to the smoke detector
 Smoke detector type RM-O-3-D and/or spring return actuator
 Cover grille
 Extension piece, dependent on height

7
Construction · Dimensions
FK-EU with spring return actuator (Ex)

Characteristics Approved installation positions for horizontal ducts


– Classified according to EN 13501-3
– For classes of performance see the tables on pages 4 and 5
– Airflow in either direction
– Release temperature 72 °C
Release mechanism
Construction features
– Two casing lengths to allow for wall and ceiling slabs
of various thicknesses
– Rectangular construction, rigid frame
– Flanges with pre-drilled holes on both sides
– Two inspection panels
– Intermediate dimensions in 1 mm increments for both width
and height are available
– Closed blade air leakage according to EN 1751, class 2
– Casing air leakage to EN 1751, class C
(B + H) ≤ 700, class B
For additional details, see page 26.

FK-EU with spring return actuator (Ex)


311

260  35 B 35

35


 


H



35


L = 375 bzw. 500 x ≈ 220

 Casing x 94 mm for B < 251 mm


 Damper blade 115 mm for all other dimensions
 Thermoelectric release mechanism
 Spring return actuator
 ExBox (explosion-proof terminal box)
 Inspection access Keep clear to provide access to the
 Travel stop spring return actuator

8
Construction · Dimensions

The construction variants with stainless steel or powder-coated


casing meet even more critical requirements for corrosion Construction variant 1
Order code
protection. Casing Damper blade
Detailed listing on request. Galvanised Standard
Powder-coated Standard 1
Stainless steel1 Standard 2
Galvanised Coated 7
Powder-coated Coated 1-7
Stainless steel1 Coated 2-7
1 Not for fire batt installation.
Materials
– Casing in galvanised sheet steel, with powder coating
RAL 7001 (1), or in stainless steel 1.4301 (2) Construction variant 2 Order code
– Damper blade made of special insulation material Fusible link 95 °C
W2
– Damper blade coated in RAL 7001 (only for use in warm air ventilation systems)
– Damper blade shafts and driving linkage made of 2 W can be combined with all construction variants 1.
stainless steel
– Brass or stainless steel bearings
– Seals of polyurethane and elastomer

Dimensions
FK-EU with fusible link
Dimensions [mm] / weight [kg]
B
H
200 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 1100 1200 1300 1400 1500
200 10 11 12 13 15 16 17 18 19 20 22 23 24 26 28 30 31 33 35 38
250 11 12 13 15 16 17 18 19 21 22 24 25 26 28 30 32 34 36 38 41
300 12 13 14 16 17 18 19 21 23 24 25 26 28 30 31 34 36 38 40 44
350 13 15 16 17 18 20 22 23 25 26 27 29 30 32 34 37 39 41 44 48
400 15 16 17 18 20 22 24 26 27 28 30 31 32 35 38 40 43 46 48 52
450 16 17 18 20 22 24 26 28 29 29 31 32 34 37 40 44 47 49 52 57
500 17 18 19 22 24 26 28 29 30 31 33 34 36 39 45 47 50 53 56 62
550 21 23 26 28 29 30 32 34 35 37 38 43 47 50 54 57 60 67
600 23 25 27 29 30 31 34 36 37 39 42 46 50 54 57 61 64 71
650 24 26 28 29 31 33 35 37 40 42 45 49 53 57 61 64 68 75
700 25 27 28 31 33 35 37 40 43 45 48 52 56 60 64 67 71 78
750 26 28 30 32 34 37 39 42 45 48 50 55 59 63 66 69 73 81
800 27 29 32 34 36 38 42 45 47 50 52 57 62 65 68 71 75 84
FK-EU with spring return actuator: weight + 3 kg. FK-EU as air transfer application: weight + 6 kg.
FK-EU with spring return actuator (Ex): weight + 4 kg.
Pre-drilled flanges
Odd number of holes Even number of holes Detail A - Corner holes
300 300 Ø10 300 300

A A
35

.5
35

11

R6

R4.5
300

.5
H
H

35

Ø10
17.5
17.5

35 B 17.5 35 B 17.5
35
35

Dimensions [mm]
* excluding corner holes
200 300 400 500 600 650 750 900 1100 1300 1500
B or H
250 350 450 550 700 800 1000 1200 1400
No. of holes horizontally (B)* 1 1 1 2 2 3 3 4 4
No. of holes vertically (H)* 1 1 1 2 2

9
Accessories 1
For dry mortarless installation in solid walls

An installation subframe and an installation kit are required


for installation without mortar (dry mortarless installation) in solid
walls. Installation subframe and installation kit for dry
Order
mortarless installation in solid walls
Fire damper, installation subframe and installation kit code
are supplied unassembled. Assembly and installation to be
L1 [mm] L [mm]
performed by others.
115 500 E1
Fire dampers with installation subframe and installation kit only
in casing length L = 500 mm. 240 500 E2
The installation subframe and the fire damper with installation kit
must be installed and attached according to the operating and
installation manual.
In case of fire an intumescent seal closes the remaining gap.
Fire dampers installed in this manner can be easily removed.

Materials
– Installation subframe in galvanised steel with intumescent seal
– Installation kit from special insulation material and mineral
wool strips
– Fixing elements in galvanised steel

FK-EU with installation subframe and installation kit E1 or E2


  

Solid wall

Installation subframe and installation kit E1 or E2 when installed


L = 500
Installation subframe and installation kit consisting of:
 Installation subframe
 Installation kit
 Fixing elements

B + 17
6
H+1 / L1
76

10
Accessories 1
For dry mortarless installation on the face of solid walls

An installation kit is required for installation (dry mortarless


installation) on the face of solid walls.
Installation kit for dry mortarless installation
The fire damper and installation kit are supplied partly on the face of solid walls
Order
assembled. Assembly and installation to be performed by code
others.
L [mm]
The fire damper and installation kit must be installed and 500 WA
attached according to the operating and installation manual and
the WA installation manual.
Fire dampers with installation kit only in casing length
L = 500 mm.

Materials
– Wall connection frame made of galvanised sheet steel,
with seal
– Installation kit from special insulation material and mineral
wool strips
– Fixing elements in galvanised steel

FK-EU with installation kit WA


   

Solid wall

Operating side

Installation kit WA when installed


L = 500

Installation kit consisting of:


 Wall connection frame
 Installation kit

 Fixing elements

11
Accessories 1
For dry mortarless installation adjacent to solid walls

An installation kit is required for installation (dry mortarless


installation) adjacent to solid walls.
Installation kit for dry mortarless installation
The installation kit can be used for the repair of old, mortared adjacent to solid walls for x ≤ 260 mm
Order
fire dampers or duct sections with x ≤ 260 mm. code
The fire damper and installation kit are supplied partly L [mm]
assembled. Assembly and installation to be performed by 500 WV
others.
The fire damper and installation kit must be installed and
attached according to the operating and installation manual
and the WV installation manual.
Fire dampers with installation kit only in casing length
L = 500 mm.

Materials
– Installation kit from special insulation material and mineral
wool strips
– Fixing elements in galvanised steel

FK-EU with installation kit WV


 

x ≤ 260

Solid wall

Operating side
   Existing fire damper or duct section
requiring repair

Installation kit WV when installed


L = 500
Installation kit consisting of:
 Installation kit
 Fixing elements

12
Accessories 1
For dry mortarless installation remote from solid walls

An installation kit is required for installation (dry mortarless The installation kit contains all special parts.
installation) remote from solid walls Further components required according to the installation
The fire damper and installation kit are supplied partly assem- manual WE are to be provided by others.
bled. Assembly and installation to be performed by others.
The fire damper and installation kit must be installed and To be provided by others
attached according to the operating and installation manual Name Property/size
and the WE installation manual. Mineral wool Gross density ≥ 80 kg/m³, melting point > 1000 °C
Fire dampers with installation kit only in casing length
L = 500 mm. Mineral wool, 80 mm thick (slab) Gross density ≥ 80 kg/m³, melting point > 1000 °C
Screw anchor HUS-H 6 × 100
Materials Washer 8.4, ISO 7093-1
– Installation kit from special insulation material and mineral Hexagon head screw M8 × 16, ISO 4017
wool strips Hexagonal nut M8, EN 24032
Dry wall screw ∅5 × 50, ∅5 × 70, ∅5 × 80
– Fixing elements in galvanised steel Threaded rod M12
Mounting rail, Hilti MQ 41-3 or equivalent
Installation kit for dry mortarless installation Perforated plate, Hilti MQZ L13 or equivalent
Order Steel wire clip 63/11, 2/1, 53
remote from solid walls
code Adhesive Promat K84
L [mm] PROMASEAL-Mastic fire Paste
protection mastic
500 WE Promatect-LS and -H –

FK-EU with installation kit WE



Solid wall

Operating side

Duct, provided by others


Calcium silicate boards,
 provided by others

Installation kit WE when installed


L = 500
Installation kit consisting of:
 Installation kit
 Fixing elements

13
Accessories 1
For dry mortarless installation in lightweight partition walls and fire walls

An installation kit is required for installation without mortar


(dry mortarless installation) in lightweight partition walls and fire
walls. Installation kit for dry mortarless installation
Order
in lightweight partition walls and fire walls
Fire damper and installation kit are supplied unassembled. code
Assembly and installation to be performed by others.
L [mm]
Fire dampers with installation kit only in casing length 500 ES
L = 500 mm.
The fire damper and installation kit must be installed, connected
and attached according to the operating and installation manual.
In case of fire an intumescent seal closes the remaining gap.

