TRANSFER PUMP HEAD CALCUALTION
Storage Capacity of Roof Tank in M3 = 15
Assuming a filling time in Hrs = 2
Rate of filling (M3/Hr) = 7.5
Rate of filling (GPM) = 33
Pipe Diameter (inch) = 1 1/2 40
SIZE (Dia) Flow STRAIGHT LENGTH FRICTION FACT. FRICTION FACT. FRICTION LOSS
VALVES & EQT. LENGTH OF TOTAL EQT. LENGTH TOTAL EQT.
LOCATION SECTION QTY
FITTINGS FITTING (Ft.) OF FITTING (Ft.) LENGTH (Ft.)
(INCH) GPM MT FT (PSI OF H20/100) (Ft. OF H20/100) IN Ft. OF H20.
A-B 1 1/2 33 13 42.64 IV 3 1 3
ST 1 10 10
GV 0 87.4 2.0 4.6 4.04
NRV 1 16.8 16.8
90 E 3 5 15
HEAD LOSS IN FT OF WG 4.04
SAFETY FACTOR 20% 0.81
STATIC HEAD (VERTICAL HEIGHT) - FT 36.00
RESIDUAL HEAD (DISCHARGE HEAD) -FT 2.00
TOTAL HEAD LOSS IN FT OF WG 42.85
TOTAL HEAD LOSS IN METER OF WG 13.06
0091 888 4437724 deltaT MEP Technical Academy Bengaluru,India.
1-Pipe Sizing Using Formulae
OHT CAPACITY(m3) 15
Filling Time(Hours) 2
Discharge Through piping (Q)m3/sec 0.0020833333
Velocity(V)m/sec 1.5
We Know Q=A x V , Then A=Q/V
A(m2) 0.0014
We Know A=3.14XD2/4
Diameter(mm) 42.062872094
Selected Pipe Size 40mm
2 -Pipe Sizing Using Chart (IPC STANDARD)
Storage Capacity of Roof Tank in M3 15
Filling Time(Hours) 2
Rate of filling (M3/Hr) 7.5
Rate of filling (GPM) 33
Pipe Diameter (inch) 40mm
Friction(PSI) 2
A
B