Modbus800-1600Ver3-20 Ing

The document provides a detailed list of MODBUS memory locations for software version V3.20, including addresses, item descriptions, read/write permissions, and measurement units. It covers various parameters such as process variables, setpoints, control outputs, alarm points, and limits for heating and cooling functions. Each entry specifies the minimum and maximum values, default settings, and measurement units where applicable.

Uploaded by

Elias Win
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views9 pages

Modbus800-1600Ver3-20 Ing

The document provides a detailed list of MODBUS memory locations for software version V3.20, including addresses, item descriptions, read/write permissions, and measurement units. It covers various parameters such as process variables, setpoints, control outputs, alarm points, and limits for heating and cooling functions. Each entry specifies the minimum and maximum values, default settings, and measurement units where applicable.

Uploaded by

Elias Win
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

800/1600/1800 MODBUS Memory Locations

Software Version V3.20

Addr. Item Description R/W Min Max Dp Def. Meas.


Unit
0 P.V. Process variable R Lo_S Hi_S dP_S - S.p.
1 _SP_ Active setpoint R/W Lo_L Hi_L dP_S - S.p.
(*1)
2 - Control output R/W -100.0 100.0 1 %
(*2)
4 - Deviation ( S.P. - P.V. ) R dP_S -
5 h_Pb Heating proportional band R/W 0.0 999.9 1 10.0 %
(*3)
6 c_Pb Cooling proportional band R/W 0.0 999.9 1 10.0 %
(*3)
7 h_It Heating integral time R/W 0.00 99.99 2 4.00 min
(*3)
8 h_dt Heating derivative time R/W 0.00 99.99 2 1.00 min
(*3)
9 _Ct.1 Cycle time if Out1 = logic or relay R/W 0 200 - 10 sec
10 Lo_S MAIN input scale minimum limit R/W -1999 9999 dP_S 0 S.p.
11 Hi_S MAIN input scale maximum limit R/W -1999 9999 dP_S 1000 S.p.
12 - Alarm point 1 R/W Lo_L Hi_L dP_S 500 S.p.
( if relative ) -999 999
13 - Alarm point 2 R/W Lo_L Hi_L dP_S 600 S.p.
( if relative ) -999 999
14 - Alarm point 3 R/W Lo_L Hi_L dP_S 700 S.p.
( if relative ) -999 999
16 - Local setpoint R/W Lo_L Hi_L dP_S 400 S.p.
18 SP.tY Remote setpoint selection R/W 0 7 - 0 -
20 Lo_L Lower limit for local setpoint and R/W Lo_S Hi_S dP_S 0 S.p.
absolute alarms
21 Hi_L Upper limit for local setpoint and R/W Lo_S Hi_S dP_S 1000 S.p.
absolute alarms
22 Gr.SP Set gradient R/W 0.0 999.9 1 0.0 digit/min
23 oFSt MAIN input offset correction R/W -999 999 dP_S 0 S.p.
24 FiLt MAIN input digital filter R/W 0.0 20.0 1 0.1 sec
25 Lo_L AL1 low limit R/W Lo_S Hi_S dP_S 0 S.p.
26 Hi_L AL1 high limit R/W Lo_S Hi_S dP_S 1000 S.p.