Materials
– Installation kit from special insulation material with
intumescent seal and mineral wool strip
– Fixing elements in galvanised steel

FK-EU with installation kit ES


   
≈ 90

Lightweight partition wall


or fire wall


B + 95
 H + 95

190

≈ 20

Installation kit ES when installed


L = 500
Installation kit consisting of:
 Installation kit
 Fixing elements

14
Accessories 1
For dry mortarless installation in lightweight partition walls with flexible ceiling joint

An installation kit is required for installation without mortar (dry


mortarless installation) in lightweight partition walls with flexible Installation kit for lightweight partition walls with
ceiling joint directly underneath solid ceiling slabs. The installa- flexible ceiling joint
Order
tion kit allows for subsidence of the slab whilst maintaining the code
sealing continuity around the fire damper. Wall thickness [mm] L [mm]
Installation kit, extension piece and U-profile underneath the 100 500 GL1001
installation kit are assembled at the factory to form a unit. The 1 For wall thickness 100 mm when 50 mm profiles are used.
fire damper is to be fixed with the fixing elements of the installa- Other wall thicknesses and profile widths upon request.
tion kit to the ceiling slab by others.
Fire dampers with installation kit only in casing length
L = 500 mm.
The fire damper and installation kit must be installed, connected
and attached according to the operating and installation manual. Materials
– Installation subframe from special insulation material
– U-profiles in galvanised steel
– Threaded rods in galvanised steel
– Fixing elements in galvanised steel
– Extension piece in galvanised steel (for construction variants
1, 2, 1-7, and 2-7 additionally with powder coating, silver-grey,
RAL 7001)

FK-EU with installation kit for flexible ceiling joint


Ceiling slab

 

B + 83

     
Lightweight partition wall

Installation kit when installed


L = 500
260
Installation kit consisting of:
 Installation subframe with U profile
 Extension piece
 U-profile
 Threaded rod
 Fixing elements

15
Accessories 2
Cover grille

Cover grille
Cover grille
If only one end is to be ducted on site, the other end must have Order code
Operating side Installation side
a cover grille.
Cover grille – A0
For certain heights an extension piece may be required,
see table. – Cover grille 0A
Fire damper, cover grille and, if applicable, extension piece are Cover grille Cover grille AA
assembled at the factory to form a unit.
The free cross sectional area of the cover grille is approx. 70 %.
The fixing holes in the cover grilles and extension pieces match Location and length of extension pieces
those in the fire damper flanges. Dimensions [mm]
Cover grilles are also available separately. Installation
H Operating side L Order code
side
For further information on extension pieces see page 19.
In Germany, cover grilles on both ends are available only in 200 – 550 – – 375 / 500 A0
combination with the FK used as an air transfer application 600 – 800 120 – 375 / 500 A0
according to general building inspectorate licence Z-6.50-2031; 200 – 300 – – 500 0A
see pages 7, 24, and 25. 350 – 550 – 120 500 0A
600 – 800 – 260 500 0A
Materials
200 – 300 – – 500 AA
– Cover grilles in galvanised sheet steel (powder-coated
silver-grey (RAL 7001) when used with powder-coated (1) 350 – 550 – 120 500 AA
and stainless steel (2) dampers) 600 – 800 120 260 500 AA

Cover grille
Note!
Operating side Installation side – Extension pieces and cover grilles are
supplied factory assembled.
– Minimum distance »a« between
the open damper blade edge and
the circular spigot should be approx.
50 mm.

A Cover grille, mesh aperture


10 mm × 10 mm, wire width 2 mm
V Extension piece

A V A

Without extension piece With one extension piece With one extension piece
Operating side Installation side

a a a a

A A
H/B

H/B

H/B

A L

V V
a a
120 L L 120/260
H/B

L A

16
Accessories 2
Circular spigot plate

Circular spigot plate


Circular spigot plate
Use of circular spigot plates facilitates the direct connection Order code
Operating side Installation side
of circular ducts. Spigot plate – R0
For certain heights an extension piece may be required,
Spigot plate Spigot plate RR
see table.
Fire damper, spigot plate(s) and, if applicable, extension
piece(s) are factory assembled to form a unit.
The fixing holes in the spigot plates and extension pieces match
those in the fire damper flanges.
Spigot plates are also available separately.
For further information on extension pieces see page 19.
Location and length of extension pieces
Dimensions [mm]
Installation
H Operating side L Order code
side
200 – 550 – – 375 / 500 R0
Materials 600 – 800 120 – 375 / 500 R0
200 – 300 – – 500 RR
– Circular spigot plate in galvanised sheet steel (powder-coated
silver-grey (RAL 7001) when used with powder-coated (1) 350 – 550 – 120 500 RR
and stainless steel (2) dampers) 600 – 800 120 260 500 RR

Circular spigot plate


Note!
Operating side Installation side – Extension pieces and spigot plates
are supplied factory assembled.
– Minimum distance »a« between
the open damper blade edge and
the circular spigot plate should be
approx. 50 mm.

R Circular spigot plate


V Extension piece

R V R

Without extension piece With one extension piece With two extension pieces
Operating or installation side Operating and installation sides

a a

a a
a a
R R

R R
H/B

H/B
H/B

ØD

ØD
ØD

V V
R L R
V V
120 L 120

120 L 260

Dimensions [mm]
Nominal size 200 250 300 350 400 450 500 550 600 650 700 750 800
B×H 200 × 200 250 × 250 300 × 300 350 × 350 400 × 400 450 × 450 500 × 500 550 × 550 600 × 600 650 × 650 700 × 700 750 × 750 800 × 800
ØD 198 248 248 313 398 448 498 498 558 628 628 708 798

17
Accessories 2
Flexible connectors

Flexible connectors
Flexible connectors
Ducting must be installed in such a manner that it does not Order code
impose any loads on the fire damper in case of a fire. Operating side Installation side
For information on how to limit such loads please refer to the Flexible connector – S0
guideline regarding fire protection requirements on ventilation – Flexible connector 0S
systems (Lüftungsanlagen-Richtlinie, LüAR).
Flexible connector Flexible connector SS
As ducts may expand and walls may become deformed in case
of a fire, we recommend for the following applications using
flexible connectors when connecting the fire damper to rigid ducts:
– in lightweight partition walls Location and length of extension pieces
– in lightweight shaft walls Dimensions [mm]
– when used with fire batts H Operating side
Installation
L Order code
side
The flexible connectors should be installed in such a way
that both ends can compensate both tension and compression. 200 – 550 – – 375 / 500 S0
Flexible ducts can be used as an alternative. 600 – 800 120 – 375 / 500 S0
For certain heights an extension piece may be required, see table. 200 – 300 – – 500 0S
The fixing holes in the flexible connectors and extension pieces 350 – 550 – 120 500 0S
match those in the fire damper flanges.
Flexible connectors are also available separately. 600 – 800 – 260 500 0S
For further information on extension pieces see page 19. 200 – 300 – – 500 SS
Materials 350 – 550 – 120 500 SS
– Flexible connectors in galvanised steel and fibre-reinforced plastic 600 – 800 120 260 500 SS

Flexible connector
Note!
Operating side Installation side – Extension pieces are supplied factory
assembled.
Flexible connectors are supplied
unassembled, connection material
is to be provided by others.
– Minimum distance »a« between
the open damper blade edge and
the flexible connector should be
approx. 50 mm.

S Flexible connector
V Extension piece

S V S

≈ 160*
* flexible length ≥ 100 mm when installed
≈ 185

Without extension piece With one extension piece With two extension pieces
Operating or installation side Operating and installation sides

a a

a a
a a
S S

S S
H/B

H/B
H/B

V V
S L S
V V
120 L 120

120 L 260

18
Accessories 2
Extension piece

Extension piece Dimensions [mm]


When using cover grilles, circular spigot plates or flexible H 200 250 300 350 400 450 500 550 600 650 700 750 800
connectors an extension piece is required for certain heights.
x -224 -199 -174 -149 -124 -99 -74 -49 -24 1 26 51 76

Fire dampers with these attachments are supplied with y


extension piece. L = 375 23 48 73 98 123 148 173 198 223 248 273 298 323
Extension pieces are also available separately. L = 500 -102 -77 -52 -27 -2 23 48 73 98 123 148 173 198

Minimum distance
= extension piece required
The distance »a« between the open damper blade edge and
the cover grille, the spigot plate or the flexible connector should
be at least 50 mm.
For further information on cover grilles, circular spigot plates
and flexible connectors see pages 16 to 18.

Materials
– Extension piece in galvanised steel (it is also powder coated
silver-grey (RAL 7001) when used with powder coated (1) and
stainless steel (2) dampers)

FK-EU FK-EU
L = 375 mm L = 500 mm
Operating side Installation side Operating side Installation side
x y x y

-x y -x -y
H/B
H/B

H/B
H/B

L = 375 L = 500

L = 375 L = 500

With one extension piece With one extension piece With two extension pieces
Operating side Installation side Operating and installation sides

a a

a a a
H/B
H/B

H/B

V V

V V
120 L = 375 or 500 L = 500 120

120 L = 500 260

V Flexible connector, on operating and/or installation side

19
Attachments
Limit switch

FK-EU with fusible link


Attachments Order code
Limit switches with volt-free contacts enable the damper
blade position indication. Relays or indicator lights for fire alarm Standard construction Z00
systems can be used up to the maximum switch rating. Standard construction with limit switch for damper
One limit switch each is required for damper blade positions Z01
blade position CLOSED
OPEN and CLOSED. Standard construction with limit switch for damper
Z02
Fire dampers with a fusible link can be supplied with one or two blade position OPEN
limit switches; the switches can also be fitted later. Standard construction with limit switches for damper
Z03
blade positions CLOSED and OPEN

Limit switch
Connecting cable length / cross section 1 m / 3 × 0.34 mm²
Protection level IP 66
Type of contact 1 changeover contact, gold-plated
Max. switching current 0.5 A
Max. switching voltage 30 V DC, 250 V AC
Contact resistance approx. 30 mΩ

Limit switch Wiring examples

Limit switch not actuated Limit switch actuated

3 – 30 V DC 3 – 30 V DC
230 V AC 230 V AC
N(-) L(+) N(-) L(+)

 

green
brown
white white

 Indicator light or relay, to be provided by others

FK-EU when OPEN FK-EU when CLOSED

Damper Damper
blade blade
Limit switch Limit switch
position position
indicator indicator
OPEN actuated OPEN not actuated
CLOSED not actuated CLOSED actuated

20
Attachments
Limit switch (Ex)

FK-EU with fusible link (Ex)


Attachments Order code
The limit switches must be connected in a separately approved
casing with a type of protection according to EN 6009-0. Standard construction (Ex) Z00EX
Indicator lights or relays can be connected as long as the Standard construction with limit switch (Ex)
Z01EX
performance specifications are taken into consideration. Damper blade position CLOSED
One limit switch each is required for damper blade positions Standard construction with limit switch (Ex)
Z02EX
OPEN and CLOSED. The electrical connection is made in the Damper blade position OPEN
explosion-proof terminal box on site. Standard construction with limit switch (Ex)
Z03EX
Damper blade positions CLOSED and OPEN
Fire dampers with a fusible link can be supplied with one or two
limit switches (Ex); the switches can also be fitted later. Limit switch (Ex)
Declaration of conformity: TÜV 11 ATEX 085420 X Connecting cable length / cross section 1 m / 3 × 0.75 mm²
Protection level IP 66
Type of contact 1 change-over contacts
ATEX areas of application for the FK-EU 250 V AC / 5 A, 250 V DC / 0.4 A
Resistive load
30 V AC/DC / 7 A
Release Marking Ambient Max. airflow Switch rating
mechanism temperature velocity Inductive load 250 V AC / 3 A, 250 V DC / 0.03 A
cos ϕ = 0.6 30 V AC/DC / 5 A
Fusible link -40 °C to +40 °C 8 m/s
II 2D c T80 °C Gases, zones 1/2 Dusts, zone 22
Fusible link with limit II 2G c IIC T 6 -20 °C to +40 °C 8 m/s ATEX marking
switch II 2G EEx d IIC T6 II 2D T80 °C

Limit switch Wiring examples

Limit switch not actuated Limit switch actuated

5 – 30 V DC 5 – 30 V DC
110 – 230 V AC 110 – 230 V AC
N(-) L(+) N(-) L(+)

 

4
2 (grey)
(brown)

1 (black) 1 (black)

Break contact: Make contact:


grey/black black/brown

 Indicator light or relay, to be provided by others

FK-EU when OPEN FK-EU when CLOSED

Damper Damper
blade blade
Limit switch Limit switch
position position
indicator indicator
OPEN actuated OPEN not actuated
CLOSED not actuated CLOSED actuated

