0% found this document useful (0 votes)
43 views14 pages

PDS 2403062 Mep 2024-05-13

The document outlines the electrical specifications for a project, detailing the scope of work, quality assurance requirements, and compliance with relevant codes. It includes sections on materials, installation practices, and responsibilities of the contractor, emphasizing the need for skilled labor and adherence to safety standards. Additionally, it specifies the installation of panelboards, wiring devices, raceways, and lighting fixtures, along with requirements for permits and coordination with other trades.

Uploaded by

Ahsan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views14 pages

PDS 2403062 Mep 2024-05-13

The document outlines the electrical specifications for a project, detailing the scope of work, quality assurance requirements, and compliance with relevant codes. It includes sections on materials, installation practices, and responsibilities of the contractor, emphasizing the need for skilled labor and adherence to safety standards. Additionally, it specifies the installation of panelboards, wiring devices, raceways, and lighting fixtures, along with requirements for permits and coordination with other trades.

Uploaded by

Ahsan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

ELECTRICAL SPECIFICATIONS

PART 1 -GENERAL
1.01 RELATED DOCUMENTS:
THE GENERAL DOCUMENTS APPLY TO WORK SPECIFIED IN THIS SECTION; CONSULT THEM IN DETAIL FOR APPLICABLE INSTRUCTIONS.
1.02 WORK INCLUDED:
PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY TO COMPLETE ALL WORK OF THIS SECTION. WITHOUT RESTRICTING THE GENERALITY OF THE FOREGOING, THE FOLLOWING ITEMS OF WORK ARE INCLUDED:
A. PERMITS AND FEES
B. TEMPORARY POWER AND LIGHT
C. SERVICE PROVISIONS AND METERING
D. PANELBOARDS
E. TELEPHONE PROVISIONS
F. RACEWAYS THIS DRAWING IS PRELIMINARY
G. BOXES UNTIL SIGNED AND SEALED BY
H. WIRING THE LICENSED PROFESSIONAL
I. GROUNDING NOTED BELOW.
J. LIGHTING FIXTURES AND LAMPS PROFESSIONAL SEAL
K. WIRING DEVICES AND PLATES
L. CONNECTIONS TO EQUIPMENT
M. DIRECTORIES AND NAMEPLATES
N. TESTING
O. CLEANING AND REMOVAL OF RUBBISH
P. SUBMITTALS
1.03 RELATED WORK OF OTHER SECTIONS
A. CONCRETE AND MASONRY
B. PAINTING
1.04 QUALITY ASSURANCE
A. USE ADEQUATE NUMBERS OF SKILLED WORKMEN WHO ARE THOROUGHLY TRAINED AND EXPERIENCED IN THE NECESSARY CRAFTS AND WHO ARE COMPLETELY FAMILIAR WITH THE SPECIFIED REQUIREMENTS AND THE METHODS NEEDED FOR THE PROPER
5/13/24
PERFORMANCE OF THE WORK OF THIS SECTION. Dr. Al Gonzalez P.E.
B. ALL WORK SHALL BE OF THE HIGHEST QUALITY IN CONFORMANCE WITH THE BEST PRACTICES OF THE TRADE AND IN COMPLIANCE WITH ALL GOVERNING CODES.
1.05 CODES, PERMITS, FEES, AND REGULATIONS DOTec Engineering
A. ALL WORK SHALL BE CARRIED OUT IN CONFORMITY WITH THE RULES AND REGULATIONS OF THE 2020 NATIONAL ELECTRICAL CODE, AS ADOPTED BY THE VARIOUS LOCAL AGENCIES HAVING JURISDICTION. 424 Jefferson Street
B. THE CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES, OBTAIN ALL PERMITS AND PAY ALL GOVERNMENTAL TAXES, FEES, DEPOSITS AND OTHER COSTS IN CONNECTION WITH HIS WORK; FILE ALL NECESSARY PLANS, PREPARE ALL DOCUMENTS AND OBTAIN St. Charles, MO 63301
NECESSARY APPROVALS OF ALL AGENCIES BEFORE REQUEST FOR ACCEPTANCE AND FINAL PAYMENT FOR THE WORK. Ph 636-724-9872
1.06 STORAGE OF MATERIALS
A. STORE MATERIALS AND EQUIPMENT ON THE PREMISES WHERE DIRECTED BY THE OWNER.
Fx 636-724-9032
WWW.DOTECENGINEERING.COM
1.07 OTHER TRADES [email protected]
A. BIDDERS SHALL EXAMINE THE SIZE AND THE COMPLETE SET OF PLANS AND SPECIFICATIONS COVERING THE ENTIRE PROJECT. THEY SHALL BECOME FULLY CONVERSANT WITH THE TYPE OF GENERAL CONSTRUCTION AS WELL AS ALL PERTINENT FACTS AFFECTING THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL

THE COST OF CARRYING OUT THE WORK THEY WILL CONTRACT TO PERFORM.
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE
FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE
B. THE CONTRACTOR SHALL COOPERATE TO THE FULLEST WITH ALL OTHER TRADES. HE SHALL PLAN HIS WORK IN SUCH A WAY, AND FURNISH ALL NECESSARY EQUIPMENT AND INFORMATION TO THE OTHER TRADES SO AS NOT TO DELAY ANY OTHER TRADE OR HINDER FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE
PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY

THE PROGRESS OF THE WORK. ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR


CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE

1.08 SUBMITTALS
CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE
NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE
A. SUBMIT MANUFACTURER'S TECHNICAL PRODUCT DATA LITERATURE FOR ALL MATERIALS SPECIFIED HEREIN. INDICATE AND HIGHLIGHT ON THE SUBMITTALS DETAILS OF ALL ITEMS TO INDICATE CORRECT INTERPRETATION OF THE CONTRACT DOCUMENTS. INCLUDE REVISION OR CHANGES.

SUBMITTALS FOR THE FOLLOWING: Digitally signed by Ildefonso


Gonzalez
1. LIGHTING FIXTURES DN:
[email protected],
2. WIRING DEVICES CN=Ildefonso Gonzalez,
Ildefonso Gonzalez
1.09 CONFLICTS OU=CEO/President, O=DOTec
Corp, L=Saint Charles,
A. ANY CONTRADICTIONS BETWEEN THE WRITTEN SPECIFICATIONS AND DRAWINGS SHALL BE CONSIDERED AMBIGUOUS, AND WILL BE THE RESPONSIBILITY OF THE BIDDER TO SECURE CLARIFICATION PRIOR TO BIDDING. S=Missouri, C=US

PART 2 - PRODUCTS
Date: 2024.05.13
14:58:46-05'00'
2.01 GENERAL
A. ALL MATERIAL, EQUIPMENT, AND INSTALLATIONS SHALL CONFORM TO THE REQUIREMENTS OF THE FOLLOWING CODES:
1. L&I CODE
2. NATIONAL ELECTRICAL CODE
3. INTERNATIONAL BUILDING CODE

