2CDC112177D0201 E CM MPN.x2 Data Sheet

The CM-MPN series of multifunctional three-phase monitoring relays are designed to monitor phase parameters such as phase sequence, phase failure, over- and undervoltage, and phase unbalance. They offer adjustable tripping delays, two connection technologies (screw and push-in terminals), and are suitable for various AC systems. The relays feature front-face controls for precise adjustments and visual indicators for operational states and fault messages.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views16 pages

2CDC112177D0201 E CM MPN.x2 Data Sheet

The CM-MPN series of multifunctional three-phase monitoring relays are designed to monitor phase parameters such as phase sequence, phase failure, over- and undervoltage, and phase unbalance. They offer adjustable tripping delays, two connection technologies (screw and push-in terminals), and are suitable for various AC systems. The relays feature front-face controls for precise adjustments and visual indicators for operational states and fault messages.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

Data sheet
D ATA S H E E T

Multifunctional three-phase monitoring relays


CM-MPN
CM-MPN.52, CM-MPN.62 and CM-MPN.72
The three-phase monitoring relays CM-MPN.x2 monitor the
phase parameters phase sequence, phase failure, over- and
undervoltage as well as phase unbalance.

All devices are available with two different terminal versions.


You can choose between the proven screw connection
technology (double-chamber cage connection terminals)
and the completely tool-free Easy Connect Technology
(push-in terminals).

2CDC 251 062 V0011


Characteristics
• Monitoring of three-phase mains for phase sequence (can • Precise adjustment by front-face operating controls
be switched off), phase failure, over- and undervoltage • Screw connection technology or Easy Connect Tech-
as well as phase unbalance nology available
• TRMS measuring principle • Housing material for highest fire protection classification
• Automatic phase sequence correction configurable UL 94 V-0
• Threshold values for over- and undervoltage as well as • Tool-free mounting on DIN rail as well as demounting
phase unbalance are adjustable as absolute values • 1 x 2 or 2 x 1 c/o (SPDT) contacts configurable
• Tripping delay Tv can be adjusted or switched off by means • 45 mm (1.78 in) width
of a logarithmic scale (0 s; 0,1-30 s) • 3 LEDs for the indication of operational states
• ON-delayed or OFF-delayed tripping delay selectable
• Powered by the measuring circuit


Order data

Three-phase monitoring relays


Type Rated control supply voltage = measuring voltage Connection technology Order code

CM-MPN.52P 3 x 350-580 V AC Push-in terminals 1SVR760487R8300


CM-MPN.52S Screw terminals 1SVR750487R8300
CM-MPN.62P 3 x 450-720 V AC Push-in terminals 1SVR760488R8300
CM-MPN.62S Screw terminals 1SVR750488R8300
CM-MPN.72P 3 x 530-820 V AC Push-in terminals 1SVR760489R8300
CM-MPN.72S Screw terminals 1SVR750489R8300

Accessories
Type Description Order code
ADP.02 Adapter for screw mounting 1SVR440029R0100
MAR.12 Marker label for devices with DIP switches 1SVR730006R0000
COV.12 Sealable transparent cover 1SVR750005R0100
2 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72


Connection technology
Maintenance free Easy Connect Technology with push-in Approved screw connection technology with double-
terminals chamber cage connection terminals

Type designation CM-xxS.yyP Type designation CM-xxS.yyS

2CDC 253 026 F0011

2CDC 253 025 F0011


Push-in terminals Double-chamber cage connection terminals
• Tool-free connection of rigid and flexible wires with wire • Terminal spaces for different wire sizes
end ferrule • One screw for opening and closing of both cages
• Easy connection of flexible wires without wire end ferrule • Pozidrive screws for pan- or crosshead screwdrivers
by opening the terminals according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x
• No retightening necessary 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in)
• One operation lever for opening both connection terminals
• For triggering the lever and disconnecting of wires you can
use the same tool (Screwdriver according to DIN ISO
2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO
8764-1 PZ1 ø 4.5 mm (0.177 in))
• Constant spring force on terminal point independent of
the applied wire type, wire size or ambient conditions
(e. g. vibrations or temperature changes)
• Opening for testing the electrical contacting
• Gas-tight

Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage
connection terminals have the same connection geometry as well as terminal position.
3 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72


Functions
Operating controls

Adjustment of the threshold value


>U for overvoltage

Adjustment of the threshold value


Asym. for phase unbalance

Indication of operational states


2CDC 251 062 V0011

R/T: yellow LED – Relay status / timing


F1: red LED – Fault message
F2: red LED – Fault message

Adjustment of the tripping delay Tv

Adjustment of the threshold value <U


for undervoltage

DIP switches (see DIP switch functions)

Application
The three-phase monitoring relays CM-MPN.x2 are designed for use in three-phase mains for monitoring the phase param-
eters phase sequence, phase failure, over- and undervoltage as well as phase unbalance.
The CM-MPN.x2 provide an adjustable tripping delay and work according to the closed-circuit principle.

Operating mode
The CM-MPN.x2 have 2 c/o (SPDT) contacts and are available for 3-wire AC systems. The units are adjusted with front-face
operating controls. The selection of ON- A or OFF- B delay, phase sequence monitoring activated k or phase
sequence monitoring deactivated l , 2 x 1 c/o i or 1 x 2 c/o j (SPDT) contacts as well as automatic phase sequence
correction activated m or automatic phase sequence correction deactivated n is made with DIP switches. Potentiome-
ters, with direct reading scale, allow the adjustment of the threshold values for overvoltage (>U), undervoltage (<U), phase
unbalance (Asym %) and the tripping delay Tv. The tripping delay Tv is adjustable with a range from instantaneous to a 30 s
delay. Timing is displayed by a flashing yellow LED labelled R/T.
4 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72


Adjustment potentiometer

Threshold values
By means of three separate potentiometers with direct reading scales, the threshold values for over- and undervoltage as
well as for phase unbalance can be adjusted within the measuring range.

Measuring range for overvoltage Measuring range for undervoltage Measuring range for phase unbalance
CM-MPN.52 3 x 480-580 V AC 3 x 350-460 V AC
CM-MPN.62 3 x 600-720 V AC 3 x 450-570 V AC 2-25 % of average of phase voltages
CM-MPN.72 3 x 690-820 V AC 3 x 530-660 V AC

Tripping delay Tv
The tripping delay Tv can be adjusted within a range of 0.1 to 30 s by means of a potentiometer with logarithmic scale.
By turning to the left stop, the tripping delay can be switched off.


Indication of operational states
LEDs, status information and fault messages
Operational state R/T: LED yellow F1: LED red F2: LED red
Control supply voltage applied,
V - -
output relay energized
Tripping delay Tv active W - -
Phase failure - V W
Phase sequence - W alternating
Overvoltage - V -
Undervoltage - - V
Phase unbalance - V V
Adjustment error 1) W W W

1)

Possible misadjustments of the front-face operating controls:


Overlapping of the threshold values: The threshold value for overvoltage is set to a smaller value than the threshold value for undervoltage.
DIP switch 3 = OFF and DIP switch 4 = ON: Automatic phase sequence correction is activated and selected operating mode is 1 x 2 c/o (SPDT) contacts.
DIP switch 2 and 4 = ON: Phase sequence detection is deactivated and the automatic phase sequence correction is actived.
5 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72


Function descriptions / diagrams

Phase sequence and phase failure monitoring


Applying control supply voltage begins the fixed start-up delay Ts. When Ts is complete and all phases are present with
correct voltage, the output relays energize and the yellow LED R/T is on.

Phase sequence monitoring


If phase sequence monitoring is activated (DIP switch 2 = OFF), the output relays de-energize as soon as a phase sequence
error occurs. The fault is displayed by alternated flashing of the LEDs F1 and F2. The output relays re-energize automatically
as soon as the phase sequence is correct again.
If phase sequence monitoring is deactivated (DIP switch 2 = ON), a phase sequence error will not cause tripping of the relays.
The output relays do not change state and the LEDs F1 and F2 don‘t flash.

Phase failure monitoring:


The output relays de-energize instantaneously if a phase failure occurs. The fault is indicated by lighting up of LED F1 and
flashing of LED F2. The output relays re-energize automatically as soon as the voltage returns to the tolerance range.