21
Attachments
Spring return actuator

FK-K90 with spring return actuator BLF


Attachments Order code
for combinations of width and height
up to B × H = 800 mm × 400 mm BLF230-T TR Z43
Operation of the fire damper with a spring return actuator allows BLF24-T-ST TR Z45
remote control and/or release by a suitable smoke detector.
If the supply voltage fails, or with thermoelectric release,
Spring return actuator BLF 230-T TR 24-T-ST TR
the damper closes (power off to close). Fire dampers with spring
return actuator can be functionally checked OPEN/CLOSED/ 24 V AC ±20 %
OPEN. Supply voltage
230 V AC ±14 % 50/60 Hz
50/60 Hz or
The actuator includes two limit switches. The connecting cables 24 V DC -10 % / +20 %
of the BLF24-T-ST TR are fitted with plugs. This ensures quick Spring compression 6W 5W
and easy connection to the TROX AS-i bus system. Power rating Hold position 3W 2.5 W
Rating 7 VA
A conversion kit is available for retrofitting an actuator
Running time Motor / spring return 40 to 75 s / 20 s
on a standard construction.
Type of contact 2 change-over contacts
Switching voltage 5 – 120 V DC / 5 – 250 V AC
Limit switch*
Switching current 1 mA – 3 A
Contact resistance < 100 mΩ
IEC protection class II III
Protection level IP54
Connecting cable Length / Cross section 1 m / 2(6*) × 0.75 mm²

Spring return actuator BLF... Wiring example


CLOSED position
230 V AC 110 – 230 V AC
24 V 24 – 48 V DC
N(-) L(+) N(-) L(+)

  CLOSED  OPEN

1 2 S1 S2 S3 S4 S5 S6
N L <5° <80°
BLF...

 Switch for opening and closing, to be provided by others


 Optional release mechanism, e.g. TROX smoke detector
type RM-O-3-D or RM-O-VS-D
 Indicator light, to be provided by others

22
Attachments
Spring return actuator

FK-EU with spring return actuator BF


Attachments Order code
Operation of the fire damper with a spring return actuator allows
remote control and/or release by a suitable smoke detector. BF230-T TR Z43
If the supply voltage fails, or with thermoelectric release,
BF24-T-ST TR Z45
the damper closes (power off to close). Fire dampers with spring
return actuator can be functionally checked OPEN/CLOSED/
OPEN. Spring return actuator BF 230-T TR 24-T-ST TR
The actuator includes two limit switches. The connecting cables 24 V AC ±20 %
of the BF24-T-ST TR are fitted with plugs. This ensures quick Supply voltage
230 V AC ±14 % 50/60 Hz
and easy connection to the TROX AS-i bus system. 50/60 Hz or
24 V DC -10 % / +20 %
A conversion kit is available for retrofitting an actuator Spring compression 8W 7W
on a standard construction. Power rating Hold position 3W 2W
Rating 12.5 VA 10 VA
Running time Motor / spring return approx. 140 s / approx. 16 s
Type of contact 2 change-over contacts
Switching voltage 5 – 120 V DC / 5 – 250 V AC
Limit switch*
Switching current 1 mA – 6 A
Contact resistance < 100 mΩ
IEC protection class II III
Protection level IP54
Connecting cable Length / Cross section 1 m / 2(6*) × 0.75 mm²

Spring return actuator BF... Wiring example


CLOSED position
230 V AC 110 – 230 V AC
24 V 24 – 48 V DC
N(-) L(+) N(-) L(+)

  CLOSED  OPEN

1 2 S1 S2 S3 S4 S5 S6
N L <5° <80°
BF...

 Switch for opening and closing, to be provided by others


 Optional release mechanism, e.g. TROX smoke detector
type RM-O-3-D or RM-O-VS-D
 Indicator light, to be provided by others

23
Attachments
Spring return actuator and smoke detector

FK-EU as air transfer application with spring return Smoke detector type RM-O-3-D
actuator BLF or BF Like the spring return actuator, the smoke detector
Operation of the air transfer application with a spring return type RM-O-3-D is a permanent part of the air transfer
actuator allows remote control and/or release by the smoke application damper.
detector. If the supply voltage fails, with thermoelectric release, Essential features of the smoke detector
or if smoke is detected, the damper closes (power off to close).
– General building inspectorate licence Z-78.6-125
Air transfer applications with spring return actuators can be
used for OPEN and CLOSED control. – For airflow velocities from 1 to 20 m/s
The actuator includes two limit switches. – Independent of the airflow direction
– Supply voltage 230 V AC, 50/60 Hz or 24 V DC
(upon request)
– Volt-free signal and alarm relays
– Integrated signal lights
– Contamination level indicator
– Automatic adjustment of alarm threshold
– Long service life
– For correct use and further technical data
see leaflet 4/6.3/EN/..

FK-EU as air transfer application

Smoke detector
type RM-O-3-D

Spring return actuator BF...

Spring return actuator


BLF...

Spring return actuator BLF230-T TR BLF24-T-ST TR BF230-T TR BF24-T-ST TR


24 V AC ±20 % 24 V AC ±20 %
230 V AC ±14 % 50/60 Hz 230 V AC ±14 % 50/60 Hz
Supply voltage
50/60 Hz or 50/60 Hz or
24 V DC -10 % / +20 % 24 V DC -10 % / +20 %
Spring compression 6W 5W 8W 7W
Power rating Hold position 3W 2.5 W 3W 2W
Rating 7 VA 7 VA 12.5 VA 10 VA
Running time Motor / spring return 40 to 75 s / 20 s approx. 140 s / approx. 16 s
Type of contact 2 change-over contacts
Switching voltage 5 – 120 V DC / 5 – 250 V AC
Limit switch*
Switching current 1 mA – 3 A 1 mA – 6 A
Contact resistance < 100 mΩ
IEC protection class II III II III
Protection level IP54
Connecting cable Length / Cross section 1 m / 2(6*) x 0.75 mm²

24
Attachments
Spring return actuator and smoke detector

Smoke detector type RM-O-3-D with spring


Order code
return actuator
BLF230-T TR
for combinations of width and height
up to B × H = 800 mm × 400 mm Z43RM
BF230-T TR

BLF24-T-ST TR
for combinations of width and height
up to B × H = 800 mm × 400 mm Z45RM
BF24-T-ST TR

Wiring example with RM-O-3-D and BLF230-T TR or BF230-T TR


CLOSED position
5 – 250 V
230 V AC
AC / DC
L N PE N(−) L(+)

  

L1 N PE PE N L1 1 2 3 4 1 2 − + S1 S2 S3 S4 S5 S6
N L <5° <80°
 L1 L2 L3 

Wiring example with RM-O-3-D and BLF24-T-ST TR or BF24-T-ST TR


CLOSED position
5 – 250 V
24 V DC
AC / DC
+ − N(−) L(+)

  

+ − + −
L4

L1 N PE PE N L1 1 2 3 4 1 2 − + S1 S2 S3 S4 S5 S6
<5° <80°
 L1 L2 L3 

 TROX smoke detector type RM-O-3-D L1 Terminal strip, 6-pole


 Spring return actuator BLF... or BF... Mains connection
 Indicator light for CLOSED position, to be provided by others L2 Terminal strip, 4-pole
 Indicator light for OPEN position, to be provided by others Contamination signalling - Terminals 1 and 2 (volt-free)
 External contamination indication, provided by customer Connection of release mechanism - Terminals 3 and 4 (volt-free)
L3 Terminal strip, 2-pole
Reset / external test - Terminals 1 and 2
L4 Terminal strip, 4-pole
Terminals + / −

25
Attachments
Spring return actuator (Ex)

FK-EU with spring return actuator ExMax


Attachments Order code
The fire damper can be used in supply and extract air systems
in areas with potentially explosive atmospheres. Operation ExMax-15-BF-TR ZEX1
of the fire damper with a spring return actuator allows remote
control and/or release by a suitable smoke detector. If the
supply voltage fails, or with thermoelectric release, the damper Spring return actuator ExMax-15-BF-TR
closes (power off to close). Fire dampers with spring return 24 – 230 V AC/DC,
actuator can be functionally checked OPEN/CLOSED/OPEN. Supply voltage ±10 % each, self-adaptive
50 – 60 Hz ±20 %
The actuator includes two limit switches. The electrical
Power rating 16 W / 15 VA
connection is made in the explosion-proof terminal box.
Switch-on current (< 1 s) 2A
Release temperature of the spring return actuator 72 °C. Running time Motor / spring return approx. 30 s / approx. 10 s
Declaration of conformity: TÜV 11 ATEX 085420 X Type of contact 2 change-over contacts
Limit switch Switching voltage 230 V AC / 24 V DC
Switching current 0.5 A / 3 A
IEC protection class I (earthed)
Protection level IP66
ATEX areas of application for the FK-EU Gases Dusts
Release Marking Ambient Max. airflow Zones 1/2 Zone 22
mechanism temperature velocity ATEX marking Spring return actuator II2G Ex d[ia] IIC T6/T5 II2D Ex tD A21 [iaD] IP66 T80 °C

ExPro-TT II 2D c T80 °C -40 °C to +40 °C 10 m/s FireSafe II2G EEx d ia IIC T6 II3D IP65 T80 °C
II 2G c IIC T 6 Terminal box II2G EEx e IIC T6 II2D IP66 T85 °C

Spring return actuator ExMax Wiring example


CLOSED position
230 V AC 110 – 230 V AC
24 V 24 – 48 V DC
N(-) L(+) N(-) L(+)

  CLOSED  OPEN

1 2 3 4 5 6 7 8
N L 5° 85°
ExMax-15-BF-TR

 Switch for opening and closing, to be provided by others


 Optional release mechanism, (installation in safe area),
e.g. TROX smoke detector type RM-O-3-D or RM-O-VS-D
 Indicator light, to be provided by others
 Terminal for equipotential bonding 4 mm²

26
Attachments
TROXNETCOM

FK-EU with spring return actuator and Order


TROXNETCOM Attachments
code
The fire dampers with spring return actuator BLF24-T-ST TR AS-EM/B and BLF24-T-ST TR* or BF24-T-ST TR ZA03
or BF24-T-ST TR and the modules shown here as attachments
form a functional unit ready for operation by an automatic fire
damper controller. The components are factory-assembled Order
Attachments
and wired. Only the bus line and the supply voltage (LON only) code
remain to be connected by others. LON-WA1/B2 and BLF24-T-ST TR* or BF24-T-ST TR ZL06
The AS interface is a world-standard bus system according LON-WA1/B2-AD and BLF24-T-ST TR* or BF24-T-ST TR ZL07
to EN 50295 and IEC 62026-2. It enables the integration of LON-WA1/B2-AD230 and BLF24-T-ST TR* or BF24-T-ST TR ZL08
different components (modules) in a network regardless of the
manufacturer and the design. The modules control actuators * for combinations of dimensions up to B x H = 800 mm × 400 mm
and/or receive signals from sensors.

