CompEx Ex01-Ex04 Course Notes
CompEx Ex01-Ex04 Course Notes
Gas Vapour
Course Notes
Cenelec Standards Inspections Ltd
Training Centre
1|Page
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Introduction
This is a National Training and Assessment Scheme for electrical craft personnel
who work or intend to work in potentially explosive atmospheres.
Aims
The aim of the course is to provide delegates’ with knowledge and understanding on
terminology and protection concepts for electrical/instrument equipment utilised in a
potentially flammable atmosphere.
Objectives
At the end of the course you will be able to:
Understand the concept of area classification and the need to zone flammable
atmospheres accordingly.
2|Page
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Understand the various protection concepts namely EExd, EExe, ExN, EExn,
EExia & EExib, EExp, EExo, EExq and EEXm.
Assessment
Combination of classroom delivery and practical/written assessment.
Certification
Successful course delegates will receive a UK JTL Certificate of Core Competence
valid for 5 years.
3|Page
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
History
Soon after the introduction of electric power into coal mines, it was discovered that
lethal explosions could be initiated by electrical equipment such as lighting, signals,
or motors. The hazard of fire damp or methane accumulation in mines was well
known by the time electricity was introduced, along with the danger of suspended
coal dust. At least two British mine explosions were attributed to an electric bell
signal system. In this system, two bare wires were run along the length of a drift, and
any miner desiring to signal the surface would momentarily touch the wires to each
other or bridge the wires with a metal tool. The inductance of the signal bell coils,
combined with breaking of contacts by exposed metal surfaces, resulted in sparks
which could ignite methane, causing an explosion.
Fire damp: consists of mostly methane, a highly flammable gas that explodes
between 5% and 15% - at 25% it causes asphyxiation
In England, The Oaks explosion remains the worst mining accident, claiming 388
lives on 12 December 1866 near Barnsley in Yorkshire. The Hulton Colliery
explosion at Westhoughton, Lancashire, in 1910 claimed the lives of 344 miners.
An explosion in 1878, at the Wood Pit, Haydock, Lancashire, killed over 200
workers, although only 189 were included in the 'official list'. Another disaster that
killed many miners was the Hartley Colliery Disaster, which occurred in January
1862 when the beam of the main steam winding engine broke suddenly and fell into
the single shaft serving the pit. It blocked the shaft, and entombed hundreds of
miners. The final death toll was 204, most of whom were suffocated by the lack of
oxygen in the mine atmosphere.
4|Page
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 1: Standards
IEC - Standards dealing with electrical apparatus for hazardous areas are numbered
in the series 79 - xx e.g. 79 – 14 this refers to electrical apparatus for explosive gas
atmospheres, Part 14: Electrical Installations in hazardous areas (other than mines)
All hazardous areas must now conform to ATEX 95 & ATEX 137 Applies to both
electrical & mechanical equipment.
The EC directive 99/92/CE concerns the minimum requirements for improving the
health and safety of workers in potentially explosive atmospheres.(Atex Directive
137( Was 118) – The UK regulations which puts into effect this directive is
DSEAR)
The main change in the EC directive 94/9/EC is that non-electrical hazards are now
brought within the scope of the directive.
Pump, mechanical seals, reducer, coupling, guard coupling and motor must be in
accordance.
5|Page
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
For new equipment, Compliance with the ATEX directive has been a legal
requirement in all European Union member states since 1st July 2003.
Equipment compliance with the ATEX directive is a legal requirement in all European
Union member states by 1st July 2006.
ATEX – An Introduction
Two main Aims
Scope of ATEX
Main exclusions are medical, military, PPE, Body repair shops, painting etc.
6|Page
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Manufacturers’ Responsibilities
• Comply with Essential Health and Safety Requirements
• Implemented by DTI
• Main aim is protection of workers (and the public) from explosion hazards
• To classify the zone and the corresponding equipment group (dust or gas) in
accordance with the EC directive 94/9/EC
7|Page
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Equipment Groups and Categories
Category 1
Category 2
Category 3
Atmosphere Type
Gas atmosphere, G
Dust atmosphere, D
Zones
8|Page
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Equipment Groups and Categories
Explosion Group
For electrical equipment, the explosion group is subdivided into three apparatus
groups:
IIC – hydrogen
The group is directly related to the minimum ignition energy required to initiate an
explosion in each group.
IIB – 60 Microjoules
IIC – 20 Microjoules
9|Page
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Zones and ATEX Categories
Zone 0 - Category 1
Zone 1 - Category 2
Zone 2 - Category 3
'New Approach' Directives (that is Community laws) set out essential requirements
(for safety, for example), written in general terms which must be met before products
may be sold in the United Kingdom or anywhere else in the Community. European
standards fill in the detail and are the main way for business to meet the essential
requirements. The Directives also say how manufacturers are to show that products
meet the essential requirements. Products meeting the requirements are to carry
CE marking, which should mean that they can be sold anywhere in the Community/
EEA(1). Directive 94/9/EC on equipment and protective systems intended for use
in potentially explosive atmospheres is one of these 'New Approach' Directives.
ATEX Directive 137 (Was 118) The UK regulations which puts into effect
this directive is DSEAR
The ATEX 137 Directive is aimed at ensuring the health and safety of workers whilst
in their place of work. This directive categorises the workplace into zones. Zones
provide a measure of the probability of the presence of a dangerous mixture with air
of any flammable gas or combustible dust.
10 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
This is intended to ensure that workers enjoy a minimum level of protection
throughout all member states.
Training of staff
11 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
The Risk Assessment
The employer is already required to carry out a risk assessment under the
requirements of the framework directive (89/391/EEC). The risk assessment is not
therefore an additional requirement.
• The intended process, installation, substances used and any possible interaction
between them
12 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
The Explosion Protection Document (EPD)
The EPD is based on the risk assessment. Once the risk assessment has been
carried out and identified a likelihood that workers may be exposed to an explosive
atmosphere, an EPD must be drawn up. This must be done before commencing
work and it must be revised in the event that the workplace, work equipment or
organisation of the work undergoes significant change. Existing documents or other
equivalent reports may be utilised to satisfy this requirement to avoid unnecessary
duplication. Any workplace which contains locations where an explosive atmosphere
may occur must be verified before it is put into operation for the first time.
This verification must be carried out by persons competent in the field of explosion
protection. This competence must be demonstrable in the form of experience and/or
professional training.
The EPD must demonstrate that all explosion risks have been determined and
assessed. Those locations or areas which have been identified as “hazardous
locations” shall be identified in the EPD.
13 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Summary of Main Duties on Employers:
• Prepare an explosion protection document (EPD)
• Classify the workplace into Zones where applicable
• Select ATEX 100a products according to Zone
• Identify, using warning signs, locations where explosive atmospheres may occur.
Conclusion
Directive 99/92/EC introduces specific legal requirements aimed at protecting
workers from the potential dangers of explosive atmospheres. Directive 94/9/EC and
directive 99/92/EC are complimentary. Although they both address the same risks
they are aimed at different sectors. Users and operators will therefore need to
ensure they are fully aware of the new requirements.
ATEX Markings
14 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Nature of the Hazard
Group I
Group II
This course is intended for Group II gases and NOT for Group I Mining (M1 & M2).
15 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 2: Area classification
Hazardous Areas
A Hazardous Area is considered to be an area where an explosive atmosphere is or
maybe expected to be present which requires special precautions to be taken for the
construction, installation and use of electrical equipment. For the standard it is
considered to be a three dimensional space .
Causes of Explosions
Explosion
16 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Explosive Material
Combustion will take place if all three elements, in one form or another, are present,
the gas/air mixture is within certain limits and the source of ignition has sufficient
energy. The removal of one element is sufficient to prevent combustion as is the
isolation or separation of the source of ignition from the gas/air mixture. These are
two techniques used in explosion protected equipment. Other protection techniques
allow the three elements to co-exist and either ensure that the energy of the source
of ignition is maintained below specific values, or allow an explosion to take place
and contain it within a robust enclosure. These techniques are addressed in the
various sections of this manual.
Ignition Sources
Welding
Electro Statics:
Lightning
Nylon Clothes
17 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Area Classification
The aim of Area Classification is:
There are many codes of practice which specify methods of grading areas of
Hazard, a few typically are:
18 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Group II Gases
Group II gases are divided into sub-divisions based on one or both of two test
methods:
MESG (Maximum Experimental Safe Gap): The maximum clearance between two
parallel metal surfaces that has been found, under specified test conditions, to
prevent an explosion in a test chamber from being propagated to a secondary
chamber containing the same gas or vapour at the same concentration.
MIC (Minimum Igniting Current) Ratio: The ratio of the minimum current required
from an inductive spark discharge to ignite the most easily ignitable mixture of a gas
or vapour, divided by the minimum current required from an inductive spark
discharge to ignite methane under the same test conditions.
19 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
The Flash Point
By definition flashpoint is: ‘the lowest temperature at which sufficient vapour is
given off a liquid, to form a flammable mixture with air that can be ignited by an arc,
spark or naked flame’.
Material Flashpoint
°C
Propane -104
Ethylene -120
Hydrogen -256
Acetylene -82
Paraffin 38
20 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
The Ignition Temperature
Ignition temperature is defined as: ‘the minimum temperature at which a flammable
material will spontaneously ignite’.
Ignition
Temperature
Material
o
C
Propane 470
Ethylene 425
Hydrogen 560
Acetylene 305
Paraffin 210
21 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
UEL and LEL Values
Chemical and physical parameters in general the greater the release rate, the larger
the zone.
22 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Extent of Zone
Concentration
Ventilation
Relative Density;
Materials which rise in the atmosphere can collect in roof spaces, and those which
fall, such as butane or propane, can drift along at ground level and possibly into a
non-hazardous location, or may collect in locations lower than ground level without
ever dispersing. Such locations should be well ventilated in order to avoid ignition
due to a stray spark or a discarded cigarette.
Knowledge of where a flammable material will collect ensures that gas detectors
when fitted will be located at the correct level
Relative vapour and ventilation is directed accordingly.
Material
density
Air 1
Propane 1.56
Ethylene 0.97
Hydrogen 0.07
Acetylene 0.9
Paraffin 4.5
23 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Area Classification
The result of an Area Classification Study is an 'Area Classification Diagram' which is
a graphical representation of the plant showing the hazardous areas (zones).
DEFINITIONS
ZONE 0
ZONE 1
ZONE 2
24 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Safe Area
An area associated with a plant which is designated free from flammable materials
and atmospheres, as designated on an area classification drawing.