L1, L2, L3

2CDC 252 094 F0207


Measured value L1, L2, L3 L1, L3, L2 L1, L2, L3 L1, L2 L1, L2, L3 L1 L1, L2, L3

Ts L3 L2, L3

15-18
15-16
25-28
25-26
2CDC 252 094 F0207

F1: red LED


F2: red LED
R/T: yellow LED
Ts = start-up delay fixed 200 ms

Over- and undervoltage monitoring 1 x 2 c/o (SPDT) contacts j


Applying control supply voltage begins the fixed start-up delay Ts. When Ts is complete and all phases are present with
correct voltage and with correct phase sequence, the output relays energize and the yellow LED R/T is on.

Type of tripping delay = ON-delay A


If the voltage to be monitored exceeds or falls below the set threshold value, the output relays de-energize after the set trip-
ping delay Tv is complete. The LED R/T flashes during timing and turns off as soon as the output relays de-energize.
The output relays re-energize automatically as soon as the voltage returns to the tolerance range, taking into account a fixed
hysteresis of 5 %. The LED R/T is on.

L1, L2, L3
2CDC 252 090 F0207

>U
>U-5%

Measured value
<U+5%
<U
Ts Tv <Tv Tv
15-18
15-16
25-28
25-26

F1: red LED


2CDC 252 090 F0207

F2: red LED


R/T: yellow LED
Ts = start-up delay fixed 200 ms
Tv = adjustable tripping delay
6 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72

Type of tripping delay = OFF-delay B


If the voltage to be monitored exceeds or falls below the set threshold value, the output relays de-energize instantaneously
and the LED R/T turns off.
As soon as the voltage returns to the tolerance range, taking into account a fixed hysteresis of 5 %, the output relays
re-energize automatically after the set tripping delay Tv is complete. The LED R/T flashes during timing and turns steady
when timing is complete.

L1, L2, L3

2CDC 252 091 F0207


>U
>U-5%

Measured value
<U+5%
<U
Ts Tv <Tv <Tv
15-18
15-16
25-28
25-26

F1: red LED

2CDC 252 091 F0207


F2: red LED
R/T: yellow LED
Ts = start-up delay fixed 200 ms
Tv = adjustable tripping delay

Over- and undervoltage monitoring 2 x 1 c/o (SPDT) contacts i


Applying control supply voltage begins the fixed start-up delay Ts. When Ts is complete and all phases are present with
correct voltage and with correct phase sequence, the output relays energize. The yellow LED R/T is on as long as at least one
output relay is energized.

Type of tripping delay = ON-delay A


If the voltage to be monitored exceeds or falls below the set threshold value, output relay R1 (overvoltage) or output relay R2
(undervoltage) de-energizes after the set tripping delay Tv is complete.The LED R/T flashes during timing.
The corresponding output relay re-energizes automatically as soon as the voltage returns to the tolerance range, taking into
account a fixed hysteresis of 5 %.

L1, L2, L3
2CDC 252 006 F0207

>U
>U-5%

Measured value
<U+5%
<U
Ts Tv <Tv Tv
15-18
15-16
25-28
25-26

F1: red LED


2CDC 252 006 F0207

F2: red LED


R/T: yellow LED
Ts = start-up delay fixed 200 ms
Tv = adjustable tripping delay
7 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72

Type of tripping delay = OFF-delay B


If the voltage to be monitored exceeds or falls below the set threshold value, output relay R1 (overvoltage)
or output relay R2 (undervoltage) de-energizes instantaneously.
As soon as the voltage returns to the tolerance range, taking into account a fixed hysteresis of 5 %, the corresponding
output relay re-energizes automatically after the set tripping delay Tv is complete. The LED R/T flashes during timing.

L1, L2, L3

2CDC 252 007 F0207


>U
>U-5%

Measured value
<U+5%
<U
Ts Tv <Tv <Tv
15-18
15-16

25-28
25-26
F1: red LED

2CDC 252 007 F0207


F2: red LED
R/T: yellow LED
Ts = start-up delay fixed 200 ms
Tv = adjustable tripping delay

Phase unbalance monitoring


Applying control supply voltage begins the fixed start-up delay Ts. When Ts is complete and all phases are present with
correct voltage and with correct phase sequence, the output relays energize and the yellow LED R/T is on.