LON and LonMark indicate a standard local operating network


system with manufacturer-independent communications.
Data is transferred by a microprocessor supplied by Echelon
Corporation using a unified protocol. LonMark defines standards
to ensure product compatibility.

AS-EM/B module Module LON-WA1/...

Controller and power unit


230 V AC
FK-EU with AS-EM/B FK-EU with LON-WA1/B2

FK-EU with AS-EM/B FK-EU with LON-WA1/B2-AD230


Flat cable insulation displacement connector LON FTT10A twisted pair

– The module sends the control signals between the spring – LON-WA1/B2
return actuator and the controller and power unit. This To control up to 2 fire dampers
enables the actuator to be controlled and the monitoring – LON-WA1/B2-AD
of running time during functional testing.
Connection box for the second fire damper with 24 V AC
– The supply voltage (24 V DC) for the module and the supply voltage
actuator is transmitted using the AS-i flat cable.
– LON-WA1/B2-AD230
– Function display: Operation
4 inputs Connection box for the second fire damper with 230 V AC
2 outputs supply voltage

For further information please refer to our website.

27
Attachments
TROXNETCOM (Ex)

FK-EU with spring return actuator (Ex) and Order


TROXNETCOM Attachments
code
The fire dampers with spring return actuator ExMax-15-BF-TR AS interface module ZEX2
and module AS-EM/C as attachments form a functional unit
for bus communication to an automatic fire damper controller.
The module is to be installed and wired outside of the Ex zone
by others.
The AS interface is a world-standard bus system according
to EN 50295 and IEC 62026-2. It enables the integration of
different components (modules) in a network regardless of the
manufacturer and the design. The modules control actuators
and/or receive signals from sensors.

AS-EM/C module

Controller
FK-EU
24 V AC / DC
230 V AC

AS-EM/C

AS-EM/C

FK-EU
Outside Ex zone Inside Ex zone

– The module sends the control signals between the spring


return actuator and the controller and power unit. This
enables the actuator to be controlled and the monitoring
of running time during functional testing.
– The supply voltage (24 V DC) for the module and the
actuator is transmitted using the AS-i flat cable.
– Function display: Operation
4 inputs
2 outputs

For further information please refer to our website.

28
Attachments
Smoke detectors

To prevent smoke from spreading in buildings through the air


conditioning system, it is extremely important that the smoke is Attachments Order code
detected at an early stage.
Smoke detectors RM-O-3-D and RM-O-VS-D operate on the Smoke detector RM-O-3-D
principle of light scattering and detect the smoke regardless of
its temperature so that the fire dampers can be closed before Smoke detector with airflow monitor RM-O-VS-D
the release temperature is reached.
If the air contains suspended particles, as is the case with Smoke detectors are to be ordered as separate attachments.
smoke, beams of light are deflected off these. A sensor When the FK-EU is used as an air transfer application, smoke
(photodiode), which does not receive light in clear air, detector RM-O-3-D is part of the supply package.
is illuminated by the scattered light. The fire or smoke control
damper is released when the brightness of the scattered light
exceeds a certain threshold.

Smoke detector type RM-O-3-D – Smoke detector for fire dampers and smoke control
dampers
– General building inspectorate licence Z-78.6-125
– For airflow velocities from 1 to 20 m/s
– Independent of the airflow direction
– Supply voltage 230 V AC, 50/60 Hz or 24 V DC
(upon request)
– Volt-free signal and alarm relays
– Integrated signal lights
– Contamination level indicator
– Automatic adjustment of alarm threshold
– Long service life
– For correct use and further technical data
see leaflet 4/6.3/EN/..

Smoke detector RM-O-VS-D – Smoke detector for fire dampers and smoke control
with airflow monitor dampers
– General building inspectorate licence Z-78.6-67
– For airflow velocities from 1 to 20 m/s
– Independent of the airflow direction
– Airflow monitoring with warning for lower limit 2 m/s
– Supply voltage 230 V AC, 50/60 Hz
– Volt-free signal and alarm relays
– Integrated signal lights
– Contamination level indicator
– Automatic adjustment of alarm threshold
– Long service life
– For correct use and further technical data
see leaflet 4/6.2/EN/..

29
Quick selection

Nomenclature LWNC : NC rating of the sound power level


LWNC ≈ LWA - 5
B [mm] : Width
K : Correction value for damper width
H [mm] : Height
B ≠ 450 mm or 600 mm (see table 6)
A [m²] : Free cross sectional area
 [m³/h] : Volume flow rate
vA [m/s] : Airflow velocity based on B × H All sound power levels are based on 1 pW.
Δpt [Pa] : Total differential pressure (duct installation) All noise levels were determined in a reverberation chamber.
The sound power data has been determined and corrected
according to ISO 5135, February 1999.
Δpt = ζ × ρ ⁄ 2 × vA²
Using quick selection for sizing fire dampers will quickly
ζ : Resistance coefficient (fully ducted) provide optimum results. It ensures compliance with normally
ρ [kg/m³] : Air density (approx. 1.2 at 20 °C) acceptable aerodynamic and acoustic limits.
fm [Hz] : Octave band centre frequency – Airflow velocity
LWA [dB(A)] : Sound power level of the air-regenerated – Total differential pressure
noise in the duct
– Sound power level
LW [dB] : Octave band sound power level
LW = LWA + correction value to obtain FK-EU-LD with lip seal in combinations of width and height up to
octave level (see tables 4 and 5) B × H = 800 mm × 400 mm

Volume flow rate [m³/h] at Δpt < 35 Pa

B [mm]
H LWA
[mm] [dB(A)] 200 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 1100 1200 1300 1400 1500

35 650 850 1050 1250 1400 1600 1750 1950 2100 2300 2450 2600 2800 1950 2150 2400 2650 2850 3100 3300
200
45 950 1200 1450 1750 2000 2250 2500 2700 2950 3200 3450 3650 3900 2750 3100 3400 3750 4050 4400 4700

35 900 1150 1400 1650 1900 2150 2350 2600 2800 3050 3250 3450 3700 2800 3150 3450 3800 4150 4450 4800
250
45 1300 1650 2000 2300 2650 3000 3300 3600 3950 4250 4550 4850 5150 4000 4450 4950 5400 5850 6350 6800

35 1150 1450 1750 2050 2350 2650 2950 3200 3500 3750 4050 4300 4550 3650 4100 4500 4950 5350 5800 6200
300
45 1600 2050 2500 2900 3300 3700 4100 4500 4850 5250 5650 6000 6400 5200 5800 6400 7050 7650 8250 8850

35 1400 1750 2100 2450 2800 3150 3500 3800 4150 4450 4800 5100 5400 4500 5050 5550 6050 6600 7100 7650
350
45 1950 2450 2950 3450 3950 4400 4850 5350 5800 6250 6700 7150 7550 6400 7150 7900 8650 9400 10100 10850

35 1600 2050 2450 2850 3250 3650 4050 4400 4800 5150 5500 5900 6250 5350 5950 6550 7200 7800 8450 9050
400
45 2250 2850 3450 4000 4550 5100 5650 6150 6700 7200 7700 8250 8750 7600 8450 9350 10200 11100 12000 12850

35 1250 1650 1850 2200 2550 2950 3300 3650 4000 4350 4700 5100 5450 6150 6850 7600 8300 9000 9700 10450
450
45 1800 2400 2600 3150 3650 4150 4650 5200 5700 6200 6700 7200 7750 8750 9750 10800 11800 12800 13800 14850

35 1550 2100 2100 2500 2900 3300 3700 4150 4550 4950 5350 5750 6150 6950 7800 8600 9400 10200 11000 11800
500
45 2200 2950 2950 3550 4150 4700 5300 5850 6450 7050 7600 8200 8750 9900 11050 12200 13350 14500 15650 16800

35 2350 2800 3250 3700 4150 4600 5050 5500 5950 6450 6900 7800 8700 9600 10500 11400 12300 13150
550
45 3300 3950 4600 5250 5900 6550 7200 7850 8500 9150 9800 11050 12350 13600 14900 16200 17450 18750

35 2600 3100 3600 4100 4600 5100 5600 6100 6600 7100 7600 8600 9600 10550 11550 12550 13550 14550
600
45 3650 4400 5100 5800 6550 7250 7950 8650 9400 10100 10800 12200 13600 15050 16450 17850 19250 20650

35 2850 3400 3950 4500 5050 5600 6150 6650 7200 7750 8300 9400 10500 11550 12650 13750 14800 15900
650
45 4000 4800 5600 6350 7150 7950 8700 9500 10250 11050 11800 13350 14900 16450 17950 19500 21050 22600

35 3050 3650 4250 4850 5450 6050 6650 7250 7850 8450 9000 10200 11350 12550 13700 14900 16050 17250
700
45 4350 5200 6050 6900 7750 8600 9450 10300 11150 12000 12800 14500 16150 17850 19500 21150 22850 24500

35 3300 3950 4600 5250 5900 6550 7200 7800 8450 9100 9700 11000 12250 13550 14800 16050 17300 18600
750
45 4700 5650 6550 7450 8400 9300 10200 11100 12000 12900 13800 15650 17450 19250 21050 22800 24600 26400

35 3550 4250 4950 5650 6350 7000 7700 8400 9050 9750 10450 11800 13150 14500 15850 17200 18550 19900
800
45 5050 6050 7050 8000 9000 9950 10950 11900 12900 13850 14850 16750 18700 20600 22550 24450 26400 28300

30
Aerodynamic selection
Differential pressure

Example 1 Result
vA = 4500 m³/h ⁄ (0.6 m × 0.4 m × 3600) = 5.2 m/s
Given data Δpt = 5 Pa (from table 1, for B = 450 mm)
Volume flow rate: 1250 l/s (4500 m³/h) Correction for B = 600 from table 2
Maximum width: 600 mm Δpt = 5 Pa × 0.8 ≈ 4 Pa
Required sound power level: 35 dB(A) LWA = 31 dB(A) (from table 3, for B = 450 mm)
Quick selection Correction for B = 600 from table 6
LWA = 31 dB(A) + 0.5 ≈ 32 dB(A)
FK-EU-LD / 600 × 400 × 500 (with lip seal)
Sound power level spectrum
fm [Hz] 63 125 250 500 1000 2000 4000 8000
LWA [dB(A)] 32
Correction
value from 13 5 2 −4 −6 −11 −17 −24
table 4
LW [dB] 45 37 34 28 26 21 15 8

Table 1: Differential pressure Δpt [Pa] for damper blade width B = 450 mm or 600 mm

vA [m/s]
H [mm] B [mm] Type
2 3 4 5 6 7 8 9 10 11 12

200 < < 6 9 13 18 23 29 36 43 51


FK-EU-LD with

250 < < 5 7 10 14 18 23 29 35 42


lip seal

300 450 < < < 6 9 12 16 20 25 30 36

350 < < < 5 8 11 14 18 22 26 31

400 < < < 5 7 10 13 16 20 24 28

450 < < 6 9 13 18 23 30 37 44 53


FK-EU with landing angles with

500 < < 5 8 12 16 21 26 32 39 47

550 < < 5 7 10 14 19 24 29 35 42


bead seals

600 < < < 7 10 13 17 22 27 32 38


600
650 < < < 6 9 12 16 20 25 30 35

700 < < < 6 8 11 15 19 23 28 33

750 < < < 5 8 11 14 18 22 26 31

800 < < < 5 7 10 13 17 21 25 30

Maximum upstream velocity: ≤ 8 m/s for standard construction, ≤ 12 m/s or 10 m/s (ExMax) for construction with spring return actuator.

