GT (7FA) startup
GT (7FA) startup
Pre-Start Checks:
Ensure Lube oil (88QA) & Hydraulic oil (88HQ) pumps are running
Checks Auxiliary Systems (Fire protection system, Cooling Water etc.) ready
Inlet Bleed Heat Isolation Valve OPEN
All MCC Breakers in AUTO
If unit is not on Cooldown ‘At Cooldown ON/OFF select’ Select ON then click OK. Unit should be on
turning gear atleast for 4 hours.
MODE Select: Select AUTO then click OK.
“Master Reset” to clear the latch and enable re-start. And select “diagnostic reset”
Initial Conditions:
Status: On Cooldown
Machine Speed: 6.3 rpm; IGV: 21 Deg
Compressor Bleed Valves: OPEN
Inlet Bleed Heat Valve: CLOSE
20TFD-1: OPEN (20TFD-1 is a solenoid valve which energize to open False Start Drain Valve VA17-1A of
Combustion Wrapper)
20TFD-2: OPEN (False Start Drain Solenoid Valve. Operates Turbine combined drain valves VA17-1B,
VA17-2, VA17-6A, VA17-6B & VA17-7)
FSR Control: Startup
Fuel gas Safety Shutoff Valve SSOV (VS4_4): CLOSED & 20VG-1 (fuel gas vent valve): OPEN
Exciter: Manual Mode
Drives in service: 88VG, 88HQ, 88QA, 88QV and 88TG-1
Heaters ON: 23HT-3; 23HG-1; 23HL-3; 23TE-1; 23FS-3
Atomizing Air Valves: 20AA-5 OPEN; 20AA-1&2 CLOSE
Turndown extraction Valves: CLOSE
From the start command and before turbine ROLL start, the following steps shall be carried out
All the above steps happen in first 36 sec of the startup sequence.