VAG
VAG
VAG
Instantaneous Voltage relay
GRID
1
VAG
The relays can be fitted, if required, with which is always energized by a normally
open, light duty contact of the VAG 11 unit. Case
an operation indicator which is hand reset
by means of a push-rod protruding through A separate ac or dc supply is required for Relays can be supplied in moulded
the relay case. the auxiliary unit. nondrawout or metal drawout cases as
required, suitable for flush mounting.
On under voltage and no voltage relays, a Type VAG 11, ac or dc no voltage relays are
reverse operation indicator is fitted. i.e., the fitted with two pairs of self reset contacts in Non-draw-out cases are finished bright
indicator operation on reduced voltage or the following combinations one ‘normally black and metal drawout cases are
complete loss of voltage. open’ one ‘normally closed’ S/R contacts finished eggshell back/twin tone and are
and two ‘normally open’ S/R contacts. tropicalised.
Contact Ratings
Make and carry continuously Make and carry for 0.5 second Break
AC 1250 VA with maxima of 5A and 660V 7500 VA with maxima of 30A and 660V 1250VA with maxima of 5A and 660V
DC 1250 W with maxima of 5A and 660V 7500 W with maxima of 30A and 660V 100W (resistive) 50W (inductive) maxima of
5A and 660V
2
VAG
The drawout feature considerably simplifies maintenance and permits testing to be carried out easily and quickly. A cradle mounted isolat-
ing switch is provided which automatically isolates the trip circuit when the cradle assembly is withdrawn from the case for maintenance.
This prevents any inadvertent tripping of the circuit breaker. The drawnout case is fitted with switches which maintains the under voltage
trip circuits on withdrawal of the relay unit from the case. A filter breather is fitted which equalises pressure inside and outside the case
without admitting dust.
Single pole relays type VAG 11 are mounted in size ¼ N Vertical or size 1D vertical cases. Type VAG 21 relays are mounted in size ½ N
horizontal or size 1 D vertical cases.
3
19/1, G.S.T. Road,
Pallavaram Works
www.grid.alstom.com
Fax: 91-44-2264 0040
http://www.alstom.com/contactcentre/
ALSTOM T&D Worldwide Contact Centre:
GRID
Figure: Case and Panel cut-out dimensions for case 1/2N (all dimensions in mm)
Figure: Case and Panel cut-out dimensions for case 1D (all dimensions in mm)
Figure: Case and Panel cut-out dimensions for case 1/4N (all dimensions in mm)
VAG
“Alstom logo and any alternative version thereof are trademarks and service marks of Alstom. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in
the document are provided for information only. Neither ALSTOM, its officers nor employees accept responsibility for or should be taken as making any representation or warranty (whether express or implied) as to the accuracy or
4
completeness of such data or the achievements of any projected performance criteria where these are indicated. No liability is accepted for any reliance placed upon the information contained in this brochure. Alstom reserves the right to
revise or change these data at any time without further notice.”