800/1600/1800 MODBUS Memory Locations
Software Version V3.20
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
0 P.V. Process variable R Lo_S Hi_S dP_S - S.p.
1 _SP_ Active setpoint R/W Lo_L Hi_L dP_S - S.p.
(*1)
2 - Control output R/W -100.0 100.0 1 %
(*2)
4 - Deviation ( S.P. - P.V. ) R dP_S -
5 h_Pb Heating proportional band R/W 0.0 999.9 1 10.0 %
(*3)
6 c_Pb Cooling proportional band R/W 0.0 999.9 1 10.0 %
(*3)
7 h_It Heating integral time R/W 0.00 99.99 2 4.00 min
(*3)
8 h_dt Heating derivative time R/W 0.00 99.99 2 1.00 min
(*3)
9 _Ct.1 Cycle time if Out1 = logic or relay R/W 0 200 - 10 sec
10 Lo_S MAIN input scale minimum limit R/W -1999 9999 dP_S 0 S.p.
11 Hi_S MAIN input scale maximum limit R/W -1999 9999 dP_S 1000 S.p.
12 - Alarm point 1 R/W Lo_L Hi_L dP_S 500 S.p.
( if relative ) -999 999
13 - Alarm point 2 R/W Lo_L Hi_L dP_S 600 S.p.
( if relative ) -999 999
14 - Alarm point 3 R/W Lo_L Hi_L dP_S 700 S.p.
( if relative ) -999 999
16 - Local setpoint R/W Lo_L Hi_L dP_S 400 S.p.
18 SP.tY Remote setpoint selection R/W 0 7 - 0 -
20 Lo_L Lower limit for local setpoint and R/W Lo_S Hi_S dP_S 0 S.p.
absolute alarms
21 Hi_L Upper limit for local setpoint and R/W Lo_S Hi_S dP_S 1000 S.p.
absolute alarms
22 Gr.SP Set gradient R/W 0.0 999.9 1 0.0 digit/min
23 oFSt MAIN input offset correction R/W -999 999 dP_S 0 S.p.
24 FiLt MAIN input digital filter R/W 0.0 20.0 1 0.1 sec
25 Lo_L AL1 low limit R/W Lo_S Hi_S dP_S 0 S.p.
26 Hi_L AL1 high limit R/W Lo_S Hi_S dP_S 1000 S.p.
27 HYS.1 Hysteresis alarm 1 R/W -999 999 dP_S -1 S.p.
28 Lo_L AL2 low limit R/W Lo_S Hi_S dP_S 0 S.p.
29 Hi_L AL2 high limit R/W Lo_S Hi_S dP_S 1000 S.p.
30 HYS.2 Hysteresis alarm 2 R/W -999 999 dP_S -1 S.p.
31 S.tun Enabling self-tuning, auto-tuning R/W 0 13 - 0
and soft-start code
39 c.SP.o Cooling setpoint R/W -25.0 25.0 1 0.0 %
42 h.P.Hi Heating maximum power limit R/W 0.0 100.0 1 100.0 %
(*3)
43 c.P.Hi Cooling maximum power limit R/W 0.0 100.0 1 100.0 %
(*3)
44 LbA.t Waiting time for L.B.A. intervention R/W 0.0 500.0 1 30.0 min
time
45 bAud Baud rate R/W 0 4 - 0 -
46 CodE Serial comm. identification code R/W 0 247 - 1 -
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
47 _PAr Parity selection R/W 0 2 - 0 -
-
49 Prot Software protection code R/W 0 127 - 1
52 _AL.3 Alarm point 3 R/W Lo_S Hi_S dP_S 700 S.p.
( if relative ) -999 999
53 HYS.3 Hysteresis alarm 3 R/W -999 999 dP_S -1 S.p.
54 AL.3.t Alarm 3 type R/W 0 31 - 0
55 AL.Hb HB alarm R/W Lo.S2 Hi.S2 1 10.0 S.p.
56 Hb_t Waiting time for HB alarm R/W 0 999 - 30 sec
intervention
57 Hb_F HB alarm function R/W 0 30 - 0
-
76 c_It Cooling integral time R/W 0.00 99.99 2 4.00 min
(*3)
77 c_dt Cooling derivative time R/W 0.00 99.99 2 1.00 min
(*3)
78 _rSt Manual reset R/W -999 999 dP_S 0 S.p.
