Jandy Pool Valve Actuator
Jandy Pool Valve Actuator
OPERATION MANUAL
WARNING
FOR YOUR SAFETY - This product must be installed and serviced by a contractor who is licensed and
qualified in pool equipment by the jurisdiction in which the product will be installed where such state
or local requirements exist. The maintainer must be a professional with sufficient experience in pool
equipment installation and maintenance so that all of the instructions in this manual can be followed
exactly. Before installing this product, read and follow all warning notices and instructions that accompany
this product. Failure to follow warning notices and instructions may result in property damage, personal
injury, or death. Improper installation and/or operation will void the warranty.
Improper installation and/or operation can create unwanted electrical hazard which can
cause serious injury, property damage, or death.
installation, operation and safe use of this product. This information should be given to
the owner/operator of this equipment.
Page 2 ENGLISH Jandy® Pro Series Valve Actuator | Installation and Operation Manual
INSTALLER INFORMATION
NOTES:
Jandy® Pro Series Valve Actuator | Installation and Operation Manual ENGLISH Page 3
Table of Contents
Section 6. Maintenance................................... 10
6.1 Actuator............................................................. 10
6.2 Valve.................................................................. 10
Page 4 ENGLISH Jandy® Pro Series Valve Actuator | Installation and Operation Manual
WARNING
This manual contains important information about the installation, operation and safe use of this product. This
information should be given to the owner/operator of this equipment.
WARNING
This product must be installed and serviced by professionals who are qualified in pool/spa product installation and
service. Improper installation and/or operation can create an unwanted electrical hazard which can cause serious
injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
Disconnect power to the system at the main circuit breaker before servicing to avoid risk of electric shock which can
result in property damage, severe injury or death. All wiring must be done in accordance with the National Electrical
Code® (NEC®), NFPA-70. In Canada, all wiring must be done in accordance with the Canadian Electrical Code
(CSA C22.1). All applicable local installation codes and regulations must be followed.
A C
B (Common Port)
3.2 Actuator Mounting 3. Turn the actuator over so you can see into the
JVA’s mount directly on all full-size Jandy Pro clear actuator shaft. There are four (4) "teeth"
Series Valves (8 screws on lid). Zodiac recommends on the inside of the shaft. Locate the smallest
motorizing Jandy Pro Series Never Lube® Valves only. "tooth" and align this "tooth" with the smallest
slot on the valve (see Figure 5).
JVA’s may be mounted onto valves in any of the four (4)
positions in Figure 3. Place actuator on valve so smallest tooth
aligns with smallest slot.
I II
Smallest Slot Smallest Tooth
A C
A C
Actuator
B B
Bottom
III IV
Rotate
actuator
• one actuator will rotate incorrectly in relation to NOTE Before resetting cams, if the valve is plumbed in
another actuator (as in pool/spa combination) Standard Plumbing position and the actuator is in
Standard Mounting position there is no need for
Figure 7 illustrates an example of the valves and resetting the cams (see Figure 9). If a port other than
actuators of a pool/spa combination that are out of "B" is plumbed as the common port or if the actuator
synchronization. The valve on the left of the illustration is mounted other than Standard Mounting, the cam
setting must be changed so the actuator shaft and
(suction) is plumbed with the spa line on the left side the valve diverter rotate properly. Refer to the Cam
of the valve and the pool line on the right; whereas, the Setting Chart on page 8 for proper settings.
valve on the right of the illustration (return) is plumbed
I II
with the pool on the left side of the valve and the spa
on the right. In this configuration, if the actuators are
activated, one will turn to spa while the other will turn
A C
to pool. The actuators will have to be synchronized. A C
Suction Return
B B
Spa Pool Pool Spa
III IV
A C
A C
B
B
Figure 7. JVA Synchronization, Example Figure 9. JVA Mounting Positions.
On the actuator that is out of synchronization, flip the 1. Turn OFF actuator power. Unscrew
toggle switch located on the bottom of the actuator to the locking knob by turning the knob
the ON 2 position (see Figure 8). The toggle positions counterclockwise. Remove the locking knob
are marked on the actuator top cover. Retry the system. and valve handle.
2. Remove the four (4) Phillips head screws that
secure the actuator lid and then remove the lid.
Page 8 ENGLISH Jandy® Pro Series Valve Actuator | Installation and Operation Manual
3. Important - Rotate the actuator shaft so the NOTE The cam is marked with the arrow at "0", a long hash
arrow mark on the top cam aligns with the mark at the 180° position, and 2 short hash marks at
the 90° and 270° positions.
microswitch actuator (bottom cam arrow mark
should also align with the bottom microswitch 4. To set the cams, rotate the cam(s) until the
actuator, see Figure 10). Locate the mounting arrow mark on the cam(s) align with the
position for the actuator (as per Figure 9, the microswitch actuator (see Figure 11).
mounting position will be either I, II, III, or IV).
