Substation Automation Products
Relion® 670/650 series IEC and ANSI
Hardware
© ABB Group
1MRG014097
October 2013
Relion® 670/650 series hardware
Contents
Relion® 670/650 series
Introduction
Modules
I/O Capability
Mounting Flexibility
Communication
IED HMI
Relion® 670 series
Hardware
Relion® 670 series
Relion 670 series
Common hardware (HW) and
Introduction
Modules software (SW) for the entire 670
I/O Capability series
Mounting Flexibility
Communication Function library according to IEC
IED HMI
61850
Extensive analog and binary I/O
capability
Type tested platform
Relion® 670 series
Relion 670 series
Few spare parts on modular level
Introduction
Modules
Type tested platform
I/O Capability
Mounting Flexibility
Easy future extensions
Communication
IED HMI
Minimized cost for maintenance
ANSI
IEC
Relion® 670 series
Relion 670 series
Ventilated casing with common
Introduction
Modules
look for all products
I/O Capability
3 sizes - 1/2, 3/4 or 1/1 of 19”
Mounting Flexibility
Communication 6U high (266mm)
IED HMI
Small or large HMI unit
Hardware structure
670 series
Relion 670 series Transformer Input Module TRM
Introduction
Modules
6I + 6U, 9I + 3U or 12I
I/O Capability
One or two - TRM1 & TRM2 for 12 or
Mounting Flexibility
Communication
24 analog CT or VT inputs
IED HMI
Analog Digital Conversion module
ADM1 and ADM2 for TRM inputs
Central Processing Unit NUM
GPS time synchronization module
GSM (option)
Time synchronization via binary signal
and communication ports IRIG-B
Binary Input / Output modules BIM,
SOM, BOM, IOM, MIM
Power supply module PSM
Hardware platform
670 series
IED 670
Power
Relion 670 series Analogue A/D Main GPS Binary Binary Binary Binary Binary mA
Input Conversion Processing Synch I/O I/O I/O I/O I/O Input Supply
Module Module Module Module Module Module Module Module Module Module Module
Introduction
TRM AD1 NUM GSM BIM BIM BIM BOM BOM MIM
Modules
I/O Capability PCU
Mounting Flexibility
Logics CAN
Communication 1Mbit/s
IED HMI 6I A/D
6U
OEM
~
~ ~
~ LDCM
Comm-
uni-
cation
I/O I/O I/O I/O I/O mA
View from rear side with contacts
670 series
Relion 670 series
Introduction
Modules
I/O Capability
Mounting Flexibility
Communication
IED HMI
View from rear side with ringlugs
670 series
Relion 670 series
Introduction
Modules
I/O Capability
Mounting Flexibility
Communication
IED HMI
Numerical module
670 series
Relion 670 series Main Controller/CPU type
Introduction
Modules
IBM 3200 PowerPC 750FX/GX,
I/O Capability
600 MHz
Mounting Flexibility
Communication
Internal communication with cPCI bus
IED HMI 100 Mbit/s
Memory
Up to 128 Mb FLASH
Up to 256 Mb DRAM
Cycle time in 670 series
1 or 3 ms for protection
8 or 100 ms for logic
Interfaces on the numerical module
670 series
Relion 670 series
Introduction
Modules
Motherboard interface
I/O Capability
Mounting Flexibility
Communication
IED HMI
Mounting position for serial
communication module with
SPA, LON, IEC -103
Mounting position for IRIG-B
module
Mounting positions for two
64 kbit communication
modules
Internal communication cPCI
bus
Analog / digital conversion module
670 series
Relion 670 series
Analog inputs from transformer
Introduction module
Modules
I/O Capability
Mounting Flexibility Mounting position for Optical
Communication
Ethernet module (only on AD1)
IED HMI
cPCIbus
Mounting positions for EIA-485
module (only on AD1)
Mounting positions for 2 extra
LDCM modules (only on AD1)
Transformer input module
670 series
Relion 670 series
Introduction
Up to 12 analog inputs can be
Modules connected
I/O Capability
Mounting Flexibility 0 - 6 U, 110-220 V rated range
Communication 50/60 Hz
IED HMI
6 -12 I, 1 A or 5 A rated current