Type of tripping delay = ON-delay A


If the voltage to be monitored exceeds or falls below the set phase unbalance threshold value, the output relays
de-energize after the set tripping delay Tv is complete. The LED R/T flashes during timing and turns off as soon as the output
relays de-energize.

The output relays re-energize automatically as soon as the voltage returns to the tolerance range, taking into account a fixed
hysteresis of 20 %. The LED R/T is on.

L1, L2, L3
2CDC 252 092 F0207

Unbalance
L3
Unbalance - 20%

Measured value
L1, L2, L3 L1, L2
Unbalance + 20%
Unbalance
Ts Tv <Tv Tv
15-18
15-16
25-28
25-26

F1: red LED


2CDC 252 092 F0207

F2: red LED


R/T: yellow LED
Ts = start-up delay fixed 200 ms
Tv = adjustable tripping delay
8 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72

Type of tripping delay = OFF-delay B


If the voltage to be monitored exceeds or falls below the set phase unbalance threshold value, the output relays de-energize
instantaneously and the LED R/T turns off.
As soon as the voltage returns to the tolerance range, taking into account a fixed hysteresis of 20 %, the output relays
re-energize automatically after the set tripping delay Tv is complete. The LED R/T flashes during timing and turns steady
when timing is complete.

L1, L2, L3

2CDC 252 093 F0207


Unbalance
L3
Unbalance - 20%

Measured value
L1, L2, L3 L1, L2
Unbalance + 20%
Unbalance
Ts Tv <Tv <Tv
15-18
15-16
25-28
25-26

F1: red LED

2CDC 252 093 F0207


F2: red LED
R/T: yellow LED
Ts = start-up delay fixed 200 ms
Tv = adjustable tripping delay

Automatic phase sequence correction


This function can be selected only if phase sequence monitoring is activated k (DIP switch 2 = ON) and operating mode
2 x 1 c/o (SPDT) contact j is selected (DIP switch 3 = OFF).
Applying control supply voltage begins the fixed start-up delay Ts1 . When Ts1 is complete and all phases are present with
correct voltage, output relay R1 energizes. Output relay R2 energizes when the fixed start-up delay Ts2 is complete and all
phases are present with correct phase sequence. Output relay R2 remains de-energized if the phase sequence is incorrect.
If the voltage to be monitored exceeds or falls below the set threshold values for phase unbalance, over- or undervoltage or if
a phase failure occurs, output relay R1 de-energizes and the LEDs F1 and F2 indicate the fault.
Output relay R2 is responsive only to a false phase sequence. In conjunction with a reversing contactor combination, this
enables an automatic correction of the rotation direction. See circuit diagrams.

L1, L2, L3

Measured value L1, L2, L3 L1, L2 L1, L2, L3 L1, L3, L2


Ts1 L3 Ts1
Ts2 Ts2
15-18
15-16
25-28
25-26

F1: red LED


2CDC 252 085 F0107

F2: red LED


R/T: yellow LED
Ts1 = start-up delay of R1 fixed 250 ms
Ts2 = start-up delay of R2 fixed 200 ms

L1 L2 L3
L1
L2 1 3 5
L3 -F1
2 4 6

K1
15

18 1 3 5 1 3 5
16 -K2 2 4 6
-K3 2 4 6

25 1 5 4 97 95
K1 -F2
2CDC 252 087 F0b07
2CDC 253 009 F0014

98 96
28 26 3 2 6

-M1
A1 A1
W1
K1 K2 K3 H1
V1 M
A2 A2 U1 3~
N

— —
Control circuit diagram (K1 = CM-MPN.x2) Power circuit diagram
9 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72


Electrical connection
L1, L2, L3 Control supply voltage = measuring voltage

L1 L2 L3 15-16/18 Output contacts - closed-circuit principle


25-26/28
L1 L2 L3 15 25
2CDC 252 038 F0008

16 18 26 28

16 15 18 26 25 28


Connection diagram CM-MPN.x2


DIP switches
Position 4 3 2 1

ON
2CDC 252 041 F0008

OFF

1 Timing function ON ON-delayed A:


In case of a fault, the de-energizing of the output relays and the respective fault message are ­suppressed
for the adjusted tripping delay Tv.