DESCRIPTION
4. OSHA
5. LOCAL JURISDICTIONAL CODES
2.03 PANELBOARDS
A. INSTALL NEW PANELBOARDS AS DETAILED ON THE DRAWINGS COMPLETE WITH REQUIRED CIRCUIT BREAKERS.
B. CIRCUIT BREAKERS SHALL BE: QUICK MAKE, QUICK BREAK, THERMAL MAGNETIC, TRIP INDICATION, AIC RATING, AMPACITY AS REQUIRED.
C. DETAILS OF THE PANELBOARDS AND BRANCH CIRCUIT BREAKERS SHALL BE AS INDICATED ON THE DRAWING PANEL SCHEDULES.
2.04 LIGHTING
A. THE CONTRACTOR SHALL PROVIDE ALL LIGHTING FIXTURES, POLES AND ACCESSORIES IN CONFORMANCE WITH THE FIXTURE SCHEDULE.
B. FURNISH PHOTOCELL(S), TIME CLOCK(S), AND CONTACTOR(S) AS REQUIRED FOR SITE LIGHTING CONTROL.
C. ALL EMERGENCY LIGHTING FIXTURES SHALL INCLUDE A 90 MINUTE BATTERY BACKUP OR GREATER.
D. 20A 1P LIGHTING CIRCUITS WITH LED LIGHTING FIXTURES SHALL USE A TYPE C CIRCUIT BREAKER.
2.05 WIRING DEVICES
A. FURNISH AND INSTALL QUALITY DEVICES BEARING UL LABEL FOR THE SERVICE AND ELECTRICAL RATING WHERE USED.
B. SWITCHES SHALL BE 20 AMPERE, 120/277 VOLT A.C. RATED AS SCHEDULED IN LEGEND.
C. GFCI RECEPTACLES SHALL BE 20 AMPERE DUPLEX, UNLESS NOTED OTHERWISE.
2.06 RACEWAYS
A. ALL PANEL FEEDER WIRING SHALL BE IN RIGID GALVANIZED CONDUIT WHERE EXPOSED TO DAMAGE AND TO THE PUBLIC. E.M.T. MAY BE USED WITHIN BUILDING INTERIORS, UNLESS CONDUIT IS EXPOSED TO SEVERE DAMAGE. SCHEDULE 40/80 PVC CONDUIT MAY BE

DATE
USED FOR BURIED CONDUIT RUNS.
B. WHERE FLEXIBLE CONNECTIONS ARE NECESSARY PROVIDE F.M.C., NO LONGER THAN 6 FEET LONG. PROVIDE LIQUID-TIGHT F.M.C. IN WET LOCATIONS.
C. ALL RACEWAYS SHALL BE 1/2" MINIMUM SIZE, UNLESS OTHERWISE NOTED.
2.07 OUTLET AND JUNCTION BOXES

#
SHEET NAME:
A. OUTLET BOXES FOR CEILING FIXTURES SHALL BE 4" OCTAGONAL GALVANIZED STEEL BOXES NOT LESS THAN 2-1/2" DEEP.
B. CONCEALED OUTLET BOX(ES) FOR WALL-MOUNTED EQUIPMENT, SWITCH(ES), OR RECEPTACLE(S) SHALL BE A 4" SQUARE GALVANIZED STEEL BOX WITH RAISED COVER OF SUFFICIENT DEPTH TO ACCOMMODATE WALL SURFACE MATERIAL, UNLESS NOTED ELECTRICAL NOTES
OTHERWISE.
C. EXPOSED OUTLET BOX(ES) IN DRY LOCATIONS FOR EQUIPMENT, SWITCHES, OR RECEPTACLES SHALL BE A 4" SQUARE GALVANIZED STEEL BOX WITH GALVANIZED STEEL COVER, UNLESS NOTED OTHERWISE.
2.08 WIRES AND CABLES
A. PROVIDE AND INSTALL ALL WIRING AND CABLE AS REQUIRED TO CONNECT ALL ELECTRICAL EQUIPMENT AND DEVICES INDICATED ON THE PLANS.
B. ALL WIRES #10 AWG AND SMALLER SHALL BE SOLID COPPER, 75 DEGREE C, AND 600 VOLT INSULATION, TYPE THWN.
C. ALL WIRES #8 AWG AND LARGER SHALL BE STRANDED COPPER, 75 DEGREE C, AND 600 VOLT INSULATION, TYPE THWN.
ISSUED FINAL:05-13-2024
D. LIGHTING FIXTURE WIRES SHALL NOT BE LESS THAN #14 AWG, SFF-2.
E. CONTROL WIRING SHALL NOT BE LESS THAN #14 AWG, THWN.
F. UNLESS INDICATED OTHERWISE ALL LIGHTING AND POWER CONDUCTORS SHALL BE #12 AWG, THWN.
PART 3 - EXECUTION
3.01 WORKMANSHIP
A. ALL WORK SHALL BE INSTALLED: IN ACCORDANCE WITH NECA 1 IN STRICT ACCORDANCE WITH THE RESPECTIVE MANUFACTURER'S PUBLISHED INSTRUCTIONS.
3.02 TEMPORARY LIGHTING AND POWER
A. FURNISH AND INSTALL TEMPORARY LIGHTING & POWER AS MAY BE REQUIRED BY ALL TRADES.
3.03 SUPPORTS
A. PROVIDE ALL MATERIALS AND LABOR REQUIRED TO ADEQUATELY SUPPORT AND BRACE EQUIPMENT AND FIXTURES FURNISHED AS PART OF THIS WORK.

12800 UNIVERSITY DR. SUITE 402


B. ALL RACEWAYS, BOXES, ETC., SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE, INDEPENDENT OF DUCT, PIPING OR OTHER WORK.

1911 S FEDERAL HWY, UNIT 206


C. ALL CONDUITS SHALL BE SECURELY AND INDEPENDENTLY SUPPORTED SO THAT NO TENSION WILL BE TRANSMITTED TO OUTLET BOX AND PULL BOX SUPPORTS, ETC.
3.04 BRANCH CIRCUITS
A. PROVIDE ALL CONDUITS, OUTLETS, BOXES, WIRES, SWITCHES, RECEPTACLES, ETC., FOR A COMPLETE ELECTRICAL SYSTEM AS SHOWN ON THE DRAWINGS.

DELRAY BEACH, FL 33483


B. CONTRACTOR SHALL REVIEW AND ACKNOWLEDGE THE MECHANICAL DRAWINGS AND SPECIFICATIONS TO CONFIRM THE EXTENT OF POWER AND CONTROL WIRING TO BE PROVIDED. CONTROL WIRING SHALL BE THE RESPONSIBILITY OF OTHERS.

POS ORDER COUNTER

FT. MEYERS, FL 33907


C. CONTRACTOR SHALL ENSURE ALL PHASES ARE BALANCED WITHIN 15% OF EACH OTHER.

PDS ARCHITECTURE
3.05 GROUNDING
A. THE ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS REQUIRED BY THE NATIONAL ELECTRICAL CODE. ALL GROUND SYSTEMS AND CONNECTIONS SHALL BE MECHANICALLY SECURE AND ELECTRICALLY CONTINUOUS.
3.06 LOCATION OF RECEPTACLES AND EQUIPMENT
A. THE PLANS SHOW CONDITIONS AS ACCURATELY AS POSSIBLE BUT DO NOT NECESSARILY SHOW ALL THE FITTINGS, ETC., NECESSARY TO SUIT BUILDING CONDITIONS. LOCATIONS OF RECEPTACLES, EQUIPMENT, ETC., ARE APPROXIMATE. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR CONFIRMING THE PROPER LOCATIONS IN ORDER TO COORDINATE WITH DETAILS FROM ARCHITECTURAL DRAWINGS.
B. THE OWNER OR ARCHITECT RESERVE THE RIGHT TO CHANGE LOCATION OF RECEPTACLES AND EQUIPMENT WITHIN A DISTANCE OF THREE FEET FROM LOCATION SHOWN AT NO ADDITIONAL COST TO THE OWNER.

