0% found this document useful (0 votes)
17 views46 pages

1MRG014097 en Relion 670-650 Series Hardware 650 1.3 IEC and ANSI

The document provides an overview of the Relion® 670/650 series hardware, detailing its modules, I/O capabilities, communication options, and mounting flexibility. It highlights the common hardware and software features, extensive I/O capabilities, and various modules for different functionalities, including power supply and synchronization. The document also discusses the design specifications and mounting arrangements suitable for new and retrofit installations.

Uploaded by

martinjara2000
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views46 pages

1MRG014097 en Relion 670-650 Series Hardware 650 1.3 IEC and ANSI

The document provides an overview of the Relion® 670/650 series hardware, detailing its modules, I/O capabilities, communication options, and mounting flexibility. It highlights the common hardware and software features, extensive I/O capabilities, and various modules for different functionalities, including power supply and synchronization. The document also discusses the design specifications and mounting arrangements suitable for new and retrofit installations.

Uploaded by

martinjara2000
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 46

Substation Automation Products

Relion® 670/650 series IEC and ANSI


Hardware

© ABB Group
1MRG014097
October 2013
Relion® 670/650 series hardware
Contents

 Relion® 670/650 series


 Introduction
 Modules
 I/O Capability
 Mounting Flexibility
 Communication
 IED HMI
Relion® 670 series
Hardware
Relion® 670 series

Relion 670 series


 Common hardware (HW) and
Introduction
Modules software (SW) for the entire 670
I/O Capability series
Mounting Flexibility
Communication  Function library according to IEC
IED HMI
61850
 Extensive analog and binary I/O
capability
 Type tested platform
Relion® 670 series

Relion 670 series


 Few spare parts on modular level
Introduction
Modules
 Type tested platform
I/O Capability
Mounting Flexibility
 Easy future extensions
Communication
IED HMI

Minimized cost for maintenance

ANSI
IEC
Relion® 670 series

Relion 670 series


 Ventilated casing with common
Introduction
Modules
look for all products
I/O Capability
 3 sizes - 1/2, 3/4 or 1/1 of 19”
Mounting Flexibility
Communication  6U high (266mm)
IED HMI

 Small or large HMI unit


Hardware structure
670 series
Relion 670 series  Transformer Input Module TRM
Introduction
Modules
6I + 6U, 9I + 3U or 12I
I/O Capability
 One or two - TRM1 & TRM2 for 12 or
Mounting Flexibility
Communication
24 analog CT or VT inputs
IED HMI
 Analog Digital Conversion module
ADM1 and ADM2 for TRM inputs
 Central Processing Unit NUM
 GPS time synchronization module
GSM (option)
 Time synchronization via binary signal
and communication ports IRIG-B
 Binary Input / Output modules BIM,
SOM, BOM, IOM, MIM
 Power supply module PSM
Hardware platform
670 series
 IED 670
Power
Relion 670 series Analogue A/D Main GPS Binary Binary Binary Binary Binary mA
Input Conversion Processing Synch I/O I/O I/O I/O I/O Input Supply
Module Module Module Module Module Module Module Module Module Module Module
Introduction
TRM AD1 NUM GSM BIM BIM BIM BOM BOM MIM
Modules
I/O Capability PCU
Mounting Flexibility
Logics CAN
Communication 1Mbit/s
IED HMI 6I A/D
6U
OEM
~
~ ~
~ LDCM
Comm-
uni-
cation
I/O I/O I/O I/O I/O mA
View from rear side with contacts
670 series
Relion 670 series
Introduction
Modules
I/O Capability
Mounting Flexibility
Communication
IED HMI
View from rear side with ringlugs
670 series

Relion 670 series


Introduction
Modules
I/O Capability
Mounting Flexibility
Communication
IED HMI
Numerical module
670 series

Relion 670 series  Main Controller/CPU type


Introduction
Modules
IBM 3200 PowerPC 750FX/GX,
I/O Capability
600 MHz
Mounting Flexibility
Communication
 Internal communication with cPCI bus
IED HMI 100 Mbit/s
 Memory
 Up to 128 Mb FLASH
 Up to 256 Mb DRAM
 Cycle time in 670 series
 1 or 3 ms for protection
 8 or 100 ms for logic
Interfaces on the numerical module
670 series

Relion 670 series


Introduction
Modules
Motherboard interface
I/O Capability
Mounting Flexibility
Communication
IED HMI
Mounting position for serial
communication module with
SPA, LON, IEC -103