79 A.rSt Antireset R/W 0 9999 dP_S 0 S.p.
80 _FFd Feedforward R/W -100.0 100.0 1 0.0 %
85 Er.nr P.V. self-diagnostic error code R 0 4 -
86 St.00 Custom scale point 0 R/W Lo_S Hi_S dP_S 0 S.p.
87 St.01 Custom scale point 1 R/W Lo_S Hi_S dP_S 31 S.p.
88 St.02 Custom scale point 2 R/W Lo_S Hi_S dP_S 62 S.p.
89 St.03 Custom scale point 3 R/W Lo_S Hi_S dP_S 94 S.p.
90 St.04 Custom scale point 4 R/W Lo_S Hi_S dP_S 125 S.p.
91 St.05 Custom scale point 5 R/W Lo_S Hi_S dP_S 156 S.p.
92 St.06 Custom scale point 6 R/W Lo_S Hi_S dP_S 188 S.p.
93 St.07 Custom scale point 7 R/W Lo_S Hi_S dP_S 219 S.p.
94 St.08 Custom scale point 8 R/W Lo_S Hi_S dP_S 250 S.p.
95 St.09 Custom scale point 9 R/W Lo_S Hi_S dP_S 281 S.p.
96 St.10 Custom scale point 10 R/W Lo_S Hi_S dP_S 313 S.p.
97 St.11 Custom scale point 11 R/W Lo_S Hi_S dP_S 344 S.p.
98 St.12 Custom scale point 12 R/W Lo_S Hi_S dP_S 375 S.p.
99 St.13 Custom scale point 13 R/W Lo_S Hi_S dP_S 406 S.p.
100 St.14 Custom scale point 14 R/W Lo_S Hi_S dP_S 438 S.p.
101 St.15 Custom scale point 15 R/W Lo_S Hi_S dP_S 469 S.p.
102 St.16 Custom scale point 16 R/W Lo_S Hi_S dP_S 500 S.p.
103 St.17 Custom scale point 17 R/W Lo_S Hi_S dP_S 531 S.p.
104 St.18 Custom scale point 18 R/W Lo_S Hi_S dP_S 563 S.p.
105 St.19 Custom scale point 19 R/W Lo_S Hi_S dP_S 594 S.p.
106 St.20 Custom scale point 20 R/W Lo_S Hi_S dP_S 625 S.p.
107 St.21 Custom scale point 21 R/W Lo_S Hi_S dP_S 656 S.p.
108 St.22 Custom scale point 22 R/W Lo_S Hi_S dP_S 688 S.p.
109 St.23 Custom scale point 23 R/W Lo_S Hi_S dP_S 719 S.p.
110 St.24 Custom scale point 24 R/W Lo_S Hi_S dP_S 750 S.p.
111 St.25 Custom scale point 25 R/W Lo_S Hi_S dP_S 781 S.p.
112 St.26 Custom scale point 26 R/W Lo_S Hi_S dP_S 813 S.p.
113 St.27 Custom scale point 27 R/W Lo_S Hi_S dP_S 844 S.p.
114 St.28 Custom scale point 28 R/W Lo_S Hi_S dP_S 875 S.p.
115 St.29 Custom scale point 29 R/W Lo_S Hi_S dP_S 906 S.p.
116 St.30 Custom scale point 30 R/W Lo_S Hi_S dP_S 938 S.p.
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
117 St.31 Custom scale point 31 R/W Lo_S Hi_S dP_S 969 S.p.
118 St.32 Custom scale point 32 R/W Lo_S Hi_S dP_S 1000 S.p.
119 LbA.P Power limit for L.B.A. alarm R/W -100.0 100.0 1 25.0 %
condition
120 Manufact trade mark ( Gefran ) R - - - 5000 -
121 Device ID ( 800 ) R - - - 800 -
122 UPdt Software Version R - - - -
124 SP.Pr Programmer function R/W 1 255 - 5 -
125 -At- Actuator travel time R/W 0.0 2000 - 60 sec
126 t_Lo Impulse minimum time/actuator R/W 0.0 25.0 1 2.0 % At
travel time
127 -db- Valve dead zone R/W 0.0 25.0 1 0 % FS
-
132 - Control output R/W -100.0 100.0 1 - %
(*2)
133 butt M/A key function R/W 0 27 - 1 -
-
136 SP.tY Remote setpoint selection R/W 0 3 - 0 -
137 - Active setpoint R S.p.
138 - Local setpoint R/W Lo_L Hi_L dP_S 400 S.p.
139 - Auxiliary input R Lo.S2 Hi.S2 dP_S - S.p.