27 HYS.1 Hysteresis alarm 1 R/W -999 999 dP_S -1 S.p.
28 Lo_L AL2 low limit R/W Lo_S Hi_S dP_S 0 S.p.
29 Hi_L AL2 high limit R/W Lo_S Hi_S dP_S 1000 S.p.
30 HYS.2 Hysteresis alarm 2 R/W -999 999 dP_S -1 S.p.
31 S.tun Enabling self-tuning, auto-tuning R/W 0 13 - 0
and soft-start code
39 c.SP.o Cooling setpoint R/W -25.0 25.0 1 0.0 %
42 h.P.Hi Heating maximum power limit R/W 0.0 100.0 1 100.0 %
(*3)
43 c.P.Hi Cooling maximum power limit R/W 0.0 100.0 1 100.0 %
(*3)
44 LbA.t Waiting time for L.B.A. intervention R/W 0.0 500.0 1 30.0 min
time
45 bAud Baud rate R/W 0 4 - 0 -
46 CodE Serial comm. identification code R/W 0 247 - 1 -
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
47 _PAr Parity selection R/W 0 2 - 0 -
-
49 Prot Software protection code R/W 0 127 - 1
52 _AL.3 Alarm point 3 R/W Lo_S Hi_S dP_S 700 S.p.
( if relative ) -999 999
53 HYS.3 Hysteresis alarm 3 R/W -999 999 dP_S -1 S.p.
54 AL.3.t Alarm 3 type R/W 0 31 - 0
55 AL.Hb HB alarm R/W Lo.S2 Hi.S2 1 10.0 S.p.
56 Hb_t Waiting time for HB alarm R/W 0 999 - 30 sec
intervention
57 Hb_F HB alarm function R/W 0 30 - 0
-
76 c_It Cooling integral time R/W 0.00 99.99 2 4.00 min
(*3)
77 c_dt Cooling derivative time R/W 0.00 99.99 2 1.00 min
(*3)
78 _rSt Manual reset R/W -999 999 dP_S 0 S.p.
79 A.rSt Antireset R/W 0 9999 dP_S 0 S.p.
80 _FFd Feedforward R/W -100.0 100.0 1 0.0 %
85 Er.nr P.V. self-diagnostic error code R 0 4 -
86 St.00 Custom scale point 0 R/W Lo_S Hi_S dP_S 0 S.p.
87 St.01 Custom scale point 1 R/W Lo_S Hi_S dP_S 31 S.p.
88 St.02 Custom scale point 2 R/W Lo_S Hi_S dP_S 62 S.p.
89 St.03 Custom scale point 3 R/W Lo_S Hi_S dP_S 94 S.p.
90 St.04 Custom scale point 4 R/W Lo_S Hi_S dP_S 125 S.p.
91 St.05 Custom scale point 5 R/W Lo_S Hi_S dP_S 156 S.p.
92 St.06 Custom scale point 6 R/W Lo_S Hi_S dP_S 188 S.p.
93 St.07 Custom scale point 7 R/W Lo_S Hi_S dP_S 219 S.p.
94 St.08 Custom scale point 8 R/W Lo_S Hi_S dP_S 250 S.p.
95 St.09 Custom scale point 9 R/W Lo_S Hi_S dP_S 281 S.p.
96 St.10 Custom scale point 10 R/W Lo_S Hi_S dP_S 313 S.p.
97 St.11 Custom scale point 11 R/W Lo_S Hi_S dP_S 344 S.p.
98 St.12 Custom scale point 12 R/W Lo_S Hi_S dP_S 375 S.p.
99 St.13 Custom scale point 13 R/W Lo_S Hi_S dP_S 406 S.p.
100 St.14 Custom scale point 14 R/W Lo_S Hi_S dP_S 438 S.p.
101 St.15 Custom scale point 15 R/W Lo_S Hi_S dP_S 469 S.p.
102 St.16 Custom scale point 16 R/W Lo_S Hi_S dP_S 500 S.p.
103 St.17 Custom scale point 17 R/W Lo_S Hi_S dP_S 531 S.p.
104 St.18 Custom scale point 18 R/W Lo_S Hi_S dP_S 563 S.p.
105 St.19 Custom scale point 19 R/W Lo_S Hi_S dP_S 594 S.p.
106 St.20 Custom scale point 20 R/W Lo_S Hi_S dP_S 625 S.p.