Heaters, heating elements or other equipment that may produce arcs, sparks
or hot particles
Auxiliary equipment such as ballasts, capacitors and starting switches for all
types of discharge luminaires, all lamps.
25 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Temperature Classification
Temperature classification is based on the maximum temperature which any relevant
part of the apparatus, (which maybe in contact with an explosive gas) will reach,
when operating within normal design ratings, (-20°c to + 40°c)
TEMPERATURE CLASS
26 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Relationship between types of protection EPL’s and Categories
In 2006 IEC 60079 introduced EPLs (Equipment Protection Levels) which mirror the
ATEX categories.
Where only the zones are identified in the area classification documentation, then
the relationship between categories/EPLs and zones should be followed.
27 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Equipment Protection Levels (EPLs)
EPL Ga (Equivalent to Atex Cat 1)
Equipment for explosive gas atmospheres, having a 'very high' level of protection,
which is not a source of ignition in normal operation, expected faults or when subject
to rare faults.
Type of
ATEX EPL Code According to
Protection
Protection of equipment
and transmission
IEC 60079 – 28
systems using optical
radiation
Equipment for explosive gas atmospheres, having a 'high' level of protection, which
is not a source of ignition in normal operation or when subject to faults that may be
expected, though not necessarily on a regular basis.
28 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
EPL Gc (Equivalent to Atex Cat 3)
29 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
IEC 60079-14:2007 (EPL APPROACH)
Traditional approach to selection of equipment
Historically it has been acceptable to install equipment into specific zones based on
the type of protection.
In some cases it has been shown that the type of protection may be divided into
different levels of protection that can be correlated against each Zone. A better risk
assessment would consider all factors. When using a risk assessment approach
instead of the inflexible approach of the past linking equipment to Zones the inherent
ignition risk of the equipment is clearly indicated, no matter what type of protection is
used.
30 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
An example using a risk assessment approach:
Plant operators often make intuitive decisions on extending (or restricting) their
Zones in order to compensate for this inflexibility.
On the other hand, it is reasonable for the owner of a remote, well secured, small
pumping station to drive the pump with a "Zone 2 Type" motor, even in Zone 1, if the
total amount of gas available to explode is small and the risk to life and property from
such as explosion can be discounted.
The situation became more complex with the publication of the first edition of IEC
60079-26 which introduced additional requirements to be applied for equipment
intended to be used in Zone 0. Prior to this, Ex ia was considered to be the only
technique acceptable in Zone 0.
It has been recognised that it is beneficial to identify and mark all products according
to their inherent ignition risk. This makes equipment selection easier and a risk
assessment approach, more appropriate.
Ingress Protection
The IP Code defined in international standard IEC 60529 classifies the degrees
of protection provided against the intrusion of solid objects (including body parts
like hands and fingers), dust, accidental contact, and water in electrical enclosures. It
consists of the letters IP (for "international protection rating" sometimes also
interpreted as "ingress protection rating") followed by two digits and an optional
letter. The standard aims to provide users more detailed information than vague
marketing terms such as "waterproof".
For example, an electrical socket rated IP22 is protected against insertion of fingers
and will not be damaged or become unsafe during a specified test in which it is
exposed to vertically or nearly vertically dripping water. IP22 or IP2X are typical
minimum requirements for the design of electrical accessories for in-door use.
31 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 3: Certification
ATEX product certification (or EC Type Examination) is the check on the design
specification of a product in relation to a series of relevant standards laid out under
the directive.
The certification process must be undertaken by a Notified Body who issue ATEX
certificates and conduct periodic surveillance of quality management systems.
Certification is the process of assessing a design to a specification set down in a
Standard.
Component Certificate
Certificate of Assurance
Certificate of Conformity
Component Certificate
Not a full certification and apparatus to which this certificate appears will need
additional protection before use in a hazardous area
‘Components’: means any item essential to the safe functioning of equipment and
protective systems but with no autonomous function.”
Certificate number will end in the letter “U”;; components do not require the CE mark
A Component Certificate needs always additional certification before bringing into
service. You could recognise a component certificate through its name and through a
‘U’ behind its certificate number. ‘U’ is German ‘Unvollständig’ and means
incomplete certification. Only the component is certified, but not - without further
action - suitable for installation in hazardous areas. Not completed component
certification has a way of protection- and a group marking. No temperature class is
mentioned on this type of certificate. Examples of component certified products are
terminals, switchgear, remote I/O. Often additional enclosures are required, however
empty enclosures belong also to the examples of component certified products.
32 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Certificate of Assurance
Certificate of Conformity
All relevant provisions fulfilled by the directive (i.e. relevant product marking,
T-class and gas groups)
Name & Address of the Notified Body who certified the equipment (if
applicable)
33 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
What is the difference between a Declaration of Conformity and a Certificate?
A Declaration of Conformity is the document that the manufacturer must enclose with
(or attach to) any equipment or protective system that is being sold in compliance
with the requirements of the ATEX Directive 94/9/EC.
The manufacturer has sole responsibility for creating this document and must do so
in accordance with the detailed list of contents given at Annex X in the directive. The
declaration complements the CE Marking which is applied to the product on the
manufacturer's responsibility.
There are many types of certification schemes, but they all involve the use of a third
party certification body which is independent from the manufacturer and purchaser of
the product (or service) that is the subject of certification.
An ATEX product which has been subject to "certification" will normally have
two documents:
Where the certification has been carried out on a voluntary basis (for example for
Category 3 equipment where certification is not mandated by the directive), the
document is simply known as a "Type Examination Certificate". Notified Bodies offer
this added service to assist manufacturers where a customer wants more assurance
than is given by the minimum legal requirements of the directive.
The existence of a certificate eases the manufacturer's task in writing his Declaration
of Conformity, but where the directive allows the use of "Internal Control of
Production" module (Annex VIII), the manufacturer is entitled to base his declaration
entirely on the technical file he has developed himself
34 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Where Special Conditions of Use Apply
Certificate will end with the letter 'X', in the past the letter 'B' was used and maybe
still encountered on some certificates
This denotes ‘special certification conditions’. These details are given on the
certificate and on the installation leaflet. The conditions usually relate to cable entry,
operation, lamps and maintenance conditions and must be observed by the user.
Always inspect/ask to see certificate to ensure all special conditions have been met.
Certification General
All equipment certified to the harmonised European Standards must carry the
following information.
Name of manufacturer
Product reference and serial number
Code and type of protection
Gas group and temperature class
Name of certifying authority and certificate number
CENELEC symbol
BASEEFA symbol
Electrical rating
35 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 4: Labelling
All equipment certified for use in hazardous areas must be labelled to show the type
and level of protection applied.
Equipment group (use in mines with pit gas hazards: Group I versus all other
explosion hazards areas: Group II)
Equipment category according to ATEX 95a (equipment safety for Group II)
Type of atmosphere (for Group II)
Ignition protection type
Explosion group
In Europe the label must show the CE mark and the code number of the certifying
body. The CE marking is complemented with the Ex mark, followed by the indication
of the Group, Category and, if group II equipment, the indication relating to gases G
or dust D. For example: Ex II 1 G Explosion protected, Group 2, Category 1, Gas
Specific type or types of protection being used will be marked.
Sierra Instruments Model 640S-EEX and 780S-EEX Flow Transmitters that have the
following label attached have been certified in compliance with the Directive 94/9/EC
of the European Parliament and the Council as published in the Official Journal of
the European Communities No. L 100/1 on 19 April 1994.
36 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
KEMA ATEX official label from Sierra Instruments, Inc.
37 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
New Marking – EPL's (Explosion Protection Levels)
The introduction of the EPL's and changes in the EN 60079 and EN 61241 series
standards has introduced new marking requirements.
Gas (Surface)
The gas group that was previously (II) for increased safety in surface applications is
now IIA, IIB or IIC, depending upon the certification
Dust
Grouping has also been applied to dusts where the marking is differentiated from
gases by the addition of another I i.e. IIIA, IIIB or IIIC.
38 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 5: Flameproof EEx d
Definition; (IEC 60079-1)
An enclosure in which the parts which can ignite an explosive gas atmosphere are
placed and which can withstand the pressure developed during an internal explosion
of an explosive mixture, and which prevents the transmission of the explosion to the
explosive gas atmosphere surrounding the enclosure.
Flameproof is one of the original methods of explosion protection developed for use
in the mining industry. It has a wide range of applications, typically junction boxes,
lighting fittings, electric motors etc.
The letter ‘d’, which symbolises this type of protection, is from the German word
‘druckfeste’ (kapselung), which roughly translated means ‘pressure tight’ (enclosure).
Covers are required to be tool removable, and secured with all the specified
fasteners in place.
The enclosure is certified along with the arrangement and its contents, no
modifications are permitted.
Principle of operation
Flameproof enclosures are not gas tight and a gas or vapour will enter the enclosure
where, for example, joints or cable entries exist. Since these enclosures are
designed to contain components which are an ignition source, ignition of the gas or
vapour may occur, and the resulting explosion pressure can reach a peak value of
around 150 p.s.i.
The enclosure must, therefore, be strong enough to contain this explosion pressure,
and the gaps at the joints and threads of cable entries must be long and narrow to
cool the flames/hot gases before they reach, and cause ignition of a flammable
atmosphere which may exist outside the enclosure.
39 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Typical materials used for the construction of flameproof apparatus include cast iron,
aluminium alloys, and where corrosion resistance is required, gun metal bronze,
phosphor bronze and stainless steel may be used. Plastic materials are also used
but the free internal volume must not exceed 10 cm3. Both standards specify that
‘THERE SHALL BE NO INTENTIONAL GAP AT THE COVER JOINTS’ and that the
average roughness Ra of the flamepath surfaces must not exceed 6.3 m.
EEx d: Flamepath/joint.
Spigot joints
Standard specifies the approved methods of making and determining the length of
flamepath, spigot joints are more effective than flanged joints with the following
noted;
40 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Minimum width of joint and maximum gap for enclosures
of groups I, IIA and IIB
Spigot joints are preferred for IIC gasses with volumes greater than 500mm3
41 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Cylindrical (shaft gland) joint
42 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Enclosure
Suitable for use in areas requiring EPL Gb and Gc or Category 2 and 3 only.
The equipment grouping and temperature classification defined in IEC 60079-0 for
the use of electrical equipment in explosive gas atmospheres apply to flameproof
enclosures. The subdivisions A, B and C for electrical equipment of Group II also
apply.