Isolation barrier preventing
disturbances to enter into IED
Adapt measured values to static
circuitry
Standardized transformer modules
670 series
Relion 670 series
Introduction Transformer module (TRM 12) 1A 5A 110/220 V
Modules
I/O Capability 6I and 6U 6 6
Mounting Flexibility
6I and 6U 6 6
Communication
IED HMI 9I + 3U 9 3
9I + 3U 9 3
9I + 3U 5 4 3
12I 12
12I 12
6I 6
5I + 5U 5 5
Power supply module
670 series
Relion 670 series Input range: 24-60 V DC
Introduction
Modules Input range: 90-250 V DC
I/O Capability
Mounting Flexibility Internal fail relay output
Communication
IED HMI DC/DC Converter provides full
isolation between IED and
external battery system
GPS time synchronization module
670 series
Relion 670 series For multi-terminal current differential
Introduction
Modules
protection
I/O Capability 1 MHz High Accuracy output; < 1μs
Mounting Flexibility
Communication Minute pulse / IRIG-B
IED HMI
Accuracy 1ms (Not suitable for differential
protection)
IEC 61850-8-1 synchronization
Accuracy < 1 ms
LON synchronization
Accuracy < 2 ms
GPS
Connection
GCM
to antenna
module CAN bus
IRIG-B
670 series
Relion 670 series
The IRIG interface to the IED
Introduction
Modules supplies two possible
I/O Capability synchronization methods, IRIG-
Mounting Flexibility
B and PPS
Communication
IED HMI IRIG-B is a protocol used only
for time synchronization
An optical PPS signal can be
supplied to the optical interface
of the IRIG module
Max 1 IRIG-B module per IED
Mounting position for the IRIG-B
module is pos 302 on NUM
GPS antenna and coaxial cable
670 series
Relion 670 series
Introduction
Accurate synchronization of
Modules sampled data
I/O Capability
Mounting Flexibility 1 microsecond accuracy
Communication
IED HMI Line Differential Protection
applications with switched
communication network
Wide Area Protection and Phasor
Measurement Unit applications
SMA contact for connection to GSM
Accurate time synchronization for
each installation
I/O-modules
670 series
Relion 670 series
Introduction
Full 19” case with 24 binary analog
Modules
inputs and up to 11 (6 with ring lug)
I/O Capability I/O modules
Mounting Flexibility
Communication Full 19” case with 12 binary analog
IED HMI inputs and up to 11 (7 with ring lug)
IEC I/O modules
¾ x 19” case with 24 analog inputs
and up to 7 (3 with ring lug) I/O
modules
¾ x 19” case with 12 analog inputs
and up to 7 (4 with ring lug) I/O
modules
ANSI
½ x 19” case with 12 analog inputs
and up to 3 (2 with ring lug) I/O
modules
Extensive I/O capability enables unique
function integration
EMC enhanced binary input module
670 series
Relion 670 series 16 independent Binary Inputs
Introduction
Modules Increased interference immunity
I/O Capability
2 x IEC requirements for 50 ms
Mounting Flexibility
Communication Debounce filter, T = 5 ms
IED HMI
Oscillation suppression detection within
1 s; > 0 - 40 Hz
No pulse counting Auxiliary voltage
24/30 V DC (± 20 %)
Increased interference 48/60 V DC (± 20 %)
[mA]
immunity 110/125 V DC (± 20 %)
30
220/250 V DC (± 20 %)
Threshold voltage 60 %
1
35 70 [ms]
Binary input module for pulse counting
670 series
Relion 670 series 16 independent Binary Inputs
Introduction
Modules Debounce filter, T = 5 ms
I/O Capability
Mounting Flexibility Oscillation suppression detection within
Communication 1 s; > 0 - 40 Hz
IED HMI
Pulse counting available for all inputs
Auxiliary voltages
24/30 V DC (± 20 %)
48/60 V DC (± 20 %)
Standard interference immunity 110/125 V DC (± 20 %)
[mA] 220/250 V DC (± 20 %)
30
Threshold voltage 60 %
1
3,5 7 [ms]
Binary output module
670 series
Relion 670 series Two variants
Introduction
