Wind Load Calculations ASCE 7-10

The document outlines wind load calculations for a preheater tower project as per ASCE 7-10 standards, detailing parameters such as basic wind speed, exposure category, and importance factor. It includes specific equations and values for design wind loads at various elevations, along with internal pressure coefficients and wind direction effects. Additionally, it provides seismic design parameters relevant to the project, including risk category and seismic response coefficients.

Uploaded by

Sreenivas Bandla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
20 views20 pages

Wind Load Calculations ASCE 7-10

The document outlines wind load calculations for a preheater tower project as per ASCE 7-10 standards, detailing parameters such as basic wind speed, exposure category, and importance factor. It includes specific equations and values for design wind loads at various elevations, along with internal pressure coefficients and wind direction effects. Additionally, it provides seismic design parameters relevant to the project, including risk category and seismic response coefficients.

Uploaded by

Sreenivas Bandla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 20

AAES ENGINEERING, INC. Project no.

1013

Prep By ERK Date 3/4/25 Project Preheater Tower Sheet of


Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10

Basic Wind Speed V = 120 mph (Fig 26.5-1)


Exposure Category = C
Importance Factor I = 1.00
Risk Category = III
Enclosure Classification = Partially Enclosed

Design Wind Loads Partially Enclosed Buildings


@ Elev 0.00 with grade elevation @ 0.00
p = qzGCp - qi(GCpi) (Eqn 27.4-1)

where
qz = 0.00256KzKztKdV2 (Eq. 27.3-1)

For z= 0.0 ft. Kz = ### (Table 27.3-1)


Kzt = (1 + K1K2K3)2 (Eq. 26.8-1) K1 = 0 K2 = 0 K3 = 0 (Fig 26.8-1)
= 1 + 0.00 x ### x ### 2
= 1.00
Kd = 0.85 (Table 26.6-1)

\ qz = 0.00256 x ### x ### x ### x 120 2


x ###
= 27 lbs/ft2

G= 0.85 (Section 26.9.4)

Internal Pressure Coefficient, GCpi = 0.55 (Table 26.11-1)

Wind in +X Direction (Cp Values)

L/B = 0.87 L/B = 0-1


-0.7

B= 68 ft
Wind Direction +X ### -0.5

-0.7

L= 59 ft

Wind in +Z Direction (Cp Values)

L/B = 1.15 L/B = 1-2


-0.3

L= 68 ft
-0.7 -0.7 -0.7

### 0.8

B= 59 ft

Wind Direction +Z
AAES ENGINEERING, INC. Project no. 1013

Prep By ERK Date 3/4/25 Project Preheater Tower Sheet of


Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10

Design Wind Loads on Open Buildings and Other Structures (ASCE 7-05 - 6.5.15)
@ Elev 23.00 with grade elevation @ 0.00
F = qzGCfAf (Eq. 6-28)

where
qz = 0.00256KzKztKdV2I (Eq. 6-15)

For z= 23.0 ft. Kz = ERROR (Table 6-3)


Kzt = (1 + K1K2K3)2 (Eq. 6-3) ; K1 = 0 K2 = 0 K3 = 0 (Fig. 6-4)
= 1 + 0.00 x ### x ### 2
= 1.00
Kd = 0.85 (Table 6-4) Conservative

\ qz = 0.00256 x ERROR x ### x ### x 0 2


x ###
= ### lbs/ft2

G= 0.85 (Section 6.5.8.1)

Cf = #REF! (Fig. 6-6) ###

\ F= ### x ### x ### = #VALUE! lbs/ft2

Basic Wind Speed V = 120 mph


Exposure Category = c
Importance Factor I = 1.00
Occupancy Category = III

Design Wind Loads on Open Buildings and Other Structures (ASCE 7-05 - 6.5.15)
@ Elev 34.00 with grade elevation @ 0.00
F = qzGCfAf (Eq. 6-28)

where
qz = 0.00256KzKztKdV2I (Eq. 6-15)

For z= 34.0 ft. Kz = ### (Table 6-3)


Kzt = (1 + K1K2K3)2 (Eq. 6-3) ; K1 = 0 K2 = 0 K3 = 0 (Fig. 6-4)
= 1 + 0.00 x ### x ### 2
= 1.00
Kd = 0.85 (Table 6-4) Conservative

\ qz = 0.00256 x ### x ### x ### x 120 2


x ###
= 32 lbs/ft2

G= 0.85 (Section 6.5.8.1)

Cf = #REF! (Fig. 6-6) ###

\ F= 32 x ### x ### = #REF! lbs/ft2


AAES ENGINEERING, INC. Project no. 1013

Prep By ERK Date 3/4/25 Project Preheater Tower Sheet of


Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10

Basic Wind Speed V = 120 mph


Exposure Category = C
Importance Factor I = 1.00
Occupancy Category = III

Design Wind Loads on Open Buildings and Other Structures (ASCE 7-05 - 6.5.15)
@ Elev 45.00 with grade elevation @ 0.00
F = qzGCfAf (Eq. 6-28)

where
qz = 0.00256KzKztKdV2I (Eq. 6-15)

For z= 45.0 ft. Kz = ### (Table 6-3)


Kzt = (1 + K1K2K3)2 (Eq. 6-3) ; K1 = 0 K2 = 0 K3 = 0 (Fig. 6-4)
= 1 + 0.00 x ### x ### 2
= 1.00
Kd = 0.85 (Table 6-4) Conservative

\ qz = 0.00256 x ### x ### x ### x 120 2


x ###
= 34 lbs/ft2

G= 0.85 (Section 6.5.8.1)

Cf = #REF! (Fig. 6-6) ###

\ F= 34 x ### x ### = #REF! lbs/ft2

Basic Wind Speed V = 120 mph


Exposure Category = C
Importance Factor I = 1.00
Occupancy Category = III

Design Wind Loads on Open Buildings and Other Structures (ASCE 7-05 - 6.5.15)
@ Elev 56.00 with grade elevation @ 0.00
F = qzGCfAf (Eq. 6-28)

where
qz = 0.00256KzKztKdV2I (Eq. 6-15)

For z= 56.0 ft. Kz = ### (Table 6-3)


Kzt = (1 + K1K2K3)2 (Eq. 6-3) ; K1 = 0 K2 = 0 K3 = 0 (Fig. 6-4)
= 1 + 0.00 x ### x ### 2
= 1.00
Kd = 0.85 (Table 6-4) Conservative