OFF OFF-delayed B:
In case of a fault, the output relays de-energize instantaneously and a fault message is displayed and
stored for the length of the ­adjusted tripping delay Tv. Thereby, also momentary undervoltage conditions
are recognized.
2 Phase sequence ON Phase sequence monitoring deactivated l
monitoring Phase sequence errors will not cause tripping of the relays.
OFF Phase sequence monitoring activated k
The output relays de-­energize as soon as a phase sequence error occurs. The output relays re-­energize
automatically as soon as the phase sequence is correct again.
3 Operating principle ON 2x1 c/o (SPDT) contact i
of the output relays Depending on the configuration of automatic phase sequence correction and on the fault type, the output
relays R1 (15-16/18) and R2 (25-26/28) react differently, if operating principle 2x1 c/o (SPDT) contact is
selected.
Automatic phase sequence correction deactivated n:
• Overvoltage:
only 1st c/o (SPDT) contact R1 (15-16/18) switches
• Undervoltage:
only 2nd c/o (SPDT) contact R2 (25-26/28) switches
• Phase unbalance, phase sequence, phase failure, interrupted neutral: both output relays R1
(15-16/18) and R2 (25-26/28) react synchronously
Automatic phase sequence correction activated m:
• Overvoltage, undervoltage, phase unbalance, phase failure, interrupted neutral: only 1st c/o (SPDT)
contact R1 (15-16/18) switches
• Phase sequence: only 2nd c/o (SPDT) contact R2 (25-26/28) switches
Operating principle 2x1 c/o (SPDT) contact is mandatory if automatic phase sequence correction is
activated.
OFF 1x2 c/o (SPDT) contacts j
If operating principle 1x2 c/o (SPDT) contacts is selected, both output relays R1 (15-16/18) and R2
(25-26/28) react synchronously, independent of the fault type.
4 Automatic phase ON Phase sequence correction activated m
sequence correction In conjunction with a reversing contactor combination, it is ensured that the correct phase sequence is
applied to the input terminals of the load.
OFF Phase sequence correction deactivated n
No automatic phase sequence correction in case of phase sequence error.
10 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72


Technical data
Data at Ta = 25 °C and rated values, unless otherwise indicated


Input circuit
Type CM-MPN.52 CM-MPN.62 CM-MPN.72
Supply circuit = measuring circuit L1, L2, L3
Rated control supply voltage Us = measuring voltage 3 x 350-580 V AC 3 x 450-720 V AC 3 x 530-820 V AC
Rated control supply voltage Us tolerance -15...+10 %
Rated frequency 50/60 Hz
Frequency range 45-65 Hz
Typical current / power consumption 29 mA / 41 VA 29 mA / 52 VA 29 mA / 59 VA
(480 V AC) (600 V AC) (690 V AC)

Measuring circuit L1, L2, L3


Monitoring functions Phase failure J
Phase sequence can be switched off
Automatic phase sequence correction configurable
Over-/undervoltage J
Phase unbalance J
Measuring range Overvoltage 3 x 480-580 V AC 3 x 600-720 V AC 3 x 690-820 V AC
Undervoltage 3 x 350-460 V AC 3 x 450-570 V AC 3 x 530-660 V AC
Phase unbalance 2-25 % of average of phase voltages
Thresholds Overvoltage adjustable within measuring range
Undervoltage adjustable within measuring range
Phase unbalance (switch-off value) adjustable within measuring range
Tolerance of the adjusted threshold value 6 % of full-scale value
Hysteresis related to Over-/undervoltage fixed 5 %
the threshold value
Phase unbalance fixed 20 %
Rated frequency of the measuring signal 50/60 Hz
Frequency range of the measuring signal 45-65 Hz
Maximum measuring cycle time 100 ms
Accuracy within the rated control supply voltage tolerance DU  0.5 %
Accuracy within the temperature range DU  0.06 % / °C
Measuring method True RMS