Mounting position for IRIG-B


module

Mounting positions for two


64 kbit communication
modules

Internal communication cPCI


bus
Analog / digital conversion module
670 series

Relion 670 series


Analog inputs from transformer
Introduction module
Modules
I/O Capability
Mounting Flexibility Mounting position for Optical
Communication
Ethernet module (only on AD1)
IED HMI

cPCIbus

Mounting positions for EIA-485


module (only on AD1)

Mounting positions for 2 extra


LDCM modules (only on AD1)
Transformer input module
670 series

Relion 670 series


Introduction
 Up to 12 analog inputs can be
Modules connected
I/O Capability
Mounting Flexibility  0 - 6 U, 110-220 V rated range
Communication 50/60 Hz
IED HMI
 6 -12 I, 1 A or 5 A rated current
 Isolation barrier preventing
disturbances to enter into IED
 Adapt measured values to static
circuitry
Standardized transformer modules
670 series

Relion 670 series


Introduction Transformer module (TRM 12) 1A 5A 110/220 V
Modules
I/O Capability 6I and 6U 6 6
Mounting Flexibility
6I and 6U 6 6
Communication
IED HMI 9I + 3U 9 3
9I + 3U 9 3
9I + 3U 5 4 3
12I 12
12I 12
6I 6
5I + 5U 5 5
Power supply module
670 series

Relion 670 series  Input range: 24-60 V DC


Introduction
Modules  Input range: 90-250 V DC
I/O Capability
Mounting Flexibility  Internal fail relay output
Communication
IED HMI  DC/DC Converter provides full
isolation between IED and
external battery system
GPS time synchronization module
670 series
Relion 670 series  For multi-terminal current differential
Introduction
Modules
protection
I/O Capability  1 MHz High Accuracy output; < 1μs
Mounting Flexibility
Communication  Minute pulse / IRIG-B
IED HMI
 Accuracy 1ms (Not suitable for differential
protection)

 IEC 61850-8-1 synchronization


 Accuracy < 1 ms
 LON synchronization
 Accuracy < 2 ms

GPS
Connection
GCM
to antenna
module CAN bus
IRIG-B
670 series

Relion 670 series


 The IRIG interface to the IED
Introduction
Modules supplies two possible
I/O Capability synchronization methods, IRIG-
Mounting Flexibility
B and PPS
Communication
IED HMI  IRIG-B is a protocol used only
for time synchronization
 An optical PPS signal can be
supplied to the optical interface
of the IRIG module
 Max 1 IRIG-B module per IED
 Mounting position for the IRIG-B
module is pos 302 on NUM
GPS antenna and coaxial cable
670 series
Relion 670 series
Introduction
 Accurate synchronization of
Modules sampled data
I/O Capability
Mounting Flexibility  1 microsecond accuracy
Communication
IED HMI  Line Differential Protection
applications with switched
communication network
 Wide Area Protection and Phasor
Measurement Unit applications
 SMA contact for connection to GSM

Accurate time synchronization for


each installation
I/O-modules
670 series
Relion 670 series
Introduction
 Full 19” case with 24 binary analog
Modules
inputs and up to 11 (6 with ring lug)
I/O Capability I/O modules
Mounting Flexibility
Communication  Full 19” case with 12 binary analog
IED HMI inputs and up to 11 (7 with ring lug)
IEC I/O modules
 ¾ x 19” case with 24 analog inputs
and up to 7 (3 with ring lug) I/O
modules
 ¾ x 19” case with 12 analog inputs
and up to 7 (4 with ring lug) I/O
modules
ANSI

 ½ x 19” case with 12 analog inputs


and up to 3 (2 with ring lug) I/O
modules
Extensive I/O capability enables unique
function integration
EMC enhanced binary input module
670 series

Relion 670 series  16 independent Binary Inputs


Introduction
Modules  Increased interference immunity
I/O Capability
2 x IEC requirements for 50 ms
Mounting Flexibility
Communication  Debounce filter, T = 5 ms
IED HMI
 Oscillation suppression detection within
1 s; > 0 - 40 Hz
 No pulse counting Auxiliary voltage
 24/30 V DC (± 20 %)

Increased interference  48/60 V DC (± 20 %)