Table 2: Correction values based on other damper widths B

B [mm]
B
Type
[mm] 200 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 1100 1200 1300 1400 1500

FK-EU-
450 LD 1.9 1.6 1.3 1.2 1.1 1.0 0.9 0.9 0.8 0.8 0.7 0.7 0.7

600 FK-EU 2.4 1.9 1.6 1.4 1.3 1.2 1.1 1.0 1.0 1.0 0.9 0.9 0.9 0.8 0.8 0.8 0.8 0.8 0.7 0.7

31
Aerodynamic selection
Sound power level

Example 2 Result
vA = 15300 m³/h ⁄ (1.0 m × 0.7 m × 3600) = 6.1 m/s
Given data Δpt = 8 Pa (from table 1, for B = 600 mm)
Volume flow rate: 4250 l/s (15300 m³/h) Correction for B = 1000 from table 2
Maximum width: 1000 mm Δpt = 8 Pa × 0.8 ≈ 7 Pa
Required sound power level: 45 dB(A) LWA = 44 dB(A) (from table 3, for B = 600 mm)
Quick selection Correction for B = 1000 from table 6
LWA = 44 dB(A) − 1 = 43 dB(A)
FK-EU / 1000 × 700 × 500 (with landing angles with bead seals)
Sound power level spectrum
fm [Hz] 63 125 250 500 1000 2000 4000 8000
LWA [dB(A)] 43
Correction
value from 4 6 1 −3 −6 −9 −17 −25
table 5
LW [dB] 47 49 44 40 37 34 26 18

Table 3: Sound power level LWA [dB(A)] for damper width B = 450 mm or 600 mm

vA [m/s]
H [mm] B [mm] Type
2 3 4 5 6 7 8 9 10 11 12

200 <15 20 29 35 41 45 49 53 56 59 62
FK-EU-LD with

250 <15 18 27 33 39 44 48 51 54 57 60
lip seal

300 450 <15 17 26 32 38 42 46 50 53 56 59

350 <15 17 25 32 37 42 46 49 53 55 58

400 <15 16 25 31 37 42 46 49 52 55 58

450 <15 26 34 41 46 50 54 57 60 63 65
FK-EU with landing angles with

500 <15 25 34 40 45 50 53 57 60 62 65

550 <15 25 33 40 45 49 53 56 59 62 64
bead seals

600 <15 25 33 39 44 49 53 56 59 62 64
600
650 <15 24 33 39 44 48 52 56 59 61 64

700 <15 24 32 39 44 48 52 55 58 61 64

750 <15 24 32 38 44 48 52 55 58 61 63

800 <15 24 32 38 43 48 52 55 58 61 63

Maximum upstream velocity: ≤ 8 m/s for standard construction, ≤ 12 m/s or 10 m/s (ExMax) for construction with spring return actuator.

Table 4: Correction values for FK-EU-LD with lip seal to Table 5: Correction values for FK-EU with landing angles
obtain octave levels in dB/Oct. with bead seals to obtain octave levels in dB/Oct.
vA fm [Hz] vA fm [Hz]
[m/s] 63 125 250 500 1000 2000 4000 8000 [m/s] 63 125 250 500 1000 2000 4000 8000
2 17 8 3 −2 −8 −17 −26 −33 2 10 13 3 −3 −15 −17 −28 −36
4 15 5 2 −3 −7 −12 −19 −26 4 8 10 3 −3 −7 −11 −21 −29
6 10 4 2 −4 −6 −10 −16 −22 6 4 6 1 −3 −6 −9 −17 −25
8 7 3 1 −4 −6 −8 −13 −19 8 2 4 −1 −3 −4 −7 −14 −22
10 5 2 1 −5 −5 −6 −11 −17 10 −1 −2 −3 −4 −4 −7 −12 −20

32
Aerodynamic selection
Free cross sectional area, resistance coefficient and correction values

Table 6: Free cross sectional area, resistance coefficient and correction values

B [mm]
H
[mm] 200 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 1100 1200 1300 1400 1500

A [m²] 0.020 0.027 0.034 0.041 0.048 0.055 0.062 0.069 0.076 0.083 0.090 0.097 0.104 0.084 0.094 0.104 0.114 0.124 0.134 0.144

200 ζ 1.12 0.94 0.77 0.71 0.65 0.59 0.53 0.53 0.47 0.47 0.41 0.41 0.41 2.18 2.18 2.18 2.18 2.18 1.90 1.90

K 1 1 0 0 0 0 0 0 0.5 0.5 1 1 1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.029 0.039 0.048 0.058 0.067 0.077 0.086 0.096 0.105 0.115 0.124 0.134 0.143 0.126 0.141 0.156 0.171 0.186 0.201 0.216

250 ζ 0.91 0.77 0.62 0.58 0.53 0.48 0.43 0.43 0.38 0.38 0.34 0.34 0.34 1.26 1.26 1.26 1.26 1.26 1.11 1.11

K 1 1 0 0 0 0 0 0 0.5 0.5 1 1 1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.038 0.050 0.062 0.074 0.086 0.098 0.11 0.122 0.134 0.146 0.158 0.17 0.182 0.168 0.188 0.208 0.228 0.248 0.268 0.288

300 ζ 0.78 0.66 0.53 0.49 0.45 0.41 0.37 0.37 0.33 0.33 0.29 0.29 0.29 0.89 0.89 0.89 0.89 0.89 0.78 0.78

K 1 1 0 0 0 0 0 0 0.5 0.5 1 1 1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.047 0.062 0.076 0.091 0.105 0.12 0.134 0.149 0.163 0.178 0.192 0.207 0.221 0.21 0.235 0.26 0.285 0.31 0.335 0.36

350 ζ 0.68 0.58 0.47 0.43 0.40 0.36 0.32 0.32 0.29 0.29 0.25 0.25 0.25 0.69 0.69 0.69 0.69 0.69 0.60 0.60

K 1 1 0 0 0 0 0 0 0.5 0.5 1 1 1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.056 0.073 0.090 0.107 0.124 0.141 0.158 0.175 0.192 0.209 0.226 0.243 0.26 0.252 0.282 0.312 0.342 0.372 0.402 0.432

400 ζ 0.63 0.53 0.43 0.40 0.36 0.33 0.30 0.30 0.26 0.26 0.23 0.23 0.23 0.57 0.57 0.57 0.57 0.57 0.50 0.50

K 1 1 0 0 0 0 0 0 0.5 0.5 1 1 1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.049 0.067 0.084 0.102 0.119 0.137 0.154 0.172 0.189 0.207 0.224 0.242 0.259 0.294 0.329 0.364 0.399 0.434 0.469 0.504

450 ζ 1.48 1.13 0.98 0.85 0.79 0.73 0.67 0.61 0.61 0.61 0.55 0.55 0.55 0.49 0.49 0.49 0.49 0.49 0.43 0.43

K 5.5 3.5 2 2 1 1 0 0 0 0 0 0 -1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.056 0.076 0.096 0.116 0.136 0.156 0.176 0.196 0.216 0.236 0.256 0.276 0.296 0.336 0.376 0.416 0.456 0.496 0.536 0.576

500 ζ 1.35 1.03 0.86 0.76 0.70 0.65 0.59 0.54 0.54 0.54 0.49 0.49 0.49 0.43 0.43 0.43 0.43 0.43 0.38 0.38

K 5.5 3.5 2 2 1 1 0 0 0 0 0 0 -1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.108 0.131 0.153 0.176 0.198 0.221 0.243 0.266 0.288 0.311 0.333 0.378 0.423 0.468 0.513 0.558 0.603 0.648

550 ζ 0.78 0.69 0.64 0.59 0.54 0.49 0.49 0.49 0.44 0.44 0.44 0.39 0.39 0.39 0.39 0.39 0.34 0.34

K 2 2 1 1 0 0 0 0 0 0 -1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.12 0.145 0.17 0.195 0.22 0.245 0.27 0.295 0.32 0.345 0.37 0.42 0.47 0.52 0.57 0.62 0.67 0.72

600 ζ 0.70 0.62 0.57 0.53 0.48 0.44 0.44 0.44 0.40 0.40 0.40 0.35 0.35 0.35 0.35 0.35 0.31 0.31

K 2 2 1 1 0 0 0 0 0 0 -1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.132 0.16 0.187 0.215 0.242 0.27 0.297 0.325 0.352 0.38 0.407 0.462 0.517 0.572 0.627 0.682 0.737 0.792

650 ζ 0.66 0.57 0.53 0.49 0.45 0.41 0.41 0.41 0.37 0.37 0.37 0.33 0.33 0.33 0.33 0.33 0.29 0.29

K 2 2 1 1 0 0 0 0 0 0 -1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.144 0.174 0.204 0.234 0.264 0.294 0.324 0.354 0.384 0.414 0.444 0.504 0.564 0.624 0.684 0.744 0.804 0.864

700 ζ 0.61 0.53 0.49 0.46 0.42 0.38 0.38 0.38 0.34 0.34 0.34 0.31 0.31 0.31 0.31 0.31 0.27 0.27

K 2 2 1 1 0 0 0 0 0 0 -1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.156 0.189 0.221 0.254 0.286 0.319 0.351 0.384 0.416 0.449 0.481 0.546 0.611 0.676 0.741 0.806 0.871 0.936

750 ζ 0.58 0.50 0.47 0.43 0.40 0.36 0.36 0.36 0.32 0.32 0.32 0.29 0.29 0.29 0.29 0.29 0.25 0.25

K 2 2 1 1 0 0 0 0 0 0 -1 -1 -1 -1 -1 -1 -1 -1

A [m²] 0.168 0.203 0.238 0.273 0.308 0.343 0.378 0.413 0.448 0.483 0.518 0.588 0.658 0.728 0.798 0.868 0.938 1.008

800 ζ 0.54 0.48 0.44 0.41 0.37 0.34 0.34 0.34 0.31 0.31 0.31 0.27 0.27 0.27 0.27 0.27 0.24 0.24

