Broken delta refers to a connection of Voltage Transformers (VT) used for ground fault detection in ungrounded systems, requiring three VTs in series to calculate zero-sequence voltage. This method allows for effective ground fault detection by utilizing the change in voltage during a fault, where the faulted phase voltage collapses to zero while the others rise. The document also compares broken delta with open delta connections, highlighting their distinct applications and characteristics.

Uploaded by

Baidyanath Mahto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
222 views6 pages

Broken Delta - Voltage Disturbance

Broken delta refers to a connection of Voltage Transformers (VT) used for ground fault detection in ungrounded systems, requiring three VTs in series to calculate zero-sequence voltage. This method allows for effective ground fault detection by utilizing the change in voltage during a fault, where the faulted phase voltage collapses to zero while the others rise. The document also compares broken delta with open delta connections, highlighting their distinct applications and characteristics.

Uploaded by

Baidyanath Mahto
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

1/27/25, 3:43 PM Broken Delta – Voltage Disturbance

AC Drives / Interference Control

POWER ENGINEERING POWER QUALITY GROUNDING

Search 

ENGINEERING CALCULATORS 

BROKEN DELTA
 July 22, 2018  admin  Power Engineering

Broken delta refers to the connection of Voltage Transformers (VT) or Potential Transformers (PT) in
a series fashion to calculate the zero-sequence voltage of the system. Three VTs are required for
this connection. This connection is primarily used in ground fault detection of ungrounded
systems.
When a ground fault occurs in an ungrounded system, the fault current will be close to zero
making it difficult to locate and isolate ground fault using traditional ground overcurrent relay. A
parameter that can be used to our advantage in the detection and isolation of ground fault on
ungrounded system is the zero-sequence voltage during ground fault.
When a single line to ground fault occurs on ungrounded system, the faulted phase voltage will
collapse to zero while the other two phases remain healthy. From sequence components theory,
we know that when we add the three phase voltages, we get three times the zero-sequence
voltage (V0) as shown below. This is sometimes also referred to as 3V0 protection though the term
is not very common.

When there is a ground fault on A phase, the Vag voltage will be zero. However, Vbg and Vcg
voltage rise from normal line to ground voltage to line to line voltage. This can be seen in the
vector diagram below.

Also note that the Vbg and Vcg phase angles change from normal 1200 to 1500 , a 300 degree
change when ‘a’ phase is faulted to ground.

https://voltage-disturbance.com/power-engineering/broken-delta/ 1/6
1/27/25, 3:43 PM Broken Delta – Voltage Disturbance

Ground fault on ungrounded system

The voltage available at the secondary of the broken delta VT will be hence 3 times the rated line-
neutral voltage when a single line to ground fault occurs in an ungrounded system.
A method to get 3V0 is to add the three phase voltages vectorially by connecting three VTs in
series. The ends of the VT are not ‘joined’ and hence the term broken delta. Note that this is
different from open delta which uses only two transformers and is used for different purposes
but not ground fault detection.

https://voltage-disturbance.com/power-engineering/broken-delta/ 2/6
1/27/25, 3:43 PM Broken Delta – Voltage Disturbance

Broken delta ground fault detection

The three VT connected are connected in series as shown above. The voltage at both the ends of
the connection is 3V0 (see equation for zero sequence voltage above). Under normally operating
condition (unfaulted condition), the voltage across the three VT will sum to zero. When a single line
to ground fault occurs, the voltage across the VT will be 3V0 and this can be used for ground fault
detection. The ground fault relay element (59N) is connected across the open end of the series
connected VT and need to be set below 3pu for effective detection of ground fault.
A resistor (called ballast resistor) is used to load the VT secondary as shown in the figure above.
This is done for two purposes:
Stabilize the VT secondary voltage.
Prevent ferroresonance between VT and system capacitance.

Broken Delta Transformer Design Considerations


Use Line-Line rated VT: Under a fault condition, each VT is exposed to 1.73 times the nominal
phase-ground voltage even though they are connected line to ground. This is due to shifting of
the ‘neutral’ position of delta voltage triangle during a single line to ground fault. The individual
VT should be rated for line-line voltage.
Use Loading resistor: Since broken delta connection is used typically in ungrounded systems,
the configuration has a tendency to drift in to ferroresonance. If you notice the circuit diagram
for broken delta connection, the primary VT circuit is wye grounded. This configuration makes it
vulnerable to damaging ferroresonant oscillations between VT magnetizing reactance and
system stray capacitance. The easy way to prevent this is to load the VT secondary with a
loading resistor (ballast resistor). The resistor is sized anywhere from 30-50% of the VA rating of
the voltage transformer.

Broken Delta ground fault detection on grounded systems


Commonly, broken delta is used for ground fault detection on ungrounded system. Use of this
scheme for ground fault detection on grounded wye systems are not common since other

https://voltage-disturbance.com/power-engineering/broken-delta/ 3/6
1/27/25, 3:43 PM Broken Delta – Voltage Disturbance

sensitive methods of ground detection using current transformers (CT) and ground overcurrent
relays are readily available.
Broken delta scheme can however be used on grounded wye systems. See the vector position
below for normal condition and when a ground fault occurs on ‘A’ phase.

Ground fault on grounded system

This indicates that when broken delta is applied in grounded systems we get normal line to
neutral voltage across the windings unlike when applied on ungrounded systems which
provide 3 times the line to neutral voltage.
Here is the summary of the broken delta output voltage for various grounding conditions:

If there is a system that can become alternatively grounded and ungrounded depending on the
source connection, then the ground fault 59N relay can be set to lower than VLN for ground
detection in both cases when broken delta is used. Broken delta can also detect double line to

https://voltage-disturbance.com/power-engineering/broken-delta/ 4/6
1/27/25, 3:43 PM Broken Delta – Voltage Disturbance

ground fault if the relay is set sensitively. An engineering review will be needed to arrive at suitable
relay settings.

Broken Delta vs Open Delta


Broken Delta
Primarily used for ground detection on ungrounded systems
Uses three Voltage Transformers connected in series
Used to gather zero sequence voltage for ground fault detection and other relaying applications
Needs line-line rated VT for ground fault detection
Secondary circuit of broken delta needs to be loaded to prevent ferroresonance

Broken delta connection

Open Delta
Open delta connection is primarily an economical way to provide three-phase power using only
two single phase transformers.
Providing power using open delta connection is not very efficient
Open delta power transformer connection is prone to voltage unbalance issues
Requires larger kVA size transformers for a given load compared to regular three phase
transformers
Open delta connection can be used for economical voltage metering application especially at
medium voltage (>1kV).
For voltage metering using open delta connection, two VT provide all three line-line voltages.

https://voltage-disturbance.com/power-engineering/broken-delta/ 5/6
1/27/25, 3:43 PM Broken Delta – Voltage Disturbance

Open delta connection

More details about open delta connection can be found here.