The document outlines the electrical specifications for an integrated meter designed for testing, verification, and power quality analysis. It includes detailed information on accuracy, measurement ranges, resolutions, and test currents for various parameters such as insulation resistance, RCDs tripping time, and earth resistance. Additionally, it provides specifications for voltage, current, power factor, and leakage current measurements across single and three-phase systems.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views7 pages

PDF GSC53N EN1-00

The document outlines the electrical specifications for an integrated meter designed for testing, verification, and power quality analysis. It includes detailed information on accuracy, measurement ranges, resolutions, and test currents for various parameters such as insulation resistance, RCDs tripping time, and earth resistance. Additionally, it provides specifications for voltage, current, power factor, and leakage current measurements across single and three-phase systems.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

GSC53N Rel. 1.

00 del 27/07/04

Integrated meter for test verify and Power Quality analysis Pag 1 of 7

1. ELECTRICAL SPECIFICATIONS – VERIFY TESTS


Accuracy is indicated as ± (% readings + no. of digits) at 23°C ± 5°C, con relative humidity <60%UR.

Continuity test on protective and equalizing conductors


Range (Ω) Resolution (Ω) Accuracy (*)
0.01 ÷ 9.99 0.01
±(2.0%rdg + 2dgt)
10.0 ÷ 99.9 0.1
(*) after cable calibration (which eliminates the cable resistance).
Test current: > 200mA DC for R≤5Ω (included calibration)
Resolution on current measurement: 1mA
Open-circuit voltage: 4V ≤ V0 ≤ 24V

Insulation Resistance (DC voltage)


Test voltage(V) Range (MΩ) Resolution (MΩ) Accuracy
0.01 ÷ 9.99 0.01
±(2.0%rdg + 2dgt)
50 10.0 ÷ 49.9 0.1
50.0 ÷ 99.9 0.1 ±(5.0%rdg + 2dgt)
0.01 ÷ 9.99 0.01
±(2.0%rdg + 2dgt)
100 10.0 ÷ 99.9 0.1
100.0 ÷ 199.9 0.1 ±(5.0%rdg + 2dgt)
0.01 ÷ 9.99 0.01
10.0 ÷ 199.9 0.1 ±(2.0%rdg + 2dgt)
250
200 ÷ 249 1
250 ÷ 499 1 ±(5.0%rdg + 2dgt)
0.01 ÷ 9.99 0.01
10.0 ÷ 199.9 0.1 ±(2.0%rdg + 2dgt)
500
200 ÷ 499 1
500 ÷ 999 1 ±(5.0%rdg + 2dgt)
0.01 ÷ 9.99 0.01
10.0 ÷ 199.9 0.1 ±(2.0%rdg + 2dgt)
1000
200 ÷ 999 1
1000 ÷ 1999 1 ±(5.0%rdg + 2dgt)
Open-circuit voltage: <1.3 x nominal test voltage
Short circuit current: <6.0mA at 500V test voltage
ominal test current: >2.2mA on 230kΩ load (500V); >1mA su 1kΩ per Vnom (others)
Measurement limits fitted: 0.05, 0.10, 0.23, 0.25, 0.50, 1.00, 100MΩ

RCDs Tripping time


Range (ms) Resolution (ms) Accuracy
½ I∆N, I∆N 1÷999
2 I∆N 1÷200 general
1÷250 selective 1 ±(2.0%rdg + 2dgt)
5 I∆N RCD 1÷ 50 general
1÷160 selective
Nominal trip-out currents: 10mA, 30mA, 100mA, 300mA, 500mA
RCDs type: AC, A, General and Selective
Phase-PE voltage: 100V ÷ 255V
Frequency: 50Hz ± 0.5Hz

HT ITALIA srl Tel: +39-0546-621002 - Fax: +39-0546-621144


Via Righi 126 - 48018 Faenza (RA)- Italy email: [email protected] - web: http://www.htitalia.com
GSC53N Rel. 1.00 del 27/07/04

Integrated meter for test verify and Power Quality analysis Pag 2 of 7

Tripping current of RCDs


RCD type I∆N Range I∆N (mA) Resolution (mA) Accuracy I∆N
AC (0.5 ÷ 1.4) I∆N
I∆N ≤ 10mA 0.1 I∆N -0%, +(5.0% I∆N)
A (0.5 ÷ 2.4) I∆N
AC (0.5 ÷ 1.4) I∆N
I∆N > 10mA 0.1 I∆N -0%, +(5.0% I∆N)
A (0.5 ÷ 2.0) I∆N