( remote setpoint )
140 d.i.F.1 Digital input 1 ( IN1 ) function R/W 0 50 - 0 -
141 d.i.F.2 Digital input 2 ( IN2 ) function R/W 0 50 - 0 -
142 Lo_L Lower limit for local setpoint and R/W Lo_S Hi_S dP_S 0 S.p.
absolute alarms
143 Hi_L Upper limit for local setpoint and R/W Lo_S Hi_S dP_S 1000 S.p.
absolute alarms
-
146 h.P.Hi Heating maximum power limit R/W 0.0 100.0 1 100.0 %
(*3)
147 SoFt Soft-Start time R/W 0.0 500.0 1 0.0 min
148 h_Pb Heating proportional band R/W 0.0 999.9 1 10.0 %
(*3)
149 h_b Heating hysteresis ( ON/OFF ) R/W 0.0 999.9 1 10.0 %
(*3)
150 h_It Heating integral time R/W 0.00 99.99 2 4.00 min
(*3)
151 h_dt Heating derivative time R/W 0.00 99.99 2 1.00 min
152 _Ct.1 Cycle time if Out1 = logic or relay R/W 0 200 10 sec
159 _Ct.2 Cycle time if Out2 = logic or relay R/W 0 200 - 10 sec
160 rL.o.1 Out1 R/W 0 65 - 0 -
Allocation of reference signal
163 rL.o.2 Out2 R/W 0 61 - 1 -
Allocation of reference signal
166 rL.o.3 Out3 R/W 0 61 - 2 -
Allocation of reference signal
169 _Ct.3 Cycle time if Out3 = logic or relay R/W 0 200 - 10 sec
170 rL.o.4 Out4 R/W 0 61 - 3 -
Allocation of reference signal
173 _Ct.4 Cycle time if Out4 = logic or relay R/W 0 200 - 10 sec
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
177 - Alarm point 1 R/W Lo_L Hi_L dP_S 500 S.p.
( if relative ) -999 999
178 - Alarm point 2 R/W Lo_L Hi_L dP_S 600 S.p.
( if relative ) -999 999
179 FiLd Digital filter on display process R/W 0.0 9.9 1 0.5 S.p.
variable
180 CtrL Control type R/W 0 78 - 8 -
-
187 HYS.1 Hysteresis alarm 1 R/W -999 999 dP_S -1 S.p.
188 HYS.2 Hysteresis alarm 2 R/W -999 999 dP_S -1 S.p.
189 HYS.3 Hysteresis alarm 3 R/W -999 999 dP_S -1 S.p.
-
191 hrd.1 Hardware configuration 1: R/W 0 95 - -
Auxiliary inputs
Logic inputs
Serial interface
192 hrd.2 Hardware configuration 2: R/W 0 127 - -
Out1,..., Out4 outputs
W1, W2 analogue outputs
193 SEnS Probe type for MAIN input selection R/W 0 15 - -
194 SnS.2 Probe type for auxiliary input R/W 0 7 - -
selection
195 AL.nr Select number of enabled alarms R/W 0 31 - -
196 diSP Defining SV display function R/W 0 3 - -
197 LEd.1 LED 1 function ( MAN ) R/W 0 31 - -
198 LEd.2 LED 2 function ( AUX ) R/W 0 31 - -
199 LEd.3 LED 3 function ( REM ) R/W 0 31 - -
200 HEAd Set number of parameters in R/W 0 14 - 0 -
custom menù
201 PA.01 Identification code for parameter 1 R/W 0 241 - 15 -
202 PA.02 Identification code for parameter 2 R/W 0 241 - 16 -
203 PA.03 Identification code for parameter 3 R/W 0 241 - 17 -
204 PA.04 Identification code for parameter 4 R/W 0 241 - 18 -
205 PA.05 Identification code for parameter 5 R/W 0 241 - 19 -
206 PA.06 Identification code for parameter 6 R/W 0 241 - 20 -
207 PA.07 Identification code for parameter 7 R/W 0 241 - 21 -
208 PA.08 Identification code for parameter 8 R/W 0 241 - 22 -
209 PA.09 Identification code for parameter 9 R/W 0 241 - 23 -
210 PA.10 Identification code for parameter 10 R/W 0 241 - 24 -
211 PA.11 Identification code for parameter 11 R/W 0 241 - 25 -
212 PA.12 Identification code for parameter 12 R/W 0 241 - 26 -
213 PA.13 Identification code for parameter 13 R/W 0 241 - 27 -
214 PA.14 Identification code for parameter 14 R/W 0 241 - 28 -
215 AL.1.r Reference signal for alarm 1 R/W 0 5 - 0 -
216 AL.2.r Reference signal for alarm 2 R/W 0 5 - 0 -
217 AL.3.r Reference signal for alarm 3 R/W 0 5 - 0 -
218 tYP.2 Auxiliary analogue input function R/W 0 13 - -
219 FLt.2 Digital filter on auxiliary input R/W 0.0 20.0 1 0.1 sec
220 oF.S2 Auxiliary input offset correction R/W -999 999 dP_S S.p.