NOTE The upper cam stops counterclockwise rotation and
Next, determine what valve port is the common the lower cam stops clockwise rotation.
or inlet port (as per Figure 9, the common port
will be either A, B, or C). Then refer to the 5. Turn power ON to the actuator and use the
Cam Setting Chart below to determine what toggle switch located on the bottom of the
the cam settings should be. For example, if the actuator to check rotation. Move the toggle
actuator is in JVA mounting position "I", and the switch to either ON 1 or ON 2. Allow the
common port on the valve is port "A", the cam actuator shaft to move until it stops. Check
settings would be 90° for the top cam and 180° valve diverter position*, if the position is
for the bottom. correct flip the toggle switch in the opposite
direction and allow the shaft to stop again. If
Final minor adjustments may be necessary
the stop positions are correct, go to step 6. If
they are not, reset the cams until correct.
Lower Upper
Cam Cam NOTE If the actuator does not move in either direction, refer
to Section 6, Troubleshooting.
180°
6. Replace the lid and tighten screws. Replace the
handle and locking knob.
270° NOTE The end of the handle which has the word OFF
0
Figure 11. JVA Cam Adjustment 4. To return the actuator to automatic position, pull
up on the handle while turning it clockwise or
counterclockwise until you feel the shaft slide
Section 5. Manual Operation up into the gear train. Turn the locking knob
down (clockwise) until snug.
5.1 Manual Override
5. Put toggle switch back to the original position.
It is sometimes necessary to rotate valve(s) manually,
without using the system controller. This occurs when
the controller is not accessible/operational or when the
spa or pool/spa combination require filling or draining.
CAUTION
To prevent damage to your equipment and to
minimize the possibility of any injury resulting from
such damage, make sure that the pool filtration pump
is OFF BEFORE rotating the valve handle.
ON 1
On/Off Switch is
OFF on Bottom of JVA
ON 2
WARNING NC NC
Disconnect power to the system at the main circuit
breaker before servicing to avoid risk of electric shock
which can result in property damage, severe injury
White
White
or death. All wiring must be done in accordance with
Red
Red
the National Electrical Code® (NEC®), NFPA-70.
In Canada, all wiring must be done in accordance
Bottom Cam
with the Canadian Electrical Code (CSA C22.1). All Motor Red
Connector
applicable local installation codes and regulations to PCB
Top Cam
Motor
Header White
must be followed. Black
Black
Connector
to PCB
Header
CAUTION
POWER
Black
To avoid damage to the equipment and minimize Red
White
risk of injury, use a properly sized, listed Class 2 Wiring to Toggle
Switch Underneath
transformer for connection to the power supply. Red Black
Circuit Board
White
Secondary Primary
Time
(24 VAC) (120 VAC) Clock
Transformer*
Neutral
Neutral
120 VAC
Load
Double Pole/
Line
Double Throw 2 amp
Secondary Primary
Toggle Switch fuse (24 VAC) (120 VAC)
Hot
Normally Closed RED
Common 1 amp
Normally Open WHITE fuse
120 VAC
BLACK BLACK
RED Normally Closed RED
WHITE Common
Normally Open WHITE
* Transformer must be sized for the number of JVA's. * Transformer must be sized for the number of JVA's.
Each JVA requires .75 amp. at 24 VAC. Each JVA requires .75 amp. at 24 VAC.
Page 12 ENGLISH Jandy® Pro Series Valve Actuator | Installation and Operation Manual
Section 8. Troubleshooting
8.1 Troubleshooting
All major components, including the power cord, are replaceable without replacing the entire actuator. Each item may
be replaced as a separate piece allowing easy infield repair. See Section 8, Exploded Views and Replacement Kits, for
actuator replacement part numbers.
NOTES
Jandy® Pro Series Valve Actuator | Installation and Operation Manual ENGLISH Page 15
NOTES
Zodiac Group Australia.
219 Woodpark Road
Smithfield, NSW AU 2164
1.800.688.552 | www.Zodiac.com.au ETL LISTED CONFORMS TO
UL-STD 1563
Zodiac Pool Systems, Inc. CERTIFIED TO CAN/CSA C22.2 NO.218.1
2620 Commerce Way, Vista, CA 92081
1.800.822.7933 | www.ZodiacPoolSystems.com
©2016 Zodiac Pool Systems, Inc. ZODIAC ® is a registered trademark of Zodiac International,
S.A.S.U., used under license. All trademarks referenced herein are the property of their respective
owners.
H0570800 Rev J