PROJECT:
C. UNLESS NOTED OTHERWISE ON THE DRAWINGS, ALL DEVICES SHALL BE MOUNTED AT A STANDARD HEIGHT OR ADJUSTED BY THE CONTRACTOR. 18" AFF FOR STANDARD RECEPTACLES, 42" AFF FOR COUNTERTOP RECEPTACLES.

CLIENT:
D. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF ELECTRICAL EQUIPMENT WITH THE WORK OF OTHERS.
E. VERIFY ALL DOOR SWINGS BEFORE ROUGHING IN FOR SWITCHES.
SHEET NUMBER:
F. ALL ELECTRICAL INSTALLATIONS IN AREAS OF NEW CONSTRUCTION SHALL BE FLUSH MOUNTED. ELECTRICAL EQUIPMENT IS NOT TO BE SURFACE MOUNTED WITHOUT THE APPROVAL OF THE ENGINEER OR ARCHITECT, WITH THE EXCEPTION OF SURFACE MOUNTED
LIGHTING FIXTURES, UNLESS NOTED OTHERWISE.
3.07 CLEANING AND REMOVAL OF RUBBISH E-100
A. CONTRACTOR SHALL KEEP THE PREMISES FREE OF ALL WASTE, SURPLUS MATERIALS, RUBBISH OR DEBRIS GENERATED BY HIS CREW.
PROJECT NUMBER: 2403062
B. RUBBISH SHALL BE PLACED IN DUMPSTERS DAILY.
C. AFTER ALL EQUIPMENT AND DEVICES HAVE BEEN INSTALLED, REMOVE ALL TEMPORARY LABELS, STICKERS, STAINS, TEMPORARY COVERS, ETC. DRAWN BY: AJK

CHECKED BY: ALG

PRELIMINARY DOCUMENTS
PANEL A PANEL B
VOLTAGE: 120/208 NEUTRAL BUS: FULL BUS AMPS: 200 A MCB VOLTAGE: 120/208 NEUTRAL BUS: FULL BUS AMPS: 400 A MCB
PANEL TYPE: NEMA-1 GROUND BUS: FULL MINIMUM A.I.C.: 22,000 A PANEL TYPE: NEMA-1 GROUND BUS: FULL MINIMUM A.I.C.: 22,000 A FAULT CURRENT NOTES:
MOUNTING: SURFACE FED FROM: PP-B MAINS: 200 A MLO MOUNTING: SURFACE FED FROM: SERVICE MAIN MAINS: 400 A MCB THE AMOUNT OF AVAILABLE FAULT CURRENT FROM THE UTILITY COMPAN AND TRANSFORMER
LOAD BRKR CKT VA LOAD PER PHASE CKT BRKR LOAD LOAD BRKR CKT VA LOAD PER PHASE CKT BRKR LOAD LOCATION WAS NOT KNOWN TO DOTEC CORP. DURING THE DESIGN PHASE. THE DRAWINGS
TYPE CIRCUIT DESCRIPTION SIZE NO. A B C NO. SIZE CIRCUIT DESCRIPTION TYPE TYPE CIRCUIT DESCRIPTION SIZE NO. A B C NO. SIZE CIRCUIT DESCRIPTION TYPE ASSUME VALUES AND DISTANCES BASED UPON THE SITE LAYOUT AND BUSSMAN METHODS.
C SALAD FRIDGE 1 (201) 15 1 506 GFI M EXH-1 1 985
GFI 640 2 20 FOOD PROCESSOR K 1,494 2 CU-1 M PRIOR TO SUBMITTING POWER DISTRIBUTION EQUIPMENT PRODUCT DATA FOR REVIEW, THE
C SALAD FRIDGE 2 (201) 15 3 506 GFI M EXH-1
15/3
3 985
20/3 ELECTRICAL CONTRACTOR SHALL CONTACT THE UTILITY COMPANY TO VERIFY THE FAULT
GFI 1,200 4 20 BLENDER K 1,494 4 CU-1 M CURRENT VALUES AVAILABLE FROM THE UTILITY COMPANY AND SUBMIT THE UTILITY COMPANY THIS DRAWING IS PRELIMINARY
UNTIL SIGNED AND SEALED BY
C SALAD HOLDER (206) 15 5 322 GFI 1 DRAWER CHIP WARMER 2 M EXH-1 5 985 FAULT CURRENT INFORMATION TO THE ENGINEER FOR REVIEW AND EVALUATION. THE LICENSED PROFESSIONAL
GFI 450 6 15 (135) C 1,494 6 CU-1 M NOTED BELOW.
R DRINK STATION 20 7 1,242 GFI M SUP-3 7 913 AFTER THE UTILITY FAULT CURRENT INFORMATION HAS BEEN REVIEWED AND EVALUATED BY THE
GFI 1,800 8 15 COOKIE OVEN K 1,210 8 CU-2 M ENGINEER, ANY REVISIONS TO THE BASIS OF DESIGN AIC VALUES IDENTIFIED ON THE DRAWINGS PROFESSIONAL SEAL
K TEA BREWER 20 9 1,700 GFI M SUP-3 9 913 THAT MAY BE REQUIRED BASED ON THE FAULT CURRENT INFORMATION RECEIVED FROM THE
15/3 20/3
GFI 1,500 10 15 HOLDING CABINET 1 (130) C 1,210 10 CU-2 M UTILITY COMPANY SHALL BE COMMUNICATED TO THE ELECTRICAL CONTRACTOR.
C EXTERIOR SIGN 15 11 1,200 GFI M SUP-3 11 913
GFI 1,500 12 15 HOLDING CABINET 2 (130) C 1,210 12 CU-2 M CONTRACTOR SHALL NOT SUBMIT THE POWER DISTRIBUTION EQUIPMENT FOR REVIEW OR ORDER
R HALO SIGN 15 13 600 GFI M COOLER (CONFIRM WITH 13 2,882 THE POWER DISTRIBUTION EQUIPMENT UNTIL THE FAULT CURRENT INFORMATION FROM THE
GFI 479 14 15 REACH-IN FRIDGE (228) C MFG.) 1,027 14 MUA-1 M UTILITY COMPANY HAS BEEN SUBMITTED TO THE ENGINEER BY THE CONTRACTOR AND THE
R MENU SIGNS 15 15 900 GFI MANAGER'S DESK RECEPTACLES M COOLER (CONFIRM WITH MFG.) 15 2,882 ENGINEER HAS EVALUATED THE INFORMATION AND PROVIDED FINAL DIRECTION REGARDING THE
30/3 15/3
GFI 1,440 16 20 X8 R 1,027 16 MUA-1 M AIC RATING OF THE POWER DISTRIBUTION EQUIPMENT.
R POS 1 15 17 360 GFI M COOLER (CONFIRM WITH MFG.) 17 2,882
GFI 353 18 15 KITCHEN LIGHTS C 1,027 18 MUA-1 M 5/13/24
R POS 2 15 19 360 GFI M RTU-2 19 8,807
GFI 358 20 15 DINING LIGHTS C 4,577 20 RTU-1 M Dr. Al Gonzalez P.E.
R DINING AREA RECEPTACLES 15 21 900 GFI M RTU-2 21 8,807 DOTec Engineering
80/3 40/3
X5 GFI 360 22 15 GAS WATER HEATERS R 4,577 22 RTU-1 M 424 Jefferson Street
K PANINI PRESS 1 (108) 20 23 1,750 GFI M RTU-2 23 8,807 St. Charles, MO 63301
GFI 900 24 15 2 DRAWER CHIP WARMER (136) C 4,577 24 RTU-1 M
K PANINI PRESS 2 (108) 20 25 1,750 GFI 1 DRAWER CHIP WARMER 1 - PP-A 25 12,597
Ph 636-724-9872
GFI 450 26 15 (135) C 373 26 KEF-1 M Fx 636-724-9032
K PANINI PRESS 3 (108) 20 27 1,750 GFI - PP-A 27 12,597 WWW.DOTECENGINEERING.COM
200/3 30/3 [email protected]
GFI 540 28 15 KITCHEN TVS X3 R 373 28 KEF-1 M THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
K PANINI PRESS 4 (108) 20 29 1,750 GFI GLASS DOOR MERCHANDISER - PP-A 29 12,597 RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE
FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND

GFI 1,070 30 15 (226) C 373 30 KEF-1 M


DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE
FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE
PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
C THREE BAY HOT FOOD (113) 15 31 240 GFI M CO2 PUMP (1/2 HP) 30 31 1,127 ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE

GFI 180 32 20 ROOF GFCI R GFI 1,318 32 PP-K - CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE
NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE
C FOUR BAY HOT FOOD (114) 15 33 240 GFI C HOOD LIGHTS & CONTROL 15 33 500 REVISION OR CHANGES.
50/3
GFI 360 34 15 RESTROOM GFCIS X2 R GFI 1,318 34 PP-K - Digitally signed by Ildefonso
Gonzalez
R BEVERAGE COUNTER 15 35 180 GFI K STEAMER 2 (NOTE 2) 35 3,362 DN:
RECEPTACLE GFI 1,600 36 20 HAND DRYER 1 - 1,318 36 PP-K -
[email protected],
CN=Ildefonso Gonzalez,
K STEAMER (NOTE 1) 37 3,362 GFI K STEAMER 2 (NOTE 2) 30/3 37 3,362 Ildefonso Gonzalez OU=CEO/President, O=DOTec
Corp, L=Saint Charles,
1,600 38 20 HAND DRYER 2 - GFCI 38 SPACE S=Missouri, C=US
Date: 2024.05.13
K STEAMER (NOTE 1) 30/3 39 3,362 K STEAMER 2 (NOTE 2) 39 3,362 14:58:53-05'00'
GFCI 40 SPACE 40 SPACE
K STEAMER (NOTE 1) 41 3,362 SPACE 41
42 SPACE 42 SPACE
CONNECTED LOADS 13,567 14,758 14,797 CONNECTED LOADS 40,673 41,546 40,043 NOTES:
"C" CONTINUOUS AND LIGHTING LOAD (25%) 508 562 1,449 1. MOCP BY MANUFACTURER "C" CONTINUOUS AND LIGHTING LOAD (25%) 0 125 0 1. MOCP MY MANUFACTURER

DESCRIPTION
"M" 25% OF LARGEST MOTOR 0 0 0 "M" 25% OF LARGEST MOTOR 2,202 2,202 2,202
SUBTOTALS PER PHASE 14,076 15,320 16,246 SUBTOTALS PER PHASE 42,875 43,873 42,245
SUBTOTAL 45,642 SUBTOTAL 128,993
"R" RECEPTACLE DEMAND PER 220-44 0 "R" RECEPTACLE DEMAND PER 220-44 0
"K" KITCHEN LOAD PER 220-56 -7,850 "K" KITCHEN LOAD PER 220-56 -1,009
CODE VOLT-AMPERES 37,792 CODE VOLT-AMPERES 127,984
CODE LOAD AMPS 104.9 CODE LOAD AMPS 355.2

PP-A 001 PP-B 001


12" = 1'-0" 12" = 1'-0"

PANEL K
VOLTAGE: 120/208 NEUTRAL BUS: FULL BUS AMPS: 100 A PANEL SCHEDULE NOTES:
PANEL TYPE: NEMA-1 GROUND BUS: FULL MINIMUM A.I.C.: 22,000 A 1. SQUARE D NF466L4 WITH MAIN BREAKER KIT OR SIMILIAR
MOUNTING: SURFACE FED FROM: PP-B MAINS: 100 A SHUNT BREAKER 2. WIRE ALL EM LIGHTING FIXTURES AHEAD OF ALL SWITHING DEVICES

DATE
LOAD BRKR CKT VA LOAD PER PHASE CKT BRKR LOAD
TYPE CIRCUIT DESCRIPTION SIZE NO. A B C NO. SIZE CIRCUIT DESCRIPTION TYPE
C WORKTOP FRIDGE 15 1 600 GFI
GFI 679 2 15 GAS GRILL K

#
SPACE 3 GFI SHEET NAME:
960 4 15 FRYER (100) K
ELECTRICAL DETAILS
- MAIN 5 - GFI
AND PANEL SCHEDULE
1,920 6 20 COUNTERTOP WARMER K
- MAIN 7 - LOCAL UTILITY
8 SPACE INCOMING
50/3 CONNECTION
- MAIN 9 -
10 SPACE
SHUNT 11 ISSUED FINAL:05-13-2024
12 SPACE
13 400A METER WITH
SPACE 14 SPACE M 400A DISCONNECT
15
SPACE 16 SPACE
17 8#350MCM CU, 1#3G CU GROUND
METAL FRAME
SPACE 18 SPACE OF BUILDING WIRE SCHEDULE AND NOTES 4" EMT
CONNECTED LOADS 1,279 960 1,920 LOAD WIRE SIZE
MAXIMUM LENGTH OF BRANCH CIRCUIT PER
UTILIZATION VOLTAGE NOTE
PER ANDS
"C" CONTINUOUS AND LIGHTING LOAD (25%) 150 0 0 PH (KVA) (AWG)
(120, 1PH, MAX (240, 1PH, MAX (240, 3PH, MAX
V.D. 3%) V.D. 3%) V.D. 3%) REMARKS
GROUNDING 56 FT 85 FT 98 FT 5