Certified equipment may not be modified in any way, other than as indicated on the
certificate. Modification may invalidate the certificate.
Use of any constructional screw for any purpose other than that originally
intended
43 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Pressure piling
Components not to be removed from flameproof equipment - pressure piling.
44 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Eex d Motors
Motors must be specially designed to meet the stringent constructional and test
requirements for flameproof devices. A motor complying with the requirements
stated above will require a thermal test at manufacturer’s rated full load to determine
normal running temperatures.
Glanding
New revision of IEC 60079 - 14 (2007) requires 'newly installed' glands to meet IEC
60079 - 0
Glands certified with an 'x' can only be used for fixed installations
Many of cables exhibit ‘cold flow’ of the inner sheath bedding. That is, the material
will flow away from pressure applied to it, such as that of a Cable Gland inner seal of
the compression or displacement type, hence creating an inefficient seal
Must be certified
The threaded part should be at least 8mm in length and comprise at least six full
threads
45 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Barrier Gland
The minimum length of the compound shall be 20 mm when installed. The
manufacturer shall specify:
– the maximum diameter over cores of the cable that the gland is intended to accept;
– the maximum numbers of cores that can pass through the compound.
These specified values shall ensure that, throughout the required 20 mm compound
length, at least 20 % of that cross-sectional area is filled with compound.
The cable gland shall be capable of being fitted and removed from electrical
equipment without disturbing the compound seal after the specified curing period of
the compound.
The filling compound and appropriate installation instructions shall be provided with
the cable gland.
Zone 1 and IIA or IIB gas present and volume of apparatus greater than 2L
Barrier
Gland
46 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Blanks
Examples of blanking elements for unused apertures
47 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 6: Increased safety EEx e
Definition; (IEC 60079-7)
The explosion protection concept Increased Safety was invented in Germany where
it has been widely used for many years. It is has become popular in the UK mainly
because it has a number of advantages for certain applications over the traditional
flameproof method of explosion protection. America has traditionally relied on the
use of explosion-proof enclosures in hazardous locations, and the prospect of using
an Increased Safety enclosure, which is not designed to withstand an internal
explosion, as an alternative, has probably been viewed with a little trepidation.
This method of protection has a good safety record and comparable with the other
methods of protection. The letter ‘e’ which symbolises this method of protection is
taken from the German phrase Erhohte Sicherheit, which roughly translated means
‘increased security’. Typical applications are induction motors, lighting fittings and
junction boxes.
The equipment is also designed so that it does not exceed specific temperatures
during normal operation (and in specified abnormal operation.
The equipment is robust in construction and tested to ensure that it meets the
requirements of impact testing in the standard (BS EN 60079-7).
Suitable for use in areas requiring EPL Gb and Gc or Category 2 and 3 only.
The equipment grouping and temperature classification defined in IEC 60079-0 for
the use of electrical equipment in explosive gas atmospheres apply to increased
safety enclosures.
The subdivisions A, B and C for electrical equipment of Group II also apply. Live
maintenance not permitted.
Equipment will have warning label affixed, DO NOT OPEN WHEN ENERGISED.
Minimum of IP 54 to be maintained (if cable entry less than 6mm thick). Refer to
glanding. No unauthorised modifications permitted.
48 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
EEx e Terminations
Creepage Distance 6mm - The shortest distance along the surface of an insulating
material between two electrically conductive parts
Clearance Distance 3mm - The shortest distance in air between two electrically
conducting parts
49 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
50 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Conductors per terminal
Terminals, such as slot types, may receive
and clamp more than one conductor.
Unless permitted by the certification, two
wires of different cross sections should not
be connected into one terminal unless first
secured within a single compression type
ferrule.
Note;
The manufacturer’s details of terminal types, sizes, number of terminals, conductor
size and maximum current ratings will be specified on the certificate and
manufacturers documentation and must be followed.
Eex e Motors
EEx e motors operate at a lower temperature rise than normal motors
Must be able to withstand stall rotor current for five seconds without damage to
insulation
Under stall (locked rotor) conditions, the rotor surface temperature will normally
increase faster than that of the stator windings, and hence, the T rating applies to
both internal and external surface temperatures.
Under fault conditions, the motor must trip within the tE time specified on the motor
data plate.
51 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Time 'tE' of Increased Safety Motors:-
Time 'tE' is the locked rotor withstand time. It is the time taken for heating up any
part of the motor from the steady state temperature up to the limiting temperature
under the locked rotor condition. This time is determined separately for stator and
rotor and the minimum one is taken as the tE.
Time tE is the time when, during the flow of the starting current, the motor
winding heats up to the limit temperature from the temperature of rated
conditions at maximum ambient temperature.
The current dependent protective devices must be so selected that the stalled motor
will be disconnected positively within the time tE, temperature class and starting
current are indicated on the name plate of ME motors.
The starting time normally permitted for these motors is up to 1.5 times the time tE
i.e. up to 1.5 x tE. If starting time is approximately of the order of tE, motor
protection becomes difficult, since over current protection may operate spuriously in
a repeated start. Hence, for heavy and frequent starting, an enquiry should be made
starting:
a) Duty Cycle
b) GD2 value of driven equipment referred to motor, and
c) Speed-Torque characteristic of the driven equipment
Motor current will cause a rise in winding temperature, which in turn will cause a rise
in casing temperature, as the motor load increases the winding current will rise
causing an increase in winding and casing temperatures
52 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
In the graph;
If a fault should occur and the rotor becomes locked, then the conditions shown in
part 2 of the graph apply.
The motor temperature will increase rapidly towards C which is just less than the T
rating of the motor.
The motor will reach point BC in time tE, control gear must be provided to disconnect
the motor from the supply within this time.
These motors are intended for S1 duty (continuous running and are unsuitable for
frequent start/stop duty or long run-up times.
Hence, they have special design features to prevent arcs, sparks and excessive
surface temperatures occurring both internally and externally.
53 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
The principal design features are.....
Special terminal block with good creepage/clearance distances and locking devices
on terminals
Increased safety motors are intended for continuous duty only, i.e. they are
unsuitable for applications which require frequent stopping and starting and/or long
run-up times.
The above characteristic would trip the motor after 8 secs, which
is within the tE time and therefore acceptable.
54 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
For these values the tripping time is 10 secs, which is outside the tE time assigned to
the motor, therefore an overload device with this characteristic would not be suitable
for the values specified.
Glanding
Prior to December 2007 EEx'e' only required glands to meet type of protection
requirements 'Ingress Protection and Mechanical Impact Strength'
New revision of IEC 60079 - 14 (2007) requires 'newly installed' glands to meet IEC
60079 - 0
Glands certified with an 'x' can only be used for fixed installations
55 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Blanks
Blanks (Plugs) must be certified for the apparatus. EEx e or EExd plugs go in EEx e
Equipment.
4. Conductor insulation should extend to within 1 mm from the metal throat of the
terminal.
7. An additional single conductor, min 1.0 mm2, may be connected within the same
terminal way when an insulated comb is used.
8. Only the conductors from each cable entry shall be loomed together.
9. The insulation of cables shall be suitable for use at least 80°C for a T5 temperature
class.
10. The individual earth continuity plates within plastic enclosures must be bonded
together and locknuts used to secure glands to the continuity plates.
a. For clearance holes, serrated metal washers must be used between locknuts
and the glandplate.
11. When Intrinsic and Increased Safety circuits occupy the same enclosure the two
types of circuit must have at least 50 mm clearance between them.
56 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
12. There must be adequate clearance between adjacent enclosures to allow proper
installation of cables and glands.
13. All unused cable entries should be closed using suitable plugs.
14. The schedule of the appropriate certificate should be consulted before cable entry
holes are drilled.
15. Cable glands or conduit entries must maintain the minimum ingress protection of IP
54.
16. All lid and gland plate bolts must be fully tightened after installation.
57 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 7: Reduced Risk Eex n
Definition; (IEC 60079-15)
A type of protection applied to electrical equipment such that, in normal operation
and in certain specified abnormal conditions, it is not capable of igniting a
surrounding explosive atmosphere.
Since the presence of a flammable gas or vapour is less likely in Zone 2, the
constructional requirements for electrical equipment used in these hazardous
locations are not as strict as those for equipment used in Zone 1. A method of
protection which falls into this category is type ‘n’ apparatus, which is basically
similar to increased safety type “e” apparatus except that there is a relaxation in the
constructional requirements.
Additional, the requirements of IEC 60079-15 are intended to ensure that a fault
capable of causing an ignition is not likely to occur.
The equipment grouping and temperature classification defined in IEC 60079-0 for
the use of electrical equipment in explosive gas atmospheres apply to increased
safety enclosures. The subdivisions A, B and C for electrical equipment of Group II
also apply.
Principle
58 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Since the design requirements are not as strict as those for increased safety type ‘e’
protection, it is possible for the manufacturer to install within type ‘n’ apparatus,
components which produce hot surfaces, arcs or sparks, providing these
components have incorporated in them additional methods of protection. These
additional methods are described later in this unit. The principal design features for
type ‘n’ apparatus are as follows.
1. Enclosures and motor fan guards, where exposed to high risk of mechanical
damage, to have resistance to impact of 3.5J;
2. Minimum ingress protection IP54 where an enclosure has exposed live parts
internally;
59 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Sub Divisions of Type EEx n Apparatus
EEx nA Non-sparking Apparatus
Terminal Boxes
Light Fittings
Transformers
If sparking occurs it; will occur in a hermetically sealed device & will occur in an
enclosed break device.
Non-incentive component
Marking Ex nC Gc II 3 G in accordance with IEC 60079-0.
Principle
Variant of the Ex n type of protection with contacts which close and open a circuit
potentially able to trigger an explosion, where the contact mechanism or the
enclosure into which the contacts are enclosed is designed in such a way that the
ignition of a mixture of subgroup IIA, IIB or IIC in the surrounding environment is
prevented as long as defined operating conditions apply.
Type EEx nC
This technique is used in, for example, the lamp holders of type ‘n’ apparatus. The
example below shows a typical lamp holder in which there are two sets of contacts.
One set of contacts is enclosed in what is effectively a flameproof enclosure in which
the free internal volume must not exceed 20 cm3. This enclosure is designed to
withstand an internal explosion and the voltage and current limitations are 600 V and
15 A respectively.
60 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
HERMETICALLY SEALED DEVICE
A device which prevents an external gas or vapour gaining access to the interior by
sealing of joints by fusion, e.g. welding, soldering, brazing, or the fusion of glass to
metal. The example of hermetic sealing shown below is a reed switch which
comprises a set of contacts hermetically sealed within a glass envelope.