Timing circuit
Start-up delay Ts and Ts2 fixed 200 ms
Start-up delay Ts1 fixed 250 ms
Tripping delay Tv ON- or OFF-delay
0 s; 0.1-30 s adjustable
Repeat accuracy (constant parameters) < w0.2 %
Accuracy within the rated control supply voltage tolerance Dt  0.5 %
Accuracy within the temperature range Dt  0.06 % / °C


User interface
Indication of operational states
Relay status / timing R/T yellow LED
Fault message F1 red LED
Fault message F2 red LED

Details see table ‚LEDs, status information and fault messages‘ on page 4 and ‚Function descriptions / diagrams‘ on page 5.
11 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72


Output circuits
Kind of output 15-16/18
relays, 1 x 2 or 2 x 1 (SPDT) contact(s) configurable
25-26/28
Operating principle closed-circuit principle 1)
Contact material AgNi alloy, Cd free
Rated operational voltage Ue 250 V
Minimum switching voltage / Minimum switchting current 24 V / 10 mA
Maximum switchting voltage / Maximum switching current see load limit curves
Rated operational current Ie AC-12 (resistive) at 230 V 4A
AC-15 (inductive) at 230 V 3A
DC-12 (resistive) at 24 V 4A
DC-13 (inductive) at 24 V 2A
AC rating (UL 508) Utilization category
B 300
(Control Circuit Rating Code)
max. rated operational voltage 300 V AC
max. continuous thermal current at B 300 5A
max. making/breaking apparent power
3600/360 VA
at B 300
Mechanical lifetime 30 x 10 6 switching cycles
Electrical lifetime AC-12, 230 V, 4 A 0.1 x 10 6 switching cycles
Maximum fuse rating to achieve n/c contact 10 A fast-acting
short-circuit protection
n/o contact 10 A fast-acting


General data
MTBF on request
Duty time 100 %
Dimensions see ‘Dimensional drawings’
Weight Screw connection technology Easy Connect Technology (push-in)
net weight CM-MPN.52 0.230 kg (0.507 lb) 0.226 kg (0.498 lb)
CM-MPN.62 0.229 kg (0.504 lb) 0.224 kg (0.494 lb)
CM-MPN.72 0.224 kg (0.494 lb) 0.220 kg (0.485 lb)
gross weight CM-MPN.52 0.255 kg (0.562 lb) 0.251 kg (0.553 lb)
CM-MPN.62 0.254 kg (0.560 lb) 0.250 kg (0.551 lb)
CM-MPN.72 0.249 kg (0.549 lb) 0.245 kg (0.540 lb)
Mounting DIN rail (IEC/EN 60715), snap-on mounting without any tool
Mounting position any
Minimum distance to other units not necessary
Material of housing UL 94 V-0
Degree of protection housing IP50
terminals IP20

1) Closed-circuit principle: Output relay(s) de-energize(s) if measured value exceeds or falls below the adjusted threshold value.


Electrical connection
Screw connection Easy Connect
technology Technology (push-in)
Connnecting capacity fine‑strand with(out) 1 x 0.5-2.5 mm² 2 x 0.5-1.5 mm²
wire end ferrule (1 x 18-14 AWG) (2 x 18-16 AWG)
2 x 0.5-1.5 mm²
(2 x 18-16 AWG)

rigid 1 x 0.5-4 mm² 2 x 0.5-1.5 mm²


(1 x 20-12 AWG) (2 x 20-16 AWG)
2 x 0.5-2.5 mm²
(2 x 20-14 AWG)

Stripping length 8 mm (0.32 in)


Tightening torque 0.6 - 0.8 Nm -
(7.08 lb.in)
12 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72


Environmental data
Ambient temperature ranges operation -25...+60 °C
storage -40...+85 °C
Damp heat, cyclic (IEC/EN 60068-2-30) 6 x 24 cycle, 55 °C, 95 % RH
Climatic class 3K3
Vibration, sinusoidal Class 2
Shock Class 2