221 L.An.1 W1 analogue signal output 1 R/W -1999 9999 dP_S S.p.
minimum limit
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
222 H.An.1 W1 analogue signal output 1 R/W -1999 9999 dP_S S.p.
maximum limit
223 An.o.1 W1 assignment of signal or R/W 0 63 - -
reference value
224 L.An.2 W2 analogue signal output 2 R/W -1999 9999 dP_S S.p.
minimum limit
225 H.An.2 W2 analogue signal output 2 R/W -1999 9999 dP_S S.p.
maximum limit
226 An.o.2 W2 assignment of signal or R/W 0 63 - -
reference value
227 InP.2 Amperometric input value or remote R Lo.S2 Hi.S2 dP_S S.p.
setpoint
228 FAC.P Power in fault action R/W -100.0 100.0 1 0.0 %
229 _rEL. Fault action ( sets state in case of R/W 0 7 - 0 -
probe fault )
230 _SP.1 Setpoint 1 R/W Lo_L Hi_L dP_S 100 S.p.
231 _SP.2 Setpoint 2 R/W Lo_L Hi_L dP_S 200 S.p.
232 _SP.3 Setpoint 3 R/W Lo_L Hi_L dP_S 300 S.p.
233 _SP.4 Setpoint 4 R/W Lo_L Hi_L dP_S 400 S.p.
234 Gr.SP Set gradient R/W 0.0 999.9 1 0.0 digit/min
235 _ _tS Limit value of timer R/W 0 9999 0 10 sec
236 _S.S.t. Start/Stop timer R/W 0 63 - -
237 _ _r.t. Reset timer R/W 0 31 - -
238 -At- Actuator travel time R/W 0.0 2000 - 60 sec
239 t_Lo Impulse minimum time/actuator R/W 0.0 25.0 1 2.0 % At
travel time
240 t_Hi Pulse alarm point R/W 0.0 100.0 1 0.0 % FS
241 -db- Valve dead zone R/W 0.0 25.0 1 0.0 %
242 At.tY Valves control type R/W 0 11 - -
243 SP.Pr Programmer function R/W 1 127 - 5 -
244 - Active program number R -
245 - Active step number R -
246 - Active segment R -
247 - Actual time program R
248 - Program actual setpoint ( stop ) R S.p.
249 SP.tY Remote setpoint selection R/W 0 7 - 0 -
250 - Remote setpoint from serial R/W Lo_L Hi_L S.p.
251 - Out W from serial (*4) R/W 0 65535
252 - Manual control output R/W -100.0 100.0 1 %
253 SP.Pt Programmer installation and R/W 0 3 - 0 -
resource selection
254 h.P.Lo Heating minimum power limit R/W 0.0 100.0 1 0.0 %
(*3)
255 c.P.Lo Cooling minimum power limit R/W 0.0 100.0 1 0.0 %
(*3)
256 hrd.3 “ * ” key and bargraph installation R/W 0 3 - 0 -
257 but.2 “ * ” key function R/W 0 11 - 0 -
258 BarG Bargraph function R/W 0 8 - 0 -
-
400 tYPE Probe type, signal, enable custom R/W 0 21 - 0
linearization, main input scale
401 Lo_S MAIN input scale minimum limit R/W -1999 9999 dP_S 0 S.p.
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
402 Hi_S MAIN input scale maximum limit R/W -1999 9999 dP_S 1000 S.p.
403 dP_S Decimal point position R/W 0 3 - 0
404 Lo.S2 Auxiliary input minimum range R/W -1999 9999 dP_S 0 S.p.
405 Hi.S2 Auxiliary input maximum range R/W -1999 9999 dP_S 1000 S.p.
406 AL.1.t Alarm 1 type R/W 0 31 - 0
407 AL.2.t Alarm 2 type R/W 0 31 - 0
408 AL.3.t Alarm 3 type R/W 0 31 - 0
513 C.MEd Cooling medium R/W 0 2 - 0 -
-
516 P.rSt Reset power R/W -100.0 100.0 1 0.0 %
519 oFSt MAIN input offset correction R/W -999 999 dP_S 0 S.p.
