Wind Load Calculations ASCE 7-10
Wind Load Calculations ASCE 7-10
1013
where
qz = 0.00256KzKztKdV2 (Eq. 27.3-1)
B= 68 ft
Wind Direction +X ### -0.5
-0.7
L= 59 ft
L= 68 ft
-0.7 -0.7 -0.7
### 0.8
B= 59 ft
Wind Direction +Z
AAES ENGINEERING, INC. Project no. 1013
Design Wind Loads on Open Buildings and Other Structures (ASCE 7-05 - 6.5.15)
@ Elev 23.00 with grade elevation @ 0.00
F = qzGCfAf (Eq. 6-28)
where
qz = 0.00256KzKztKdV2I (Eq. 6-15)
Design Wind Loads on Open Buildings and Other Structures (ASCE 7-05 - 6.5.15)
@ Elev 34.00 with grade elevation @ 0.00
F = qzGCfAf (Eq. 6-28)
where
qz = 0.00256KzKztKdV2I (Eq. 6-15)
Design Wind Loads on Open Buildings and Other Structures (ASCE 7-05 - 6.5.15)
@ Elev 45.00 with grade elevation @ 0.00
F = qzGCfAf (Eq. 6-28)
where
qz = 0.00256KzKztKdV2I (Eq. 6-15)
Design Wind Loads on Open Buildings and Other Structures (ASCE 7-05 - 6.5.15)
@ Elev 56.00 with grade elevation @ 0.00
F = qzGCfAf (Eq. 6-28)
where
qz = 0.00256KzKztKdV2I (Eq. 6-15)
Design Wind Loads on Open Buildings and Other Structures (ASCE 7-05 - 6.5.15)
@ Elev 67.00 with grade elevation @ 0.00
F = qzGCfAf (Eq. 6-28)
where
qz = 0.00256KzKztKdV2I (Eq. 6-15)
WIND LOADS
WIND (W - E)
1.0 x Fx / 4 (0' TO 0 0 #VALUE! #REF! #REF! #REF! #VALUE!
67') (LBS)
WIND (E - W)
0.5 x Fx / 4 (0' TO 67') 0 0 #VALUE! #REF! #REF! #REF! #VALUE!
(LBS)
WIND (N - S)
0.75 x Fz / 4 (0' TO 67') 0 0 #VALUE! #REF! #REF! #REF! #VALUE!
(LBS)
WIND (S - N)
1.0 x
0 0 #VALUE! #REF! #REF! #REF! #VALUE!
Fz / 4 (0' TO 67')
(LBS)
Prep By ERK Date 3/4/25 Project Cooler vent Modification, Brooksville, GA Sheet of
Chkd By JE Date 3/4/25 Subject Load Summary
Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10
X-Dir
Basic Wind Speed V = 115 mph For exposure B, Kz = 0.57
Exposure Category = C Z- For exposure C, Kz = 0.85
Dir
Importance Factor I = 1.00 For exposure D, Kz = 1.03
Risk Category = II
Design Wind Loads on Open Buildings and Other Structures (ASCE 7-10) 1 2 3
@ Elev 0.00 with grade elevation @ 0.00 col
F = qzGCfAf (Eq. 27…….) 35' 18'
where
A
qz = 0.00256KzKztKdV2 (Eq. 27.3-1)
28'
For z= 0.0 ft. Kz = ### (Table 27.3-1)
Kzt = (1 + K1K2K3) 2
(Eq. 26.8-1) K1 = 0 K2 = 0 K3 = 0 (Fig 26.8-1)
B
= 1 + 0.00 x ### x ### 2
= 1.00
Kd = 0.85 (Table 26.6-1) 30'
Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10
Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10
C-3
Width 9.20
Factor 0.50 Direction GZ
Elevation Height, z Kz p = qG UDL Col No's Staad input
36' 36' 1.02 24.97 114.8 257 257 TRAP GZ 114.8 132
70' 70' 1.17 28.72 132.1 258 258 TRAP GZ 132.1 142
99' 99' 1.26 30.88 142.0 259 259 TRAP GZ 142 154.7
148' 148' 1.37 33.63 154.7 260 260 TRAP GZ 154.7 164
197' 197' 1.46 35.72 164.3 261 261 TRAP GZ 164.3 171
242' 242' 1.52 37.30 171.6 262 262 TRAP GZ 171.6 177
286' 286' 1.58 38.62 177.6 263 263 TRAP GZ 177.6 182
323' 323' 1.62 39.62 182.2 264 264 TRAP GZ 182.2 182
AAES ENGINEERING, INC. Project no.
Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10
X-Dir
Basic Wind Speed V = 115 mph For exposure B, Kz =
Exposure Category = C Z- For exposure C, Kz =
Dir
Importance Factor I = 1.00 For exposure D, Kz =
Risk Category = II
Design Wind Loads on Open Buildings and Other Structures (ASCE 7-10) 1 2 3
@ Elev 0.00 with grade elevation @ 0.00 col
F = qzGCfAf (Eq. 27…….) 35' 18'
where
A
qz = 0.00256KzKztKdV2 (Eq. 27.3-1)
28'
For z= 0.0 ft. Kz = ### (Table 27.3-1)
Kzt = (1 + K1K2K3)2 (Eq. 26.8-1) K1 = 0 K2 = 0 K3 = 0 (Fig 26.8-1)
B
= 1 + 0.00 x ### x ### 2
= 1.00
Kd = 0.85 (Table 26.6-1) 30'
Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10
Velocity Pressure Exposure Coefficient Kz (Table 27.3 Grade elevation @ 0'
Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10
C-3
Width 9.20
Factor 0.80 Direction GZ
Elevation Height, z Kz p = qG UDL Col No's Staad input
36' 36' 1.02 24.97 183.8 257 257 TRAP GZ -183.8 -21
70' 70' 1.17 28.72 211.4 258 258 TRAP GZ -211.4 -22
99' 99' 1.26 30.88 227.3 259 259 TRAP GZ -227.3 -24
148' 148' 1.37 33.63 247.5 260 260 TRAP GZ -247.5 -26
197' 197' 1.46 35.72 262.9 261 261 TRAP GZ -262.9 -27
242' 242' 1.52 37.30 274.5 262 262 TRAP GZ -274.5 -28
286' 286' 1.58 38.62 284.2 263 263 TRAP GZ -284.2 -29
323' 323' 1.62 39.62 291.6 264 264 TRAP GZ -291.6 -29
AAES ENGINEERING, INC. Project no. 1173
Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Cyclone Wind load calculations per IBC - 2006 and ASCE 7-05
Velocity Pressure,
qz = 0.00256KzKztKdV2I (Eq. 6-15)
Topographic Factor Kzt = 1.00
Wind Directionality FactorKd = 0.95 (Table 6.4) For Round tanks
Gust Effect Factor G = 0.85 (Section 6.5.8.1) Gust Factor for Rigid Structures
Force Coefficient Cf = 0.80 (h/D = 2.0 ) (Figure 29.5-1)
Shear:
V = (766.8 + 734.3) x 45 = 33775 lb
2
Moment:
2 2
M = 734.3 x 45 + 32.50 x 45
2 3 734.3lb/ft
###
M = 743478.8 + ### = 765416 lb-ft
DEAD LOAD:
Weight of Cyclone = 62.00 KIPS
62.00
Weight = FDL = = 7.750 kips per point
8
Operating LOAD:
Operating Weight = 258.00 KIPS
258.00
Oper. Weight = FLL = = 32.250 kips per point
8
Y 23.0 f
S1
N= 8 R = ### ft
S8
Polar Moment of Inertia J :
S2
J = N • R2 ® J = ### in.4
J
Ix= Iy= I = ® I = 529 in.4
S7 S3 X 2
S6 S4
S5
Comparision of Loads with and without Up-Down Wind Load on free standing Cyclone
Equipment load
Maximum considered earthquake spectral response acceleration at short period of 0.2 second (Ss) = ### g
R= 1.5 Ordinary steel concentrically braced frames (With Unlimited heig(Table 15.4-1)
Cs = SDS.I = ### x ### = 0.076 (Eq 12.8-2)
R 1.5
The Seismic Response Coefficient,CS, shall not be less than the following:
..
.
V= Cs W = 0.08 W (Eq 12.8-1)
Prep By MCR Date 3/4/25 Project Cooler vent Modification, Brooksville, GA Sheet of
Chkd By ERK Date 3/4/25 Subject Wind Load Calculations as per ASCE 7-10
where
qz = 0.00256KzKztKdV2 (Eq. 29.3-1)
= 38 lbs/ft2
Live loads
All grating Floors + Concrete with metal deck floors = 100 psf
At roof level at 44.4m = 50 psf
Dead loads:
All Grating Floors = 25 psf
Hand Rail and Toe Plate = 10 lb/ft
Concrete Slab with W/2" Metal Deck = 75 psf