V275
V275
GENERAL CHARACTERISTICS
Frequency (Hz) 50
Reference voltage (V) T51A2
Max power ESP (kVA) 275
Max power ESP (kWe) 220
Max power PRP (kVA) 250
Max power PRP (kWe) 200
Intensity (A) 397
Standard Control Panel TELYS
Optional control panel KERYS
POWERS
ESP PRP
Voltage Standby Amps
kWe kVA kWe kVA
POWER DEFINITION
PRP : Prime Power is available for an unlimited number 415/240 211 264 192 240 367
of annual operating hours in variable load applications, in 400/230 220 275 200 250 397
accordance with ISO 8528-1.
380/220 220 275 200 250 418
ESP : The standby power rating is applicable for 240 TRI 211 264 192 240 635
supplying emergency power in variable load applications in 230 TRI 220 275 200 250 690
accordance with ISO 8528-1. 220 TRI 220 275 200 250 722
Overload is not allowed.
200/115 220 275 200 250 794
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to
improve the quality of its products.
V275C2
TECHNICAL SPECIFICATIONS
AIR INTAKE
EMISSIONS Max. intake restriction (mm EC) 300
Emission PM (g/kW.h) 0.05 Intake air flow (L/s) 272
Emission CO (g/kW.h) 0.35
Emission HCNOx (g/kWh) N/A
Emission HC (g/kW.h) 0.08
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to
improve the quality of its products.
V275C2
ALTERNATOR SPECIFICATIONS
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to
improve the quality of its products.
V275C2
CONTROL PANEL
The highly versatile TELYS control unit is complex yet The KERYS control unit has been designed to fulfil
accessible, thanks to the particular attention paid to the specific requirements of professionals in terms of
optimising its ergonomics and ease of use. With its operating and monitoring generating sets. It therefore
large display screen, buttons and scroll wheel, it offers a wide range of functions.
places the accent on simplicity and communication. This control unit is fitted as standard to all generating
sets designed to be used for coupling and is offered
The TELYS offers the following functions: as an option across the rest of our range.
The KERYS can be built into the central console, fitted
Electrical measurements: voltmeter, frequency directly on the generating set, or in a separate cabinet,
meter, ammeter. to fulfil all the requirements for low and high output
power plants.
Engine parameters: working hours counter, oil
>The KERYS offers the following functions:
pressure, coolant temperature, fuel level, engine
speed, battery voltage.
Electrical measurements: voltmeter, frequency
meter, ammeter.
Alarms and faults: oil pressure, coolant
temperature, failure to start, overspeed, alternator
min./max., battery voltage min./max., emergency stop, Engine parameters: working hours counter, oil
fuel level. pressure, coolant temperature, fuel level, engine
speed, battery voltage.
Ergonomics: wheel for navigating around the
various menus. Alarms and faults: oil pressure, coolant
temperature, failure to start, overspeed, alternator
min./max., battery voltage min./max., emergency stop.
Communication: remote control and operation
software, USB connections, PC connection.
Additional functions: coupling, website,
For more information on the product and its options, diagnostic aid, assistance and maintenance, graphs
please refer to the sales documentation. and archiving, load impact management, 8 available
installation configurations, certification in line with
international standards.
This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to