Contact voltage Ut
Range (V) Resolution (V) Accuracy
0 ÷ 2Utlim 0.1 -0%, +(5.0% rdg + 3dgt)
Utlim (Ul): 25V , 50V

Line Impedance (Phase-Phase, Phase-Neutral)


Range (Ω) Resolution (Ω) Accuracy (*)
0.01 ÷ 9.99 0.01
±(5.0% rdg + 3dgt)
10.0 ÷ 199.9 0.1
(*) 0.1 mΩ on range 0.0 ÷ 199.9 mΩ (with IMP57 optional accessory)
Maximum peak current: 3.65A (at 127V); 6.64A (at 230V); 11.5A (at 400V)
Test voltage: 100÷265V (Phase-Neutral) / 100÷460V (Phase-Phase); 50Hz ± 0.5Hz

Fault Loop Impedance (Phase-Ground)


Range (Ω) Resolution (Ω) Accuracy (*)
0.01 ÷ 19.99 0.01
20.0 ÷ 199.9 0.1 ±(5.0% rdg + 3dgt)
200 ÷ 1999 1
(*) 0.1 mΩ on range 0.0 ÷ 199.9 mΩ (with IMP57 optional accessory)
Maximum peak current: 3.65A (at 127V); 6.64A (at 230V)
Test voltage: 100÷265V (Phase-Ground); 50Hz ± 0.5Hz

Fault Loop Resistance RA without RCDs tripping


Range (Ω) Resolution (Ω) Accuracy
1 ÷ 1999 1 -0%, +(5.0% rdg + 3dgt)
Test current: 0.5 I∆N set on Ut test
15mA on Ra15mA test

Earth Resistance with rods


Range (Ω) Resolution (Ω) Accuracy (*)
0.01 ÷ 19.99 0.01
20.0 ÷ 199.9 0.1 ±(5.0% rdg + 3dgt)
200 ÷ 1999 1
Test current: <10mA – 77.5Hz
Open-circuit voltage: < 20V rms

Earth resistivity
Range ρ (*) Resolution Accuracy (*)
0.06 ÷ 19.99 Ωm 0.01 Ωm
20.0 ÷ 199.9 Ωm 0.1 Ωm
200 ÷ 1999 Ωm 1 Ωm ±(5.0% rdg + 3dgt)
2.00 ÷ 99.99 kΩm 0.01 kΩm
100.0 ÷ 125.5 kΩm 0.1 kΩm
(*) with distance d=10m
Distance range d: 1 ÷ 10m
Test current: <10mA – 77.5Hz
Open-circuit voltage: < 20V rms

HT ITALIA srl Tel: +39-0546-621002 - Fax: +39-0546-621144


Via Righi 126 - 48018 Faenza (RA)- Italy email: [email protected] - web: http://www.htitalia.com
GSC53N Rel. 1.00 del 27/07/04

Integrated meter for test verify and Power Quality analysis Pag 3 of 7

Voltage (RCD, LOOP, Phase Sequence)


Range (V) Resolution (V) Accuracy
15 ÷ 460 1 ±(3.0% rdg + 2dgt)

Frequency
Range (Hz) Resolution (Hz) Accuracy
47.0 ÷ 63.6 0.1 ±(0.1% rdg + 1dgt)

HT ITALIA srl Tel: +39-0546-621002 - Fax: +39-0546-621144


Via Righi 126 - 48018 Faenza (RA)- Italy email: [email protected] - web: http://www.htitalia.com
GSC53N Rel. 1.00 del 27/07/04

Integrated meter for test verify and Power Quality analysis Pag 4 of 7

2. ELECTRICAL SPECIFICATIONS – ANALYZER AND AUX


Accuracy is indicated as ± (% readings + no. of digits) at 23°C ± 5°C, con relative humidity <60%UR.

Voltage – Single phase / Three phase systems (Autorange)


Range (V) Resolution (V) Accuracy Input Impedance
15 ÷ 310 0.2 300 kΩ (Phase-Neutral)
±(0.5% rdg + 2dgt)
310 ÷ 600 0.4 300 kΩ (Phase-Phase)

Voltage Anomalies – Single / Three phase systems (Manual range)


Resolution Resolution Accuracy Accuracy
Range (V)
Voltage (V) Time Voltage Time (ref. 50Hz)
15 ÷ 310 0.2
10ms ±(1.0%rdg + 2dgt) ±10ms
30 ÷ 600 0.4
Input Impedance: 300 kΩ (Phase-Neutral and Phase-Phase)