K 2 2 1 1 0 0 0 0 0 0 -1 -1 -1 -1 -1 -1 -1 -1

33
Installation details
Solid walls and ceiling slabs

Mortar-based installation Recommendations


Installation of the fire damper in solid walls and ceiling slabs – Casing length L = 500 mm, if the thickness of the wall
is approved with perimeter mortar infill (wet installation). exceeds 100 mm or the thickness of the ceiling slab exceeds
Installation in horizontal and vertical ducts. Airflow direction 125 mm
is not critical. Installation details
Requirements – An opening or a cut hole with a minimum width B + 80 mm
– Solid walls or fire walls (if referred to as such) made of, and minimum height H + 80 mm is required; alternatively,
for example, concrete, aerated concrete, masonry, or solid the fire damper can be concreted into the wall or ceiling slab
gypsum wallboards according to EN 12859 (without hollow during construction
spaces), gross density ≥ 500 kg/m³, and a minimum thickness – Completely close off the perimeter gap »s« with one of the
of 100 mm following: mortar of group II, IIa, III or IIIa according to
– Solid ceiling slabs made of concrete or aerated concrete, DIN 1053; fire protection mortar of group II or III or equivalent
gross density ≥ 600 kg/m³, and a minimum thickness of according to EN 998-1/2 (classes M 2.5 to 10); fire protection
125 mm mortar of class M 2.5 or 10; gypsum mortar; or, if necessary,
concrete.
– 75 mm minimum distance to load bearing structural elements, The mortar bed depth must be at least 100 mm.
40 mm minimum distance when installed in ceiling slabs
– The perimeter gap »s« can be reduced if the fire damper
– 70 mm minimum distance between two fire dampers when is concreted into a wall during construction.
installed in walls, 100 mm when installed in ceiling slabs

Wall installation Ceiling slab installation, upright


W = 100 up to ≤ 240 mm
260 W

L = 375
or 500

260
L = 375 or 500
100

D
s ≥ 40

Mortar, concrete
or gypsum mortar Mortar, concrete
or gypsum mortar

s ≥ 40

W > 240 mm Ceiling slab installation, suspended


W
≥ 100

Mortar, concrete
Extension piece or gypsum mortar

s ≥ 40
L = 375 or 500
D
260

34
Installation details
Solid walls and ceiling slabs

Mortar-based installation and dry mortarless installation are Installation details


approved for the installation of the fire damper into solid walls. – Seal difficult to access gaps with metal profiles and mineral
– Mortar-based installation with partial mortaring wool
– Mortar-based installation of multiple dampers flange to flange – Completely close off perimeter gap »x« with mineral wool to
– Dry mortarless installation with installation subframe and DIN 4102, fire rating class A1, non-combustible, gross density
installation kit approximately 100 kg/m³
– Dry mortarless installation with fire batt – Completely close off the remaining gap »s« with one of
the following: mortar of group II, IIa, III or IIIa according to
Installation in horizontal ducts. Airflow direction is not critical
DIN 1053; fire protection mortar of group II or III or equivalent
Mortar-based installation with partial mortaring according to EN 998-2 (classes M 2.5 to 10); fire protection
mortar of class M 2.5 or 10; gypsum mortar; or, if necessary,
Requirements concrete.
– Solid walls or fire walls (if referred to as such) made of, The mortar bed depth must be at least 100 mm.
for example, concrete, aerated concrete, masonry, or solid – The perimeter gap »s« can be reduced if the fire damper
gypsum wallboards according to EN 12859 (without hollow is concreted into a wall during construction.
spaces), gross density ≥ 500 kg/m³, and a minimum thickness
of 100 mm
– Connection of rigid ducts using flexible connectors
is recommended

Installation with partial mortaring


Difficult to access gap on one side, wall joint Difficult to access gap on one side, ceiling joint

Ceiling slab Ceiling slab

x ≤ 40
L = 375 or 500
Solid wall

L = 375 or 500 Mineral wool and


metal profile
Mortar, concrete
or gypsum mortar,
on three sides

Mineral wool and


metal profile
s ≥ 40

Mortar, concrete
or gypsum mortar, s≥4
on three sides 0

Solid wall
x ≤ 40

Difficult to access gap on two sides, wall and


ceiling joint

Ceiling slab
x ≤ 40
x ≤ 40

L = 375 or 500

Mineral wool and


metal profile
s ≥ 40

Solid wall Mortar, concrete or gypsum mortar,


on two sides

35
Installation details
Solid walls and ceiling slabs

Mortar-based installation of multiple dampers – Completely close off gaps »s« and »a« with one of the
flange to flange following: mortar of group II, IIa, III or IIIa according to
DIN 1053; fire protection mortar of group II or III or equivalent
Requirements
according to EN 998-2 (classes M 2.5 to 10); fire protection
– Solid walls or fire walls (if referred to as such) made of, mortar of class M 2.5 or 10; gypsum mortar; or, if necessary,
for example, concrete, aerated concrete, masonry, or solid concrete.
gypsum wallboards according to EN 12859 (without hollow The mortar bed depth must be at least 100 mm.
spaces), gross density ≥ 500 kg/m³, and a minimum thickness
– The perimeter gap »s« can be reduced if the fire damper
of 100 mm
is concreted into a wall during construction.
Installation details
– An opening or a cut hole with a minimum 2 × B + 150 mm and
H + 80 mm or B + 80 mm and 2 × H + 150 mm is required or
the fire damper is concreted into the wall during construction
– The flanges of the horizontally or vertically arranged fire
dampers are next to one another, the spacing between the
casings is »a« = 70 mm

Flange to flange
Horizontal arrangement Vertical arrangement
260
W 260 W
A W ≥ 100 mm
L = 375
L = 375
or 500
or 500

a = 70

Mortar
a=7
0

s≥4
0

View A
Mortar
a = 70

Mortar

36
Installation details
Solid walls and ceiling slabs

Dry mortarless installation with installation subframe – Completely close off the perimeter gap »s« with one of the
and installation kit E1 or E2 following: mortar of group II, IIa, III or IIIa according to
DIN 1053; fire protection mortar of group II or III or equivalent
Requirements
according to EN 998-1/2 (classes M 2.5 to 10); fire protection
– Solid walls or fire walls (if referred to as such) made of, mortar of class M 2.5 or 10; gypsum mortar; or, if necessary,
for example, concrete, aerated concrete, masonry, or solid concrete.
gypsum wallboards according to EN 12859 (without hollow The mortar bed depth must be at least 100 mm.
spaces), gross density ≥ 500 kg/m³, and a minimum thickness
– The perimeter gap »s« can be reduced if the fire damper
of 100 mm
is concreted into a wall during construction.
– Casing length L = 500 mm
For further information on installation subframe and installation
– 75 mm minimum distance to load bearing structural elements kit E1 or E2, see page 10.
– 200 mm minimum distance between two fire dampers
Installation details
– An installation opening with B + 185 mm and H + 185 mm
is required
– Fire damper is fitted with the installation kit and pushed into
the installation subframe

Dry mortarless installation with installation ≈ 290


W
subframe and installation kit E1 or E2
5/
B + 18
5
L = 500 H + 18
A L1 = 115
260
or 240

Installation kit

Installation subframe

Mortar, concrete
or gypsum mortar

Solid wall
s ≥ 40

Detail A
W

Solid wall
s ≥ 40

Mortar, concrete
or gypsum mortar

Installation subframe

Installation kit

37
Installation details
Solid walls and ceiling slabs

Dry mortarless installation with fire batt Combinations of width and height up to
B × H = 800 mm × 400 mm
Requirements
– Solid walls or fire walls (if referred to as such) made of, Installation details
for example, concrete, aerated concrete, masonry, or solid – An opening or cut hole with B + 100...800 mm and
gypsum wallboards according to EN 12859 (without hollow H + 100...800 mm is required
spaces), gross density ≥ 500 kg/m³, and a minimum thickness – 400 mm maximum distance between the fire damper and wall
of 100 mm opening
– Solid ceiling slabs made of concrete or aerated concrete, – Completely close off the perimeter gap with two layers of fire
gross density ≥ 600 kg/m³, and a minimum thickness batt (boards made of mineral wool, coated) ≥ 140 kg/m³.
of 150 mm – Apply intumescent fire protection sealant to all connections.
– Casing length L = 500 mm – Apply a fire protection coat, at least 2.5 mm thick, to the fire
– 75 mm minimum distance to load bearing structural elements damper casing perimeter on both sides of the wall or ceiling
– 200 mm minimum distance between two fire dampers but slab. Apply the coat on the installation side up to the flange.
dependent on the selected gap width (50...400 mm) – The actuator and release unit must not be coated
– For suspension systems, see pages 52 and 53. – The fire dampers must be installed, connected and secured
according to the operating and installation manual.

Wall installation Wall installation


Combinations of width and height up to Combinations of width and height up to
B × H = 800 mm × 400 mm B × H = 801 mm × 401 mm
260 W 260 W

Mineral wool frame,


L = 500 L = 500 on three sides

Fire protection
coating, applied
Fire protection up to flange
coating, applied
up to flange

Fire batt
50
Fire batt

Mineral wool frame,


on three sides
Fire protection 50
50 coating Fire protection
coating

B + 10 B + 10
0 0
H + 1 ...800 / H + 1 ...800 /
00...8 00...8
00 00

W W

90

Mineral wool frame,


on three sides

Fire protection coating, Fire protection coating,


applied up to flange applied up to flange

38
Installation details
Solid walls and ceiling slabs

Combinations of width and height up to


B × H = 801 mm × 401 mm
Installation details
– Same as for combinations of width and height up to
B × H = 800 mm × 400 mm
– For wall installation, additionally provide on both sides of the
wall and on three sides of the damper a frame of mineral wool
≥ 140 kg/m³
– The fire dampers must be installed, connected and secured
according to the operating and installation manual.

Ceiling slab installation, upright Ceiling slab installation, upright


Fire batt, flush with the floor Fire batt, flush with the ceiling and the floor

Fire protection Fire protection


coating coating
260

260
L = 500

L = 500
50
50

D
50...400 H/B 50...400 H/B
50 50

Fire batt Fire protection coating, Fire batt Fire protection coating,
applied up to flange applied up to flange

Ceiling slab installation, suspended Ceiling slab installation, suspended


Fire batt, flush with the ceiling Fire batt, flush with the ceiling and the floor
Fire protection coating, Fire protection coating,
Fire batt applied up to flange Fire batt applied up to flange
50 50

50...400 H/B 50...400 H/B


D

D
L = 500

L = 500
50

50
260

260

Fire protection Fire protection


coating coating

39
Installation details
On the face of solid walls and ceiling slabs

Mortar-based installation and dry mortarless installation are Dry mortarless installation with installation kit WA
approved for the installation of the fire damper on the face of on the face of solid walls
solid walls and ceiling slabs.
Installation details
– Dry mortarless installation with installation kit WA on the face
The fire dampers must be installed, connected and secured
of solid walls
according to the operating and installation manual and the
– Mortar-based installation on the face of solid ceiling slabs WA installation manual.
Installation in horizontal and vertical ducts. Airflow direction For more information about installation kit WA, see page 11.
is not critical.
Requirements Mortar-based installation on the face of solid
ceilings slabs, upright
– Solid walls or fire walls (if referred to as such) made of,
for example, concrete, aerated concrete, masonry, or solid Installation details
gypsum wallboards according to EN 12859 (without hollow – 100 mm minimum distance between two fire dampers
spaces), gross density ≥ 500 kg/m³, and a minimum thickness – Perimeter concrete casting on the bare ceiling
of 100 mm
– Sufficient bonding with the concrete ceiling slab must be
– Solid ceiling slabs made of concrete or aerated concrete, guaranteed.
gross density ≥ 600 kg/m³, and a minimum thickness
– The fire dampers must be installed and attached according
of 125 mm
to the operating and installation manual.
– 400 mm minimum distance to adjacent walls and 200 mm
minimum distance above and below for the installation on the
face of solid walls