61 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
ENCAPSULATED DEVICE
Designed to restrict the entry of gases, this technique is often applied to luminaires
where, because of the high temperatures developed, the air within the enclosure
expands and will develop an increase in pressure (thus excluding any entry of a
potential explosive atmosphere), when the luminaire is switched off and cools down,
the enclosure regulates the slow ingress of air across the gaskets. It is important
therefore to maintain I.P. ratings, minimum of I.P 54.
Terminals
Certified terminal assemblies are required to be used.
Lighting – General
Luminaires with fluorescent tubes and electronic ballasts not to be used in T5 or T6
Areas or where ambient temperature exceeds 60°C.
Lamps/tubes with conductive coated connections shall NOT to be used unless tested
with equipment.
Low Pressure Sodium lamps shall not be installed above a hazardous area.
62 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Glanding
Prior to December 2007 Ex'n' only required glands to meet type of protection
requirements 'Ingress Protection and Mechanical Impact Strength'
New revision of IEC 60079 - 14 (2007) requires 'newly installed' glands to meet IEC
60079 - 0
Glands certified with an 'x' can only be used for fixed installations
Because I.P 54 must be maintained then I.P washers and locknuts are required
when;
Glands entering unthreaded holes, threaded holes with less than 6mm thread length,
require an I.P washer on the outside and a locknut on the inside. A star washer may
be specified to ensure earth continuity.
Where an earth tag is required, this shall be placed between the gland body and the
seal washer, it should not be placed between enclosure and I.P washer.
Blanks
Blanks (Plugs) must be certified for the apparatus,Ex n equipment to maintain IP54
minimum.
63 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 8: Oil-Immersion EEx o
Definition IEC 60079-6
Protection is provided by immersing the equipment in oil to a sufficient depth, such
that any ignition capable products do not reach the surface where they could ignite
any potentially explosive atmosphere.
Use of mineral insulating oil to provide protection, with the fluid actually quenching
the electrical arc or spark.
Principle
The oil level is used to completely cover the components within the apparatus which
arc/spark or produce hot surfaces during normal operation, thereby effectively
establishing a barrier between the components below the oil and any flammable
gases which may be present above the oil or outside the enclosure. A particular
advantage of this method of protection is that circulation of the oil, by convection,
enables hot-spots to be dispersed.
One function of the oil is to quench arcs occurring at the contacts and, where mineral
oil is used, a by-product of this process is the production of hydrogen and acetylene.
This condition was considered to be undesirable for apparatus intended for use in
hazardous locations, which may explain why, until recently, its use was limited to
Zone 2 in the UK. The revised standards, however, have stricter specifications and
this type of protection is now permitted in Zone 1.
64 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Circulation of oil around apparatus allows for any hot spots to be dispersed allowing
for improved apparatus reliability
Suitable for use in areas requiring EPL Gb and Gc or Category 2 and 3 only.
The equipment grouping and temperature classification defined in IEC 60079-0 for
the use of electrical equipment in explosive gas atmospheres apply to oil immersion
enclosures.
Sealed enclosure IP 66
Potential Health Hazard with old oil & PCB's (polychlorinated biphenyl).
65 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 9: Sand/powder filling EEx q
Protection is provided by covering the parts that may cause ignition to a critical depth
in a fine powder such as quartz. This quenches any arc before the combustion
products can ignite a surrounding gas. An additional form of external protection is
required to limit the maximum current that may be safely used.
Principle
The filling, which may be quartz, or another material which complies with the
requirements of relevant standards, achieves safety by what is known as
“suppression of flame propagation”. It is inevitable that a flammable gas or vapour
may permeate the granules and reach the parts producing arcs/sparks or hot
surfaces. The quantity of gas or vapour, however, will be too small to support an
explosion within the inert powder. The depth of granules is influenced by the level
and duration of the of the arc current produced by the components within the filling
material, and tests specified in the construction standard enable a safe correlation
between these two parameters to be established. This method of protection is
suitable for use in all group II gases or vapours.
Code 'q' stands for quartz - medium used in the form of small glass or silica beads
Suitable for use in areas requiring EPL Gb and Gc or Category 2 and 3 only.
The equipment grouping and temperature classification defined in IEC 60079-0 for
the use of electrical equipment in explosive gas atmospheres apply to powder filling
enclosures.
Minimum IP 54 Required
66 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 10: Encapsulation EEx m
Protection is obtained by encapsulating/encasing hot or sparking components with a
material (organic resin) that prevents ingress of any explosive gas, cools heat
producing components and can withstand maximum temperature during normal and
under fault conditions
Apparatus is not readily repairable and mostly used for low cost throw away items.
Principle
Suitable for use in areas requiring EPL Ga,Gb and Gc or Category 1, 2 and 3.
The equipment grouping and temperature classification defined in IEC 60079-0 for
the use of electrical equipment in explosive gas atmospheres apply to powder filling
enclosures.
67 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 11: Cables for fixed wiring.
Electrical equipment in hazardous areas may be wired using cable having metallic or
non-metallic sheath, or conduit. The use of cable is generally predominant and one
reason is its ease of installation compared to conduit.
The principal reasons for earthing and bonding in electrical installations are:
BS EN60079-17 clause 4.7 states: ‘Care shall be taken to ensure that the earthing
and potential equalisation bonding provisions in hazardous areas are maintained in
good condition’
68 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Explanation of Terms
Conductors installed to provide a low impedance path for the current which flows
under fault conditions to the general mass of earth. Normally the CPC is connected
directly to any associated metal work of the equipment.
Electrical bonding
Conductors installed to establish continuity between adjoining metal work and the
armouring of separate cables to ensure that, under fault conditions, all metal work
and cable armouring are maintained at the same potential.
Exposed conductive parts include the metal work of switchboards, enclosures, motor
frames and transformer tanks.
My metal work associated with the plant, for example pipe work which can be
touched at the same time as a metal switch board cover or motor frame, will be
deemed extraneous conductive parts.
T Terra
At least one point of the supply is directly earthed. (Terra is the Latin word for dry
earth)
I Impedance
69 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
The second letter indicates the installation earthing system.
T Terra
N Neutral
The third and fourth letters indicate the arrangement of the earthed supply
conductors.
S Separate
C Combined
Note: the TN-C system is no longer allowed as a new installation with the
introduction of ESQCR.
70 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
TNC SYSTEMS
The regulations specifically prohibit the use of TNC systems within buildings that is
distribution systems with a combined neutral and earth as used in the PME supply
systems are not allowed within an electrical installation. This reflects concerns with
respect to the need for multiple earthing of TNC installations and the effects on EMC
and building life of load currents flowing through structural steelwork of buildings.
71 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
72 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
BS EN60079-14 specifies the conditions for the following earthing systems in hazardous
areas.
Type TN systems
If a type TN earthing system is used, it shall be type TN-S (with separate neutral N and
protective conductor PE) in the hazardous area, i.e. the neutral and the protective conductor
shall not be connected together, or combined in a single conductor, in the hazardous area.
At any point of the transition from type TN-C to type TN-S, the protective conductor shall be
connected to the equipotential bonding system in the non-hazardous area.
The monitoring of leakage between the neutral and PE conductors in the hazardous area is
also recommended in the standard.
Type TT system
If a type TT earthing system (separate earth’s for power system and exposed conductive
parts) is used in zone 1, then it shall be protected by a residual current device.
This system may not be acceptable where the earth resistivity is high.
Type IT system
If a type IT earthing system (neutral isolated from earth or earthed through an impedance) is
used, an insulation monitoring device shall be provided to indicate the first earth fault.
With this system, there may be a requirement for local bonding which is also known as
supplementary equipotential bonding.
Potential equalisation
In order to prevent different voltage potentials occurring in the metal work of plant in
hazardous areas, potential equalisation will be necessary. This applies to TN, TT and IT
systems where all exposed and extraneous conductive parts are required to be connected to
the equipotential bonding system. The bonding system may comprise protective conductors,
metal conduits, metal cable sheaths, steel wire armouring and metallic parts of structures,
but not neutral conductors. The security of connections must be assured by non-loosening
devices.
73 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Fixed apparatus
Cables may also be selected with consideration to their fire resistant and/or flame
retardant properties, and two standards are relevant in this respect.
Glands for use with MICC (Mineral Insulated Copper Cable) or MIMS (Mineral
Insulated Metal Sheath) cable for use in hazardous areas will be marked EEx d.
This gland, however, may be used as a means of entry to Increased Safety
apparatus providing an alternative EEx e seal is used. This seal is specially
constructed to comply with the requirements for Increased Safety apparatus as
illustrated by the diagrams.
74 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Seal Assemblies
The EEx e seal assembly must only be used with double bond non-metallic black
epoxy putty 1536. The Component Certificate for this seal will contain a ‘schedule for
conditions of use’ which must be observed.
Difficulty may be experienced in achieving the desired level of ingress protection with
MICC/MIMS cable glands due to the very small shoulder on the gland body, and may
be overcome by the use of hard plastic washers manufactured for this purpose.
Jointing of cables
75 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Conduit
The use of conduit in hazardous areas requires particular care, especially when used
with flameproof enclosures. In addition to maintaining the ingress protection (IP)
rating of an enclosure - this applies to all types of protection - the integrity of the
enclosure must be maintained, i.e. the conduit in the run between the enclosure wall
and the conduit sealing device must also be able to withstand the force of an
explosion within the enclosure so that the flames/hot gases are prevented from
reaching the external atmosphere. Where two flameproof enclosures are connected
by means of conduit, seals must be fitted to avoid pressure piling occurring during an
internal explosion.
Sealing devices are also used to prevent the migration of gases from one hazardous
location to another. Although not entirely gas-tight, they will limit, to an acceptable
level, the quantity of gas which will pass at normal atmospheric pressure. Where
positive or negative pressures are likely, appropriate measures must be
implemented.
Selection of conduit
Conduit used with explosion protected apparatus will be that recommended by the
manufacturer and selected from either:
76 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Sealing of conduit
(b) Within a distance of 450 mm from the wall of any enclosure which
contains a source of ignition in normal operation;
Instrument and Control Cables will be specified by the design engineer and indicated
on the system documentation (see I.S. Section later).
Not allowed where exposed to heavy mechanical stress, for example hand lamps,
barrel pumps, etc.
Cable Terminations
Normally one cable per terminal (Cable terminations as per the manufacturers
documentation)
Ex e terminations
77 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
General
All cables, cores and terminals should be marked for identification purposes by
permanent indelible methods (cable markers). All cable wiring and identification
should be documented.
