CRTAG - CRTAG-205H - Product Report
CRTAG - CRTAG-205H - Product Report
Unit Overview
RTAG - air cooled chiller series
Chiller Model
R
Refrigeration Capacity 164.3 tons
Cooling Efficiency 2.199 COP (kW/kW)
Evaporator Configuration Standard Cooling (4 To 27C)
High Ambient (14-125F/-10-
Condenser Configuration
52C)
AHRI IPLV.IP 4.380 COP (kW/kW)
AHRI NPLV.IP 3.939 COP (kW/kW)
Unit Voltage 415.V/50.Hz/3 Phase
Refrigerant Type R134a
Agency Listing No agency listing
Pressure Vessel Code ASME code
A-weighted sound power 101 dBA
Model Number R
Evaporator Information
Fluid Properties Flow Rate Construction Features
Fluid Type Water Design Flow 27.52 L/s 2 Pass arrangement,
Number of Passes
insulated
Fluid Temperatures Min Flow 16.50 L/s
0.000100 hr-sq ft-deg
Evaporator Leaving 7.0 C Fluid Pressure Drop Fouling Factor
F/Btu
Evaporator Entering 12.0 C Design PD 30.5 kPa
Saturated evap - ckt 1 5.1 C Min PD 11.0 kPa
Saturated evap - ckt 2 5.5 C Max PD 141 kPa
Condenser Information
Ambient air temp 46.0 C Elevation 0.0 m
Condenser Options Copper tube/Al fin coil Saturated cond temp - ckt 1 64.1 C
Number of Condenser Fans 10.00 Each Saturated cond temp - ckt 2 64.3 C
Fan Motor Power 11.92 kW
Unit Electrical
Unit Voltage 415.V/50.Hz/3 Phase Single Point unit starting current 634.00 A
Total Power 262.6 kW RLA - condenser fan (each) 3.80 A
Compressor Power 249.9 kW Fan motor power 11.92 kW
RLA - compressor 1A 185.00 A LRA - compressor 1A 371.00 A
Number of condenser fans 10.00 Each LRA - compressor 2A 371.00 A
Wye-delta closed transition
Compressor starter type
starter
RLA - compressor 2A 185.00 A
Single Point Max amps 485.00 A
Physical Information
Dimensions Weights Charge
Length 6200. mm Operating Weight 5085 kg Ckt 1 Charge 82 kg
Width 2245 mm Shipping Weight 4798 kg Ckt 2 Charge 82 kg
Height 2501 mm Oil charge circuit 1 8.00 L
Oil charge circuit 2 8.00 L
Sound Information
A-weighted sound power 101 dBA Octave band sound pressure - 500 Hz 65 dBA
10m sound pressure full load 69 dBA Octave band sound pressure - 1000 Hz 66 dBA
Octave band sound pressure - 63 Hz 41 dBA Octave band sound pressure - 2000 Hz 62 dBA
Octave band sound pressure - 125 Hz 44 dBA Octave band sound pressure - 4000 Hz 53 dBA
Octave band sound pressure - 250 Hz 54 dBA Octave band sound pressure - 8000 Hz 45 dBA
Note: Sound data may vary ±3 dBA in any specific octave band due to normal variation in chiller construction
Warranty
Standard Warranty