Remarks:
(*1) They can be written in local ( controller ) and STOP ( programmer ) mode only
(*2) They can be written in manual mode only
(*3) Read only for programmer with control parameter ( SP.Pt = 2 )
(*4) 32.768 ( 8000 H ) value is not allowed
800/1600/1800 MODBUS Programmer Memory Locations
Software Version V3.20
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
Program
Selection
2731 + 4*N LEn Number of program steps R/W 1 8 -
0≤N≤3
2732 + 4*N P.tY Program type and restart R/W 0 127 -
mode
Steps
Selection
1530 + 12*m SP.S m “ m “ step setpoint R/W Lo_L Hi_L dP_S S.p.
0≤m≤11 (§)
1532 + 12*m rP.t m “ m “ step ramp time R/W 00.00 99.59 2 0 hh.mm
o
mm.sec
1534 + 12*m So.t m “ m “ step hold time R/W 00.00 99.59 2 0 hh.mm
o
mm.sec
1535 + 12*m Hbb m “ m “ hold back band value R/W 0 999 dP_S 0 S.p.
1536 + 12*m St.Y m Defines “ m “ step type R/W 0 15 -
1537 + 12*m SL.S m Setpoint slaved for second R/W 0.0 100.0 - 0 %
external channel
1538 + 12*m EU.r m “ m “ step 4 ramp events R/W 0 15 - 0
1539 + 12*m EU.S m “ m “ step 4 hold events R/W 0 15 - 0
1540 + 12*m IPt m 2 enabling inputs R/W 0 3 - 0
1541 + 12*m GrP. m PID control parameter group R/W 0 31 - 0 -
selection
Remarks:
(§) m step number: 0 ≤m≤15 setting SP.Pt = 3
CONTROL PARAMETERS GROUP ( only for SP.Pt = 2 mode )
GROUPES ( g = 0, 1, 2, 3 )
2930 + 12*g h_Pb Heating proportional band R/W 0.0 999.9 1 0 %
group g
2931 + 12*g h_It Heating integral time R/W 0.00 99.99 2 0 min
group g
2932 + 12*g h_dt Heating derivative time R/W 0.00 99.99 2 0 min
group g
2933 + 12*g h.P.Hi Heating max. power limit R/W 0.0 100.0 1 100.0 %
group g
2934 + 12*g h.P.Lo Heating min. power limit R/W 0.0 100.0 1 100.0 %
group g
2935 + 12*g c_Pb Cooling proportional band R/W 0.0 999.9 1 0 %
group g
2936 + 12*g c_It Cooling integral time R/W 0.00 99.99 2 0 min
group g
2937 + 12*g c_dt Cooling derivative time R/W 0.00 99.99 2 0 min
group g
2938 + 12*g c.P.Hi Cooling max. power limit R/W 0.0 100.0 1 100.0 %
group g
2939 + 12*g c.P.Lo Cooling min. power limit R/W 0.0 100.0 1 100.0 %
group g
800/1600/1800 MODBUS BIT
Software Version V3.20
Addr. Description R/W
0 Active self-tuning R
1 Auto/Man R/W
-
4 AL1 status R
5 AL2 status R
8 AL_LBA status R
9 Sbr faulty sensor R
10 Local/Remote SP R/W
11 ON ( =0 )/OFF ( =1 ) software R/W
12 Out1 status R
13 Out2 status R
14 Out3 status R
15 Out4 status R
16 ( Run ) active programmer R
17 Running programmer R
18 Start ( =1 )/Stop ( =0 ) programmer or timer R
19 Reset ( =0 )/Go ( =1 ) programmer or timer R
20 Program end ( =1 ) R
21 Program in ramp ( =1 ) R
22 Program in hold ( =1 ) R
23 Waiting enabling R
24 Start/Stop program for serial line R/W
25 Reset program from serial line R/W
26 AL.HB alarm status R
27 HBB active R
28 Auto-Tuning active R
-
46 AL1 direct/inverse R/W
47 AL1 absolute/relativ R/W
48 AL1 normal/symmetric R/W
49 AL1 disabled when switching ON R/W
50 AL1 with memory R/W
-
54 AL2 direct/inverse R/W
55 AL2 absolute/relativ R/W
56 AL2 normal/symmetric R/W
57 AL2 disabled when switching ON R/W
58 AL2 with memory R/W
-
62 AL3 status R
63 Running soft-start R
64 Hold input active R
65 Timer at zero R
66 Auto ( =0 )/Man ( =1 ) programmer R
67 Ramp type: up ( =0 )/down ( =1 ) R
68 Digital input 1 status R
69 Digital input 2 status R
-