Grundfos Manual
Grundfos Manual
www.grundfos.com
DK-8850 Bjerringbro
Poul Due Jensens Vej 7
Grundfos Holding A/S
grundfos boiler feed manual
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks
owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. 98376735 0714
grundfos
grundfos
categoryINDUSTRY
heading
Boiler Feed Manual
grundfos boiler feed manual grundfos ENGINEERING MANUAL
ENGINEERING MANUAL
Copyright law and international treaties protect this material. No part of this material
may be reproduced in any form or by any means without prior written permission from
GRUNDFOS Holding A/S.
All reasonable care has been taken to ensure the accuracy of the contents of this mate-
rial: However, GRUNDFOS shall not be held liable for any losses whether direct or indirect,
incidental or consequential arising out of the use of or reliance upon on any content of this
material.
2
grundfos boiler feed manual grundfos table of contents
General.......................................................... 6
Boiler types.................................................... 6
Hot water boiler...................................................7
Thermal oil boiler................................................7
Steam boiler........................................................ 8
Steam generator................................................. 8
Exhaust gas boiler.............................................. 9
Boiler house components............................10
Deaerator.............................................................10
Condenser........................................................... 12
Economizer.......................................................... 12
Hot-well...............................................................14
Make-up water...................................................18
Level control valve and actuators..................19
Boiler systems..............................................21
Pumps.................................................................. 21
Hot water boiler................................................. 21
On/off shunt pump.......................................... 22
Shunt pump with variable speed................. 22
Steam boiler.......................................................23
On/off control.....................................................23
Through feed valve.......................................... 24
Through feed valve and variable speed.......25
Variable speed................................................... 26
Condensate system..................................... 29
Feed water.......................................................... 29
Where to dose what.........................................32
Chemicals used................................................. 36
Available technologies.....................................37
Pump sizing................................................. 39
Grundfos solutions...................................... 45
Theory/Problems....................................... .54
FAQ............................................................... 59
Certificates:.................................................60
4
grundfos boiler feed manual grundfos boiler types
General Fig. 1: A typical boiler construction in the manufac- Hot water boiler
turing industry
Hot water boilers are normally used in room and
The production of steam and hot water is one of the building heating. These kinds of systems are suitable
world’s largest industries. Grundfos is pleased to be for discharge temperatures of up to 140°C. The advan-
the preferred supplier of pumps for boiler systems for tage of hot water over steam is that the energy loss is
these industries. much lower than with steam boilers. Fig. 4 shows how
Grundfos pumps are reliable, efficient and cover the pumps are normally installed in a hot water boiler.
a wide performance range. As an experienced
Fig. 4
consultant in the implementation of boiler systems,
discharge
we engage in the process of close partnership and
Hot water
dialogue to find the best solution for your system.
boiler End
Grundfos is a global enterprise with a worldwide
service network. When you need export or on-the-
Burner
spot advice in a particular part of the world, we have Shunt
Fig. 2: This construction is typically seen in marine,
the technical expertise close by. but is also used in manufacturing industry
Return
6 7
grundfos boiler feed manual grundfos boiler types
Fig. 6
The advantages using a steam generator compared to
conventional steam boilers:
Deaerator
From water
• Easy to operate - normally no requirement for
treatment Level
sensor boiler authorisation
• Rapid start-up and establishing full steam pressure
Control • Compact and easy to adapt in the existing
box
Return
machinery arrangement
condensate
• Price attractive - especially at low steam rates.
Condensate
pumps Exhaust gas boiler
Steam can be produced not only by oil or gas-fired
Control Level
Condensate tank box sensor burners, but also by utilising the substantial amount
E
of waste heat in hot flue gasses or exhaust air. The
Burner
steam evapouration is done like the steam genera-
tors, and gives therefore a rapid acting and compact Fig. 8: Exhaust gas boiler
E unit.
Feed pumps
Steamboiler
Utilisation of the waste heat in flue gas of the steam
Steam generator boiler / steam generator itself, is called either an
In the steam generator, the feed water and steam are economizer or an exhaust gas boiler. It can be used
in principle passing through one long tube - designed for preheating the feed water, but also for external
as winded-up tube coils serially connected. In this purposes including preheating of make-up water,
long tube (tube coils), the feed water is heated up domestic water or central heating water.
to the evaporation temperature in the first part and
then evaporated in the second part. The intensity of
the heat, the feed water flow and the size/length
of the tube are adapted, so that the water is exactly
fully evaporated at the exit of the tube. This ensures
a very small water and steam volume (content of the
8 9
grundfos boiler feed manual grundfos boiler house components
10 11
grundfos boiler feed manual grundfos boiler house components
Flue gas
to chimney
Condenser
Fig. 11
A condenser ensures that all steam is condensed
before being pumped back into the deaerator and
then into the boiler. New treated water is normally
fed into the condenser.