\ qz = 0.00256 x ### x ### x ### x 120 2


x ###
= 35 lbs/ft2

G= 0.85 (Section 6.5.8.1)

Cf = #REF! (Fig. 6-6) ###

\ F= 35 x ### x ### = #REF! lbs/ft2


AAES ENGINEERING, INC. Project no. 1013

Prep By ERK Date 3/4/25 Project Preheater Tower Sheet of


Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10

Basic Wind Speed V = 0 mph


Exposure Category = 0
Importance Factor I = 0.00
Occupancy Category = 0

Design Wind Loads on Open Buildings and Other Structures (ASCE 7-05 - 6.5.15)
@ Elev 67.00 with grade elevation @ 0.00
F = qzGCfAf (Eq. 6-28)

where
qz = 0.00256KzKztKdV2I (Eq. 6-15)

For z= 67.0 ft. Kz = ERROR (Table 6-3)


Kzt = (1 + K1K2K3)2 (Eq. 6-3) ; K1 = 0 K2 = 0 K3 = 0 (Fig. 6-4)
= 1 + 0.00 x ### x ### 2
= 1.00
Kd = 0.00 (Table 6-4) Conservative

\ qz = 0.00256 x ERROR x ### x ### x 0 2


x ###
= ### lbs/ft2

G= 0.00 (Section 6.5.8.1)

Cf = 0.0 (Fig. 6-6) 0

\ F= ### x ### x 0.0 = #VALUE! lbs/ft2

Basic Wind Speed V = 0 mph


Exposure Category = 0
Importance Factor I = 0.00
Occupancy Category = 0
AAES ENGINEERING, INC. Project no. 1013

Prep By ERK Date 3/4/25 Project Preheater Tower Sheet of


Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10

WIND LOADS

Wind along X- Direction :


B= 14 FT.
Bz = 15.0 FT.
LEVEL 0 ' ### 12 ' #################################
WIND PRESSURE (PSF) 0.00 0.00 #VALUE! #REF! #REF! #REF! #VALUE!

HEIGHT BETWEEN LEVELS:


6.00 11.50 11.00 11.00 11.00 11.00 9.50
DH (FT)

Fx = qDHBz 0 0 #VALUE! #REF! #REF! #REF! #VALUE!

WIND (W - E)
1.0 x Fx / 4 (0' TO 0 0 #VALUE! #REF! #REF! #REF! #VALUE!
67') (LBS)

WIND (E - W)
0.5 x Fx / 4 (0' TO 67') 0 0 #VALUE! #REF! #REF! #REF! #VALUE!
(LBS)

Wind along Z- Direction :


B= 11.5 FT.
Bx = 12.5 FT.
LEVEL 0 ' ### 12 ' #################################
WIND PRESSURE (PSF) 0.00 0.00 #VALUE! #REF! #REF! #REF! #VALUE!

HEIGHT BETWEEN LEVELS:


6.00 11.50 11.00 11.00 11.00 11.00 9.50
DH (FT)

Fz = qDHBx 0 0 #VALUE! #REF! #REF! #REF! #VALUE!

WIND (N - S)
0.75 x Fz / 4 (0' TO 67') 0 0 #VALUE! #REF! #REF! #REF! #VALUE!
(LBS)

WIND (S - N)
1.0 x
0 0 #VALUE! #REF! #REF! #REF! #VALUE!
Fz / 4 (0' TO 67')
(LBS)
Prep By ERK Date 3/4/25 Project Cooler vent Modification, Brooksville, GA Sheet of
Chkd By JE Date 3/4/25 Subject Load Summary

WIND DESIGN PARAMETERS :-


Design Code : IBC 2006 and ASCE 7-10
Risk Category = II (Table 1.5-1 ASCE 7-10)
Basic Wind Speed V = 115 mph
Exposure Category = C (Section 26.7.3 ASCE 7-10)
Gust Effect Factor G = 0.85 (Section 26.9.1, ASCE 7-10)
Wind Directionality Factor Kd = 0.90 (Table 26.6-1, ASCE 7-10)

SEISMIC DESIGN PARAMETERS :-


Design Code : IBC 2006 and ASCE 7-10
Risk Category = II (Table 1.1 ASCE 7-10)
Site Class = D
Importance Factor I = 1 (Table 11.5.1 ASCE 7-10)
Maximum considered earthquake spectral response acceleration at a period of 1 second (S 1) = 0.066 g
Maximum considered earthquake spectral response acceleration at short periods of 0.2 secs (Ss) = 0.107 g
Spectral Acceleration Coefficien SDS = 0.115
SD1 = 0.106
Seismic Design Category = D
Basic Seismic Force Resisting System = Ordinary steel concentrically braced frames (With Unlimited height)
Response Modification Factor R = 1.5 (Table 15.4-1)
System Overstrength Factor mo = 1.0 (Table 15.4-1)
Deflection Amplification Factor Cd = 1.5 (Table 15.4-1)
Seismic Response Coefficient Cs = 0.076 W
W: Effective Seismic Weight of the Structure per section 12.7.2
Analysis Procedure Equivalent Lateral Force Procedure (Section 12.8 ASCE 7-10)
AAES ENGINEERING, INC. Project no.

Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10
X-Dir
Basic Wind Speed V = 115 mph For exposure B, Kz = 0.57
Exposure Category = C Z- For exposure C, Kz = 0.85
Dir
Importance Factor I = 1.00 For exposure D, Kz = 1.03
Risk Category = II

Design Wind Loads on Open Buildings and Other Structures (ASCE 7-10) 1 2 3
@ Elev 0.00 with grade elevation @ 0.00 col
F = qzGCfAf (Eq. 27…….) 35' 18'

where
A
qz = 0.00256KzKztKdV2 (Eq. 27.3-1)

28'
For z= 0.0 ft. Kz = ### (Table 27.3-1)
Kzt = (1 + K1K2K3) 2
(Eq. 26.8-1) K1 = 0 K2 = 0 K3 = 0 (Fig 26.8-1)
B
= 1 + 0.00 x ### x ### 2
= 1.00
Kd = 0.85 (Table 26.6-1) 30'

\ qz = 0.00256 x ### x ### x ### x 115 2


x ###
C
= 24.4 lbs/ft2

G = 0.85 (Section 26.9.4)


34'
Cf = 1.30 (Fig. 29.5-1) for h/D = 6.2 Cf = ### taken Wind-ward side facto = 0.80
Lee-ward side factor = 0.50
D
PLAN
Grade Elevation = 0 ft
Top Plan Elevatio = 323 ft
Plan Dimension = 52 x 57 ft
AAES ENGINEERING, INC. Project no.

Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10

Velocity Pressure Exposure Coefficient Kz (Table 27.3Grade elevation @ 0'

WIND LOAD IN DIRECTION +X


COLUMN A-1 B-1 C-1
Width 14.05 29.165 32.34
Factor Cf = 0.80 Direction GX 0.80 Direction GX 0.80 Direction GX
Elevation Height, z Kz p = qG UDL Col No's Staad input UDL Col No'sStaad input UDL Col No's Staad input
36' 36' 1.02 24.97 280.6 1 1 TRAP GX 280.6 322.8 582.5 17 17 TRAP GX 582.5 670.1 645.9 33 33 TRAP GX 645.9 743
70' 70' 1.17 28.72 322.8 2 2 TRAP GX 322.8 347.1 670.1 18 18 TRAP GX 670.1 720.5 743.0 34 34 TRAP GX 743 798.9
99' 99' 1.26 30.88 347.1 3 3 TRAP GX 347.1 378 720.5 19 19 TRAP GX 720.5 784.6 798.9 35 35 TRAP GX 798.9 870
148' 148' 1.37 33.63 378.0 4 4 TRAP GX 378 401.5 784.6 20 20 TRAP GX 784.6 833.5 870.0 36 36 TRAP GX 870 924.2
197' 197' 1.46 35.72 401.5 5 5 TRAP GX 401.5 419.2 833.5 21 21 TRAP GX 833.5 870.2 924.2 37 37 TRAP GX 924.2 965
242' 242' 1.52 37.30 419.2 6 6 TRAP GX 419.2 434 870.2 22 22 TRAP GX 870.2 901 965.0 38 38 TRAP GX 965 999.1
286' 286' 1.58 38.62 434.0 7 7 TRAP GX 434 445.3 901.0 23 23 TRAP GX 901 924.3 999.1 39 39 TRAP GX 999.1 1025
323' 323' 1.62 39.62 445.3 8 8 TRAP GX 445.3 445.3 924.3 24 24 TRAP GX 924.3 924.3 1025.0 40 40 TRAP GX 1025 1025

D-1 A-3 B-3


Width 17.23 14.05 29.165
Factor 0.80 Direction GX 0.50 Direction GX 0.50 Direction GX
Elevation Height, z Kz p = qG UDL Col No's Staad input UDL Col No'sStaad input UDL Col No's Staad input
36' 36' 1.02 24.97 344.0 49 49 TRAP GX 344 395.7 175.4 65 65 TRAP GX 175.4 201.7 364.1 81 81 TRAP GX 364.1 418.8
70' 70' 1.17 28.72 395.7 50 50 TRAP GX 395.7 425. 201.7 66 66 TRAP GX 201.7 216.9 418.8 82 82 TRAP GX 418.8 450.3
99' 99' 1.26 30.88 425.5 51 51 TRAP GX 425.5 463. 216.9 67 67 TRAP GX 216.9 236.2 450.3 83 83 TRAP GX 450.3 490.4
148' 148' 1.37 33.63 463.4 52 52 TRAP GX 463.4 492. 236.2 68 68 TRAP GX 236.2 250.9 490.4 84 84 TRAP GX 490.4 520.9
197' 197' 1.46 35.72 492.2 53 53 TRAP GX 492.2 514 250.9 69 69 TRAP GX 250.9 262 520.9 85 85 TRAP GX 520.9 543.9
242' 242' 1.52 37.30 514.0 54 54 TRAP GX 514 532.1 262.0 70 70 TRAP GX 262 271.3 543.9 86 86 TRAP GX 543.9 563.1
286' 286' 1.58 38.62 532.1 55 55 TRAP GX 532.1 545. 271.3 71 71 TRAP GX 271.3 278.3 563.1 87 87 TRAP GX 563.1 577.7
323' 323' 1.62 39.62 545.9 56 56 TRAP GX 545.9 545. 278.3 72 72 TRAP GX 278.3 278.3 577.7 88 88 TRAP GX 577.7 577.7

C-3 C-2 D-2


Width 15.115 17.225 17.225
Factor 0.50 Direction GX 0.50 Direction GX 0.50 Direction GX
Elevation Height, z Kz p = qG UDL Col No's Staad input UDL Col No'sStaad input UDL Col No's Staad input
36' 36' 1.02 24.97 188.7 97 97 TRAP GX 188.7 217 215.0 113 113 TRAP GX 215 247.3 215.0 129 129 TRAP GX 215 247.3
70' 70' 1.17 28.72 217.0 98 98 TRAP GX 217 233.4 247.3 114 114 TRAP GX 247.3 266 247.3 130 130 TRAP GX 247.3 266
99' 99' 1.26 30.88 233.4 99 99 TRAP GX 233.4 254. 266.0 115 115 TRAP GX 266 289.6 266.0 131 131 TRAP GX 266 289.6
148' 148' 1.37 33.63 254.1 100 100 TRAP GX 254.1 270 289.6 116 116 TRAP GX 289.6 307.7 289.6 132 132 TRAP GX 289.6 307.7
197' 197' 1.46 35.72 270.0 101 101 TRAP GX 270 281.9 307.7 117 117 TRAP GX 307.7 321.2 307.7 133 133 TRAP GX 307.7 321.2
242' 242' 1.52 37.30 281.9 102 102 TRAP GX 281.9 291 321.2 118 118 TRAP GX 321.2 332.6 321.2 134 134 TRAP GX 321.2 332.6
286' 286' 1.58 38.62 291.8 103 103 TRAP GX 291.8 299 332.6 119 119 TRAP GX 332.6 341.2 332.6 135 135 TRAP GX 332.6 341.2
323' 323' 1.62 39.62 299.4 104 104 TRAP GX 299.4 299 341.2 120 120 TRAP GX 341.2 341.2 341.2 136 136 TRAP GX 341.2 341.2
AAES ENGINEERING, INC. Project no.

Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10

WIND LOAD IN DIRECTION +Z


A-1 A-2 A-3
Width 17.50 26.70 9.2
Factor ### Direction GZ ### Direction GZ ### Direction GZ
Elevation Height, z Kz p = qG UDL Col No's Staad input UDL Col No'sStaad input UDL Col No's Staad input
36' 36' 1.02 24.97 349.5 33 33 TRAP GZ 349.5 402. 533.3 1 1 TRAP GZ 533.3 613.4 183.8 97 97 TRAP GZ 183.8 211.4
70' 70' 1.17 28.72 402.1 34 34 TRAP GZ 402.1 432. 613.4 2 2 TRAP GZ 613.4 659.6 211.4 98 98 TRAP GZ 211.4 227.3
99' 99' 1.26 30.88 432.3 35 35 TRAP GZ 432.3 470. 659.6 3 3 TRAP GZ 659.6 718.3 227.3 99 99 TRAP GZ 227.3 247.5
148' 148' 1.37 33.63 470.8 36 36 TRAP GZ 470.8 500. 718.3 4 4 TRAP GZ 718.3 763 247.5 100 100 TRAP GZ 247.5 262.9
197' 197' 1.46 35.72 500.1 37 37 TRAP GZ 500.1 522. 763.0 5 5 TRAP GZ 763 796.7 262.9 101 101 TRAP GZ 262.9 274.5
242' 242' 1.52 37.30 522.2 38 38 TRAP GZ 522.2 540. 796.7 6 6 TRAP GZ 796.7 824.8 274.5 102 102 TRAP GZ 274.5 284.2
286' 286' 1.58 38.62 540.6 39 39 TRAP GZ 540.6 554. 824.8 7 7 TRAP GZ 824.8 846.2 284.2 103 103 TRAP GZ 284.2 291.6
323' 323' 1.62 39.62 554.6 40 40 TRAP GZ 554.6 554. 846.2 8 8 TRAP GZ 846.2 846.2 291.6 104 104 TRAP GZ 291.6 291.6

D-1 D-2 C-2


Width 17.50 17.50 9.2
Factor 0.50 Direction GZ 0.50 Direction GZ 0.50 Direction GZ
Elevation Height, z Kz p = qG UDL Col No's Staad input UDL Col No'sStaad input UDL Col No's Staad input
36' 36' 1.02 24.97 218.5 81 81 TRAP GZ 218.5 251. 218.5 225 225 TRAP GZ 218.5 251.3 114.8 241 241 TRAP GZ 114.8 132.1
70' 70' 1.17 28.72 251.3 82 82 TRAP GZ 251.3 270. 251.3 226 226 TRAP GZ 251.3 270.2 132.1 242 242 TRAP GZ 132.1 142
99' 99' 1.26 30.88 270.2 83 83 TRAP GZ 270.2 294. 270.2 227 227 TRAP GZ 270.2 294.2 142.0 243 243 TRAP GZ 142 154.7
148' 148' 1.37 33.63 294.2 84 84 TRAP GZ 294.2 312. 294.2 228 228 TRAP GZ 294.2 312.6 154.7 244 244 TRAP GZ 154.7 164.3
197' 197' 1.46 35.72 312.6 85 85 TRAP GZ 312.6 326. 312.6 229 229 TRAP GZ 312.6 326.4 164.3 245 245 TRAP GZ 164.3 171.6
242' 242' 1.52 37.30 326.4 86 86 TRAP GZ 326.4 337. 326.4 230 230 TRAP GZ 326.4 337.9 171.6 246 246 TRAP GZ 171.6 177.6
286' 286' 1.58 38.62 337.9 87 87 TRAP GZ 337.9 346. 337.9 231 231 TRAP GZ 337.9 346.6 177.6 247 247 TRAP GZ 177.6 182.2
323' 323' 1.62 39.62 346.6 88 88 TRAP GZ 346.6 346. 346.6 232 232 TRAP GZ 346.6 346.6 182.2 248 248 TRAP GZ 182.2 182.2

C-3
Width 9.20
Factor 0.50 Direction GZ
Elevation Height, z Kz p = qG UDL Col No's Staad input
36' 36' 1.02 24.97 114.8 257 257 TRAP GZ 114.8 132
70' 70' 1.17 28.72 132.1 258 258 TRAP GZ 132.1 142
99' 99' 1.26 30.88 142.0 259 259 TRAP GZ 142 154.7
148' 148' 1.37 33.63 154.7 260 260 TRAP GZ 154.7 164
197' 197' 1.46 35.72 164.3 261 261 TRAP GZ 164.3 171
242' 242' 1.52 37.30 171.6 262 262 TRAP GZ 171.6 177
286' 286' 1.58 38.62 177.6 263 263 TRAP GZ 177.6 182
323' 323' 1.62 39.62 182.2 264 264 TRAP GZ 182.2 182
AAES ENGINEERING, INC. Project no.

Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10
X-Dir
Basic Wind Speed V = 115 mph For exposure B, Kz =
Exposure Category = C Z- For exposure C, Kz =
Dir
Importance Factor I = 1.00 For exposure D, Kz =
Risk Category = II

Design Wind Loads on Open Buildings and Other Structures (ASCE 7-10) 1 2 3
@ Elev 0.00 with grade elevation @ 0.00 col
F = qzGCfAf (Eq. 27…….) 35' 18'

where
A
qz = 0.00256KzKztKdV2 (Eq. 27.3-1)

28'
For z= 0.0 ft. Kz = ### (Table 27.3-1)
Kzt = (1 + K1K2K3)2 (Eq. 26.8-1) K1 = 0 K2 = 0 K3 = 0 (Fig 26.8-1)
B
= 1 + 0.00 x ### x ### 2
= 1.00
Kd = 0.85 (Table 26.6-1) 30'

\ qz = 0.00256 x ### x ### x ### x 115 2


x ###
C
= 24.4 lbs/ft2

G = 0.85 (Section 26.9.4)


34'
Cf = 1.30 (Fig. 29.5-1) for h/D = 6.2 Cf = ### Considere Wind-ward side facto = 0.80
Lee-ward side factor = 0.50
D
PLAN
Grade Elevation = 0 ft
Top Plan Elevatio = 323 ft
Plan Dimension = 52 x 57 ft
AAES ENGINEERING, INC. Project no.

Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10
Velocity Pressure Exposure Coefficient Kz (Table 27.3 Grade elevation @ 0'

WIND LOAD IN DIRECTION -X


COLUMN A-1 B-1 C-1
Width 14.05 29.165 32.34
Factor Cf = 0.50 Direction GX 0.50 Direction GX 0.50 Direction GX
Elevation Height, z Kz p = qG UDL Col No's Staad input UDL Col No'sStaad input UDL Col No's Staad input
36' 36' 1.02 24.97 175.4 1 1 TRAP GX -175.4 -201. 364.1 17 17 TRAP GX -364.1 -418.8 403.7 33 33 TRAP GX -403.7 -464.4
70' 70' 1.17 28.72 201.7 2 2 TRAP GX -201.7 -216. 418.8 18 18 TRAP GX -418.8 -450.3 464.4 34 34 TRAP GX -464.4 -499.3
99' 99' 1.26 30.88 216.9 3 3 TRAP GX -216.9 -236. 450.3 19 19 TRAP GX -450.3 -490.4 499.3 35 35 TRAP GX -499.3 -543.8
148' 148' 1.37 33.63 236.2 4 4 TRAP GX -236.2 -250. 490.4 20 20 TRAP GX -490.4 -520.9 543.8 36 36 TRAP GX -543.8 -577.6
197' 197' 1.46 35.72 250.9 5 5 TRAP GX -250.9 -262 520.9 21 21 TRAP GX -520.9 -543.9 577.6 37 37 TRAP GX -577.6 -603.1
242' 242' 1.52 37.30 262.0 6 6 TRAP GX -262 -271.3 543.9 22 22 TRAP GX -543.9 -563.1 603.1 38 38 TRAP GX -603.1 -624.4
286' 286' 1.58 38.62 271.3 7 7 TRAP GX -271.3 -278. 563.1 23 23 TRAP GX -563.1 -577.7 624.4 39 39 TRAP GX -624.4 -640.6
323' 323' 1.62 39.62 278.3 8 8 TRAP GX -278.3 -278. 577.7 24 24 TRAP GX -577.7 -577.7 640.6 40 40 TRAP GX -640.6 -640.6

D-1 A-3 B-3


Width 17.23 14.05 29.165
Factor 0.50 Direction GX 0.80 Direction GX 0.80 Direction GX
Elevation Height, z Kz p = qG UDL Col No's Staad input UDL Col No'sStaad input UDL Col No's Staad input
36' 36' 1.02 24.97 215.0 49 49 TRAP GX -215 -247. 280.6 65 65 TRAP GX -280.6 -322.8 582.5 81 81 TRAP GX -582.5 -670.1
70' 70' 1.17 28.72 247.3 50 50 TRAP GX -247.3 -26 322.8 66 66 TRAP GX -322.8 -347.1 670.1 82 82 TRAP GX -670.1 -720.5
99' 99' 1.26 30.88 266.0 51 51 TRAP GX -266 -289. 347.1 67 67 TRAP GX -347.1 -378 720.5 83 83 TRAP GX -720.5 -784.6
148' 148' 1.37 33.63 289.6 52 52 TRAP GX -289.6 -307 378.0 68 68 TRAP GX -378 -401.5 784.6 84 84 TRAP GX -784.6 -833.5
197' 197' 1.46 35.72 307.7 53 53 TRAP GX -307.7 -321 401.5 69 69 TRAP GX -401.5 -419.2 833.5 85 85 TRAP GX -833.5 -870.2
242' 242' 1.52 37.30 321.2 54 54 TRAP GX -321.2 -332 419.2 70 70 TRAP GX -419.2 -434 870.2 86 86 TRAP GX -870.2 -901
286' 286' 1.58 38.62 332.6 55 55 TRAP GX -332.6 -341 434.0 71 71 TRAP GX -434 -445.3 901.0 87 87 TRAP GX -901 -924.3
323' 323' 1.62 39.62 341.2 56 56 TRAP GX -341.2 -341 445.3 72 72 TRAP GX -445.3 -445.3 924.3 88 88 TRAP GX -924.3 -924.3

C-3 C-2 D-3


Width 15.115 17.225 17.225
Factor 0.80 Direction GX 0.80 Direction GX 0.80 Direction GX
Elevation Height, z Kz p = qG UDL Col No's Staad input UDL Col No'sStaad input UDL Col No's Staad input
36' 36' 1.02 24.97 301.9 97 97 TRAP GX -301.9 -347 344.0 113 113 TRAP GX -344 -395.7 344.0 129 129 TRAP GX -344 -395.7
70' 70' 1.17 28.72 347.3 98 98 TRAP GX -347.3 -373 395.7 114 114 TRAP GX -395.7 -425. 395.7 130 130 TRAP GX -395.7 -425.5
99' 99' 1.26 30.88 373.4 99 99 TRAP GX -373.4 -406 425.5 115 115 TRAP GX -425.5 -463. 425.5 131 131 TRAP GX -425.5 -463.4
148' 148' 1.37 33.63 406.6 100 100 TRAP GX -406.6 -4 463.4 116 116 TRAP GX -463.4 -492. 463.4 132 132 TRAP GX -463.4 -492.2
197' 197' 1.46 35.72 432.0 101 101 TRAP GX -432 -451 492.2 117 117 TRAP GX -492.2 -514 492.2 133 133 TRAP GX -492.2 -514
242' 242' 1.52 37.30 451.0 102 102 TRAP GX -451 -466 514.0 118 118 TRAP GX -514 -532.1 514.0 134 134 TRAP GX -514 -532.1
286' 286' 1.58 38.62 466.9 103 103 TRAP GX -466.9 -4 532.1 119 119 TRAP GX -532.1 -545. 532.1 135 135 TRAP GX -532.1 -545.9
323' 323' 1.62 39.62 479.0 104 104 TRAP GX -479 -479 545.9 120 120 TRAP GX -545.9 -545. 545.9 136 136 TRAP GX -545.9 -545.9
AAES ENGINEERING, INC. Project no.

Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Wind load calculations as per ASCE 7-10