107 St.21 Custom scale point 21 R/W Lo_S Hi_S dP_S 656 S.p.
108 St.22 Custom scale point 22 R/W Lo_S Hi_S dP_S 688 S.p.
109 St.23 Custom scale point 23 R/W Lo_S Hi_S dP_S 719 S.p.
110 St.24 Custom scale point 24 R/W Lo_S Hi_S dP_S 750 S.p.
111 St.25 Custom scale point 25 R/W Lo_S Hi_S dP_S 781 S.p.
112 St.26 Custom scale point 26 R/W Lo_S Hi_S dP_S 813 S.p.
113 St.27 Custom scale point 27 R/W Lo_S Hi_S dP_S 844 S.p.
114 St.28 Custom scale point 28 R/W Lo_S Hi_S dP_S 875 S.p.
115 St.29 Custom scale point 29 R/W Lo_S Hi_S dP_S 906 S.p.
116 St.30 Custom scale point 30 R/W Lo_S Hi_S dP_S 938 S.p.
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
117 St.31 Custom scale point 31 R/W Lo_S Hi_S dP_S 969 S.p.
118 St.32 Custom scale point 32 R/W Lo_S Hi_S dP_S 1000 S.p.
119 LbA.P Power limit for L.B.A. alarm R/W -100.0 100.0 1 25.0 %
condition
120 Manufact trade mark ( Gefran ) R - - - 5000 -
121 Device ID ( 800 ) R - - - 800 -
122 UPdt Software Version R - - - -
124 SP.Pr Programmer function R/W 1 255 - 5 -
125 -At- Actuator travel time R/W 0.0 2000 - 60 sec
126 t_Lo Impulse minimum time/actuator R/W 0.0 25.0 1 2.0 % At
travel time
127 -db- Valve dead zone R/W 0.0 25.0 1 0 % FS
-
132 - Control output R/W -100.0 100.0 1 - %
(*2)
133 butt M/A key function R/W 0 27 - 1 -
-
136 SP.tY Remote setpoint selection R/W 0 3 - 0 -
137 - Active setpoint R S.p.
138 - Local setpoint R/W Lo_L Hi_L dP_S 400 S.p.
139 - Auxiliary input R Lo.S2 Hi.S2 dP_S - S.p.
( remote setpoint )
140 d.i.F.1 Digital input 1 ( IN1 ) function R/W 0 50 - 0 -
141 d.i.F.2 Digital input 2 ( IN2 ) function R/W 0 50 - 0 -
142 Lo_L Lower limit for local setpoint and R/W Lo_S Hi_S dP_S 0 S.p.
absolute alarms
143 Hi_L Upper limit for local setpoint and R/W Lo_S Hi_S dP_S 1000 S.p.
absolute alarms
-
146 h.P.Hi Heating maximum power limit R/W 0.0 100.0 1 100.0 %
(*3)
147 SoFt Soft-Start time R/W 0.0 500.0 1 0.0 min
148 h_Pb Heating proportional band R/W 0.0 999.9 1 10.0 %
(*3)
149 h_b Heating hysteresis ( ON/OFF ) R/W 0.0 999.9 1 10.0 %
(*3)
150 h_It Heating integral time R/W 0.00 99.99 2 4.00 min
(*3)
151 h_dt Heating derivative time R/W 0.00 99.99 2 1.00 min
152 _Ct.1 Cycle time if Out1 = logic or relay R/W 0 200 10 sec
159 _Ct.2 Cycle time if Out2 = logic or relay R/W 0 200 - 10 sec
160 rL.o.1 Out1 R/W 0 65 - 0 -
Allocation of reference signal
163 rL.o.2 Out2 R/W 0 61 - 1 -
Allocation of reference signal
166 rL.o.3 Out3 R/W 0 61 - 2 -
Allocation of reference signal
169 _Ct.3 Cycle time if Out3 = logic or relay R/W 0 200 - 10 sec
170 rL.o.4 Out4 R/W 0 61 - 3 -
Allocation of reference signal
