Scope Of Supply Of Fire And Smoke Detection System Panel Controller Main Board
1. The panel controller should be compatible with the existing fire alarm system
panel FPA 5000 – Bosch make installed at our premise.
2. The panel controller should have following functions
i. Displaying and processing various message types such as alarm and trouble
messages
ii. Bypassing, blocking and resetting elements
iii. Monitoring and controlling of sounders and outputs
iv. Performing a walk test
v. Display diagnostic information about every LSN element
vi. Configuration of detectors (short texts and detector sensitivity)
vii. Performing a drill
viii. Saving, displaying and printing out events
ix. Switching the system to day or night mode.
3. The fire panel controller should have the capacity to be configured on a laptop
using the FSP-5000-RPS programming software.
4. The panel controller should fit in the existing housing and should have all
necessary ports and connections for supporting the existing network topology of
fire and smoke detection system already installed.
5. The panel controller should have 8” touch pad with program able buttons
6. Integrated Ethernet switch for networking and interfaces to remote services,
building management and voice alarm systems
7. The panel controller should have an internal history log. The history log keeps
incoming alarms and even sinternally. The history log should have a capacity to
store 10000 messages. The messages should be shown on thedisplay, and can
export the messages.Additionally, the user should be able to connect a log printer
via a serialinterface module for real-time printing incomingmessages.
8. The panel controller should be able to support following network topologies
• CAN loop
• Ethernet loop
• Ethernet/CAN double loop
• CAN loop with Ethernet segments
• Ethernet backbone with sub-loops (Ethernet/CAN)
9. The panel controller should have minimum following interfaces
• 2 CAN interfaces (CAN1/CAN2) for networking
• 1 Rail connector
• 4 Ethernet interfaces (1 / 2 / 3 / 4) for networking,
• 2 signal inputs (IN1/IN2)
• 1 USB function interface for configuration via FSP-5000-RPS
• 1 Memory card interface
10. The panel controller should have a valid hard coded software license.
11. The panel should meet the below specifications
Technical specifications
Electrical
Current consumption (mA at 24VDC)
• standby: 190 • standby: 190
• alarm: 420 • alarm: 420
Maximum power loss (W) 11
Max. CAN cable length in networks Lmax = 1000 m, depending on
configuration, cable type and topology
Ethernet interface
Maximum copper cable length 100 m
Maximum fiber optic cable length 2km (MM) up to 40 km (SM)
Mechanical
Housing material Polycarbonate (PC)
Weight (kg) 2.4
Dimensions H x W x D (mm) 190 x 404 x 60
Flammability rating UL94-V0
LCD display (pixels) 7" color WVGA 800 x 480
Operating and display elements • 6 keys
• 18 LEDs
Interfaces CAN1, CAN2, ETH1, ETH2, ETH3,ETH4,
USB , Rail
Signal inputs IN1/IN2
Environmental
Protection class as per EN 60529 IP 30
Permissible operating temperature(°C) -5 to +50
Relative humidity at 25°C (%) ≤95 (non-condensing)