12800 UNIVERSITY DR. SUITE 402


#12
"M" 25% OF LARGEST MOTOR 0 0 0 ELECTRODE #10 94 FT 141 FT 163 FT 5 'B' PANEL 400A 4#3/0 CU, 1#6G CU GROUND,

1911 S FEDERAL HWY, UNIT 206


< 1.92
SUBTOTALS PER PHASE 1,429 960 1,920 CONDUCTOR #8 144 FT 217 FT 250 FT 5 400A
2" EMT
#6 230 FT 345 FT 398 FT 5
SUBTOTAL 4,309 #12 75 FT 113 FT 130 FT 5 208V, 3∅
SERVICE
"R" RECEPTACLE DEMAND PER 220-44 0 2/0 CU GEC
#10 125 FT 188 FT 217 FT 5
EQUIPMENT

DELRAY BEACH, FL 33483


< 1.44
20

#8 192 FT 289 FT 334 FT 5


"K" KITCHEN LOAD PER 220-56 -356 4#3G CU, 1#8G CU GROUND,
20

#6 306 FT 460 FT 531 FT 5

POS ORDER COUNTER


20
20

FT. MEYERS, FL 33907


#12 86 FT 129 FT 149 FT
CODE VOLT-AMPERES 3,953 1.25" EMT
20

PDS ARCHITECTURE
20

< 1.26 #10 143 FT 215 FT 248 FT


20

CODE LOAD AMPS 11.0 #8 220 FT 330 FT 381 FT


20

CONNECTIONS #12 100 FT 150 FT 173 FT


MADE WITHIN 5 FT. < 1.08 #10 167 FT 250 FT 289 FT
PP-k 001 OF POINT OF #8 256 FT 385 FT 445 FT
ENTRANCE OF PIPE #12 120 FT 180 FT 240 FT
12" = 1'-0" < 0.9
#10 200 FT 300 FT 347 FT
#12 150 FT 225 FT 260 FT
<0.72
CONCRETE-ENCASED #10 250 FT 376 FT 434 FT
ELECTRODE #
CONTRACTOR SHALL
NOTES
REFER TO THIS TABLE PRIOR TO START OF

PROJECT:
1 BRANCH CIRCUIT ROUGH-IN. 'A' PANEL 200A 100A 'K' PANEL 100A

CLIENT:
CONTRACTOR SHALL USE THE APPROPRIATE WIRE SIZE IN
CONJUNCTION WITH THE LENGTH OF THE PROPOSED FIELD VERIFIED
2 ROUTING OF BRANCH CIRCUIT WIRING (INCLUDING VERTICAL &
LATERAL RUN, ROUTED PARALLEL/PERPENDICULAR TO THE BUILDING
208V, 3∅ SHUT
STRUCTURE).
208V, 3∅
3 SEE PANEL SCHEDULE FOR THE CORRESPONDING KVA LOAD PER
PHASE OF A PARTICULAR BRANCH CIRCUIT.
RESISTANCE VALUES USED ARE FOR UNCOATED COPPER WIRES IN
4G CU GEC 1/0 CU GEC SHEET NUMBER:
4 STEEL CONDUIT. 75 DEGREE C., OPERATING AT 60HZ.
THE VALUES IN "120V, 1PH" COLUMN IS TO BE USED FOR GENERAL

E-101
5 PURPOSE RECEPTACLE LOADS.
6 WATER HEATER SHALL HAVE AN OCP AS RECOMMENDED BY
MANUFACTURER/VENDOR.

METAL UNDERGROUND GROUND RING PROJECT NUMBER: 2403062


WATER PIPE
GROUND ROD DRAWN BY: Author

GROUNDING ELECTRODE SYSTEM DETAIL SINGLE LINE DIAGRAM


1 CHECKED BY: Checker
NOT TO SCALE
SERVICE
EQUIPMENT

PRELIMINARY DOCUMENTS
GROUNDING
NOT TOELECTRODE
SCALE SYSTEM DETAIL
POWER LEGEND

1 POLE HOME RUN

2 POLE HOME RUN

3 POLE HOME RUN THIS DRAWING IS PRELIMINARY


UNTIL SIGNED AND SEALED BY
THE LICENSED PROFESSIONAL
120V DUPLEX RECEPTACLE NOTED BELOW.
GFCI
GFCI
J GFCI 120V GFCI RECEPTACLE
PROFESSIONAL SEAL

PP-A34
PP-A38 120V QUAD RECEPTACLE
PP-A7
GFCI
PP-A48 120V QUAD GFCI RECEPTACLE

PP-A35 PP-A9 J
WP WEATHER-PROOF GFCI
GFCI GFCIGFCI
GFCI
J USB USB RECEPTACLE
PP-A36
5/13/24
120V DROP-CORD RECEPTACLE
PP-A11 Dr. Al Gonzalez P.E.
CONFIRM LOCATION WITH OWNER DOTec Engineering
PP-A17
J
GFCI PP-A2 120V FLOOR RECEPTACLE

120V QUAD
424 Jefferson Street
PP-A37,39,41 PP-A4 St. Charles, MO 63301
PP-A8,10,12 FLOOR RECEPTACLE
PP-A30 Ph 636-724-9872
PP-A6
DATA RECEPTACLE
J Fx 636-724-9032
PP-B35,37,39 WWW.DOTECENGINEERING.COM
PP-A10 240V APPLIANCE OUTLET [email protected]
PP-A15 PP-A16
PP-A19 PP-A12
THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE

PP-A25
FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE
J JUNCTION BOX FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE

PP-A24 PP-A PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY


ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
PP-A21 GFCI CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE
S SMOKE DETECTOR CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE

PP-A6 NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE

GFCIGFCI
PP-B REVISION OR CHANGES.
PP-A14 Digitally signed by Ildefonso
Gonzalez
PP-A1 ELECTRICAL PANEL

GFCI GFCI
DN:
PP-A27 [email protected],
PP-K6 Ildefonso Gonzalez
CN=Ildefonso Gonzalez,
OU=CEO/President, O=DOTec
Corp, L=Saint Charles,
PP-A3 PP-A28 LIGHTING LEGEND S=Missouri, C=US
Date: 2024.05.13
14:58:59-05'00'
PP-C
PP-A31 PP-K1

PP-B31 CEILING FAN WITH

GFCI
PP-A31 LIGHTING FIXTURES (100W)
PP-K2

DESCRIPTION
J

GFCI RECESSED CAN LIGHT

PENDANT LIGHT
PP-A29 PP-K4

GFCIGFCI
J
PP-A23
GFCI

VANITY LIGHT FIXTURE


GFCI

GFCI

PP-A26 PP-A5
EXTERIOR SCONCE

PP-A56
PP-B1,3,5 EMERGENCY LIGHT W/ SIGN

EMERGENCY LIGHT

EMERGENCY LIGHT

POWER PLAN

DATE
1
1/4" = 1'-0" LINEAR CEILING LIGHT

#
TRACK LIGHTING FIXTURE SHEET NAME:

ELECTRICAL POWER
EXTERIOR WALL PACK LIGHT PLAN

2X4 TROFFER CEILING LIGHT

ISSUED FINAL:05-13-2024
2X2 TROFFER CEILING LIGHT

2X4 TROFFER CEILING LIGHT


WITH BATTERY BACKUP

2X2 TROFFER CEILING LIGHT


WITH BATTERY BACKUP

12800 UNIVERSITY DR. SUITE 402


EXHAUST FAN

1911 S FEDERAL HWY, UNIT 206


EXHAUST FAN W/ LIGHT

DELRAY BEACH, FL 33483


POS ORDER COUNTER

FT. MEYERS, FL 33907


SWITCH

PDS ARCHITECTURE
3
3-WAY SWITCH

4
4-WAY SWITCH

PROJECT:
FAN SWITCH

CLIENT:
OS
OCCUPANCY SENSOR SWITCH
SHEET NUMBER:
SB
SWITCH BANK (SEE DETAIL)