Crimped terminations are generally preferable to bare copper (there is a risk of stray
strands causing circuit faults), crimped connections are more readily inserted and
removed.
Crimping tools of the hand ratchet type are to be used, hydraulic in larger size cable.
The good general rule is only one wire per terminal, some terminals have special
conditions applied and the manufacturer’s documentation will need to be referred to.
For the provision of re-terminating cables, enough length of conductor core should
be left to allow for at least one termination.
Unused cores
Are not to be left un-terminated
Static Requirements
The risk of incendive sparks from non metallic installation material (plastic coated
cable tray, plastic weather protection shall be controlled by the following.
78 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Light Metals/Cable tray
Installation materials
(Example - Cable trays, Mounting plates, weather protection must not contain more
than):
Gc No requirements
79 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 11: Knowledge and Skills
Detailed knowledge of those aspects of equipment design which affect the protection
concept
80 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Knowledge and Skills - Responsible Persons
General understanding of relevant electrical engineering
81 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 12: Pressurisation (EEx p)
Pressurisation is a simple technique for providing explosion protection. If the interior
of an enclosure is at a pressure above that externally, any flammable gases around
the enclosure will be prevented from entering the enclosure. Components which are
a source of ignition, i.e. they produce arcs/sparks or hot surfaces, are permitted
within the enclosure and, clearly, safety is dependent on the maintenance of the safe
gas. The safe gas is the medium which ‘segregates’ the flammable gas from the
source of ignition, and its continued presence will be confirmed by an
approved/certified ‘fail-safe’ control/monitoring system. A slight over-pressure is
usually adequate to maintain safe operation.
Definition
Applications
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Three types of enclosure px, py and pz
ATEX certified EExp explosion protected systems must comply with following
requirements:
83 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
The test procedure for EExp systems has to be done according to the EN 50016
(EN/IEC60079-2). For example: an overpressure test, leakage compensation test,
pressurisation test, verification minimum overpressure test, etc.
In case this number fails, it is not allowed to put the installation in operation in a zone
1 area. This number can be issued only by a notified body, like: PTB, DMT, KEMA,
etc.
84 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Three types of enclosure px, py and pz
It may not be feasible to duct issuing air from purged equipment into a safe area. A
spark flame arrestor is then required in the outlet air duct.
85 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Concept
Firstly - It maintains a pressure, known as an overpressure inside the enclosure
which prevents the ingress of any flammable atmosphere
Secondly - It can be used to dilute any potential flammable material released into
the enclosure to a level below the LEL
As long as this positive pressure is maintained, no gas (or even dust) will be able to
enter the enclosure; hence the internal equipment cannot be exposed to a potentially
explosive gas. There is however a chance that an explosive gas mixture may have
entered the enclosure prior to the positive pressure being achieved. To ensure that
the enclosure is pressurised with a non-explosive gas (i.e. Air or Nitrogen) the
enclosure is 'purged' to flush out the existing contents and ensure that all areas of
the enclosure contain only the purging gas (purging of internal dusts have not yet
been considered). It normally takes between 5 and 10 volume changes to ensure
that the enclosure is 'purged'. (In Europe the first edition purge standard defined five
air changes as a minimum, in North America the minimum is defined as 10 air
changes)
In the event of a failure to complete the purging cycle (drop in flow or incomplete
duration) or if the enclosure pressure drops below the specified positive pressure,
power to the equipment shall be removed (for Zone 1) or an alarm indication shall be
given (Zone 2).
86 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
In the event either of these conditions, the entire purging cycle starts again with the
full purge time duration. The control of the automatic purging and pressurization is
normally by a 'Purge Control Unit' (PCU). The PCU is required to measure flow and
pressure, and must fail-safe in all conditions.
The enclosure that houses the equipment to be purged must have sufficient physical
integrity to withstand impacts and overpressures. The enclosure should also be
designed to facilitate the free flow of air. As enclosure integrity is required to a level
of IP40 (no holes greater than 1mm), any non-metallic material must be tested for
durability and longevity (against effects of heat and light etc.). External
considerations, such as the surface temperature of the equipment or static from
plastic parts, must be considered. To ensure incandescent particles cannot be
vented from the equipment, a spark arrestor must be fitted (or the vented gas must
be ducted to a safe area). This technique is virtually unlimited particularly in physical
size or power rating of the apparatus being protected.
Static Pressurisation
Allowed into the hazardous area without a continuous supply of a protective gas
87 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Static Pressurisation
Static pressurisation relies on the enclosure being pressurised with an inert gas and
having a sealed enclosure to maintain the pressurisation.
88 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Pressurisation with Leakage Compensation
One of two techniques most associated with EEx p
Generally used where a source of ignition exists but the flammable hazard is outside
the enclosure
Enclosure is in a Zone 2
The enclosure contains 230 volt equipment fed via plug and socket
Therefore any leakage will be of the protective gas outwards rather than the
flammable atmosphere inwards
89 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Pressurisation with Continuous Flow
The second technique most associated with EEx p and the most complex method
Flammable materials are piped into the enclosure so the potential for release and the
formation of a flammable atmosphere exist
a) The Continuous Flow system will continuously flow air through the control panel.
The flow rate depends on which orifice plate you choose. Applications: small
enclosures and analyzers.
b) The Leakage Compensation system purges the enclosure; and then shuts itself
down and just tops off for any leakages your enclosure may have. It will maintain a
minimum pressure in the enclosure.
EEx p Purging
Before pressurisation can take place, it is necessary to remove any existing
explosive atmospheres.
The enclosure volume should be changed by the protective gas at least five times
before energising.
However Zone 2 purging may be omitted if the interior of the enclosure and the
associated supply ducting is proved to be below LEL.
Purge control units must be able to measure and act on the following information:
Pressure (pressurisation)
Flow (purging)
Time (purging)
90 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
The operations performed by the PCU must be 'failsafe' by virtue of test and
assessment with one fault (i.e. a valve failing), this is even more prevalent with the
advent of the ATEX Directive. Failure modes of components must be considered;
even relays can fail open or short-circuit (normally open relays can 'arc-weld' in to a
closed position). Purging timers must always re-set to zero if they are interrupted
during the purging cycle or after a purge failure. There are two basic types of control:
Constant Flow (CF) - The air flow for the purging and pressurization stages are the
same. The flow is left as a constant after it is set, and power is applied after a set
period of time.
Leakage Compensation (LC) after purging, the air flow is reduced to a figure just
above the leakage level to maintain the pressurisation. The PCU is required to
switch from an initial high flow rate (often referred to as fast purge) to a much lower
flow rate on completion of the purge time. CF systems are simpler to design, but are
more expensive (in air or nitrogen) to run. There are other examples of hybrid
systems (CF/LC) but in reality they are just variations on the two basic types.
PCU's (Pressure Control Units) are normally either pneumatic or electrical. If the
PCU is mounted in the safe area only the operation will require verifying (unless it
contains intrinsically safe outputs). PCU's mounted in the potentially explosive
atmosphere will require certifying both as safety systems and as potential ignition
sources (although sources of ignition from pneumatic systems were not considered
until the ATEX Directive).
Practical implementation
Enclosures
A standard IP54 enclosure may not be suitable for use as a pressurised enclosure
because the sealing is in the wrong direction. The standard enclosure is designed to
prevent the external environment entering the enclosure which means that they are
generally unsuitable for retaining internal pressure.
For this reason enclosures from suppliers of pressurised systems are not generally
the same as general-purpose enclosures. Also, the enclosure must be able to
maintain the pressure, on large enclosures the unit can be seen to deform even with
relatively low pressures. Additional hinges and cover bolts may be required when the
pressure is acting on a large surface area. Plastic parts (e.g. switches) should not
penetrate the housing walls. Plastic parts may be used externally if, when the plastic
is removed, metal parts remain that provide an ingress protection rating of IP40 (no
objects greater than 1 mm can penetrate the enclosure). No live (or potentially live)
parts should be exposed outside of the purged area. As switches are normally
sealed devices that contain sparking contacts, it is preferable to either use certified
switches or mount the switches inside the purged enclosure. Plastic ducting should
not be used if the plastic part failing does not create a fail-safe condition, e.g. on the
secondary purge system.
91 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Enclosure covers/doors
When a pressurised enclosure contains components which have hot surfaces, or are
capable of storing energy, e.g. capacitors, doors/covers should be fitted with a
warning notice which states the time delay after isolation of the electrical supply to
the components before opening the doors/covers.
Special precautions are needed where the pressurisation method uses a fan or
blower. It is generally undesirable to put the fan in a hazardous area because this
means that the ducting, which extends to a non-hazardous area, will be below
atmospheric pressure and, unless it is completely leak tight, may draw in flammable
gases. The other advantages of putting the fan in the non- hazardous area is that it
does not need to be suitable for use in hazardous area itself and the ducting is under
positive pressure which prevents ingress of flammable gas.
The use of compressed air is the normal method of supplying purge air, it must be
noted that several purged enclosure on one supply line may drop the operational
pressure to below working levels for the pneumatic logic, if such a system is used.
The exhausted air from a purged enclosure may contain small particles that have
been heated by the internal sources of the enclosure. To prevent these particles
being vented into the potentially explosive atmosphere the following methods are
used:
Pressurisation
The minimum pressure required is 0.5 mbar (50 Pa) and this should be achieved
with the lowest possible flow of pressurising gas. The pressure measurement has to
at least raise an alarm if the pressure falling below this level so that the working
pressure will be above this. The enclosure has be tested to prove it will withstand 1.5
times its normal working pressure (minimum 200 Pa) for 2 minutes without distortion,
a figure of 10 mbar is not uncommon as a working pressure.
92 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Purging
Effective purging of the enclosure and its contents has to be provided. As a
guideline, 5 volume changes are generally sufficient if the enclosure has been
designed to a few basic guidelines:
Temperature Classification
Since the flammable gas is prevented from entering the enclosure the exterior of the
enclosure determines the temperature classification. It is to be noted, however, that
internal hot surfaces will remain hot even after the power has been removed. A full
assessment of the thermal properties of hot parts of a purged enclosure must be
conducted.
Naturally inert gas cannot be used and compressed air is not generally
recommended. In addition, emergency facilities for the personnel are required.
Lighting and means of escape are of prime importance. The lighting is required
under all circumstances and hence must be protected by some other suitable means
such as flameproof. Kick-out panels or crash bars on doors usually provide for
escape.