173 _Ct.4 Cycle time if Out4 = logic or relay R/W 0 200 - 10 sec
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
177 - Alarm point 1 R/W Lo_L Hi_L dP_S 500 S.p.
( if relative ) -999 999
178 - Alarm point 2 R/W Lo_L Hi_L dP_S 600 S.p.
( if relative ) -999 999
179 FiLd Digital filter on display process R/W 0.0 9.9 1 0.5 S.p.
variable
180 CtrL Control type R/W 0 78 - 8 -
-
187 HYS.1 Hysteresis alarm 1 R/W -999 999 dP_S -1 S.p.
188 HYS.2 Hysteresis alarm 2 R/W -999 999 dP_S -1 S.p.
189 HYS.3 Hysteresis alarm 3 R/W -999 999 dP_S -1 S.p.
-
191 hrd.1 Hardware configuration 1: R/W 0 95 - -
Auxiliary inputs
Logic inputs
Serial interface
192 hrd.2 Hardware configuration 2: R/W 0 127 - -
Out1,..., Out4 outputs
W1, W2 analogue outputs
193 SEnS Probe type for MAIN input selection R/W 0 15 - -
194 SnS.2 Probe type for auxiliary input R/W 0 7 - -
selection
195 AL.nr Select number of enabled alarms R/W 0 31 - -
196 diSP Defining SV display function R/W 0 3 - -
197 LEd.1 LED 1 function ( MAN ) R/W 0 31 - -
198 LEd.2 LED 2 function ( AUX ) R/W 0 31 - -
199 LEd.3 LED 3 function ( REM ) R/W 0 31 - -
200 HEAd Set number of parameters in R/W 0 14 - 0 -
custom menù
201 PA.01 Identification code for parameter 1 R/W 0 241 - 15 -
202 PA.02 Identification code for parameter 2 R/W 0 241 - 16 -
203 PA.03 Identification code for parameter 3 R/W 0 241 - 17 -
204 PA.04 Identification code for parameter 4 R/W 0 241 - 18 -
205 PA.05 Identification code for parameter 5 R/W 0 241 - 19 -
206 PA.06 Identification code for parameter 6 R/W 0 241 - 20 -
207 PA.07 Identification code for parameter 7 R/W 0 241 - 21 -
208 PA.08 Identification code for parameter 8 R/W 0 241 - 22 -
209 PA.09 Identification code for parameter 9 R/W 0 241 - 23 -
210 PA.10 Identification code for parameter 10 R/W 0 241 - 24 -
211 PA.11 Identification code for parameter 11 R/W 0 241 - 25 -
212 PA.12 Identification code for parameter 12 R/W 0 241 - 26 -
213 PA.13 Identification code for parameter 13 R/W 0 241 - 27 -
214 PA.14 Identification code for parameter 14 R/W 0 241 - 28 -
215 AL.1.r Reference signal for alarm 1 R/W 0 5 - 0 -
216 AL.2.r Reference signal for alarm 2 R/W 0 5 - 0 -
217 AL.3.r Reference signal for alarm 3 R/W 0 5 - 0 -
218 tYP.2 Auxiliary analogue input function R/W 0 13 - -
219 FLt.2 Digital filter on auxiliary input R/W 0.0 20.0 1 0.1 sec
220 oF.S2 Auxiliary input offset correction R/W -999 999 dP_S S.p.
221 L.An.1 W1 analogue signal output 1 R/W -1999 9999 dP_S S.p.
minimum limit
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
222 H.An.1 W1 analogue signal output 1 R/W -1999 9999 dP_S S.p.
maximum limit