T
E-102
60 MINUTE TIMER SWITCH
PROJECT NUMBER: 2403062
CEILING MOUNTED DRAWN BY: AJK
OS
OCCUPANCY SENSOR
CHECKED BY: ALG

PRELIMINARY DOCUMENTS
POWER LEGEND

1 POLE HOME RUN


PP-B13,15,17
NEMA 3R 30A DISCONNECT
2 POLE HOME RUN

3 POLE HOME RUN THIS DRAWING IS PRELIMINARY


UNTIL SIGNED AND SEALED BY
THE LICENSED PROFESSIONAL
J 120V DUPLEX RECEPTACLE NOTED BELOW.

GFCI 120V GFCI RECEPTACLE


PROFESSIONAL SEAL

COOLER
120V QUAD RECEPTACLE

PP-B26,28,30
GFCI
NEMA 3R 80A DISCONNECT 120V QUAD GFCI RECEPTACLE

RTU-1 RTU-2 WP WEATHER-PROOF GFCI

PP-B2,4,6
NEMA 3R 20A DISCONNECT USB USB RECEPTACLE
5/13/24
120V DROP-CORD RECEPTACLE
Dr. Al Gonzalez P.E.
J
J 120V FLOOR RECEPTACLE DOTec Engineering
120V QUAD
424 Jefferson Street
MUA-1
FLOOR RECEPTACLE St. Charles, MO 63301
Ph 636-724-9872
J J PP-B8,10,12 DATA RECEPTACLE
NEMA 3R 20A DISCONNECT Fx 636-724-9032
WWW.DOTECENGINEERING.COM
WP
240V APPLIANCE OUTLET [email protected]
THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE

J FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND


PP-B14,16,18 J JUNCTION BOX
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE
FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE

PP-B20,22,24 NEMA 3R 15A DISCONNECT PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE

NEMA 3R 40A DISCONNECT SMOKE DETECTOR CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
S CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE
NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE
REVISION OR CHANGES.

Digitally signed by Ildefonso


Gonzalez
ELECTRICAL PANEL DN:
[email protected],
KEF-1 CN=Ildefonso Gonzalez,
Ildefonso Gonzalez OU=CEO/President, O=DOTec
Corp, L=Saint Charles,
PP-A32 LIGHTING LEGEND S=Missouri, C=US
Date: 2024.05.13
14:59:05-05'00'

J
CEILING FAN WITH
LIGHTING FIXTURES (100W)

DESCRIPTION
PP-B26,28,30
RECESSED CAN LIGHT

PENDANT LIGHT

VANITY LIGHT FIXTURE

EXTERIOR SCONCE

roof power plan


1 EMERGENCY LIGHT W/ SIGN
1/4" = 1'-0"
EMERGENCY LIGHT

EMERGENCY LIGHT

DATE
LINEAR CEILING LIGHT

#
TRACK LIGHTING FIXTURE SHEET NAME:

ROOF POWER PLAN


EXTERIOR WALL PACK LIGHT

2X4 TROFFER CEILING LIGHT

ISSUED FINAL:05-13-2024
2X2 TROFFER CEILING LIGHT

2X4 TROFFER CEILING LIGHT


WITH BATTERY BACKUP

2X2 TROFFER CEILING LIGHT


WITH BATTERY BACKUP

12800 UNIVERSITY DR. SUITE 402


EXHAUST FAN

1911 S FEDERAL HWY, UNIT 206


EXHAUST FAN W/ LIGHT

DELRAY BEACH, FL 33483


POS ORDER COUNTER

FT. MEYERS, FL 33907


SWITCH

PDS ARCHITECTURE
3
3-WAY SWITCH

4
4-WAY SWITCH

PROJECT:
FAN SWITCH

CLIENT:
OS
OCCUPANCY SENSOR SWITCH
SHEET NUMBER:
SB
SWITCH BANK (SEE DETAIL)

T
E-103
60 MINUTE TIMER SWITCH
PROJECT NUMBER: 2403062
CEILING MOUNTED DRAWN BY:
OS Author
OCCUPANCY SENSOR
CHECKED BY: Checker

PRELIMINARY DOCUMENTS
POWER LEGEND

1 POLE HOME RUN

2 POLE HOME RUN

WALK IN COOLER LIGHTING BY 3 POLE HOME RUN THIS DRAWING IS PRELIMINARY


PRE-FABERICATED COOLER MANUFACTURER UNTIL SIGNED AND SEALED BY
THE LICENSED PROFESSIONAL
C1 PP-A20 120V DUPLEX RECEPTACLE NOTED BELOW.
C1 C1 C1
GFCI 120V GFCI RECEPTACLE
PROFESSIONAL SEAL
PA2 C1 C1

PA2 PA2 120V QUAD RECEPTACLE

OS
C1
OS
C1
GFCI 120V QUAD GFCI RECEPTACLE
C1 PP-A18
C1
WP WEATHER-PROOF GFCI
OS
C1 C1
PP-A20 USB USB RECEPTACLE
TR1 TR1 5/13/24
NL
120V DROP-CORD RECEPTACLE
Dr. Al Gonzalez P.E.
T T T T T 3

120V FLOOR RECEPTACLE DOTec Engineering


120V QUAD
424 Jefferson Street
TR1 PP-A20 FLOOR RECEPTACLE St. Charles, MO 63301
PA2
Ph 636-724-9872
DATA RECEPTACLE
PA2
PA1 Fx 636-724-9032
PA2 C1 WWW.DOTECENGINEERING.COM
240V APPLIANCE OUTLET [email protected]
TR1 TR1 THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
NL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE
FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE
J JUNCTION BOX
C1 FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE
PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE
S SMOKE DETECTOR CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE
PA1 NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE
REVISION OR CHANGES.
C1 TR1 TR1
PA1 Digitally signed by Ildefonso
Gonzalez
ELECTRICAL PANEL DN:
[email protected],

PA2 PA2 PA4 Ildefonso Gonzalez


CN=Ildefonso Gonzalez,
PA2 OU=CEO/President, O=DOTec
Corp, L=Saint Charles,
LIGHTING LEGEND S=Missouri, C=US
TR1