Modules 24 single output relays
I/O Capability
Mounting Flexibility 12 double pole command
Communication output relays
IED HMI
EMC enhanced binary input/output module
670 series
Relion 670 series 8 independent Binary Inputs and 10 +
Introduction
Modules
2 Binary Output relays
I/O Capability
Increased interference immunity 2 x
Mounting Flexibility
Communication
IEC for 50 ms
IED HMI
Fixed filter time 3/5 ms
Auxiliary voltage
24/30 V DC (± 20 %)
48/60 V DC (± 20 %)
110/125 V DC (± 20 %)
[mA]
30 Increased interference 220/250 V DC (± 20 %)
immunity
1
35 70 [ms]
Static output module
670 series
Relion 670 series
High Speed Applications
Introduction
Modules 6 static binary outputs
I/O Capability
Mounting Flexibility 6 change-over contacts
Communication
IED HMI
mA input module
670 series
Relion 670 series 6 independent input channels
Introduction
Modules Software selected input ranges
I/O Capability
Mounting Flexibility 0-5, 0-10, 0-20, mA
Communication
1-5, 2-10, 4-20, mA
IED HMI
± 5, ± 10, ± 20 mA
Resolution: 16 bit
Accuracy: 0,1 %
Independent settable digital filters
Supervision of
Limits
Overflow
Max/Min Range
Mounting arrangements
670 series
Relion 670 series Several mounting alternatives
Introduction
Modules ½, ¾ and 1/1 rack size
I/O Capability
Mounting Flexibility
Flush-, Semi-flush, wall- and rack
Communication
mounting
IED HMI
IP 54 front protection flush mounting
Side by side
Rack, panel or surface mounting
670 series
Relion 670 series
Introduction 1/2, 3/4 or 1/1 of 19” wide
Modules Wiring cover
I/O Capability 6U = 266 mm high
Mounting Flexibility
Communication
205 - 245 mm deep
IED HMI
Suitable for new and retrofit
installations
Serial communication module
670 series
Relion 670 series Communication protocols
Introduction
Modules LON
I/O Capability
Mounting Flexibility
SPA
Communication IEC 60870-5-103
IED HMI
DNP 3.0
Alternative media
Glass fiber
Plastic fiber
Combination of glass & plastic
fiber
Max 1 module per IED
EIA-485 for DNP-3
670 series
Relion 670 series
Galvanic EIA-485
Introduction
Modules communication module for
I/O Capability DNP 3.0
Mounting Flexibility
Communication Either two or four wire
IED HMI
connection
Max 1 EIA-485 module per
IED
Mounting position for the
EIA-485 module is pos 312
on AD1
Line data communication module
670 series
Relion 670 series Two versions for fiber optic communication:
Introduction
Multi mode ST fiber 50/125 m or 62,5/125 m for short
Modules range
I/O Capability
Mounting Flexibility
Single mode FC fiber 8/125 m for medium and long range
Communication Transmission of 4 analog values and 8 binary signals
IED HMI
Transmission of up to 192 binary signals when no
analog
64 kbit communication channel in HDLC
Optical budget:
Long range 26 dB or up to typically 120 km
Medium range 20 dB or up to typically 80 km
Short range 11 dB 62,5/125 m and 7 dB 50/125 m
Galvanic X21 short range for connection to multiplexers
The IEEE/ANSI C37.94 standard format is used
Up to 4 modules per IED with restrictions for case size
Mounting position for the 64 kbit communication module
is on NUM, AD1 or AD2
Optical ethernet module
670 series
Module with two ports IEC 61850-8-1 protocol
Ethernet 100 Mbit/s link
One or two optical ports
Multimode fiber 62,5/125 m
ST fiberoptic connector
Optical budget 13 dB
Glass or Typical maximum distance between
fiber nodes, 1 km
Max one module located on A/D
converter one
Versatile selection of
Module with one port communication protocols
Internal communication bus
Optimized local control and monitoring
670 series
Relion 670 series
Direct interaction with IEDs without
Introduction
Modules any tools
I/O Capability