93 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 13: Intrinsic Safety EEx i
Basic principles of IS
Intrinsically Safe circuits achieve safety by maintaining very low energy levels such
that hot surfaces will not be produced, and electrical sparks, if they occur, will have
insufficient energy to ignite the most easily ignitable concentration of a flammable
mixture. This is achieved by limiting the voltage and current supplied to the
apparatus in the hazardous area. To maintain safety, it is of paramount importance
that these levels of voltage and current are not exceeded under normal, or even fault
conditions.
The circuit parameters, i.e. voltage, current, resistance, inductance and capacitance
are factors which have to be considered in the design of an IS circuit. Consultation
with the characteristic ignition curves given in the construction standard, and
reproduced in this section, and the application of appropriate safety factors, will
ensure that safe values are established for these parameters during the design
stage.
Typical uses:
Three Categories:
94 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Ex “ia”
Suitable for use in areas requiring EPL Ga,Gb and Gc or Category 1, 2 and 3.
Ex “ib”
Suitable for use in areas requiring EPL Gb and Gc or Category 2 and 3.
Ex “ic”
Suitable for use in areas requiring EPL Gc or Category 3.
Equipment to type of protection 'nL' may be used in an intrinsically safe 'ic' circuit
95 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Intrinsic Safety - A System Concept
Other types of protection achieve their safety on an item-by-item basis, for example
flameproof equipment
Intrinsic Safety relies on the associated apparatus and the energy levels of the
equipment and cables connected to the hazardous area terminals
Electrical apparatus
Assembly of electrical components, electrical circuits or parts of electrical circuits
normally contained in a single enclosure.
NOTE 1 – The term "normally" has been introduced to indicate that an apparatus
may occasionally be in more than one enclosure, for example, a telephone or a radio
transceiver with a hand microphone.
NOTE 2 – This definition is more precise than that contained in IEC 60079-0.
96 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Intrinsically Safe Equipment
Equipment that is energy storing or produces energy, and is intended for use in an
Intrinsically Safe Circuit needs to be certified intrinsically safe.
The temperature classification awarded is generally T4, however JB's, switches and
terminals may be T6 because they do not contain heat dissipating components
97 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Certified Associated Apparatus
The certification may appear in square brackets [EEx ia], Provides a defined point at
which the intrinsically safe circuit start. Normally installed in the non-hazardous safe
area.
Zener barriers are used in control and instrumentation systems for the processing of
standardised signals, such as 20 mA and 10 V. Zener barriers contain intrinsically
safe circuits that are used to drive intrinsically safe field devices within hazardous
areas. The manufacturer’s data sheets must be consulted.
The relevant regulations and directives governing the intended application must be
observed.
98 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
The Zener barrier
The faults which can jeopardise the security of IS systems are either overvoltage or
overcurrent, and protection against these conditions is afforded by the use of an
interface, typically a Zener barrier, the construction of which will be considered in
terms of its individual components.
The interface, which is connected between the safe area and hazardous area
apparatus, is normally located in the safe area and situated as close as possible to
the boundary with the hazardous area, but may be located in the hazardous area if
installed in a flameproof enclosure.
A simple zener barrier has three principal components, (1) a resistor, (2) a zener
diode, and (3) a fuse, all of which must have infallible properties.
Infallibility, with regard to the current limiting resistor, means that in the event of it
failing, failure will be to a higher resistance value or open-circuit. Clearly, failure to a
lower resistance value or short-circuit would allow more current to flow in the IS
circuit, which is contrary to the concept of this type of protection. Infallibility will be
satisfied by the use of a quality wire-wound or metal film resistor, and its operating
power, as required in the standards, should not exceed 2/3 of its maximum quoted
rating for a specified ambient rating. The next component for consideration is the
zener diode, the purpose of which is to limit the voltage available to the apparatus in
the hazardous area. The zener diode, as a single item, is not considered to be an
infallible component, must also be operated at only 2/3 of its maximum stated rating.
For infallibility to be satisfied, the zener diode is required to fail to a short-circuit.
Failure to a higher resistance or open-circuit could allow voltage levels beyond safe
limits to “invade” the hazardous area.
Note: Tests by manufacturers have shown that diodes virtually always fail to a short-
circuit state, but there can be no guarantee of this. Diodes can only be
considered infallible when two or more are connected in parallel as discussed
later.
The third component, a fuse, is located at the input (safe) end of the zener barrier, its
purpose being to protect the zener diodes, and not to protect against, for example, a
short-circuit in the field apparatus. Infallibility of the fuse is assured by the use of a
sand-filled ceramic type capable of operating properly even when exposed to a
prospective fault-current of up to 4000 A. A fuse of this type avoids the problem
which can occur with other types of fuses when they rupture, namely vapourisation
which can allow the fuse to continue to conduct.
99 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
As required by the standards, the fuse is encapsulated along with the other
components of the barrier to deter replacement. The repair of Zener barriers is not
permissible, even by the manufacturer.
If a voltage greater than the normal maximum voltage of the IS system invades the
circuit at the input terminals of
the zener barrier, this will
trigger the zener diode, and
the resulting fault current will
be shunted to earth. The
excessive voltage is,
therefore, prevented from
reaching the apparatus in the
hazardous area.
The transmission characteristics of the devices remain stable over long periods, so
that regular adjustments or other precautions are not required. This also means that
no maintenance work is required.
Fault elimination
No modifications may be made to devices that are operated in connection with
hazardous areas. Repairs must only be carried out by specially trained and
authorised personnel.
100 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Intrinsically Safe Earth
I.S. systems using Zener barriers require a high integrity earth and good earth
connections are required.
Minimum of one 4mm2 or two 1.5mm2 conductors required from the barrier earth bar
in an enclosure to the main I.S. earth bar. Good practice is two conductors in
parallel to allow for testing.
The impedance from the barrier earth bar to the star point of the transformer should
be less than 1
EN 60079-14;
Tells us that the barrier earth terminals should be connected to a high integrity earth
point which will ensure a path of not more than 1 ohm to the main power system
earth point.
It is perhaps unfortunate that for many years the expression “main power system
earth point” has been taken to mean the point at which the electricity supply
company makes the earth connection to its substation transformer neutral. Many
diagrams which show the barrier earth connected back to this point may have been
misleading-especially as not all power systems have an earthed neutral point.
The “main power system earth point” should be understood to mean the earth point
to which all the electrical (and often structural) earth connections are made (directly
or indirectly) from the hazardous area to be protected.
EN 60079-14 Clarifies that the use of the power supply earth point applies to TN-S
systems only (separate neutral and earth conductors in the hazardous area), i.e. not
TN-C systems in which both earthing and neutral power share the same conductor,
nor IT systems in which the supply neutral is not directly earthed.
The standard gives the useful alternative instruction that the barrier earth terminals
shall be connected to the equipotential bonding system by the shortest practicable
route. This alternative earthing method is not affected by the style of power supply
system, nor is the limiting maximum path resistance of 1 ohm stated. This means
that in almost all cases a suitable earthing point can be found without any difficulty.
101 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
For the earth connection which is related to the main power system earth point both
the standards give the same advice, in suggesting a connection to the earth bar
which may be found in a local switch room or by the use of separate earth rods.
while the use of the switch room earth busbar is usually a good choice, in a practical
situation it is often very difficult to ensure that the path resistance of less than 1 ohm
can be relied upon by the use of separate earth rods and it is strongly recommended
that providing a barrier earth in this way is avoided.
The connection between the Zener barrier earth busbar and the chosen earthing
points needs to be made by at least one conductor having a cross section of not less
than 4mm squared copper. However, it is usual both for purposes of reliability and to
facilitate testing, that at least two separate conductors between the barrier earth
busbar and the chosen earthing point are provided.
In this case each shall have minimum cross section of 1.5mm squared copper, and it
is usual to run these conductors along different routes where possible.
Each conductor should have individual terminations at each end so that any one
path is completely independent of any defects which may occur in the continuity of
other paths in the earthing system.
To prevent the possibility of unrelated fault currents being passed down the barrier
earth conductor these conductors shall be installed for Zener barrier earthing
purposes alone, and shall not be used for earth connections of any other equipment
102 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Earthing and Bonding
103 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Galvanic Isolating Barriers
Although zener barriers have been, and continue to be, widely used in industry, they
have particular limitations which are:
b) A direct connection exists between the hazardous and safe area circuits and
earth, which tends to apply constraints on the rest of the system;
Devices which overcome these difficulties are isolation interfaces typically relays,
opto isolators and transformers.
This concept relies on transformer isolation between the hazardous area and safe
area circuits within the barrier.
Typical galvanic barriers will give in the region of 4000 volts isolation between these
circuits
In addition to limiting energy and providing isolation galvanic barriers usually perform
some additional function
104 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
A galvanic isolator is any device that connects two circuits together without allowing
electricity to flow directly from one circuit to the other. Instead of transferring
electricity through direct contact, galvanic isolators use other means, such as
electromagnetism, mechanical devices, optical systems, or acoustic systems to
convert the electricity into another form of energy, transfer it to an output device, and
then convert it back into electricity. There are many different types of galvanic
isolators and they can be used in a wide variety of applications.
A galvanic isolator separates two circuits by converting electricity from one circuit or
circuit component into another form of energy and then converting it back into
electricity once it has reached another circuit. Galvanic isolators prevent current that
could damage sensitive electronic circuits from traveling between one circuit section
and another. Galvanic isolators depend on light, electromagnetic waves, sound
waves, mechanical energy, inductance, capacitance, or other means to ensure that
the output current is the same or less than the input current.
Advantages
Installation of Barriers
Can be installed on open racks behind panels and in switch houses (old technique)
Recommended as good practice not to mix Zener and Galvanic Barriers on the same
mounting rail.
To increase the integrity of the I.S. circuit, I.S. and non-I.S. cables should be kept
segregated in barrier enclosure by either:
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 14: Intrinsic Safety I.S Cables
Freedom to use ordinary instrument cabling in hazardous area, armouring not
required but cable must be insulated.
Where an interconnecting cable is fitted with a screen, this should be earthed at one
point only. (Usually non-hazardous area)
Cores of circuits should be identified and made off using crimped connectors
Under no account should I.S. and none I.S. circuits be mixed in the same multicore
cable
Terminals
These methods of separation shall also be applied where intrinsic safety can be
impaired by external wiring which, if disconnected from the terminal, can come into
contact with conductors or components.