Condensate Economizer
Fig. 10: Condenser
Deaerator
To ejector
Water outlet Steam vacuum system
Flanges
Baffle Baffle
Flue gas
from boiler
Steam
Boiler
Burner
Flanged Baffle
cover Tube sheet Tube sheet Fig. 12
Feed pump
plate
Water inlet Condensate
Economizer
Condensate
As mentioned earlier, the economizer is more or less the
same as an exhaust gas boiler except it doesn’t have its
Deaerator
own steam chamber but uses the one in the boiler.
exhaust
to funnel
Talking economizers, there are normally two
different ways of mounting depending whether it is
Steam
installed on a land-based or marine-based boiler.
Boiler
On the boiler located on land we use the boiler’s flue
Economiser/
gas as shown on the sketch. The water circulated exhaust
gas boiler
above the economizer is normally supplied by the Burner
main feed pump, but can also be fitted with its own
circulation pump, see Fig. 11 on the following page.
Feed pump
The chimney will also include a bypass to allow waste Circulation
12 13
grundfos boiler feed manual grundfos boiler house components
The economizer on marine boilers differs from the both, together with flash steam from the blow down
land-based boilers because it is installed in the funnel system, flow through sparge pipes installed well
on the main engine as waste gases released from that below the water surface in the feed water tank. The
source are significantly greater. Energy produced by sparge pipes must be made from stainless steel and
marine applications often allows for the generation of be adequately supported.
overheated steam fed directly from economizer and
out into the piping. Operating temperature
It is important that the water in the feed tank is kept
Referring to the illustration in Fig. 12, the circulation at a sufficiently high temperature to minimise the
pump has to be sized to the pressure and temperature content of dissolved oxygen and other gases. The
in the boiler, which may easily be 20 bar and 170°C. correlation between the water temperature and its
Because of this, pumps featuring air-cooled top and oxygen content in a feed tank can be seen in Fig. 13.
bearing flange may be required. The pump does not
normally need to be capable of delivering a high dif-
Fig. 13: Water temperature versus oxygen content
ferential pressure as it only has to overcome the pres-
sure loss in the pipe heat exchanger (the economizer). 12
12
14 15
grundfos boiler feed manual grundfos boiler house components
additional energy, only the same energy used in a To avoid this problem, it is essential to provide the
different place. best possible Net Positive Suction Head (NPSH) to the
pump so that the static pressure is as high as possible.
The only real loss is the extra heat lost from the This is greatly aided by locating the feed tank as high
feed tank itself. Provided the feed tank is properly as possible above the boiler, and generously sizing the
insulated, this extra heat loss will be insignificant. suction pipework to the feed pump (Fig. 14).
Static height
The lower the boiler feed water temperature, the more
heat is required in the boiler to produce steam. It is
important to maintain the feed tank temperature as
high as possible, to maintain the required boiler output.
16 17
grundfos boiler feed manual grundfos boiler house components
Many water treatment plants need a substantial flow The level transmitters can be placed directly in the
in order to achieve optimum performance. A ’trickle’ boiler shell or in external chambers.
flow as a result of a modulating control into the feed
tank can, for example, have an adverse effect on the The water level detected will always deviate from the
performance of a softener. For this reason a small actual water level in the boiler. How much it devia-
plastic or galvanised steel cold make-up tank is often tes depends on boiler construction and sensor place-
fitted. The flow from the softener is controlled ’on / ment.
off’ into the make-up tank. From there a modulating
valve controls its flow into the feed tank. The use of the different control systems is described in
detail under section ”Boiler systems”.
This type of installation leads to ’smoother’ operation
of the boiler plant. To avoid the relatively cold make- Level control valve and actuators
up water sinking directly to the bottom of the tank The level control valve actuator receives a level signal
(where it will be drawn directly into the boiler feed from the level transmitter and, in response, moves
water line), and to ensure uniform temperature the valve to a position that corresponds to the signal.
distribution, it is common practice to sparge the The actuator moves the valve stem and adjusts the
make-up water into the feed tank at a higher level. flow depending on the valve characteristic. The valve
characteristic depends on valve design and will not be
Water level transmitter described further in this literature.
In all steam boilers it is of utmost importance to have
a constant water level in order to have a safe boiler Control valve sizing
operation and to maintain a good steam quality. In order to size a valve for a water application, the
The steam boiler is normally equipped with the following must be known:
following transmitters: • Volumetric flow rate through the valve
• Differential pressure across the valve
Safety
• Low low level, burner shut down. Talking valve capacities they are generally measured
• Low level alarm. in terms of Kv. More specifically, Kvs relates to the pass
• High level alarm. area of the valve when fully open, whilst Kvr relates to
the pass area of the valve required by the application.