WIND LOAD IN DIRECTION -Z


A-1 A-2 A-3
Width 17.50 26.70 9.2
Factor ### Direction GZ ### Direction GZ ### Direction GZ
Elevation Height, z Kz p = qG UDL Col No's Staad input UDL Col No'sStaad input UDL Col No's Staad input
36' 36' 1.02 24.97 218.5 33 33 TRAP GZ -218.5 -251 333.3 1 1 TRAP GZ -333.3 -383.4 114.8 97 97 TRAP GZ -114.8 -132.1
70' 70' 1.17 28.72 251.3 34 34 TRAP GZ -251.3 -270 383.4 2 2 TRAP GZ -383.4 -412.2 132.1 98 98 TRAP GZ -132.1 -142
99' 99' 1.26 30.88 270.2 35 35 TRAP GZ -270.2 -294 412.2 3 3 TRAP GZ -412.2 -448.9 142.0 99 99 TRAP GZ -142 -154.7
148' 148' 1.37 33.63 294.2 36 36 TRAP GZ -294.2 -312 448.9 4 4 TRAP GZ -448.9 -476.9 154.7 100 100 TRAP GZ -154.7 -164.3
197' 197' 1.46 35.72 312.6 37 37 TRAP GZ -312.6 -326 476.9 5 5 TRAP GZ -476.9 -497.9 164.3 101 101 TRAP GZ -164.3 -171.6
242' 242' 1.52 37.30 326.4 38 38 TRAP GZ -326.4 -337 497.9 6 6 TRAP GZ -497.9 -515.5 171.6 102 102 TRAP GZ -171.6 -177.6
286' 286' 1.58 38.62 337.9 39 39 TRAP GZ -337.9 -346 515.5 7 7 TRAP GZ -515.5 -528.9 177.6 103 103 TRAP GZ -177.6 -182.2
323' 323' 1.62 39.62 346.6 40 40 TRAP GZ -346.6 -346 528.9 8 8 TRAP GZ -528.9 -528.9 182.2 104 104 TRAP GZ -182.2 -182.2

D-1 D-2 C-2


Width 17.50 17.50 9.2
Factor 0.80 Direction GZ 0.80 Direction GZ 0.80 Direction GZ
Elevation Height, z Kz p = qG UDL Col No's Staad input UDL Col No'sStaad input UDL Col No's Staad input
36' 36' 1.02 24.97 349.5 81 81 TRAP GZ -349.5 -402 349.5 225 225 TRAP GZ -349.5 -402. 183.8 241 241 TRAP GZ -183.8 -211.4
70' 70' 1.17 28.72 402.1 82 82 TRAP GZ -402.1 -432 402.1 226 226 TRAP GZ -402.1 -432. 211.4 242 242 TRAP GZ -211.4 -227.3
99' 99' 1.26 30.88 432.3 83 83 TRAP GZ -432.3 -470 432.3 227 227 TRAP GZ -432.3 -470. 227.3 243 243 TRAP GZ -227.3 -247.5
148' 148' 1.37 33.63 470.8 84 84 TRAP GZ -470.8 -500 470.8 228 228 TRAP GZ -470.8 -500. 247.5 244 244 TRAP GZ -247.5 -262.9
197' 197' 1.46 35.72 500.1 85 85 TRAP GZ -500.1 -522 500.1 229 229 TRAP GZ -500.1 -522. 262.9 245 245 TRAP GZ -262.9 -274.5
242' 242' 1.52 37.30 522.2 86 86 TRAP GZ -522.2 -540 522.2 230 230 TRAP GZ -522.2 -540. 274.5 246 246 TRAP GZ -274.5 -284.2
286' 286' 1.58 38.62 540.6 87 87 TRAP GZ -540.6 -554 540.6 231 231 TRAP GZ -540.6 -554. 284.2 247 247 TRAP GZ -284.2 -291.6
323' 323' 1.62 39.62 554.6 88 88 TRAP GZ -554.6 -554 554.6 232 232 TRAP GZ -554.6 -554. 291.6 248 248 TRAP GZ -291.6 -291.6

C-3
Width 9.20
Factor 0.80 Direction GZ
Elevation Height, z Kz p = qG UDL Col No's Staad input
36' 36' 1.02 24.97 183.8 257 257 TRAP GZ -183.8 -21
70' 70' 1.17 28.72 211.4 258 258 TRAP GZ -211.4 -22
99' 99' 1.26 30.88 227.3 259 259 TRAP GZ -227.3 -24
148' 148' 1.37 33.63 247.5 260 260 TRAP GZ -247.5 -26
197' 197' 1.46 35.72 262.9 261 261 TRAP GZ -262.9 -27
242' 242' 1.52 37.30 274.5 262 262 TRAP GZ -274.5 -28
286' 286' 1.58 38.62 284.2 263 263 TRAP GZ -284.2 -29
323' 323' 1.62 39.62 291.6 264 264 TRAP GZ -291.6 -29
AAES ENGINEERING, INC. Project no. 1173

Prep By ERK Date 3/4/25 Project Buzzi, Maryneal- Polysius Preheater Tower Sheet of
Chkd By JE Date 3/4/25 Subject Cyclone Wind load calculations per IBC - 2006 and ASCE 7-05

WIND LOAD CALCULATIONS FOR STACK


Design Code : IBC 2006 and ASCE 7-05 Note:
Occupancy Category = II Calculations done for a typical cyclone
Basic Wind Speed V = 115 mph between EL 197' and 242' floor levels
Exposure Category = C Dia and Height of cyclone are considered
Importance Factor = 1.0 on the higher side

Velocity Pressure,
qz = 0.00256KzKztKdV2I (Eq. 6-15)
Topographic Factor Kzt = 1.00
Wind Directionality FactorKd = 0.95 (Table 6.4) For Round tanks

Gust Effect Factor G = 0.85 (Section 6.5.8.1) Gust Factor for Rigid Structures
Force Coefficient Cf = 0.80 (h/D = 2.0 ) (Figure 29.5-1)

Velocity Pressure Exposure Coefficient Kz ( Table 6-3) Grade elevation @ 0'


Elevation Height, z Kz V2 qz qz G Cf
At top 242.00' 1.5244 13225 49.03 33.34
At Bottom 197.0' 1.4598 13225 46.95 31.93
766.8lb/ft
Design Wind Force :
F = qz G Cf x Af

At top : 33.34 x 23.0 = 766.8 lb/ft

At bottom : 31.93 x 23.0 = 734.3 lb/ft ###

Shear:
V = (766.8 + 734.3) x 45 = 33775 lb
2

Moment:
2 2
M = 734.3 x 45 + 32.50 x 45
2 3 734.3lb/ft
###
M = 743478.8 + ### = 765416 lb-ft

DEAD LOAD:
Weight of Cyclone = 62.00 KIPS
62.00
Weight = FDL = = 7.750 kips per point
8

Operating LOAD:
Operating Weight = 258.00 KIPS
258.00
Oper. Weight = FLL = = 32.250 kips per point
8

Y 23.0 f

S1
N= 8 R = ### ft
S8
Polar Moment of Inertia J :
S2
J = N • R2 ® J = ### in.4

J
Ix= Iy= I = ® I = 529 in.4
S7 S3 X 2

S6 S4

S5

ADDITIONAL VERTICAL LOAD DUE TO CYCLONE MOMENT:


Fzvm = My(x) / I ------------> (X - dir.)