Current by external clamp transducer – STD


Overload
Range (*) Resolution (mV) Accuracy Input Impedance
protection
0.005 ÷ 0.26V 0.1
±(0.5%rdg + 2dgt) 200kΩ 5V
0.26 ÷ 1V 0.4
(*) Example: by using a clamp whose range is 1000A/1V, the instrument measures currents higher than 5A

Current by external clamp transducer – FlexINT (1000A AC range)


Range (A) Voltage input Resolution Accuracy
10.0 ÷ 19.9 950.0µV ÷ 1.691mV ±(4.0% rdg + 8.5µV)
20.0 ÷ 99.9 1.7mV ÷ 8.491mV 8.5µV ±(1.0% rdg + 8.5µV)
100.0 ÷ 999.9 8.5mV ÷ 84.99mV ±(1.0% rdg + 85µV)
1A = 85µV ; Rinput = 400kΩ

Current by external clamp transducer – FlexINT (3000A AC range)


Range (A) Voltage input Resolution Accuracy
30.0 ÷ 999.9 2.55mV ÷ 84.99mV 8.5µV ±(1.0% rdg +17µV)
1000 ÷ 3000 85.0mV ÷ 255mV 85µV ±(0.5% rdg +85µV)
1A = 85µV ; Rinput = 400kΩ

Power factor (Cosϕ) - Single / Three phase systems


Range (cosϕ) Resolution Accuracy (°)
0.20 ÷ 0.50 1.0
0.50 ÷ 0.80 0.01 0.7
0.80 ÷ 1.00 0.6

Leakage curreny (by optional clamp transducer)


Overload
Range (mA)* Resolution (mA) Accuracy Input Impedance
protection
0.5 ÷ 999.9 0.1 ±(5.0% rdg + 2dgt) 200kΩ 5V
(*) While recording the instrument stores only current values > 5mA with 1mA resolution
Maximum stored value is the peak value calculated with response time of 1ms

HT ITALIA srl Tel: +39-0546-621002 - Fax: +39-0546-621144


Via Righi 126 - 48018 Faenza (RA)- Italy email: [email protected] - web: http://www.htitalia.com
GSC53N Rel. 1.00 del 27/07/04

Integrated meter for test verify and Power Quality analysis Pag 5 of 7

Power – Single / Three phase systems


Measures type Range Resolution Accuracy
100.0 ÷ 999.9W 0.1W
1.000 ÷ 9.999kW 0.001kW
10.00 ÷ 99.99kW 0.01kW
ACTIVE
100.0 ÷ 999.9kW 0.1kW
POWER 1.000 ÷ 9.999MW 0.001MW
10.00 ÷ 99.99MW 0.01MW
100.0 ÷ 999.9MW 0.1MW
100.0 ÷ 999.9VAR 0.1VAR
1.000 ÷ 9.999kVAR 0.001kVAR
10.00 ÷ 99.99kVAR 0.01kVAR
REACTIVE
100.0 ÷ 999.9kVAR 0.1kVAR
POWER 1.000 ÷ 9.999MVAR 0.001MVAR
10.00 ÷ 99.99MVAR 0.01MVAR
100.0 ÷ 999.9MVAR 0.1MVAR
100.0 ÷ 999.9VA 0.1VA
1.000 ÷ 9.999kVA 0.001kVA
10.00 ÷ 99.99kVA 0.01kVA
APPARENT
100.0 ÷ 999.9kVA 0.1kVA ±(1.0% rdg + 2dgt)
POWER 1.000 ÷ 9.999MVA 0.001MVA
10.00 ÷ 99.99MVA 0.01MVA
100.0 ÷ 999.9MVA 0.1MVA
100.0 ÷ 999.9Wh 0.1Wh
1.000 ÷ 9.999kWh 0.001kWh
ACTIVE 10.00 ÷ 99.99kWh 0.01kWh
ENERGY 100.0 ÷ 999.9kWh 0.1kWh
(Class 2 EN61036) 1.000 ÷ 9.999MWh 0.001MWh
10.00 ÷ 99.99MWh 0.01MWh
100.0 ÷ 999.9MWh 0.1MWh
100.0 ÷ 999.9VARh 0.1VARh
1.000 ÷ 9.999kVARh 0.001kVARh
REACTIVE 10.00 ÷ 99.99kVARh 0.01kVARh
ENERGY 100.0 ÷ 999.9kVARh 0.1kVARh
(Class 3 IEC1268) 1.000 ÷ 9.999MVARh 0.001MVARh
10.00 ÷ 99.99MVARh 0.01MVARh
100.0 ÷ 999.9MVARh 0.1MVARh