Control
• Low level, pump start. The simplified equation for pressure drop when
• High level, pump stop. pumping water is expressed like this:
18 19
grundfos boiler feed manual grundfos boiler systems
T Boiler systems
For a boiler application, with a flow of 26 m3/h This section describes the typical positioning of the
including safety factors and the request for 2 bar various pumps and how they are controlled.
pressure drop over the control valve, the Kv value is The most common boiler applications are boiler feed,
18.3 which in practice is a Kv of 20. condensate pumping, economizer circulation and
shunt pumps.
The values can also be found in a Kv chart:
Sub-system pumps, such as dosing and water
Fig. 15 (Source: www.spiraxsarco.com)
treatment pumps, are also used but will not be
described in this literature.
20 21
grundfos boiler feed manual grundfos boiler systems
On/off shunt pump Shunt pump with variable speed Steam boiler On/off control
Fig. 16 Fig. 17
Steam boiler feeding can normally take place in below Function
4 ways: In on/off control the feed pump is switched
• On/off control on/off through a level sensor or a differential
• Through feed valve (with and without bypass) pressure sensor. When the water level falls to
• Through feed valve and variable speed the “Pump on” level, the pump starts pum-
(with and without bypass) ping a large quantity of relatively cold water
Burner Burner E • Variable speed into the boiler. This will reduce the quantity
of steam and cause the steam pressure to fall.
The 4 methods mentioned above are the most com- This is the reason why on/off control causes
mon and will be described in the following. Please be variations in steam production. It may also
T aware that you can easily find a mix of the 4 systems. cause over-boiling in the boiler, which may
cause water to enter the system.
Benefits
Function Function Fig. 18: On/off control • Inexpensive
The shunt pump must ensure that the return The shunt pump must ensure that the return • Easy to install
temperature to the boiler does not become too low. temperature to the boiler does not become too • No bypass
If the differential temperature between the return low. If the differential temperature between
pipe and the forward pipe varies too much it will give the return pipe and the forward pipe varies Deaerator Drawbacks
a huge stress on the boiler structure. The pump must too much it will give a huge stress on the • Poor steam quality
be sized according to the lowest return temperature, boiler structure. A variable speed pump may • Big stress on boiler construction.
meaning it is over-sized most of the time. be the correct choice for this type of pump
application. The pump must be installed with
Benefits a temperature sensor registering the return
• Inexpensive and easy to install temperature to the boiler, thereby ensuring a
• Safe operation (few components) constant temperature.
Important! Benefits
• Information about correct return-pipe tempe- • Always constant return temperature no Control Level
box
rature to be obtained from boiler manufacturer. matter the load on the system sensor
• Same load on boiler to keep same differen- • Energy savings
tial temperature. Burner
Important!
Information about correct return tempera-
ture to be obtained from boiler manufacturer.
Feed pumps
Accessories required Steam boiler
Temperature sensor, R100/Grundfos Go
22 23
grundfos boiler feed manual grundfos boiler systems
Deaerator
Deaerator Deaerator
Fig. 19: Through the feed valve Fig. 20: Through feed valve and variable speed
Control Level
Control box Level
sensor
Level box sensor
sensor
E Burner
M Burner
P
M Burner
E
Feed pumps
Feed pumps
Steam boiler
Steamboiler
Feed pumps
Steamboiler
Function
In this system the water level in the boiler is controlled • Constant differential pressure across the
Function by a feed valve, which is controlled by a level sensor or feed valve
In this type of system the water level in the boiler Benefits a differential pressure transmitter positioned on the
is controlled by a feed valve, which is controlled by • Boiler feed adjusted according to steam boiler. The feed valve controls the water intake, which Drawbacks
a level sensor or a differential pressure transmitter consumption, as described. is adjusted according to the steam consumption. • Bypass, with energy loss
positioned on the boiler. This, however, requires that the feed pump is set to • The feed valve is expensive
The feed valve controls the water intake, which Drawbacks continuous operation. This system operates smoothly • Pressure loss across the feed valve
is adjusted according to the steam consumption. • The pump must be set to continuous opera- and is ideal for all types of steam boilers, both small and
This, however, requires that the feed pump is set to tion (energy consumption) large, and will minimise the risk of over-boiling. Important!
continuous operation. • Bypass, creates an unnecessary energy loss. Normally there are two ways to make the bypass, Requirements vary from one country to another
This system operates smoothly and is ideal for all • The feed valve is expensive either with a valve or an orifice. If it is a valve it is as regards the sizing of boiler feed pumps.
types of steam boilers, both small and large, and will • Pressure loss across the feed valve normally controlled so that will start to open when Remember to size bypass according to the CR/
minimise the risk of over-boiling. the regulation valve is closed to a certain level. This to CV data as well as to min. flow. It may be an
Normally there are to ways to make the bypass, either Important! avoid the continuously energy loss you would have if idea to stop the pump when the valve is closed.
with a valve or an orifice. If it is a valve it is normally Remember to size bypass according to the CR it was open all the time. This requires, however, a signal from the valve.
controlled that it will start to open when the regu- pump’s min. flow, which is 10% of the nominal Find out whether variable speed control of both
lation valve is closed to a certain level. This to avoid flow for the pump. It may be an idea to stop Benefits pumps is required as this increases expenses,
the continuously energy loss you would have if it was the pump when the valve is closed. This • Boiler feed adjusted according to steam consumption but does not provide the same flexibility as to
open all the time. requires, however, a signal from the valve. • Energy savings on pump operation alternating the pump operation.