Fzvm = Mx(y) / I ------------> (Y - dir.)


NODE WIND +X WIND +Y
X Y
POINT Fz Fz
S1 0.00 11.50 0.00 -16.64
S2 8.13 8.13 -11.77 -11.77 Max Load at a point = 16.6 KIPS
S3 11.50 0.00 -16.64 0.00
S4 8.13 -8.13 -11.77 11.77
S5 0.00 -11.50 0.00 16.64
S6 -8.13 -8.13 11.77 11.77
S7 -11.50 0.00 16.64 0.00
S8 -8.13 8.13 11.77 -11.77

Comparision of Loads with and without Up-Down Wind Load on free standing Cyclone

Load combinations without up-down WL


1 1.4 D = 10.9 KIPS
2 1.2 D + 1.6 L = 60.9 KIPS

Load combinations with up-down WL


3 1.2 D + 1.6 W + 1.0 L = 68.2 KIPS > D+L load comb
4 0.9 D + 1.6 W = 33.6 KIPS < D+L load comb
Prep By MCR Date 3/4/25 Project Cooler vent Modification, Brooksville, G Sheet of
Chkd By ERK Date 3/4/25 Subject Loads

Equipment load

Unit wt of vent = 90 lb/ft3


Avg dia of cooler vent = 12.5 ft
Height of vent = 25.00 ft
Volume of cooler vent 3068 ft3
Total operating weight of Cooler vent = 276 Kips

Dead weight of cooler vent = 15% of vent operating wt


= 41 Kips

LOADS FOR DUCT -1


plate thickness = 0.375 inch
Outer Dia of duct -1 = 8.5 inch
Inner Dia of duct -1 = 8.438 inch
Duct -1 Length = 92 ft
Inside duct -1 length = 25 ft
Unit weight of duct plate = 490 lb/ft3
Duct volume for length
(3.14x(D^2-d^2)x92/4=
-1 = 75.9 ft3
Duct volume for length
(3.14x(D^2-d^2)x25/4=
-2 = 20.6 ft3
Dead weight of duct for length-1 = 37 kips
Dead weight of duct for length-2 = 10 kips

Volume of duct Length-13.14x8.438^2/4x92 = 5145 ft3


Operating weight of duct length-1 = 463 Kips

Volume of duct Length-23.14x8.438^2/4x25 = 1398 ft3


Operating weight of duct length-2 = 126 Kips

LOADS FOR DUCT -2


plate thickness = 0.375 inch
Outer Dia of duct -2 = 8.0 inch
Inner Dia of duct -2 = 7.938 inch
Duct-2 Length = 110 ft

Unit weight of duct plate = 490 lb/ft3


Duct volume for length
(3.14x(D^2-d^2)x110/4=
-1 = 85.4 ft3

Dead weight of duct for length-1 = 42 kips

Volume of duct -2 3.14x7.938^2/4x110 = 5444 ft3


Operating weight of duct -2 = 490 Kips
Prep By MCR Date 3/4/25 Project Cooler vent Modification, Brooksville, GA Sheet of
Chkd By ERK Date 3/4/25 Subject Seismic Load Calculations as per ASCE 7-10

Maximum considered earthquake spectral response acceleration at a period of 1 second(S 1) = ### g

Maximum considered earthquake spectral response acceleration at short period of 0.2 second (Ss) = ### g

Risk Category = II (Table 1.1 )


Site Class = D (Section 11.4.2)
Importance Factor I = 1 (Table 11.5.1)

Design Base Shear (ASCE 7-10)

Ct = 0.02 x= 0.75 (Table 12.8.2)


hn = 90 ft
T= Ta =Ct hnx = 0.584 (Eq 12.8-7)

Fv = 2.4 (Table 11.4-2)


SM1 = Fv S1 = ### x ### = ### (Eq 11.4-2)
SD1 = 2 x SM1 = 2 x ### = 0.106 (Eq 11.4-4)
3 3
SEISMIC DESIGN CATEGORY D

Fa = 1.6 (Table 11.4-1)


SMS = Fa Ss = ### x ### = 0.17 (Eq 11.4-1)
SDS = 2 x SMS = 2 x 0.17 = 0.115 (Eq 11.4-3)
3 3
SEISMIC DESIGN CATEGORY D

R= 1.5 Ordinary steel concentrically braced frames (With Unlimited heig(Table 15.4-1)
Cs = SDS.I = ### x ### = 0.076 (Eq 12.8-2)
R 1.5

The Seismic Response Coefficient,CS, need not exceed the following:

Cs = SD1.I = ### x ### = 0.120 ( T < TL ) (Eq 12.8-3)


RT 1.5 x ###

The Seismic Response Coefficient,CS, shall not be less than the following:

Cs = ### SDS Ie >= 0.01 (Eq 15.4-1)

..
.
V= Cs W = 0.08 W (Eq 12.8-1)
Prep By MCR Date 3/4/25 Project Cooler vent Modification, Brooksville, GA Sheet of
Chkd By ERK Date 3/4/25 Subject Wind Load Calculations as per ASCE 7-10

Basic Wind Speed V = 115 mph


Exposure Category = C
Risk Category = II (Table 1.5 - 1 )

Design MWFRS Wind Loads on Other Structures (ASCE 7-10 - 29.5)


@ Elev 90.00 with grade elevation @0.00
F = qzGCfAf (Eq. 29.5-1)

where
qz = 0.00256KzKztKdV2 (Eq. 29.3-1)

For z= 90.0 ft. Kz = ### (Table 29.3-1)


Kzt = (1 + K1K2K3)2 (Eq. 26.8.1) ; K1 = 0 K2 = 0 K3 = 0 (Fig. 26.8-1)
= 1 + 0.00 x ### x ### 2
= 1.00
Kd = 0.90 (Table 26.6-1) (Chimneys, Tanks And Similar Structures)

\ qz = 0.00256 x ### x ### x ### x 115 2

= 38 lbs/ft2

G = 0.85 (Section 26.9.1)

Cf = 1.06 (Fig. 29.5-1) for h/D =13 Duct-1

Cf = 1.06 (Fig. 29.5-1) for h/D =13 Duct-2

Cf = 0.83 (Fig. 29.5-1) for h/D =2 Cooler vent

\ F= 38 x ### x ### = 34 lbs/ft2

\ F= 38 x ### x ### = 34 lbs/ft2

\ F= 38 x ### x ### = 27 lbs/ft2


AAES ENGINEERING, INC. Project no.