223 An.o.1 W1 assignment of signal or R/W 0 63 - -
reference value
224 L.An.2 W2 analogue signal output 2 R/W -1999 9999 dP_S S.p.
minimum limit
225 H.An.2 W2 analogue signal output 2 R/W -1999 9999 dP_S S.p.
maximum limit
226 An.o.2 W2 assignment of signal or R/W 0 63 - -
reference value
227 InP.2 Amperometric input value or remote R Lo.S2 Hi.S2 dP_S S.p.
setpoint
228 FAC.P Power in fault action R/W -100.0 100.0 1 0.0 %
229 _rEL. Fault action ( sets state in case of R/W 0 7 - 0 -
probe fault )
230 _SP.1 Setpoint 1 R/W Lo_L Hi_L dP_S 100 S.p.
231 _SP.2 Setpoint 2 R/W Lo_L Hi_L dP_S 200 S.p.
232 _SP.3 Setpoint 3 R/W Lo_L Hi_L dP_S 300 S.p.
233 _SP.4 Setpoint 4 R/W Lo_L Hi_L dP_S 400 S.p.
234 Gr.SP Set gradient R/W 0.0 999.9 1 0.0 digit/min
235 _ _tS Limit value of timer R/W 0 9999 0 10 sec
236 _S.S.t. Start/Stop timer R/W 0 63 - -
237 _ _r.t. Reset timer R/W 0 31 - -
238 -At- Actuator travel time R/W 0.0 2000 - 60 sec
239 t_Lo Impulse minimum time/actuator R/W 0.0 25.0 1 2.0 % At
travel time
240 t_Hi Pulse alarm point R/W 0.0 100.0 1 0.0 % FS
241 -db- Valve dead zone R/W 0.0 25.0 1 0.0 %
242 At.tY Valves control type R/W 0 11 - -
243 SP.Pr Programmer function R/W 1 127 - 5 -
244 - Active program number R -
245 - Active step number R -
246 - Active segment R -
247 - Actual time program R
248 - Program actual setpoint ( stop ) R S.p.
249 SP.tY Remote setpoint selection R/W 0 7 - 0 -
250 - Remote setpoint from serial R/W Lo_L Hi_L S.p.
251 - Out W from serial (*4) R/W 0 65535
252 - Manual control output R/W -100.0 100.0 1 %
253 SP.Pt Programmer installation and R/W 0 3 - 0 -
resource selection
254 h.P.Lo Heating minimum power limit R/W 0.0 100.0 1 0.0 %
(*3)
255 c.P.Lo Cooling minimum power limit R/W 0.0 100.0 1 0.0 %
(*3)
256 hrd.3 “ * ” key and bargraph installation R/W 0 3 - 0 -
257 but.2 “ * ” key function R/W 0 11 - 0 -
258 BarG Bargraph function R/W 0 8 - 0 -
-
400 tYPE Probe type, signal, enable custom R/W 0 21 - 0
linearization, main input scale
401 Lo_S MAIN input scale minimum limit R/W -1999 9999 dP_S 0 S.p.
Addr. Item Description R/W Min Max Dp Def. Meas.
Unit
402 Hi_S MAIN input scale maximum limit R/W -1999 9999 dP_S 1000 S.p.
403 dP_S Decimal point position R/W 0 3 - 0
404 Lo.S2 Auxiliary input minimum range R/W -1999 9999 dP_S 0 S.p.
405 Hi.S2 Auxiliary input maximum range R/W -1999 9999 dP_S 1000 S.p.
406 AL.1.t Alarm 1 type R/W 0 31 - 0
407 AL.2.t Alarm 2 type R/W 0 31 - 0
408 AL.3.t Alarm 3 type R/W 0 31 - 0
513 C.MEd Cooling medium R/W 0 2 - 0 -
-
516 P.rSt Reset power R/W -100.0 100.0 1 0.0 %
519 oFSt MAIN input offset correction R/W -999 999 dP_S 0 S.p.