24 25
grundfos boiler feed manual grundfos boiler systems
Deaerator Fig. 22
Steam outlet
Sensor max.
Hi_hi_alarm alarm
LT
f_min stop+hysteresis
Level
Control sensor pump speed
Max.
Stop
Min.
box
Lo_alarm warning
E Burner Sensor min.
E
Feed pumps
Energy Fig. 23
Steam boiler By control of the level in the boiler directly with the
Level Sensor Signals and Alarms
variable speed pumps you also have the most energy-
Function efficient way of making boiler feeding. There is no un- Sensor max.
In this system the water level in the boiler is controlled necessary flow in a bypass and the continuous pres- Hi_hi_alarm alarm
Max. Level Stop
f_min stop+hysteresis
directly by the variable speed pumps without using a sure loss over the control valve is eliminated. Min. Speed
feed valve. The pumps are controlled by a level sensor Max. Speed
or a differential pressure transmitter positioned on Doing a simple calculation on how big the energy loss Min. Level
pump speed
Max.
Stop
Min.
the boiler. This way the water intake is controlled actually is, often is quite surprising.
Lo_alarm warning
according to the steam consumption. This system As an example: Standard steam boiler application, Sensor min.
operates smoothly and is ideal for all types of steam with a steam production of 20 m3/h, and a pressure
boilers, both small and large, and will minimise the loss over the valve at 5 bar.
risk of over-boiling. The load profile of the boiler is divided into 5 periods,
the following calculations can be made:
Regulation loop 100% load = 20 m3/h in 1752 hours a year
The regulation loop has to be set up precisely so the 75 % load = 15 m3/h in 1752 hours a year
level will be as accurate as needed and the pump will 50 % load = 10 m3/h in 1752 hours a year
stop if no water is needed. 25 % load = 5 m3/h in 1752 hours a year
And stopped in the rest 1752 hours a year
26 27
grundfos boiler feed manual grundfos condensate system
Fig. 24 Fig. 25
. . ,
. .
. . ,
. .
. . ,
. . Boiler pressure
. . ,
. .
,
Benefits
• As described, boiler feeding adjusted according to • It must be ensured that the pump stops when steam
the steam consumption consumption is zero. May for instance be carried out
• Energy savings on pump operation with a high level switch from the boiler.
• No pressure loss across the feed valve • The regulator area may be small. If the 4-20mA level
• Money earned equal to the price of an expensive sensor is for example 2 metres and regulation takes
feed valve, and its maintenance costs. place in an area of just 20 cm corresponding to app. 2
mA, then the regulation gab will be very narrow.
Drawback • The level signal is normally inverted. This means that
• Requires precise and qualified start-up if you get 20 mA from the level sensor, the boiler is full
and then the pump should stop instead of speeding
Important! up.
• A minimum frequency must be defined ensuring
that the pump can always overcome the pressure
in the boiler, and supply the minimum flow for the Condensate system
pump. May be carried out with the “min. curve” op-
tion for the pump. Feed water
The importance of correct feed-water treatment for
economic operation and for extending life of boiler
and equipment cannot be over emphasized. Feed-wa-
ter treatment is essential in boilers, feedsystems, etc.,
more particularly in modern boilers of a high evapora-
tive rate. (The faster a steam boiler or generator will
convert water to steam, the more rapidly the solids in
28 29
grundfos boiler feed manual grundfos condensate system
the water will concentrate). So, large and small water- Dissolved Gases
tube boilers, the typical fire-tube packaged boiler, and The two gases which cause corrosion are oxygen and
steam generators are all examples of this in varying carbon dioxide. The carbon dioxide does so simply by
degrees. As all untreated waters carry natural salts, dissolving in the water and forming a weak carbonic
they have to be treated to prevent scale forming. acid which attacks the metal in feed systems, boiler or
The three main reasons for water treatment are: condensate systems. Oxygen is present in all waters,
• Prevention of corrosion in feed boiler, steam and so that red iron oxide forms on a mild steel surface
condensate systems. immersed in water. This rusting or, as we call it,
• Elimination of scale. corrosion triunes until the metal is corroded away. If
• Economic boiler operation without carry-over. the amount of oxygen in the water is restricted, the
oxide film does not form so readily; but instead, the
Corrosion will reduce metal thickness of tubes or surface of the steel tarnishes. This tarnish is usually
shell. Result: pressure must be reduced and finally the development of a thin film of iron oxide on the
boiler condemned. metal surface which is not so fully oxidized as the
red iron oxide, and is more dense, thus tending to
Scale reduces the heat flow from fire side to water. resist further corrosive attack. In water of increasing
Result: higher gas temperature is needed to maintain alkalinity, the oxide film becomes more stable and
the same heat transfer and the efficiency of the boiler gives more protection to the steel, but until a definite
will drop due to higher losses through the flue gasses. alkalinity is reached, it still tends to break down in
selective areas, where pits will develop.