Prep By ERK Date 3/4/25 Project TKIS Finish Mill Sheet of


Chkd By JE Date 3/4/25 Subject DL & LL

Live loads
All grating Floors + Concrete with metal deck floors = 100 psf
At roof level at 44.4m = 50 psf
Dead loads:
All Grating Floors = 25 psf
Hand Rail and Toe Plate = 10 lb/ft
Concrete Slab with W/2" Metal Deck = 75 psf

at 13.2 m lvl Grating floor DL LL


For 4.92 ft Span = 61.5 lb/ft end 246 lb/ft
123 lb/ft mid 492 lb/ft
4.49 ft = 56.13 lb/ft end 225 lb/ft
112 lb/ft mid 449 lb/ft
at 4.7 m lvl Grating gloor & 7.3 m level
For 3.47 ft = 43.38 lb/ft end 174 lb/ft
86.75 lb/ft mid 347 lb/ft

at 5.60m lvl Grating & 9.0m & 11.40m


For 5.14 ft = 193 lb/ft end 257 lb/ft
385.5 lb/ft mid 514 lb/ft

at 9.0 m lvl conc + metal deck DL LL


For 5.17 ft = 194 lb/ft end 259 lb/ft
388 lb/ft mid 517 lb/ft
6.0 ft = 225 lb/ft end 300 lb/ft
450 lb/ft mid 600 lb/ft

at 11.8 m lvl Grating gloor


For 5.14 ft = 64.25 lb/ft end 257 lb/ft
128.5 lb/ft mid 514 lb/ft

at 11.4 m lvl Grating gloor


For 4.92 ft = 61.5 lb/ft end 246 lb/ft
123 lb/ft mid 492 lb/ft
5.42 ft = 67.75 lb/ft end 271 lb/ft

135.5 lb/ft mid 542 lb/ft

at 16.4 m lvl conc + metal deck DL LL


For 5.17 ft = 194 lb/ft end 259 lb/ft
388 lb/ft mid 517 lb/ft
AAES ENGINEERING, INC. Project no.

Prep By ERK Date 3/4/25 Project TKIS Finish Mill Sheet of


Chkd By JE Date 3/4/25 Subject DL & LL
5.0 ft = 187.5 lb/ft end 250 lb/ft
375 lb/ft mid 500 lb/ft
4.5 ft = 169 lb/ft end 225 lb/ft
337.5 lb/ft mid 450 lb/ft
1.5 ft = 56.25 lb/ft end 75 lb/ft
112.5 lb/ft mid 150 lb/ft
4.27 ft = 160 lb/ft end 213 lb/ft
320 lb/ft mid 427 lb/ft
3.6 ft = 135 lb/ft end 181 lb/ft
271 lb/ft mid 361 lb/ft
5.6 ft = 209 lb/ft end 279 lb/ft
418 lb/ft mid 557 lb/ft
5.9 ft = 220 lb/ft end 294 lb/ft

4.4 ft = 166 lb/ft end 222 lb/ft


332 lb/ft mid 443 lb/ft
4.65 ft = 174 lb/ft end 233 lb/ft
349 lb/ft mid 465 lb/ft
4.92 ft = 184.5 lb/ft end 246 lb/ft
369 lb/ft mid 492 lb/ft
2.5 ft = 92.25 lb/ft end 123 lb/ft

8.20 ft = 307.5 lb/ft end 410 lb/ft


615 lb/ft mid 820 lb/ft

at 27.15 m lvl conc + metal deck DL LL


For 5.38 ft = 202 lb/ft end 269 lb/ft
403.5 lb/ft mid 538 lb/ft
5.0 ft = 187.5 lb/ft end 250 lb/ft
375 lb/ft mid 500 lb/ft
3.8 ft = 144 lb/ft end 192 lb/ft
288 lb/ft mid 384 lb/ft
4.5 ft = 169 lb/ft end 225 lb/ft

at 27.15 m lvl Grating floor


5.38 ft = 67.25 lb/ft end 269 lb/ft
134.5 lb/ft mid 538 lb/ft
4.5 ft = 56.25 lb/ft end 225 lb/ft
112.5 lb/ft mid 450 lb/ft

at 28.4 m lvl Grating floor & 33.0 m lvl


5.14 ft = 64.25 lb/ft end 257 lb/ft
128.5 lb/ft mid 514 lb/ft
4 ft = 50 lb/ft end 200 lb/ft
100 lb/ft mid 400 lb/ft
4.62 ft = 57.75 lb/ft end 231 lb/ft
115.5 lb/ft mid 462 lb/ft

at 30.8 m lvl Grating floor


5.13 ft = 64.13 lb/ft end 257 lb/ft
128 lb/ft mid 513 lb/ft
4 ft = 50 lb/ft end 200 lb/ft
100 lb/ft mid 400 lb/ft
3.84 ft = 48 lb/ft end 192 lb/ft
96 lb/ft mid 384 lb/ft
3 ft = 37.5 lb/ft end 150 lb/ft
75 lb/ft mid 300 lb/ft
6.23 ft = 77.88 lb/ft end 312 lb/ft
156 lb/ft mid 623 lb/ft

at 32.35 m lvl Grating floor


4.93 ft = 61.63 lb/ft end 247 lb/ft
123 lb/ft mid 493 lb/ft
AAES ENGINEERING, INC. Project no.

Prep By ERK Date 3/4/25 Project TKIS Finish Mill Sheet of


Chkd By JE Date 3/4/25 Subject DL & LL
4 ft = 50 lb/ft end 200 lb/ft

at 34.85 m lvl Grating floor


4.93 ft = 61.63 lb/ft end 247 lb/ft
123 lb/ft mid 493 lb/ft
4 ft = 50 lb/ft end 200 lb/ft
100 lb/ft mid 400 lb/ft
3.5 ft = 43.75 lb/ft end 175 lb/ft
87.5 lb/ft mid 350 lb/ft
3.73 ft = 46.63 lb/ft end 187 lb/ft

5.75 ft = 71.88 lb/ft end 288 lb/ft

at 44.40 m lvl Grating floor roof level


4.93 ft = 61.63 lb/ft end 123 lb/ft
123 lb/ft mid 247 lb/ft
4.65 ft = 58.13 lb/ft end 116 lb/ft
116 lb/ft mid 233 lb/ft
Belt conveyor load 150 psf
at 0.0m to 5.6m lvl & 28.4m lvl
4 ft 300 lb/ft end