Mounting Flexibility Control of up to 30 apparatuses
Communication
IED HMI The exact presentation of your
switchgear arrangement on LCD
Easy to adapt the graphical display
to the changes in the process
The arrow keys provide easy
access to settings
All parameters can be read and set
via the local HMI
ANSI symbols in the HMI available
IEC
Quick access to important information
670 series
Relion 670 series
IED status indication LEDs
Introduction
Modules Green
I/O Capability
Steady: In service
Mounting Flexibility
Flashing: Internal failure
Communication
Dark: No power supply
IED HMI
Yellow
Steady: Disturbance
recorder triggered
Flashing: IED in test mode
Red
Steady: Trip command issued
Flashing: IED blocked
Measurements
Binary signals via indication LEDs
Relion® 650 series Ver. 1.3
Hardware
Relion® 650 series
Platform based
Few spare parts needed on module
level
Common module firmware
Easy to add hardware if needed
Minimized cost for maintenance and
training
Relion® 650 series
Time synchronization
Time synchronization – SNTP and DNP 3.0
IRIG-B serial interface
IEC
Communication
IEC 61850-8-1
Parallel Redundancy Protocol (PRP)
according to IEC 62439-3 Ed. 2
DNP 3.0
IEC 60870-5-103
ANSI
Dimension
1/1 x 19”, 3U (Ver. 1.2 and 1.3)
Mounting flexibility
Flush-, semi-flush, wall- and rack mounting
Side by side
Relion® 650 series
Communication & Processor Module, COM
Power supply module, PSM
Transformer module, TRM
IEC Transformer module (2nd), AIM
Binary input/output module, BIO
Binary input/output module, BIO, option
ANSI
Communication and processor module
650 series
Ethernet communication, LC optical
IEC61850-8-1, DNP3.0
Optical serial port, ST connection, IEC
60870-5-103 glass fiber
F
R Local HMI connection. RJ45
O IRIG-B, screw terminals
N Choice of communication
T and processor module with:
COM05: 12 binary inputs, TCP/IP
optical, IRIG-B, galvanic RS485 and
optical serial communication ports
COM03: TCP/IP optical with PRP
redundancy, IRIG-B, galvanic RS485
and optical serial communication ports
Power supply module
650 series
PSM01/02/03
Power supply modules from 24 to 30 V
DC, 48 to 250 V DC or 100 to 240 V AC
with 9 outputs, 3 of which with trip circuit
supervision
Internal fail (IRF) self-supervision contact
Two LEDs Battery and Ready
Transformer modules
650 series
TRM01/AIM01 module
10 analog inputs per module
8I+2V, 6I+4V, 4I+1I+5V, 4I+6V (TRM)
Sensitive current channel 0.1 / 0.5 A
6I+4V, 4I+1I+5V (AIM)
Input and output modules
650 series
I/O flexibility
Analoge inputs
10 or 20 analog inputs.
1A and 5A on the same CT
Binary inputs/outputs
14 – 50 binary inputs, 9 – 45 binary
outputs
Compression type or ring lug cable
termination
IED HMI
650 series
Efficient interaction with the IED
Direct interaction with IEDs without
any tools
IEC
Graphical display adapted to the
application
Local language support
Forcing of binary output when in test
mode
Monitoring
IED status indication LEDs
Measurements
Binary signals via indication LEDs
Disturbances and events
IED HMI
650 series
Control
Control of up to 8 apparatus
IEC The exact presentation of the
configured switchgear arrangement
Bypass operations
Settings
All parameters can be read and set
via the IED HMI
Five configurable push button
shortcuts with labels presented on
the display for different actions
IED HMI
650 series
Status indication LEDs indicate the
status of the IED:
Green
Steady: In service
Flashing: Internal failure
Yellow:
Steady: Disturbance recorder triggered
Flashing: IED in test mode
Red:
Steady: Trip command issued
Flashing: IED blocked
Indication of binary signals via 15 three-
color-state indication LEDs on up to
three pages