Carry-over is a collective term to describe the en-
trainment of a relatively small quantity of boiler wa- Calcium and magnesium salts
ter solids with the steam. Carryover occurs as a result There are two forms of hardness; temporary and
of either foaming or priming, or by a combination permanent. Temporary hardness is due to bicarbonates
of both. Foaming is the formation of bubbles on the of calcium and magnesium which breaking to
surface of the boiler resulting in the throwing over of carbonates when the water has boiled. In the boiler
slugs of boiler water with the steam. This is similar to the following chemical reaction takes place : Calcium
the ’bumping’ experienced when water is boiled in an bicarbonate + heat. Calcium carbonate + carbon
open vessel. dioxide + water. Calcium and magnesium bicarbonate
are soluble in water but carbonates are insoluble and
therefore precipitate as a fine white powder. This
Fig. 26
precipitate will bake unto the heating surface of a
Impurity Effect on a boiler Altitude, m Boiling point of water,boiler
°C and form a scale.
Dissolved gases Corrosion 0 (0ft) 100 (212 °F) Permanent hardness is due to calcium and magnesium
sulphates, chlorides and nitrates, and these salts
These salts are the “ hardness in the boiler “
Calcium and magnesium salts Some salts can also cause corrosion 300 (984.25ft) 99.1 (210.3°F) cannot be removed by boiling. However, under boiler
conditions (resulting in successive concentrations
Silica Can form a very hard scale 600 (1968.5ft) 98.1 (208.5 °F) of these hardness salts) the solubility of these salts
is soon exceeded and they deposit on the hottest
Suspended and dissolved solids Contribute to or cause carryover 1000 (3280.8ft) 96.8 (206.2 °F)
part of the heating surface. The salts of magnesium
M
tion time.
M
HCI 30% NaCI 25% Na3PO4 Na2SO3
ken over with the steam. If the bubbles do not burst
high in the steam space, the foam can be drawn over
with the steam.
Blowdown
Where to dose what Chemical Chemical
Dosing Dosing
Depending on the chemical and its purpose, there are
different application points in the boiler system; high-
pressure and low-pressure parts can be identified in Feed Pump
32 33
grundfos boiler feed manual grundfos condensate system
External treatment
It is generally agreed that on steam boilers, the Typical requirements for power generation
principal feed water treatment should, where of feed water:
possible, be external to the boiler. Depending
on the boiler operating pressure and the water Recommended
requirements, the treatment applied may vary. Parameter value
General guidelines include: Specific conductivity 100 (212
450 – 900 psi Demineralisation to remove calcium, magnesium and sodium hardness Copper < 3 μg/kg
>900 psi Electrodialysis reversal (EDR) and Reverse Osmosis for high-purity water Carbon < 200 μg/kg
34 35
grundfos boiler feed manual grundfos condensate system
External water treatment technologies applied can 3. Provide antifoam protection to allow a neutralize the hardness of water by forming • Oxygen scavengers: sodium sulphite,
be listed as (ordered from the lowest quality product reasonable concentration of dissolved and tricalcium phosphate, and insoluble compound that tannis, hydrazine, hydroquinone/progallol-
obtained to the highest quality product): suspended solids in the boiler water without can be disposed and blow down on a continuous based derivatives, hydroxylamine derivatives,
foam carry-over; antifoamers are applied. basis or periodically through the bottom of the hydroxylamine derivatives, ascorbic acid
• Lime – soda softening – with lime softening, 4. Eliminate oxygen from the water and provide boiler. derivatives, etc. These scavengers, catalysed or
hydrated lime (calcium hydroxide) reacts with enough alkalinity to prevent boiler corrosion. • Natural and synthetic dispersants (scale not, reduce the oxides and dissolved oxygen
calcium and magnesium bicarbonates to form Corrosion inhibitors are dosed. inhibitors): increase the dispersive properties of the and may also passivate metal surfaces. The
a removable sludge. This reduces the alkaline conditioning products. They can be: choice of product and the dose required will
(temporary) hardness. Lime/soda (soda ash) In addition, as supplementary measures an • Natural polymers: lignosulphonates, tannins depend on whether a deaerating heater is used.