Harmonics - Single / Three phase systems


Range Maximum resolution Base accuracy
DC ÷ 25a ±(5.0% rdg + 2dgt)
26a ÷ 33a 0.1V / 0.1 A ±(10% rdg + 2dgt)
34a ÷ 49a ±(15% rdg + 2dgt)

Environmental parameters (AUX function)


Range Resolution Accuracy
-20°C ÷ 80°C 0.1 °C
0 ÷ 100% UR 0.1% UR
0.001Lux ÷ 20.00 Lux (*) 0.001 ÷ 0.02 Lux ±(2.0% rdg + 2 dgt)
0.1 Lux ÷ 2000 Lux (*) 0.1 ÷ 2 Lux
1 Lux ÷ 20 kLux (*) 1 ÷ 20 Lux
(*) Accuracy of HT53 luxmeter probe is according to Class AA

HT ITALIA srl Tel: +39-0546-621002 - Fax: +39-0546-621144


Via Righi 126 - 48018 Faenza (RA)- Italy email: [email protected] - web: http://www.htitalia.com
GSC53N Rel. 1.00 del 27/07/04

Integrated meter for test verify and Power Quality analysis Pag 6 of 7

3. GENERAL SPECIFICATIONS
SINGLE/THREE PHASE RECORDING:
STORED PARAMETERS:
- Phase and delta voltages
- Phase currents, neutral current
- Phase and total three phase Active, Reactive, Apparent power
- Active energy (Class 2 EN61036), Reactive energy (Class 3 IEC1268)
- Phase and total three phase Power factor Cosϕ
- Voltages, currents harmonics (DC,1,2,…49)
- Voltage anomalies (sags, swells, breaks)
- Predefined recordings (EN50160, Voltage anomalies, Harmonics, Start up, Power & Energy)
- Max selectable parameters: 63 or 3 AUX (Environmental and/or leakage)
- Integrated period: 5 ÷ 3600 sec.
- Recording autonomy: > 30 days with integrated period of 15 minutes
- Memory capacity: 2Mbyte

DISPLAY AND MEMORY:


Features: Dot matrix with backlight
Resolution: 128x128 dots
Visible area: 73x73 mm
Memory: 999 measures

POWER SUPPLY:
Batteries: 6 batteries 1.5V type LR6-AA-AM3-MN 1500
External power supply adapter: Code A0050 (AUX e ANALYZER functions only)

MECHANICAL FEATURES:
Dimensions: 225 (W)x165(L)x105(D) mm
Weight (included batteries): about 1.7kg

WORKING ENVIRONMENTAL CONDITIONS:


Reference temperature: 23°C ± 5°C
Working temperature: 0° ÷ 40°C
Allowed relative humidity: < 80% HR
Storage temperature: -10 ÷ 60°C
Storage humidity: < 80% HR

TEST VERIFIES REFERENCE STANDARDS:


Continuity test: IEC 61557
Insulation resistance: IEC 61557
Earth resistance: IEC 61557
Fault Loop Impedance: IEC 61557
RCDs test: IEC 61557
Insulation test on switchboards: EN60439-1

POWER/ENERGY MEASUREMENTS REFERENCE STANDARDS:


Features of voltage supplied by public utilities: EN50160
Active energy static counters for AC current EN61036 (Class 2)
Reactive energy static counters for AC current IEC1268 (Class 3)

NOISE MEASUREMENTS REFERENCE STANDARDS:


Sound measurements (with HT55 probe): EN60651:1994/A1 type 1
EN60804:1994/A2 type 1

HT ITALIA srl Tel: +39-0546-621002 - Fax: +39-0546-621144


Via Righi 126 - 48018 Faenza (RA)- Italy email: [email protected] - web: http://www.htitalia.com
GSC53N Rel. 1.00 del 27/07/04

Integrated meter for test verify and Power Quality analysis Pag 7 of 7

GENERAL REFERENCE STANDARDS:


Safety of measuring instruments: EN61010-1 + A2(1997)
Product type standard: IEC61557-1, 2, 3, 4, 5, 6
Insulation: class 2 (double insulation)
Pollution degree: 2
Overvoltage category: CAT II 600V CA / 350V CA (to ground)
CAT III 600V CA / 300V CA (to ground)
Use: internal use; max altitude: 2000m
EMC: EN61326-1 (1998) + A1 (1999)

This instrument complies with the European Directive for CE marking.

HT ITALIA srl Tel: +39-0546-621002 - Fax: +39-0546-621144


Via Righi 126 - 48018 Faenza (RA)- Italy email: [email protected] - web: http://www.htitalia.com