Remarks:

(*1) They can be written in local ( controller ) and STOP ( programmer ) mode only
(*2) They can be written in manual mode only
(*3) Read only for programmer with control parameter ( SP.Pt = 2 )
(*4) 32.768 ( 8000 H ) value is not allowed
800/1600/1800 MODBUS Programmer Memory Locations
Software Version V3.20

Addr. Item Description R/W Min Max Dp Def. Meas.


Unit
Program
Selection
2731 + 4*N LEn Number of program steps R/W 1 8 -
0≤N≤3
2732 + 4*N P.tY Program type and restart R/W 0 127 -
mode
Steps
Selection
1530 + 12*m SP.S m “ m “ step setpoint R/W Lo_L Hi_L dP_S S.p.
0≤m≤11 (§)
1532 + 12*m rP.t m “ m “ step ramp time R/W 00.00 99.59 2 0 hh.mm
o
mm.sec
1534 + 12*m So.t m “ m “ step hold time R/W 00.00 99.59 2 0 hh.mm
o
mm.sec
1535 + 12*m Hbb m “ m “ hold back band value R/W 0 999 dP_S 0 S.p.
1536 + 12*m St.Y m Defines “ m “ step type R/W 0 15 -
1537 + 12*m SL.S m Setpoint slaved for second R/W 0.0 100.0 - 0 %
external channel
1538 + 12*m EU.r m “ m “ step 4 ramp events R/W 0 15 - 0
1539 + 12*m EU.S m “ m “ step 4 hold events R/W 0 15 - 0
1540 + 12*m IPt m 2 enabling inputs R/W 0 3 - 0
1541 + 12*m GrP. m PID control parameter group R/W 0 31 - 0 -
selection

Remarks:

(§) m step number: 0 ≤m≤15 setting SP.Pt = 3


CONTROL PARAMETERS GROUP ( only for SP.Pt = 2 mode )

GROUPES ( g = 0, 1, 2, 3 )
2930 + 12*g h_Pb Heating proportional band R/W 0.0 999.9 1 0 %
group g
2931 + 12*g h_It Heating integral time R/W 0.00 99.99 2 0 min
group g
2932 + 12*g h_dt Heating derivative time R/W 0.00 99.99 2 0 min
group g
2933 + 12*g h.P.Hi Heating max. power limit R/W 0.0 100.0 1 100.0 %
group g
2934 + 12*g h.P.Lo Heating min. power limit R/W 0.0 100.0 1 100.0 %
group g
2935 + 12*g c_Pb Cooling proportional band R/W 0.0 999.9 1 0 %
group g
2936 + 12*g c_It Cooling integral time R/W 0.00 99.99 2 0 min
group g
2937 + 12*g c_dt Cooling derivative time R/W 0.00 99.99 2 0 min
group g
2938 + 12*g c.P.Hi Cooling max. power limit R/W 0.0 100.0 1 100.0 %
group g
2939 + 12*g c.P.Lo Cooling min. power limit R/W 0.0 100.0 1 100.0 %
group g
800/1600/1800 MODBUS BIT
Software Version V3.20

Addr. Description R/W


0 Active self-tuning R
1 Auto/Man R/W
-
4 AL1 status R
5 AL2 status R
8 AL_LBA status R
9 Sbr faulty sensor R
10 Local/Remote SP R/W
11 ON ( =0 )/OFF ( =1 ) software R/W
12 Out1 status R
13 Out2 status R
14 Out3 status R
15 Out4 status R
16 ( Run ) active programmer R
17 Running programmer R
18 Start ( =1 )/Stop ( =0 ) programmer or timer R
19 Reset ( =0 )/Go ( =1 ) programmer or timer R
20 Program end ( =1 ) R
21 Program in ramp ( =1 ) R
22 Program in hold ( =1 ) R
23 Waiting enabling R
24 Start/Stop program for serial line R/W
25 Reset program from serial line R/W
26 AL.HB alarm status R
27 HBB active R
28 Auto-Tuning active R
-
46 AL1 direct/inverse R/W
47 AL1 absolute/relativ R/W
48 AL1 normal/symmetric R/W
49 AL1 disabled when switching ON R/W
50 AL1 with memory R/W
-
54 AL2 direct/inverse R/W
55 AL2 absolute/relativ R/W
56 AL2 normal/symmetric R/W
57 AL2 disabled when switching ON R/W
58 AL2 with memory R/W
-
62 AL3 status R
63 Running soft-start R
64 Hold input active R
65 Timer at zero R
66 Auto ( =0 )/Man ( =1 ) programmer R
67 Ramp type: up ( =0 )/down ( =1 ) R
68 Digital input 1 status R
69 Digital input 2 status R
-