106 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
a) When separation is accomplished by distance then the clearance between
terminals shall be at least 50 mm. Care shall be exercised in the layout of terminals
and in the wiring method used so that contact between circuits is unlikely if a wire
becomes dislodged.
2) Metal partitions shall be earthed and shall have sufficient strength and rigidity to
ensure that they are not likely to be damaged during field wiring. Such partitions shall
be at least 0,45 mm thick or shall conform to 10.10.2 if of lesser thickness. In
addition, metal partitions shall have sufficient current-carrying capacity to prevent
burn-through or loss of earth connection under fault conditions;
The minimum clearance between the bare conducting parts of external conductors
connected to terminals and earthed metal or other conducting parts shall be 3 mm,
unless the possible interconnection has been taken into account in the safety
analysis.
107 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Plugs and sockets
Plugs and sockets used for connection of external intrinsically safe circuits shall be
separate from and non-interchangeable with those for non-intrinsically safe circuits.
Where intrinsically safe or associated apparatus is fitted with more than one plug and
socket for external connections and interchange could adversely affect the type of
protection, such plugs and sockets shall either be arranged, for example by keying,
so that interchange is not possible, or mating plugs and sockets shall be identified,
for example by marking or colour coding, to make interchanging obvious.
Where a plug or a socket is not prefabricated with its wires, the connecting facilities
shall require the use of a special tool, for example by crimping, such that there is no
possibility of a strand of wire becoming free, then the connection facilities need only
conform to table 4.
Where earthing, for example of enclosures, conductors, metal screens, printed wiring
board conductors, segregation contacts of plug-in connectors and diode safety
barriers, is required to maintain the type of protection, the cross-sectional area of any
conductors, connectors and terminals used for this purpose shall be such that they
are rated to carry the maximum possible current to which they could be continuously
subjected.
Terminals which are intended for clamping stranded cores shall include resilient
intermediate part. Terminals for conductors of cross-sections up to 4 mm² shall also
be suitable for the effective connection of conductors having a smaller cross-section.
Terminals which comply with the requirements of IEC 60079-7 are considered to
conform to these requirements.
108 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Permanently connected cable
109 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Separation of Intrinsically Safe and Non-Intrinsically Safe Wiring
To reduce the possibility of their interconnection, additional requirements exist for the
separation of intrinsically safe and non-intrinsically safe circuits. IEC 60079-11
requires a minimum separation distance of 50 mm (2 in.) be provided between
intrinsically safe and non-intrinsically safe conductors.
Cores of circuits should be identified and made off using crimped connectors
Under no account should I.S. and none I.S. circuits be mixed in the same multicore
cable
I.S. and power cables can be run together on the same cable tray provided that on of
the cables is armoured, the armour earthed and the I.S cable screened
Spare cores installed in barrier boxes should be connected to the I.S. earth.
(Easily achieved using a dummy barrier)
All cable cores and screens should be connected as per the hook up or installation
diagrams
110 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Cable Screens
The screen wire should be insulated adequately to prevent it touching earth or any
other circuit terminations
At the field device the screen wire is normally insulated, coiled and tied back
When I.S. circuit contains a Shunt Diode (Zener) Barrier, the screen is normally
connected to the I.S. earth at the barrier end of the cable
When I.S. circuit contains a Galvanic Barrier the screen is normally connected to the
dirty or equipment earth and NOT the I.S. Earth
These cable screens must be kept isolated from earth in the hazardous area to avoid
spurious earth currents been fed back into the barrier earthing system.
The colour light blue is used to indicate I.S. and greatly assists in the identification of
cables, I.S. apparatus and junction boxes
Raceways, cable trays, and other wiring methods for intrinsically safe system wiring
shall be identified with permanently affixed labels with the wording “Intrinsically Safe
Wiring” or the equivalent. The distance between labels shall not be more than 7.5 m
(25 ft.). Alternatively, colour coding may be used as a method of identification
provided that the colour light blue is used, and that no other conductors or wiring are
coloured light blue.
111 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 15: I.S Junction boxes
I.S Junction boxes are by definition simple apparatus and therefore DO NOT need to
be certified. The minimum required is IP54.
A label is required to indicate I.S. circuits or I.S. equipment are contained in the
enclosure
I.S. and non-I.S. circuits must be kept separate: (a minimum distance of 50mm
required)
Cable entry must maintain IP54: if less than 6mm an IP washer is required
The choice of glands is determined by the cables used and the requirement to
maintain the integrity of the enclosure. In practice the use of a large number of
glands frequently lowers the enclosure integrity from IP 65 to IP54. The use of
anything other than round cables should be avoided
Terminals
Terminals are by definition simple apparatus and therefore DO NOT need to be
certified. They should maintain creepage and clearance distances (6mm between
bare conductors and 3mm to earth)
I.S. and non-I.S. circuits must be kept separate (a minimum distance of 50mm
required)
It is common practice to use terminals of the type used in low powered ‘Exe’ circuits
[sometimes blue] because these satisfy the requirements of segregation between
circuits and clearance to ground. Their construction ensures a degree of operational
reliability, which is desirable, and there is usually an adequate provision for marking.
Terminals carrying intrinsically safe levels of current are allocated a temperature
classification of T6 [85C from 40C ambient] and consequently the temperature
classification of intrinsically safe junction boxes is never a problem.
112 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 16: I.S Certification
This includes, for example, Test Equipment which should normally be certified I.S.
This should be approved for use by the Technical Authority and must be installed
and used in accordance with its certification when in the hazardous area.
Simple Systems
Defined as a system in which all electrical is certified as I.S. or as associated
apparatus
Systems which contain simple apparatus do not require any additional certification
Complex Systems
If there is any doubt, between the compatibility of two components then the system
should be considered by a National Authority
113 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 17: Combined methods (Hybrid).
Electrical equipment may be manufactured with more than one method of explosion
protection. Equipment of this type has combined methods of protection but may also
be known as a hybrid. Such an approach combines the best features of each type of
protection into one piece of equipment for both economic and practical purposes.
114 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
The advantages of the hybrid arrangement discussed over the traditional flameproof
method are:
Motors - EEx de
Motors - EEx de
Manufacturers also produce electric motors in which there are combined methods of
protection. The main body of the motor will be flameproof EEx d and the terminal
box increased safety EEx e. An alternative terminal plate is fitted to a motor of this
type to accommodate special terminals which are screwed into the terminal plate.
These are hybrid terminals, i.e. they employ both flameproof EEx d and increased
safety EEx e concepts in their construction.
115 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
EEx de motor terminal box
To achieve the required level of ingress protection, gaskets are fitted between the
terminal box and it’s cover, between the terminal plate and box, and between the
gland plate and terminal box. On no account, however, should a gasket be fitted
between the terminal plate and the frame of the motor as this joint is a flamepath.
It must be emphasised that, on some motors, the increased safety terminal box looks
very much like a flameproof box in terms of its construction. This likeness means
that there is a possibility that the gaskets may be removed by personnel unaware of
this concept and, therefore, it is important that certification labels are studied before
any work is carried out. Removal of the gaskets in attempt to return the box to it’s
assumed status, i.e. flameproof, would be an unauthorised modification which would
invalidate the certification.
116 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Lighting fittings - EEx edq
The lighting fitting illustrated below employs three protection concepts, i.e. increased
safety type ‘e’, flameproof type ‘d’ and powder filling type ‘q’. This type of fitting is
widely used in the petro-chemical industry.
1) flameproof lampholders;
In this lighting fitting, the circuits include capacitors which are protected by a method
of protection, powder filling type ‘q’. Switches will be of flameproof type ‘d’
construction and terminals will be increased safety type ‘e’.
117 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
EEx e m ib
EEx pde
Enclosures which employ the protection concept, pressurisation type ‘p’, may have
internal apparatus which have to remain energised in the absence of overpressure.
Such apparatus must be protected in accordance with the Zone in which the
enclosure is located. A typical example is an anti-condensation heater within a
pressurised machine which will be energised when the machine is idle.
Apparatus outside the machine, e.g. junction boxes, pressure sensors etc., will also
have to be protected in accordance with the Zone.
Note: Since anti-condensation heaters are normally ‘live’ when a machine is idle,
notices warning of this danger should be displayed.
118 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
EEx pi
The part(s) of an IS system which are marked to indicate that they should be
installed in a non-hazardous area may be used in a hazardous area if installed in, for
example, a pressurised enclosure as illustrated below.
119 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 18: Inspections
BS EN 60079-17:2007 Explosive atmospheres. Electrical installations inspection and
maintenance.
General
Before a plant is brought into service for the first time, it must be given an initial
inspection. This work can be done by the operator or an outside company (third
party). To ensure that the installation is maintained in a satisfactory condition, it is
necessary to carry out either:
Correct functional operation of hazardous area installations does not mean, and
should not be interpreted as meaning, that the integrity of the special features
referred to above is preserved.
Definition
An action comprising careful scrutiny of an item, carried out with either visual partial
dismantling or dismantling in order to arrive at a reliable conclusion as to the
condition of an item
Types of Inspection
Initial
Periodic
Sample
Continuous Supervision
120 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Initial Inspection
The purpose of an initial inspection is to ensure that the apparatus is suitable for the
hazardous area in which it has been installed
During the act of installation no item of equipment has invalidated its certification
Periodic Inspections
Even if the apparatus is initially installed correctly there is no guarantee it will remain
in this condition, due to the effects of environmental corrosion, vibration, plant and
operational changes.
Operation conditions
Environment
To set an appropriate inspection interval accurately is not easy, but it should be fixed
taking into account the expected deterioration of the equipment. Major factors
effecting the deterioration of apparatus include: susceptibility to corrosion, exposure
to chemicals or solvents, likelihood of accumulation of dust or dirt, likelihood of water
ingress, exposure to excessive ambient temperatures, risk of mechanical damage,
exposure to undue vibration, training and experience of personnel, likelihood of
unauthorised modifications or adjustments, likelihood of inappropriate maintenance,
e.g. not in accordance with manufacturer’s recommendation. Once intervals have
been set, the installation can be subjected to interim sample inspections to support
or modify the proposed intervals or inspection grades. Where inspection grades and
intervals have been established for similar apparatus, plants and environments, this
experience can be used to determine the inspection strategy.
121 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Sample Inspection
This is an inspection that reflects a proportion of the installed apparatus
Continuous Supervision
Frequent attendance by skilled personnel
Therefore, it may be possible to dispense with the regular periodic inspection and
utilise the more frequent presence of the skilled personnel to ensure the ongoing
integrity of the apparatus.