[mA]
immunity  110/125 V DC (± 20 %)
30

 220/250 V DC (± 20 %)
 Threshold voltage 60 %

1
35 70 [ms]
Binary input module for pulse counting
670 series

Relion 670 series  16 independent Binary Inputs


Introduction
Modules  Debounce filter, T = 5 ms
I/O Capability
Mounting Flexibility  Oscillation suppression detection within
Communication 1 s; > 0 - 40 Hz
IED HMI
 Pulse counting available for all inputs
 Auxiliary voltages
 24/30 V DC (± 20 %)
 48/60 V DC (± 20 %)
Standard interference immunity  110/125 V DC (± 20 %)
[mA]  220/250 V DC (± 20 %)
30
 Threshold voltage 60 %

1
3,5 7 [ms]
Binary output module
670 series

Relion 670 series  Two variants


Introduction
Modules  24 single output relays
I/O Capability
Mounting Flexibility  12 double pole command
Communication output relays
IED HMI
EMC enhanced binary input/output module
670 series

Relion 670 series  8 independent Binary Inputs and 10 +


Introduction
Modules
2 Binary Output relays
I/O Capability
 Increased interference immunity 2 x
Mounting Flexibility
Communication
IEC for 50 ms
IED HMI
 Fixed filter time 3/5 ms
 Auxiliary voltage
 24/30 V DC (± 20 %)
 48/60 V DC (± 20 %)
 110/125 V DC (± 20 %)
[mA]
30 Increased interference  220/250 V DC (± 20 %)
immunity

1
35 70 [ms]
Static output module
670 series

Relion 670 series


 High Speed Applications
Introduction
Modules  6 static binary outputs
I/O Capability
Mounting Flexibility  6 change-over contacts
Communication
IED HMI
mA input module
670 series

Relion 670 series  6 independent input channels


Introduction
Modules  Software selected input ranges
I/O Capability
Mounting Flexibility  0-5, 0-10, 0-20, mA
Communication
 1-5, 2-10, 4-20, mA
IED HMI

 ± 5, ± 10, ± 20 mA
 Resolution: 16 bit
 Accuracy: 0,1 %
 Independent settable digital filters
 Supervision of
 Limits
 Overflow
 Max/Min Range
Mounting arrangements
670 series

Relion 670 series  Several mounting alternatives


Introduction
Modules  ½, ¾ and 1/1 rack size
I/O Capability
Mounting Flexibility
 Flush-, Semi-flush, wall- and rack
Communication
mounting
IED HMI
 IP 54 front protection flush mounting
 Side by side
Rack, panel or surface mounting
670 series

Relion 670 series


Introduction  1/2, 3/4 or 1/1 of 19” wide
Modules Wiring cover
I/O Capability  6U = 266 mm high
Mounting Flexibility
Communication
 205 - 245 mm deep
IED HMI

Suitable for new and retrofit


installations
Serial communication module
670 series

Relion 670 series  Communication protocols


Introduction
Modules  LON
I/O Capability
Mounting Flexibility
 SPA
Communication  IEC 60870-5-103
IED HMI
 DNP 3.0
 Alternative media
 Glass fiber
 Plastic fiber
 Combination of glass & plastic
fiber
 Max 1 module per IED
EIA-485 for DNP-3
670 series
Relion 670 series
 Galvanic EIA-485
Introduction
Modules communication module for
I/O Capability DNP 3.0
Mounting Flexibility
Communication  Either two or four wire
IED HMI
connection
 Max 1 EIA-485 module per
IED
 Mounting position for the
EIA-485 module is pos 312
on AD1
Line data communication module
670 series

Relion 670 series  Two versions for fiber optic communication:


Introduction
 Multi mode ST fiber 50/125 m or 62,5/125 m for short
Modules range
I/O Capability
Mounting Flexibility
 Single mode FC fiber 8/125 m for medium and long range
Communication  Transmission of 4 analog values and 8 binary signals
IED HMI
 Transmission of up to 192 binary signals when no
analog
 64 kbit communication channel in HDLC
 Optical budget:
 Long range 26 dB or up to typically 120 km
 Medium range 20 dB or up to typically 80 km
 Short range 11 dB 62,5/125 m and 7 dB 50/125 m
 Galvanic X21 short range for connection to multiplexers
 The IEEE/ANSI C37.94 standard format is used
 Up to 4 modules per IED with restrictions for case size
 Mounting position for the 64 kbit communication module
is on NUM, AD1 or AD2
Optical ethernet module
670 series

Module with two ports  IEC 61850-8-1 protocol


 Ethernet 100 Mbit/s link
 One or two optical ports
 Multimode fiber 62,5/125 m
 ST fiberoptic connector
 Optical budget 13 dB
Glass or  Typical maximum distance between
fiber nodes, 1 km
 Max one module located on A/D
converter one