Isolation data
Type
Rated insulation input circuit / output circuit 1000 V
voltage Ui
output circuit 1 / output circuit 2 300 V
Rated impulse withstand input circuit / output circuit 6 kV, 1.2/50 µs
voltage Uimp
output circuit 1 / output circuit 2 4 kV, 1.2/50 µs
Basic insulation input circuit / output circuit 1000 V
Protective separation input circuit / output circuit -
(IEC/EN 61140, EN 50178)
Pollution degree 3
Overvoltage category III


Standards / Directives
Standards IEC/EN 60947-5-1, IEC/EN 60255-27, EN 50178
Low Voltage Directive 2014/35/EU
EMC directive 2014/30/EU
RoHS directive 2011/65/EU


Electromagnetic compatibility
Type
Interference immunity to IEC/EN 61000-6-2
electrostatic discharge IEC/EN 61000-4-2 Level 3 (6 kV / 8 kV)
radiated, radio-frequency, IEC/EN 61000-4-3 Level 3 (10 V/m)
electromagnetic field
electrical fast transient / burst IEC/EN 61000-4-4 Level 3 (2 kV / 2 kHz)
surge IEC/EN 61000-4-5 Level 4 (2 kV L-L)
conducted disturbances, induced by IEC/EN 61000-4-6 Level 3 (10 V)
radio-frequency fields
harmonics and interharmonics IEC/EN 61000-4-13 Class 3
Interference emission IEC/EN 61000-6-3
high-frequency radiated IEC/CISPR 22, EN 55022 Class B
high-frequency conducted IEC/CISPR 22, EN 55022 Class B
13 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72


Technical diagrams
Load limit curves

V V
300 300
V 200 V 200
resistive load
resistive load
100 100
80 80
60 60
50 50
40 40
30 30

2CDC 252 194 F0205


20 20

2CDC 252 193 F0205


10 10
0.1 0.2 0.5 1 2 4 6 10
0.1 0.2 0.5 1 2 4 6 10
I A
I A

— —
AC load (resistive) DC load (resistive)

1.0
Switching cycles

0.9

0.8
F
0.7 250 V
resistive load
0.6
2CDC 252 192 F0205

0.5

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

2CDC 252 148 F0206


cos ϕ


Derating factor F for inductive AC load Switching current [A]


Contact lifetime
14 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72


Dimensions
in mm and inches

114.5 4.51”

107.0 4.21” 45.0 1.77”

85.6 3.37”

2CDC 252 022 F0011


104.8 4.13”


Accessories
in mm and inches

9.3 0.37”
45.0 0.89”
0.453”

5.75 0.23”
11.5
0.256”
35 1.378”
45 1.772”

68 2.68”
6.5

22.2
0.394”

2CDC 252 009 F0010


0.787”

2CDC 252 020 F0011

2CDC 252 023 F0011


0.874”
20
10

4T22
0.309”
7.85

60 2.362”
62.5 2.461” 19.9 front to back
70 2.756” 0.783” 111.8 4.40”

— — —
ADP.02 ‑ Adapter for screw mounting MAR.12 ‑ Marker label for COV.12 ‑ Sealable transparent cover
devices with DIP switches
15 DATA SHEET CM-MPN.52 / CM-MPN.62 / CM-MPN.72

Further documentation

Document title Document type Document number


Electronic relays and controls Catalog 2CDC 110 004 C02xx
CM-MPS.23, CM-MPS.43, Instruction manual 1SVC 730 530 M0000
CM-MPN.52, CM-MPN.62, CM-MPN.72

You can find the documentation on the internet at www.abb.com/lowvoltage


-> Automation, control and protection -> Electronic relays and controls -> Measuring and monitoring relays.

CAD system files


You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com
-> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls.
2CDC112177D0201 Rev. E (01/2020)

— —
ABB STOTZ-KONTAKT GmbH We reserve the right to make technical We reserve all rights in this document and
Eppelheimer Strasse 82 changes or modify the contents of this in the subject matter and illustrations
69123 Heidelberg, Germany document without prior notice. With regard contained therein. Any reproduction,
to purchase orders, the agreed particulars disclosure to third parties or utilization
shall prevail. ABB Ltd. does not accept any of its contents – in whole or in parts – is
responsibility whatsoever for potential forbidden without prior written consent of
errors or possible lack of information in ABB Ltd. Copyright© 2020 ABB Ltd.
this document. All rights reserved