Dry mortarless installation with installation kit WA Mortar-based installation on the face of solid
on the face of solid walls ceilings slabs, upright
with duct
≥ 100
L = 500

260
L = 500
240
D
150

Installation kit WA Solid wall Ceiling slab Duct

Reinforced concrete

40
Installation details
Adjacent to solid walls and ceiling slabs

Installation of the fire damper adjacent to solid walls and Dry mortarless installation with installation kit WV
ceiling slabs is approved with mortar and without mortar adjacent to solid walls
(dry installation).
Installation details
– Dry mortarless installation with installation kit WV adjacent
The fire dampers must be installed, connected and secured
to solid walls
according to the operating and installation manual and the
– Mortar-based installation on the face of solid ceiling slabs WV installation manual.
Installation in horizontal and vertical ducts. Airflow direction For more information about installation kit WV, see page 12.
is not critical.
Requirements Mortar-based installation on the face of solid
ceilings slabs, upright
– Solid walls or fire walls (if referred to as such) made of,
for example, concrete, aerated concrete, masonry, or solid Installation details
gypsum wallboards according to EN 12859 (without hollow – 100 mm minimum distance between two fire dampers
spaces), gross density ≥ 500 kg/m³, and a minimum thickness – Perimeter concrete casting on the bare ceiling
of 100 mm
– Sufficient bonding with the concrete ceiling slab must be
– Solid ceiling slabs made of concrete or aerated concrete, guaranteed.
gross density ≥ 600 kg/m³, and a minimum thickness
– The fire dampers must be installed and attached according
of 125 mm
to the operating and installation manual.
– 400 mm minimum distance to adjacent walls and above and
below for the installation adjacent to solid walls

Dry mortarless installation with installation kit WV Mortar-based installation on the face of solid
adjacent to solid walls ceilings slabs, upright
with existing fire damper casing
≥ 100
L = 500
≤ 260

260
L = 500
≤ 500

≤ 260
150

Installation kit WV Solid wall


D

Ceiling slab Existing fire damper casing

Reinforced concrete

41
Installation details
Remote from solid walls and ceiling slabs

Mortar-based installation and dry mortarless installation in sheet Dry mortarless installation with installation kit WE
steel ducts remote from solid walls and ceiling slabs is approved remote from solid walls
if the intermediate duct has an external fire-resistant cladding
between the plane of the fire damper blade and the solid wall Installation details
and has no openings. – The fire dampers must be installed, connected and secured
– Dry mortarless installation with installation kit WE remote from according to the operating and installation manual and the
solid walls installation manual WE.
– Mortar-based installation on the face of solid ceiling slabs For more information about installation kit WE, see page 12.
Installation in horizontal and vertical ducts. Airflow direction is Mortar-based installation on the face of solid
not critical. ceilings slabs, upright
Requirements Installation details
– No openings in the insulated ducts between the fire damper
and the solid wall – 100 mm minimum distance between two fire dampers
– 400 mm minimum distance to adjacent walls and above and – Perimeter concrete casting on the bare ceiling
below for the installation remote from solid walls – Sufficient bonding with the concrete ceiling slab must be
Installation details guaranteed.
– For details of suspension systems see pages 52 and 53 – The fire dampers must be installed and attached according
to the operating and installation manual.
– Suspensions can be fixed on top of the ceiling slab using nuts
and washers made of galvanised steel
– Further components required according to the installation
manual WE are to be provided by others

Dry mortarless installation with installation kit WE Mortar-based installation on the face of solid
remote from solid walls ceilings slabs, upright
with duct
≥ 150
L = 500

260
L = 500
≤ 750
175

≤ 1500

Installation kit WE Solid wall


D

Ceiling slab Duct

Reinforced concrete

42
Installation details
Lightweight partition walls with metal support structure and cladding on both sides

Mortar-based installation and dry mortarless installation – 75 mm minimum distance to load bearing structural elements
of fire dampers in lightweight partition walls with metal support – 200 mm minimum distance between two fire dampers
structure and cladding on both sides are approved.
Installation details
– Mortar-based installation
– An installation opening with a minimum size of
– Dry mortarless installation with installation kit ES B + 80...120 mm and H + 80...120 mm is required
– Dry mortarless installation with fire batt – Completely close off the perimeter gap »s« with one of the
– Dry mortarless installation with installation kit GL100 following: mortar of group II, IIa, III or IIIa according to
for flexible ceiling joint DIN 1053; fire protection mortar of group II or III or equivalent
Installation in horizontal ducts. Airflow direction is not critical. according to EN 998-1/2 (classes M 2.5 to 10); fire protection
mortar of class M 2.5 or 10; gypsum mortar; or, if necessary,
Mortar-based installation concrete.
Requirements The mortar bed depth is the same as the wall thickness.
– Lightweight partition walls with a metal support structure – Fit trim panels (optional)
and cladding on both sides, with European classification to
EN 13501-2 or comparable national classification
– Cladding made of gypsum bonded or cement bonded panel
materials and a minimum thickness of 100 mm
– Additional layers of cladding or double stud systems are
approved

Mortar-based installation

260 W 260 W

A
L = 375 L = 375
or 500 or 500

Mortar or gypsum Mortar or gypsum


mortar mortar

Perimeter metal Perimeter metal


profile profile

Dry wall screw Dry wall screw

Optional trim
s = 40 panels s = 40
...60 ...60

Detail A Metal support structure


W
for mortar-based installation

Perimeter metal z
x

profile

Optional trim panels

Mortar or gypsum ≤ 625


mortar

x = H + 80...120 mm
z = B + 80...120 mm

43
Installation details
Lightweight partition walls with metal support structure and cladding on both sides

Dry mortarless installation with installation kit ES


Requirements
– Lightweight partition walls with a metal support structure
and cladding on both sides, with European classification to
EN 13501-2 or comparable national classification
– Cladding made of gypsum bonded or cement bonded panel
materials and a minimum thickness of 100 mm
– Additional layers of cladding or double stud systems are
approved
– Casing length L = 500 mm
– 200 mm minimum distance between two fire dampers
Installation details
– An opening with B + 95 mm and H + 95 mm is required
– Assemble the fire damper with the installation kit and push it
into the ready made lightweight partition wall. Fixing is carried
out with clamps and screws to the perimeter metal profile.
For more information about installation kit ES, see page 14.

Dry mortarless installation with installation kit ES

W
L = 500 B + 95 /
H + 95 B
260

Lightweight
partition wall

Perimeter metal
profile

Detail B Metal support structure


W
for dry mortarless installation with installation kit ES

Perimeter metal z
x

profile

Installation kit ≤ 625

x = H + 95 mm
z = B + 95 mm

44
Installation details
Lightweight partition walls with metal support structure and cladding on both sides

Dry mortarless installation with fire batt Combinations of width and height up to
B × H = 800 mm × 400 mm
Requirements
– Lightweight partition walls with a metal support structure Installation details
and cladding on both sides, with European classification to – An installation opening with B + 100...800 mm and
EN 13501-2 or comparable national classification H + 100...800 mm plus 2 × trim panel thickness is required.
– Cladding made of gypsum bonded or cement bonded panel – 400 mm maximum distance between the fire damper and wall
materials and a minimum thickness of 100 mm opening
– Casing length L = 500 mm – Completely close off the perimeter gap with two layers of fire
– 200 mm minimum distance between two fire dampers but batt (boards made of mineral wool, coated) ≥ 140 kg/m³.
dependent on the selected gap width (50...400 mm plus – Apply intumescent fire protection sealant to all trim panels and
profile width) connections
– 75 mm minimum distance to load bearing structural elements – Apply a fire protection coat, at least 2.5 mm thick, to the fire
– For suspension systems, see pages 52 and 53. damper casing perimeter on both sides of the wall or ceiling
slab. Apply the coat on the installation side up to the flange.
– The actuator and release unit must not be coated
– The fire dampers must be installed, connected and secured
according to the operating and installation manual.

Dry mortarless installation with fire batt


Combinations of width and height up to B × H = 800 mm × 400 mm W
260

L = 500

A Trim panel

Fire protection
coating, applied
up to flange

Fire batt
Fire protection coating,
applied up to flange

Fire protection
50 coating
B + 10
0
H + 1 ...800 /
00...8
00

W
Metal support structure
Detail A for dry mortarless installation with fire batt
W

Perimeter metal
profile
z
x

Trim panel

≤ 625
Fire batt x = H + 100...800 mm + 2 × trim panel thickness
z = B + 100...800 mm + 2 × trim panel thickness

45
Installation details
Lightweight partition walls with metal support structure and cladding on both sides

Combinations of width and height up to


B × H = 801 mm × 401 mm
Installation details
– Same as for combinations of width and height up to
B × H = 800 mm × 400 mm
– For wall installation, additionally provide on both sides of the
wall and on three sides of the damper a frame of mineral wool
≥ 140 kg/m³
– The fire dampers must be installed, connected and secured
according to the operating and installation manual

Dry mortarless installation with fire batt


Combinations of width and height up to B × H = 801 mm × 401 mm W
260

L = 500 Mineral wool frame,


on three sides
A Trim panel
Fire protection
coating, applied
up to flange
Mineral wool frame,
on three sides
Fire batt
50
Fire protection coating,
Mineral wool frame, applied up to flange
on three sides
50 90
Fire protection
B + 10 coating
0
H + 1 ...800 /
00...8
00

W
Metal support structure
Detail A for dry mortarless installation with fire batt
W

Perimeter metal
profile
z
x

Trim panel

≤ 625
Fire batt Mineral wool frame,
on three sides x = H + 100...800 mm + 2 × trim panel thickness
z = B + 100...800 mm + 2 × trim panel thickness

46
Installation details
Lightweight partition walls with metal support structure and cladding on both sides

Flexible ceiling joint with installation kit GL100 Installation details


Requirements – Fire damper is fixed to the ceiling slab using the supplied
installation kit
– Lightweight partition walls with a metal support structure
and cladding on both sides, with European classification to – Cladding of the lightweight partition wall can only be carried
EN 13501-2 or comparable national classification out after installation of the fire damper
– Cladding made of gypsum bonded or cement bonded panel – A three-side metal profile frame with B + 305 mm and
materials and a minimum thickness of 90 mm; different H + a + 186 mm is required
thickness upon request. – The fire dampers must be installed, connected and secured
– Additional layers of cladding or double stud systems are according to the operating and installation manual.
approved For further information on installation kit GL100, see page 15.
– Maximum subsidence of the ceiling slab »a« = 40 mm
– Casing length L = 500 mm
– 400 mm minimum distance between two fire dampers
– 205 mm minimum distance to adjacent wall