A technical person with executive function will be responsible for each installation
and its skilled personnel. He will assess the viability of the concept and define the
scope of equipment to be considered under continuous supervision.
He will also determine the frequency and grade of inspection as well as the content
of reporting to enable meaningful analysis of apparatus performance.
Close
Detailed
122 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Visual Inspection
An inspection which identifies, without the use of access equipment or tools, those
defects which are apparent to the eye
Close Inspection
An inspection which encompasses those aspects covered by a visual inspection and
in addition those defects apparent by the use of access equipment and tools, i.e.
loose bolt
Detailed Inspection
An inspection that encompasses those aspects covered by a close inspection and in
addition identifies defects only apparent by opening the enclosure/ equipment, where
the necessary tools and test equipment are required, i.e. loose terminations.
Moveable/Portable Equipment
Hand-held portable equipment is particularly prone to damage or misuse and
therefore the intervals between detailed inspections may need to be reduced
Generally twelve monthly close inspection intervals should be used and recorded
Six monthly detailed for equipment with battery casing for example frequently
opened housings
123 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Maintenance
Appropriate remedial measures might have to be taken following an inspection
report. Care must be taken, to maintain the integrity of the type of protection
provided for the apparatus; this may require consultation with the manufacturer.
When necessary, the area of work shall be confirmed gas-free prior to
commencement of work.
Maintenance requires more detailed knowledge than when the equipment is first
installed. Defective parts should only be replaced by manufacturers' authorised
replacement parts, and modifications that might invalidate the certificate or other
documents should not be made. For equipment that is manufactured and certified
according to ATEX 95, the maintenance requirements, including the need for special
tools, can be found in the operating instructions supplied with each piece of
equipment.
A wrap of non-hardening tape may also be used in conjunction with gases allocated
to group IIA.
The gasket on increased safety enclosures should be checked for damages and
replaced if necessary. Terminals might have to be tightened. Any discoloration could
indicate a rise in temperature and the development of a potential hazard.
When replacing lamps in luminaries, the correct rating and type should be used,
otherwise excessive temperatures may result.
124 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Repair
Ideally, repair work on explosion-proof electrical equipment should only be carried
out by the manufacturer. This rule can be waived in cases where the repairs are
carried out by instructed and specially trained, skilled personnel, and only genuine
spare parts are used. IEC 60079-19 gives guidance on the repair and overhaul of
certified equipment. It is not permissible for modifications and rework to be carried
out that could jeopardise the characteristics essential to explosion protection (type of
protection and temperature class). Rewiring of installations is permissible if carried
out by trained, skilled personnel. The rewiring work done must be properly logged.
It is forbidden to rework the gap lengths and gap widths of flameproof enclosures by
machining, or to apply paint or other coatings to the respective joints. Such
modifications could impair the integrity of the enclosure and cause an uncontrolled
explosion.
125 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 19: Isolation & Testing
For hazardous areas the neutral is considered to be a LIVE conductor, therefore
must be isolated.
Candidates attending the 5-day CompEx course are required to carry out four
practical assessments in the simulated hazardous areas. During these
assessments, candidates must demonstrate their ability to work safely by ensuring
that all precautions are taken to prevent ignition of a flammable gas which, for the
purpose of the assessments, it is assumed may be present at any time.
Work permit
In order to ensure that safety is maintained, candidates must operate within the
control of a work permit - which must be requested from the Assessor / Authorised
Person.
In association with the work permit, a gas-free certificate must be endorsed by the
Assessor/Authorised Person at all instances when, for example, a particular action is
likely to produce a source of ignition. Such situations occur when electrical test
instruments and/or portable electric tools are used.
Safe Isolation
The Electricity at Work Regulations 1989 require those in control of part or all of an
electrical system to ensure that it is safe to use and that it is maintained in a safe
condition.
Unsuitable test probes, leads, lamps, voltage indicators and multimeters have
caused arcs due to:
(a) Inadequately insulated test probes (typically having an excessive length of bare
metal at the contact end) accidentally bridging a live conductor and adjacent
earthed metalwork; or
(b) Excessive current drawn through test probes, leads and measuring instruments.
This happens when a multimeter is set to the wrong function, e.g. set on a current or
resistance range when measuring voltage.
126 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Other causes of accidents which could lead to electric shock are:
(c) A lead falling off one of the terminals of a meter and either the meter terminal or
the lead terminal remaining live;
(e) Use of poorly constructed makeshift test equipment, eg a test lamp consisting of
a combination of a bayonet lamp holder, bulb and two single insulated conductors
with bared ends;
(f) The use of long intertwined leads which were not easily distinguished, resulting in
one lead being connected across the instrument and the other short circuiting the
live conductors under test.
Instruments used solely for detecting voltage fall into two categories.
These are:
Detectors which rely on an illuminated bulb (test lamp) or a meter scale (test Meter).
Test lamps fitted with glass bulbs should not give rise to danger if the bulb is broken,
It may be protected by a guard.
127 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
These detectors require protection against excess current. This may be provided by
a suitable high breaking capacity (hbc or hrc) fuse or fuses, with a low current rating
(usually not exceeding 500 mA), or by means of a current-limiting resistor and a
fuse. These protective devices are housed in the probes themselves. The test lead
or leads are held captive and sealed into the body of the voltage detector.
Detectors which use two or more independent indicating systems (one of which may
be audible) and limit energy input to the detector by the circuitry used. An example is
a 2-pole voltage detector, ie a detector unit with an integral test probe, an
interconnecting lead and a second test probe.
These detectors are designed and constructed to limit the current and energy which
can flow into the detector. The limitation is usually provided by a combination of
circuit design, using the concept of protective impedance, and current limiting
resistors built into the test probes. These detectors are provided with in-built test
features to check the functioning of the detector before and after use. The
interconnecting lead and second test probe are not detachable components.
Test lamps and voltage indicators are recommended to be clearly marked with:
(a) The maximum voltage which may be tested by the device; and
(b) Any short time rating for the device if applicable. This rating is the recommended
maximum current which should pass through the device for a few seconds. These
devices are generally not designed to be connected for more than a few seconds.
128 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Precautions before testing
Before testing begins it is essential to establish that the test device including all
leads, probes and connectors is suitably rated for the voltages and currents which
may be present on the system under test.
(a) The equipment which is to be worked on is safe for the intended tests; and
(b) The working environment does not present additional dangers. These dangers include:
Where a test is being made simply to establish the presence or absence of voltage,
the preferred method is to use a proprietary test lamp or 2-pole voltage detector
suitable for the working voltage of the system rather than a multimeter. Accident
history has shown that the use of incorrectly set multimeters or makeshift devices for
voltage detection has often caused accidents.
Note: Test lamps and some voltage indicators may fail to danger, eg a faulty lamp
not indicating a live circuit. These devices should be proved before and after use on
a known live source of similar voltage to the circuit under test, or alternatively on a
portable test source.
Testing
It is essential that instruments be regularly checked if correct test results are to be
achieved.
Check boxes or test resistors may be used as an interim check for instruments used
for insulation and continuity testing.
A socket of known impedance can be used as a simple routine check of Earth Fault
Loop Impedance (EFLI) testers.
Each instrument should have its own serial/identification number and this should be
recorded against test results when it has been used for that particular test, this will
also help to avoid unnecessary re-testing when one of a number of instruments is
found to be faulty. Test instruments and their leads should be kept in their cases to
protect them from mechanical damage.
129 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
Unit 20: Self Assessment.
1. The Areas A, B, C are zoned, Gas grouped and temperature classified as follows.
Area A B C D
Zone 1 Gc 2 Gb
Temp Class T6 T6 T5 T3
Indicate, if any, the areas in which the following items may be installed:
1 Gb IIA T6
2 EExn II T4
3 EExe II T5
4 Gc II T6
5 EExd II T4
6 EExn IIB T6
7 EExe IIA T5
8 Ga IIB T5
9 Cat 2 IIA T6
10 Cat 1 IIC T5
130 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
2. If an item is marked EEXe IIA T5 where may it be used?
Area Yes/No
Zone 0 IIC T6
Zone 1 IIA T4
Area Yes/No
Zone 1 IIA T5
Zone 2 IIC T2
4. According to IEC 60079 – 14 what is the minimum distance from flamepaths when
installing IIB Equipment?
5mm
10mm
30mm
40mm
131 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
5. BS EN60079-14 specifies conditions which require the use of a barrier gland.
Consider the statements in the table below and indicate by answering ‘true’ or ‘false’
when a barrier gland is or is not required.
3mm
4mm
8mm
6mm
132 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
7. Which ATEX Directive covers the use of equipment in Potentially Hazardous
Areas?
ATEX 59
ATEX 97
ATEX 137
ATEX 95
8. What is the Maximum safe gap permitted with flameproof Equipment designated
IIC ?
1.0mm
0.15mm
0.1mm
1.15mm
Close
Sample
Detailed
Visual
133 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
10. Which one of the following methods of explosion protection is suitable for use in
locations requiring EPL “Ga” ( Category “1G”) ?
EEx “d”
EEx “q”
EEx “mb”
EEx “Ia”
11. What are the Voltage and Current restrictions when using portable equipment in
Hazardous area?
16 Amps,200V
220V, 6 Amps
12. Which of the following protection methods of explosion protection are suitable
For use in locations EPL “Gb” ( Category “2G)?
134 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
13. If an explosive gas/air mixture is present continuously or for long periods,
Zone 2
Zone 3
Zone 0
Zone 1
14. To identify Zones on a drawing, special markings are used. Which of the
Following applies to a Zone O?
Small circles
Cross Hatching
Small squares
15. What is the abbreviation uses internationally which corresponds to The ATEX
Categories?
E.I
AEI
IEC
EPL
135 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
16. New equipment should be installed in accordance to which standard;
BS EN 60079-10.
BS EN 60079-14.
BS EN 60079-19.
BS EN 60079-20.
I.
IIA
IIB
IIC
18. Which aspect of flamable gas has to be considered when assessing the T rating
of equipment to be used?
The flashpoint.
The U.E.L.
136 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
19. An item marked EEx ib IIC T6 can be used where.
137 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV
21. Glands installed into Ex n junction boxes after December 2007 need to be.
Certified Ex d.
Certified Ex e.
22. A EEx e motor rating plate shows Te 6.5 sec T3, what does it mean.
138 | P a g e
Your training was delivered by a licenced brand ambassador, Cenelec Standards Inspections,
21-22 Apex Business Village, Northumberland Business Park, Cramlington, Newcastle upon Tyne, NE23 7BF
Ref: CC14GV