softening reduces non-alkaline (permanent) internal treatment should prevent corrosion • Synthetic polymers: polyacrilates, maleic acrylate
hardness by chemical reaction. and scaling of the feed water system and protect copolymer, maleic styrene copolymer, polystyrene • Antifoaming or anti-priming agents: mixture
• Ion exchange – by far the most widely used method against corrosion in the steam condensate sulphonates etc. of surface-active agents that modify the surface
of water treatment for shell boilers producing systems. • Sequestering agents: such as inorganic phosphates, tension of a liquid, remove foam and prevent
saturated steam. which act as inhibitors and implement a threshold the carry-over of fine water particles in the
• Reverse Osmosis Feed water, i.e. treated make-up water mixed effect. steam.
with condensate returns, can be treated to
Processes applied for an external boiler feed remove oxygen. This can be done through a feed Available technologies
treatment (depending on the level of water purity): water heater, deaerator, or economiser. Often Pumps:
• Water softening oxygen scavengers may be added to further
• Dealkalisation: Removes more TDS than the classic reduce oxygen.
water softening. Process Equipment Grundfos products Comments
• Demineralisation: Used for very high pressure Further treatment: Boiler feeding Multi-stage centrifugal CR pump with Case story: CRN 64-2 with Air-Cooled Top for
boilers such as those in power stations. Special attention must be paid to steam and pump (low NPSH) modified software boiler feeding at high temperature in Indonesia
Case story: CR32 and CR45 for boiler feeding
condensate treatment, as the steam will leave allow energy saving efficiency up to 40%.
In many cases external treatment of the water behind most chemicals. Special volatilising
supply is not necessary and the water can be treated chemicals are added to travel with the steam Condensate recirculation Centrifugal pumps CR, NB/NK, MTR
38 39
grundfos boiler feed manual grundfos pump sizing
sure. Remember to add the pressure loss in regulation It is seen on the illustration above, that 175°C
valve and pipes between pump and boiler.) mentioned on the nameplate is the temperature of
the steam in the outlet of the boiler. This information,
Besides the rules and regulations above, you can- however, is of no use, as the pump never registers
not just read the flow and pressure on the boiler what happens in the boiler. When sizing, always use
nameplate and use this data to size the pump. This the temperature in the deaerator.
is because of the high temperature of the water and
hereby the lower density of the pumped water. See From the vapour table the following data of water at
the example below. a temp. of 104°C is given.
Density (rho)= 955.2 kg/m3
Be aware that pumps in boiler applications are not Vapour pressure = 1.1668 bar
part of the Pressure Equipment Directive 97/23/EC
(PED) according to guideline 1/11. First the data from the nameplate have to be converted
into m3/h and mWC, which can be used in the sizing.
Example of flow and head calculation
The following information is taken from the boiler
nameplate, see fig. 28.
QBoiler = 20 tons/hour
PBoiler max = 12.5 bar
PBoiler operating = 10 bar
Temp. = 175°C
Fig. 27 Condensate
Deaerator
Apply safety factors from EN 12952-7, flow and head
becomes as specified below.
Steam
20 tons/hour
175°C
Q Pump max = 1.25 x Q Boiler = 1.25 x 20.9 = 26.1 m3/h
Q Pump continuous = 1.15 x Q Boiler = 1.15 x 20.9 = 24.0 m3/h
h Pump = 1.1 x h Boiler = 1.1 x 133.4 = 146.7 m
5m
Boiler
40 41
grundfos boiler feed manual grundfos pump sizing
It should be carried out as shown below and in fig 29. Fig. 28 Example:
H
CRE 20-14
With the value from earlier and the tank placed 5 m
(m)
Situation 1: 100% above the pumps, the following formula is found:
200 Q = 26.1 m³/h
Flow 26.1 m3/h with safety factor at 133.4 m H = 133 m
180 n = 100% / 50 Hz
Situation 2: 160
120
From these situations the following pump is chosen As mentioned earlier the density of 104°C water must
100
as it can handle both situations. be used as this is what the pump meets.
80
However, taking another look at the formula it is
Now the pump is selected but before ordering, the 60 obvious that the hb and the hv equalize each other.
NPSHA value has to be calculated. 40 The reason is that the water in the deaerator is
Q = 20.9 m³/h
H = 147 m normally kept at the boiling point.
20 Eta pump = 68.9%
NPSHA = Pressure AVAILABLE to the pump Eta pump+motor = 58.9%
0
from the system. 0 5 10 15 20 25 Q(m³/h) This phenomenon will always occur in a boiler system
P P2 = 13.6 kW NPSH
NPSHR = Pressure REQUIRED from the pump (kW) P1 = 16 kW (m) and because of that, the formula can be simplified:
16 P1 8
to avoid cavitation.