Flexible ceiling joint with installation kit GL100


Ceiling slab

260
A

Reinforcing
board

Metal profile Lightweight partition


wall
W

Detail A Metal support structure


for flexible ceiling joint GL100

Ceiling slab

Reinforcing board
x

Drywall steel profile


UW

Drywall steel profile


CW z

Installation kit ≤ 625

x = H + a + 186 mm
z = B + 305 mm

47
Installation details
Fire walls with metal support structure and cladding on both sides

Installation of the fire damper in fire walls with metal support Installation details
structure and cladding on both sides is approved with perimeter – An installation opening with a minimum size of
mortar infill (wet installation) or without mortar (dry installation). B + 80...120 mm and H + 80...120 mm is required
– Mortar-based installation – Completely close off the perimeter gap »s« with one of the
– Dry mortarless installation with installation kit ES following: mortar of group II, IIa, III or IIIa according to
Installation in horizontal ducts. Airflow direction is not critical DIN 1053; fire protection mortar of group II or III or equivalent
according to EN 998-1/2 (classes M 2.5 to 10); fire protection
Mortar-based installation mortar of class M 2.5 or 10; gypsum mortar; or, if necessary,
Requirements concrete.
The mortar bed depth is the same as the wall thickness.
– Lightweight partition walls with a metal support structure
and cladding on both sides, with European classification to – Fit trim panels (optional)
EN 13501-2 or comparable national classification
– Cladding made of gypsum bonded or cement bonded panel
materials and a minimum thickness of 115 mm
– Sheet steel inserts, additional layers of cladding, or double
stud systems are approved
– Wall height 5000 mm max.
– 75 mm minimum distance to load bearing structural elements
– 200 mm minimum distance between two fire dampers

Mortar-based installation

260 W 260 W
A A
L = 375 L = 375
or 500 or 500

Mortar or gypsum Mortar or gypsum


mortar mortar

Perimeter metal Perimeter metal


profile profile

Optional trim
s = 40 panels s = 40
...60 ...60

Detail A Metal support structure


W
for mortar-based installation

Drywall steel profile


UW

Drywall steel profile


UA z
x

Optional trim panels

Mortar or gypsum
mortar ≤ 312.5

x = H + 80...120 mm
z = B + 80...120 mm

48
Installation details
Fire walls with metal support structure and cladding on both sides

Dry mortarless installation with installation kit ES


Requirements
– Lightweight partition walls with a metal support structure
and cladding on both sides, with European classification to
EN 13501-2 or comparable national classification
– Cladding made of gypsum bonded or cement bonded panel
materials and a minimum thickness of 115 mm
– Sheet steel inserts, additional layers of cladding, or double
stud systems are approved
– Wall height 5000 mm max.
– Casing length L = 500 mm
– 200 mm minimum distance between two fire dampers
Installation details
– An opening with B + 95 mm and H + 95 mm is required
– The fire dampers must be installed, connected and secured
according to the operating and installation manual.
For more information about installation kit ES, see page 14.

Dry mortarless installation with installation kit ES

W
L = 500 B + 95 /
H + 95 B
260

Fire wall

Perimeter metal
profile

Detail B Metal support structure


W
for dry mortarless installation with installation kit ES

Drywall steel profile


UW

Drywall steel profile


UA z
x

Installation kit
≤ 312.5

x = H + 95 mm
z = B + 95 mm

49
Installation details
Lightweight partition walls with metal support structure and cladding on one side

Dry mortarless installation with installation kit ES Installation details


Installation of the fire damper in lightweight partition walls with – An opening with B + 95 mm and H + 95 mm is required
metal support structure and cladding on one side is approved – The fire dampers must be installed, connected and secured
without mortar (dry installation). according to the operating and installation manual.
Dry mortarless installation in the ready made lightweight For more information about installation kit ES, see page 14.
partition wall is performed using an installation kit ES.
Installation in horizontal ducts. Airflow direction is not critical.
Requirements
– Lightweight partition walls with a metal support structure and
cladding on one side with European classification according
to EN 13501-2 or comparable national classification
– Cladding made of gypsum bonded or cement bonded panel
materials and a minimum thickness of 90 mm
– Wall height 5000 mm max.
– Casing length L = 500 mm
– 200 mm minimum distance between two fire dampers

Dry mortarless installation with installation kit ES

W
L = 500 B + 95 /
H + 95 A
260

Lightweight
partition wall

Perimeter metal
profile
Reinforcing board
100

Detail A Metal support structure


W
for dry mortarless installation with installation kit ES

Perimeter metal z
profile
x

Installation kit ≤ 625

x = H + 95 mm
z = B + 95 mm

50
Installation details
Lightweight partition walls without metal support structure but with cladding on one side

Dry mortarless installation with installation kit ES Shaft walls made of Promaxon fire protection panels
Installation of the fire damper in lightweight partition walls Requirements
without metal support structure but with cladding on one side – Lightweight partition walls without metal support structure,
is approved without mortar (dry installation). with minimum thickness 40 mm
Dry mortarless installation in the ready made lightweight – Any wall width; wall height 5000 mm max.
partition wall is performed using an installation kit ES. – Casing length L = 500 mm
Installation in horizontal ducts. Airflow direction is not critical.
– 200 mm minimum distance between two fire dampers
Shaft walls made of plasterboard panels – 75 mm minimum distance to load bearing structural elements
Requirements Installation details
– Lightweight partition walls without metal support structure, – An opening with B + 95 mm and H + 95 mm is required
with minimum thickness 40 mm – The fire dampers must be installed, connected and secured
– Wall width 2000 mm max., wall height 5000 mm max. according to the operating and installation manual.
– Casing length L = 500 mm For further information on installation kit see page 14.
– 200 mm minimum distance between two fire dampers
– 75 mm minimum distance to load bearing structural elements

Dry mortarless installation with installation kit ES

W
L = 500 B + 95 /
H + 95 B
260

Lightweight
partition wall

Perimeter metal
profile
Reinforcing board
100

Detail B Metal support structure


W
for dry mortarless installation with installation kit ES

Perimeter metal z
x

profile

Installation kit

x = H + 95 mm
z = B + 95 mm

51
Installation details
Suspension systems

Suspension systems are required for the dry mortarless Thread M8 M10 M12 M14 M16 M20
installation of the fire damper with fire batt in solid walls and
ceiling slabs, for dry mortarless installation in lightweight Fmax (N) per threaded rod 219 348 505 690 942 1470
partition walls with cladding on both sides, and for dry
mortarless installation remote from solid walls. Max. loading capacity (kg)
22* 35* 52* 70* 96* 150*
Fire dampers can be suspended from solid ceiling slabs using per threaded rod
adequately sized threaded rods. Load the suspension system * Weight of the fire damper, see page 9
only with the weight of the fire damper. Ducts must be
suspended separately.
Suspension systems longer than 1.5 m require fire-resistant
insulation.
Only metal anchors with certified fire protection qualification and
suitable for the wall or ceiling must be used. Instead of anchors,
threaded rods can be used (push through installation).
Additional details regarding the suspension systems can be
found in the operating and installation manual.
 Threaded rod, galvanised steel
 Washer, galvanised steel
 Nut, galvanised steel
 L-shaped bracket according to EN 10056-1,
L ≥ 40 mm × 40 mm × 5 mm, galvanised steel, coated or equivalent

Suspension system for dry mortarless installation


with fire batt
Horizontal duct
Ceiling slab


A 

Flexible connector Flexible connector

B/H

Detail A – L-shaped bracket




52
Installation details
Suspension systems

 Mounting rail
Würth Varifax 36 × 36 × 2.5, Müpro MPC 38/40 or equivalent
 Bracket
Varifax, Müpro MPC or equivalent
 Screw M10 × 70
 Threaded rod, galvanised steel
 Washer, galvanised steel
 Nut, galvanised steel
 Underlay material, non-combustible
 Bracket
Varifax ANSHWNKL-PRFL36-90GRAD, Müpro mounting bracket 90°
galvanised, or equivalent

Suspension system for dry mortarless installation Suspension system for dry mortarless installation
with fire batt with fire batt
vertical duct – ceiling slab installation, upright vertical duct – ceiling slab installation, suspended
H/B

H/B

Flexible
A connector Flexible
connector
Ceiling slab Ceiling slab

B
B Flexible Flexible
connector connector

Detail A Detail B

 
 
 
 






53
Order Details

Specification text * Differential pressure range 20 to 2000 Pa.


Square or rectangular fire dampers in many dimension Closed blade air leakage according to EN 1751, class 2;
combinations for the isolation of duct penetrations between Casing air leakage to EN 1751, class C;
fire compartments. (B + H) ≤ 700, class B.
Ready-for-operation unit includes a fire-resistant damper Fire damper variant with: spring return actuator with
blade and a release mechanism. thermoelectric release mechanism. Two limit switches
Application-dependent integrated into actuator for indicating damper blade positions
EI 90 (ve, ho i ↔ o) S or EI 120 (ve, ho i ↔ o) S. OPEN and CLOSED.
Tested for fire resistance properties to EN 1366-2. Materials:
With declaration of performance Casing made of galvanised sheet steel, damper blade
DoP / FK-EU / DE / 2013 / 001 and CE marking. made of special insulating material, damper blade shaft and
For mortar-based installation and dry mortarless installation driving linkage made of stainless steel, plain bearings made
into solid walls and ceiling slabs, lightweight partition walls of brass, seals made of polyurethane and elastomer.
with cladding on both sides, lightweight fire walls, and shaft * Text for an FK-EU with fusible link.
walls; for mortar-based installation, upright, in solid ceiling For texts applying to different construction variants, attachments and
accessories, please refer to the design programme on our website.
slabs; for dry mortarless installation on the face of, adjacent
to and remote from solid walls. Also for dry mortarless
installation with fire batt in solid walls, solid ceiling slabs and
lightweight partition walls with cladding on both sides.
Special features:
– Complies with the requirements of EN 15650
– Tested for fire resistance properties according
to EN 1366-2
– Classified according to EN 13501-3
– Low differential pressure and sound power level
– Integration into the central BMS with TROXNETCOM

Order code

FK-EU - 1 / DE / 600 × 400 × 500 / ES / SS / Z43

      

 Type  Country of destination 1 Not for fire batt installation

 Construction DE Germany 2 W can be combined with all construction variants


Other destination countries listed under , but not with attachments 
No entry: standard construction ZEX1 – ZEX2 and Z43RM – Z45RM
1 Powder-coated casing upon request
3 GL100 for wall thickness 100 mm when 50 mm
21 Stainless steel casing  Nominal size [mm]
profiles are used.
7 Coated damper blade B×H×L Other wall thicknesses and profile widths upon
1-7 Powder-coated casing  Accessories 1 request.
and coated damper blade
No entry: none
2-71 Stainless steel casing
VP – GL1003
and coated damper blade
Subject to change · All rights reserved © TROX GmbH (9/2013)

W2 With fusible link 95 °C  Accessories 2


(only for use in warm air No entry: none
ventilation systems) R0 – 0A
 Attachments
Z00 – ZEX2

Order example for FK-EU with fusible link Order example: FK-EU, powder-coated,
with cover grille on the operating side and spring
return actuator 230 V AC

Make: TROX Make: TROX


Type: FK-EU / DE / 600 × 400 × 500 / Z00 Type: FK-EU - 1 / DE / 1000 × 700 × 500 / A0 / Z43

54