Versatile selection of
Module with one port communication protocols
Internal communication bus
Optimized local control and monitoring
670 series
Relion 670 series
 Direct interaction with IEDs without
Introduction
Modules any tools
I/O Capability
Mounting Flexibility  Control of up to 30 apparatuses
Communication
IED HMI  The exact presentation of your
switchgear arrangement on LCD
 Easy to adapt the graphical display
to the changes in the process
 The arrow keys provide easy
access to settings
 All parameters can be read and set
via the local HMI

 ANSI symbols in the HMI available

IEC
Quick access to important information
670 series

Relion 670 series


 IED status indication LEDs
Introduction
Modules  Green
I/O Capability
Steady: In service
Mounting Flexibility
Flashing: Internal failure
Communication
Dark: No power supply
IED HMI

 Yellow
Steady: Disturbance
recorder triggered
Flashing: IED in test mode

 Red
Steady: Trip command issued
Flashing: IED blocked

 Measurements
 Binary signals via indication LEDs
Relion® 650 series Ver. 1.3
Hardware
Relion® 650 series

 Platform based
 Few spare parts needed on module
level
 Common module firmware
 Easy to add hardware if needed
 Minimized cost for maintenance and
training
Relion® 650 series

 Time synchronization
 Time synchronization – SNTP and DNP 3.0
 IRIG-B serial interface

IEC
 Communication
 IEC 61850-8-1
 Parallel Redundancy Protocol (PRP)
according to IEC 62439-3 Ed. 2
 DNP 3.0
 IEC 60870-5-103

ANSI
 Dimension
 1/1 x 19”, 3U (Ver. 1.2 and 1.3)

 Mounting flexibility
 Flush-, semi-flush, wall- and rack mounting
 Side by side
Relion® 650 series

 Communication & Processor Module, COM


 Power supply module, PSM
 Transformer module, TRM
IEC  Transformer module (2nd), AIM
 Binary input/output module, BIO
 Binary input/output module, BIO, option

ANSI
Communication and processor module
650 series

 Ethernet communication, LC optical


IEC61850-8-1, DNP3.0
 Optical serial port, ST connection, IEC
60870-5-103 glass fiber
F
R  Local HMI connection. RJ45
O  IRIG-B, screw terminals
N  Choice of communication
T and processor module with:
 COM05: 12 binary inputs, TCP/IP
optical, IRIG-B, galvanic RS485 and
optical serial communication ports
 COM03: TCP/IP optical with PRP
redundancy, IRIG-B, galvanic RS485
and optical serial communication ports
Power supply module
650 series

 PSM01/02/03
 Power supply modules from 24 to 30 V
DC, 48 to 250 V DC or 100 to 240 V AC
with 9 outputs, 3 of which with trip circuit
supervision
 Internal fail (IRF) self-supervision contact
 Two LEDs Battery and Ready
Transformer modules
650 series

TRM01/AIM01 module
 10 analog inputs per module
 8I+2V, 6I+4V, 4I+1I+5V, 4I+6V (TRM)
 Sensitive current channel 0.1 / 0.5 A
 6I+4V, 4I+1I+5V (AIM)
Input and output modules
650 series

 I/O flexibility
 Analoge inputs
 10 or 20 analog inputs.
 1A and 5A on the same CT
 Binary inputs/outputs
 14 – 50 binary inputs, 9 – 45 binary
outputs
 Compression type or ring lug cable
termination
IED HMI
650 series

 Efficient interaction with the IED


 Direct interaction with IEDs without
any tools
IEC

 Graphical display adapted to the


application
 Local language support
 Forcing of binary output when in test
mode

 Monitoring
 IED status indication LEDs
 Measurements
 Binary signals via indication LEDs
 Disturbances and events
IED HMI
650 series

 Control
 Control of up to 8 apparatus
IEC  The exact presentation of the
configured switchgear arrangement
 Bypass operations

 Settings
 All parameters can be read and set
via the IED HMI

 Five configurable push button


shortcuts with labels presented on
the display for different actions
IED HMI
650 series

 Status indication LEDs indicate the


status of the IED:
 Green
 Steady: In service
 Flashing: Internal failure
 Yellow:
 Steady: Disturbance recorder triggered
 Flashing: IED in test mode
 Red:
 Steady: Trip command issued
 Flashing: IED blocked

 Indication of binary signals via 15 three-


color-state indication LEDs on up to
three pages