P2
12 6 NPSHA = hf – ± hgeo – hs
To avoid pump cavitation, the following has to be
8 4
accomplished, NPSHA > NPSHR
4 2 Instead of using boiling to drive the oxygen out of
NPSHA = hb – hf – hv ± hgeo – hs NPSH = 3.83 m
the water, it is possible to add chemicals instead. In
0 0
that type of application the water is heated to approx.
NPSHA = Pressure available at inlet of pump. 80°C instead.
hb = Atmospheric and deaerator operating
pressure at pump site. The application gives an NPSHA at 2 m, and the
hf = Friction loss in suction pipe. selected pump has a NPSH-value way above that. Due
hv = Vapour pressure of liquid. to this it is necessary to look at the low NPSH versions
hgeo = Height between water level in deaerator of the pumps, see fig. 29.
and suction side of pump.
hs = Safety factor. Normally estimated Fig. 29
between 0.5 and 1 m.
H NPSH
[m] [m]
20 QH 2900 rpm1 8
15 QH 2900 rpm1n NPSH 6
10 4
5 2
LOW NPSH
0 0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 Q[m³/h]
42 43
grundfos boiler feed manual grundfos grundfos solutions
As the curve shows, this pump can be used in a low Grundfos iSOLUTIONS
NPSH version.
A pump to do the job has been found, fig. 31. Put in Grundfos iSOLUTIONS
the actual duty point and it looks alright, but if it is Grundfos iSOLUTIONS is bringing intelligence
compared to the pump with 2 impellers less, the latter into the complete pumping process. Grundfos
looks even better, fig. 32. However, please be aware iSOLUTIONS takes a holistic approach to the pump
if the pump with 12 impellers is chosen, it must run control and utilises the intelligence to reduce the
over-synchronous to reach the duty point according to number of control valves and unnecessary energy
the EN norm. The choice depends on the application consumption.
and requests.
General benefits
1. Energy saving
Fig. 30 Fig. 31 • Reduced Life Cycle Cost and reduced CO2 emission
H
CRE 20-14 H
CR 20-12 eta 2. Increased comfort
(m) (m) 100% (%)
100% • Reduced noise from installation,
200 Q = 20.9 m³/h Q = 20.9 m³/h
H = 107 m 160 H = 107 m • Constant pressure
n = 85% / 42 Hz n = 90%
180 90%
140 • No water hammering
160
85% 120
140 3. Make processes work
100
120 • Adapts automatically to changes in system
80 80
100 70 • Control and regulation of critical parameters
60 60
80 50
40 “EN” duty point 40 4. Reduced total system cost
60 Q = 26.1 m³/h 30
20 H = 133 m 20 • Speed controlled pumps can make some valves etc.
40 10
0
Eta pump = 72.5%
0 unnecessary
0 5 10 15 20 25 Q(m³/h)
20 Eta pump = 71.3% P2 NPSH • Reduced installation and commissioning costs
Eta pump+motor = 60.9% P2 = 8.41 kW (m)
(kW)
0
0 5 10 15 20 25 Q(m³/h)
NPSH
P P2 = 8.55 kW
(kW) P1 = 10 kW (m) 12 6 5. Protection of pump, motor and electronics
16 P1 8
• Reduced stress on motor, pump and system
P2 8 4
• Overload protection of motor and electronics
12 6
4 2
8 4
0 NPSH = 1.93 m 0
Pump curve compensation
4 2
In boiler feed the pumps are often operating at low
NPSH = 2.13 m
flow and still at full boiler pressure. When these
0 0
conditions are present centrifugal pumps have some
limitations in their natural performance as the pump
curve gets unstable in the low flow area. This gets
even more explicit when the load curve is flat, like in
boiler feed, and that is a regulating challenge. See fig.
32 and 33.
44 45
grundfos boiler feed manual grundfos grundfos solutions
Fig. 32 Fig. 34
H
CRN 10-10
As a special function in the Grundfos frequency con-
(m) Setpoint verter. it is possible to compensate for this phenom-
100
enon by altering the internal motor control.
90
Inverse Normal
80
regulation The maximum RPM of the motor is increased to 55 Hz,
70
or 58 Hz if required, and at the same time the slippage
60 of the motor is increased.
50 When the pump is running at low load, due to low
40 flow, the speed of the pump is high. When the flow
30
increases the load increases and because of the larger
slippage the pump speed will decrease and fold back
20
Flow range to the original pump curve at 50 Hz, even though the
10
motor is still running 55 Hz. See fig. 34.
0 1 2 3 4 5 6 7 8 9 10 11 12 Q(m³/h)
P2 NPSH
(kW) (m) The pump curve is now continuously decreasing and
4 8
the instable part of the pump curve is eliminated. Fig. 35
3 6
Air-cooled top
0 0
As mentioned in passage Economizer, the boiler feed
pumps are sometimes installed so that they meet the
Fig. 33
boiler pressure and temperature. These temperatures
H
(m)
are sometimes higher than what the shaft seals can
Q
160 handle.
rpm
140 Set point
Q
The solution can be an air-cooled top.
rpm rpm
120
rpm Q A CR pump equipped with air-cooled top can handle
100 Q temperatures of 180°C in water and 240°C in thermal oil.
Inverse regulation Normal regulation
80
46 47
grundfos boiler feed manual grundfos grundfos solutions
48 49
grundfos boiler feed manual grundfos grundfos solutions
52 53
grundfos boiler feed manual grundfos theory/problems
54 55
grundfos boiler feed manual grundfos theory/problems
56 57
grundfos boiler feed manual grundfos FAQ
58 59
grundfos boiler feed manual grundfos certificates
21 294.15 0.02485 998.1 81 354.15 0.4931 971.0 230 503.15 27.976 827.3
22 295.15 0.02642 997.8 82 355.15 0.5133 970.4 235 508.15 30.632 820.5
23 296.15 0.02808 997.6 83 356.15 0.5342 969.7 240 513.15 33.478 813.6
24 297.15 0.02982 997.4 84 357.15 0.5557 969.1 245 518.15 36.523 806.5
25 298.15 0.03166 997.1 85 358.15 0.5780 968.4 250 523.15 39.776 799.2
26 299.15 0.03360 996.8 86 359.15 0.6011 967.8 255 528.15 43.246 791.6
27 300.15 0.03564 996.6 87 360.15 0.6249 967.1
28 301.15 0.03778 996.3 88 361.15 0.6495 966.5 260 533.15 46.943 783.9
29 302.15 0.04004 996.0 89 362.15 0.6749 965.8 265 538.15 50.877 775.9
30 303.15 0.04241 995.7 90 363.15 0.7011 965.2 270 543.15 55.058 767.8
275 548.15 59.496 759.3
31 304.15 0.04491 995.4 91 364.15 0.7281 964.4 280 553.15 64.202 750.5
32 305.15 0.04753 995.1 92 365.15 0.7561 963.8
33 306.15 0.05029 994.7 93 366.15 0.7849 963.0 285 558.15 69.186 741.5
34 307.15 0.05318 994.4 94 367.15 0.8146 962.4 290 563.15 74.461 732.1
35 308.15 0.05622 994.0 95 368.15 0.8453 961.6 295 568.15 80.037 722.3
36 309.15 0.05940 993.7 96 369.15 0.8769 961.0 300 573.15 85.927 712.2
37 310.15 0.06274 993.3 97 370.15 0.9094 960.2 305 578.15 92.144 701.7
38 311.15 0.06624 993.0 98 371.15 0.9430 959.6 310 583.15 98.700 690.6
39 312.15 0.06991 992.7 99 372.15 0.9776 958.6
40 313.15 0.07375 992.3 100 373.15 1.0133 958.1 315 588.15 105.61 679.1
320 593.15 112.89 666.9
41 314.15 0.07777 991.9 102 375.15 1.0878 956.7 325 598.15 120.56 654.1
42 315.15 0.08198 991.5 104 377.15 1.1668 955.2 330 603.15 128.63 640.4
43 316.15 0.08639 991.1 106 379.15 1.2504 953.7 340 613.15 146.05 610.2
44 317.15 0.09100 990.7 108 381.15 1.3390 952.2
45 318.15 0.09582 990.2 110 383.15 1.4327 950.7 350 623.15 165.35 574.3
46 319.15 0.10086 989.8 360 633.15 186.75 527.5
47 320.15 0.10612 989.4 112 385.15 1.5316 949.1
48 321.15 0.11162 988.9 114 387.15 1.6362 947.6 370 643.15 210.54 451.8
49 322.15 0.11736 988.4 116 389.15 1.7465 946.0 374.15 647.30 221.2 315.4
50 323.15 0.12335 988.0 118 391.15 1.8628 944.5
120 393.15 1.9854 942.9
51 324.15 0.12961 987.6
52 325.15 0.13613 987.1 122 395.15 2.1145 941.2
53 326.15 0.14293 986.6 124 397.15 2.2504 939.6
54 327.15 0.15002 986.2 126 399.15 2.3933 937.9
55 328.15 0.15741 985.7 128 401.15 2.5435 936.2
56 329.15 0.16511 985.2 130 403.15 2.7013 934.6
57 330.15 0.17313 984.6
58 331.15 0.18147 984.2 132 405.15 2.8670 932.8
59 332.15 0.19016 983.7 134 407.15 3.041 931.1
60 333.15 0.19920 983.2 136 409.15 3.223 929.4
60 61
grundfos boiler feed manual
62