3
Date: 2024.05.13
PA4 14:59:11-05'00'

PA1
PP-A18
PA1 C1
CEILING FAN WITH
PP-A18 LIGHTING FIXTURES (100W)
TR1

DESCRIPTION
C1
RECESSED CAN LIGHT
PA2 PA2 PA2
C1 PENDANT LIGHT
E07 E07
E07 TR2
VANITY LIGHT FIXTURE

EXTERIOR SCONCE

EMERGENCY LIGHT W/ SIGN

ELECTRICAL LIGHTING PLAN EMERGENCY LIGHT


1
1/4" = 1'-0"
EMERGENCY LIGHT

DATE
LINEAR CEILING LIGHT

LIGHTING SCHEDULE
TYPE TAG QUANTITY COLOR (K) LUMENS LAMP TYPE VOLTAGE WATTS NOTES

#
TRACK LIGHTING FIXTURE
RECESSED CAN C1 18 3500-4000 - LED 120 14 COORDINATE WITH ARCHITECT SHEET NAME:

2X2 TROFFER TR2 1 3500-4000 - LED 120 25 COORDINATE WITH ARCHITECT ELECTRICAL LIGHTING
2X4 TROFFER TR1 8 3500-4000 - LED 120 35 COORDINATE WITH ARCHITECT EXTERIOR WALL PACK LIGHT PLAN
WALL SCONCE E07 3 3500-4000 - LED 120 15 COORDINATE WITH ARCHITECT
PENDANT LIGHT '22491' PA4 2 3500-4000 - LED 120 24 COORDINATE WITH ARCHITECT
PENDANT LIGHT 6" PA2 15 3500-4000 - LED 120 24 COORDINATE WITH ARCHITECT 2X4 TROFFER CEILING LIGHT

LARGE PENDANT LIGHT PA1 7 3500-4000 - LED 120 24 COORDINATE WITH ARCHITECT
ISSUED FINAL:05-13-2024
2X2 TROFFER CEILING LIGHT

2X4 TROFFER CEILING LIGHT


WITH BATTERY BACKUP

2X2 TROFFER CEILING LIGHT


WITH BATTERY BACKUP

12800 UNIVERSITY DR. SUITE 402


EXHAUST FAN

1911 S FEDERAL HWY, UNIT 206


EXHAUST FAN W/ LIGHT

DELRAY BEACH, FL 33483


POS ORDER COUNTER

FT. MEYERS, FL 33907


SWITCH

PDS ARCHITECTURE
3
3-WAY SWITCH

4
4-WAY SWITCH

PROJECT:
FAN SWITCH

CLIENT:
OS
OCCUPANCY SENSOR SWITCH
SHEET NUMBER:
SB
SWITCH BANK (SEE DETAIL)

T
E-104
60 MINUTE TIMER SWITCH
PROJECT NUMBER: 2403062
CEILING MOUNTED DRAWN BY: AJK
OS
OCCUPANCY SENSOR
CHECKED BY: ALG

PRELIMINARY DOCUMENTS
MECHANICAL NOTES
NOTE DESCRIPTION

AIR DISTIBUTION
1. ALL DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED IRON SHEET METAL AND FABRICATED ACCORDING TO THE SMACNA LOW VELOCITY DUCT MANUAL, ASHRAE HANDBOOK VOLUME "HVAC
SYSTEMS AND EQUIPMENT", AND TYPICAL DUCTWORK DETAILS SHOWN IN THESE DRAWINGS. ALL ELBOWS SHALL HAVE PROPER RADIUS, OR MECHANICAL CONTRACTOR SHALL PROVIDE DOUBLE
THICKNESS AIRFOIL TURNING VANES REQUIRED BY SMACNA. NO SQUARE THROAT ELBOWS SHALL BE INSTALLED WITHOUT DOUBLE THICKNESS TURNING VANES. SIZES SHOW ON PLAN ARE INSIDE
FREE AREA.
2. ALL FLEXIBLE DUCTWORK SHALL FACTORY ASSEMBLED CLASS 1 AIR DUCT (UL 181) WITH FIBERGLASS INSULATION AND REINFORCED OUTER PROTECTIVE COVER/VAPOR BARRIER. FLEX DUCT SHALL THIS DRAWING IS PRELIMINARY
MEET NFPA 90A WITH FLAME SPREAD UNDER 25, SMOKE DEVELOPED UNDER 50, AND SHALL BE RATED FOR 2" W.C. PRESSURE AND 0 TO 250 DEGREE TEMPERATURE. MAXIMUM STRETCHED OUT UNTIL SIGNED AND SEALED BY
LENGTH SHALL BE AS PER CODES. THE LICENSED PROFESSIONAL
MECHANICAL ABBREVIATIONS NOTED BELOW.
3. PROVIDE UL APPROVED FIRE DAMPERS FOR ALL PENETRATIONS THROUGH FIRE RATED WALLS, PARTITIONS, CEILINGS, AND FLOORS. INSTALL FIRE DAMPERS AS PER MANUFACTURER'S DIRECTIONS
AND PER UL GUIDELINES. DAMPERS AS PER MANUFACTURER'S DIRECTIONS AND PER UL GUIDELINES. CONSTRUCTION AS REQUIRED FOR SERVICING OF FIRE DAMPERS. PROFESSIONAL SEAL
AFF ABOVE FINISHED FLOOR
4. ALL DUCT CONNECTIONS TO EQUIPMENT SHALL BE MADE WITH NEOPRENE, DOUBLE COATED, HEAVY GLASS FABRIC, VIBRATION ELIMINATION CONNECTIONS, (F.C) FLEXIBLE CONNECTIONS, EQUAL TO BATT BATTING INSULATION
VENTFABRICS, INC. TYPE VENTGLAS, UNLESS NOTED OTHERWISE. BLD'G BUILDING
BOT BOTTOM
5. ALL BRANCH SUPPLY DUCTS SHALL HAVE (VD) MANUAL VOLUME DAMPERS INSTALLED FOR BALANCING. CL'G CEILING
6. PROVIDE A VOLUME DAMPER FOR EVERY INLET AND OUTLET (DIFFUSERS, REGISTERS, GRILLES, ETC.) OF THE DUCTWORK DISTRIBUTION SYSTEMS DAMPERS OR EXTRACTORS AT BRANCH TAKE-OFFS COL COLUMN
DEG F DEGREES FAHRENHEIT
FROM DUCTWORK MAINS AS REQUIRED TO ACHIEVE AIR VOLUME DISTRIBUTION AND BALANCING. DIA DIAMETER
7. ALL DUCTWORK TRANSITIONS SHALL BE (FOT) "FLAT ON TOP", UNLESS OTHERWISE SPECIFIED ON PLAN. DWG DRAWING
EA EXHAUST AIR
8. ALL CONTRACTOR FABRICATED AND MANUFACTURER FABRICATED COMPONENTS OF THE OUTSIDE AIR, SUPPLY AIR, RETURN AIR AND EXHAUST SYSTEMS SHALL BE CONSTRUCTED AND INSTALLED EAT ENTERING AIR TEMPERATURE
AIR-TIGHT. THE INSTALLED SYSTEMS SHALL BE PRESSURE TESTED AS SPECIFIED. PIPE OPENINGS IN SYSTEM COMPONENTS SHALL HAVE SHEET METAL BAFFLES, SET IN SEALANT, TO PREVENT ETR EXISTING TO REMAIN
LEAKAGE. EWT ENTERING WATER TEMPERATURE 5/13/24
FC FLEXIBLE CONNECTION
AUTOMATIC TEMPERATURE CONTROLS FD FIRE DAMPER Dr. Al Gonzalez P.E.
FL'R FLOOR
1. CONTRACTOR SHALL FURNISH AND INSTALL ALL CONTROL WIRING AS REQUIRED. THERMOSTATS SHALL BE REMOTELY CONTROLLED "NEST" OR APPROVED EQUAL. PROVIDE TRANSFORMERS AS FOB FLAT ON BOTTOM DOTec Engineering
REQUIRED. FOT FLAT ON TOP
GC GENERAL CONTRACTOR 424 Jefferson Street
2. THERMOSTATS TO BE PLACED IN AN APPROVED LOCKABLE ENCLOSURE. LAT LEAVING AIR TEMPERATURE St. Charles, MO 63301
BASIC MATERIALS AND METHODS LWT LEAVING WATER TEMPERATURE
MOD MOTOR OPERATED DAMPER Ph 636-724-9872
1. MATERIALS SHALL BEAR UNDERWRITERS LABEL WHERE SUCH STANDARDS HAVE BEEN ESTABLISHED AND LISTED BY UNDERWRITER'S LABORATORIES, INC. MATERIALS, EQUIPMENT AND APPLIANCES
SHALL CONFORM TO THE LATEST STANDARDS OF:
MT'D
MVD
MOUNTED
MANUAL VOLUME DAMPER
Fx 636-724-9032
NC NEW CONNECTION TO EXISTING WWW.DOTECENGINEERING.COM
NTS NOT TO SCALE [email protected]
AMCA - AIR MOVING AND CONDITIONING ASSOCIATIONS, INC. OA OUTSIDE AIR THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL

SMACNA - SHEET METAL AND AIR CONDITIONING CONTRACTOR NATIONAL ASSOCIATION, INC
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE
OC ON CENTER FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE
ASHRAE - AMERICAN SOCIETY OF HEATING, REFRIGERATION AND AIR CONDITIONING ENGINEERS UCD UNDER CUT DOOR, FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE
PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
UNO UNLESS NOTED OTHERWISE
ASME - AMERICAN SOCIETY OF MECHANICAL ENGINEERS RA RETURN AIR
ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE

ASTM - AMERICAN SOCIETY FOR TESTING MATERIALS


CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE

REQ'D REQUIRED CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE


NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE
NEMA - NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION SA SUPPLY AIR REVISION OR CHANGES.

ARI - AIR CONDITIONING AND REFRIDGERATION INSTITUTE W/ WITH Digitally signed by Ildefonso
Gonzalez
Ø DIAMETER/ROUND
ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE DN:
[email protected],

CLOSEOUT DOCUMETATION
CN=Ildefonso Gonzalez,
Ildefonso Gonzalez OU=CEO/President, O=DOTec

1. THE CONTRACTOR SHALL FURNISH TO THE BUILDING OWNER WITHIN 90 DAYS OF DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY THE FOLLOWING:
Corp, L=Saint Charles,
S=Missouri, C=US

A. OPERATING AND MAINTENANCE MANUAL. MANUAL SHALL CONSIST OF MANUFACTURER'S RECOMMENDATIONS, PROGRAMMING PROCEDURES AND DATA POINTS, NARRATIVE AND OTHER MEANS OF
Date: 2024.05.13
14:59:17-05'00'
ILLUSTRATING TO THE OWNER HOW THE BUILDING, EQUIPMENT AND SYSTEMS ARE INTENDED TO BE INSTALLED, MAINTAINED AND OPERATED.
B. AS-BUILT HVAC DRAWINGS.
C. BALANCE REPORT OF HVAC SYSTEMS.
COORDINATION

DESCRIPTION
1. COORDINATE WITH GENERAL CONTRACTOR FOR ALLOWABLE DAYS OF WEEK AND TIMES OF DAY FOR SYSTEMS SHUT DOWNS AS REQUIRED FOR THE CONSTRUCTION WORK.
2. THE MECHANICAL CONTRACTOR SHALL COORDINATE DUCTWORK INSTALLATION WITH ARCHITECTS/OWNERS REPRESENTATIVE IN FIELD AND OTHER TRADES.
3. THE MECHANICAL CONTRACTOR SHALL COORDINATE VOLTAGE OF ALL EQUIPMENT WITH ELECTRICAL PRIOR TO ORDERING EQUIPMENT.
EQUIPMENT
1. THE MECHANICAL CONTRACTOR SHALL INSTALL MECHANICAL SYSTEMS AS SHOWN, NOTED AND SPECIFIED. EQUIPMENT MAY NOT BE SUBSTITUTED UNLESS WRITTEN APPROVAL BY THE ARCHITECT, MECHANICAL SYMBOLS
ENGINEER OR OWNER'S REPRESENTATIVE IS OBTAINED. ANY CHANGES TO THE DUCTWORK LAYOUT WILL NECESSITATE SUBMISSION OF SHEET METAL SHOP DRAWINGS FOR ENGINEER'S REVIEW. ANY
UNAUTHORIZED CHANGES WILL BE REMOVED AT CONTRACTOR'S EXPENSE, IF DEEMED NECESSARY BY ARCHITECT, ENGINEER, OR OWNER'S REPRESENTATIVE. RUSKIN MODEL NO. MD-35 OPPOSED BLADE DAMPER
MANUAL VOLUME DAMPER (MVD) WITH LOCKING
2. UPON SELECTION OF THE MECHANICAL APPLIANCES, SUBMIT THE MANUFACTURER'S INSTALLATION INSTRUCTIONS TO THE BUILDING DEPARTMENT, INCLUDING LISTING FOR OUTSIDE INSTALLATION HANDLE AND AIR-TIGHT END BEARINGS.
WHERE APPLICABLE.
GENERAL T TEMPERATURE CONTROL DEVICE.
1. MECHANICAL SYSTEMS SHALL BE INSTALL IN ACCORDANCE WITH ALL APPLICABLE BUILDING CODES.
2. DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC, SHOWING THE GENERAL LOCATION, TYPE, LAYOUT AND EQUIPMENT REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR EXACT TAG
MEASUREMENTS. REFER TO MANUFACTURERS STANDARD INSTALLATION DRAWINGS FOR EQUIPMENT CONNECTIONS AND INSTALLATION REQUIREMENTS AS REQUIRED. FURNISH AND INSTALL TYPICAL SUPPLY DIFFUSER. CFM
DUCTWORK, CONNECTIONS, ACCESSORIES, OFFSETS AND MATERIALS NECESSARY TO FACILITATE THE SYSTEMS FUNCTIONING AS INDICATED BY THE DESIGN AND THE EQUIPMENT INDICATED. THE
WORK SHALL BE IN ACCORDANCE WITH LOCAL CODES AND ORDINANCES AND SUBJECT TO INSPECTION.

DATE
TAG
3. THE MECHANICAL SYSTEMS SHALL BE COMPLETE WITH ALL NECESSARY APPURTENANCES FOR A COMPLETE OPERATING SYSTEM. TYPICAL RETURN GRILLE. (SIZE)
4. THE CONTRACTOR SHALL WARRANTEE ALL MATERIAL AND GUARANTEE ALL WORKMANSHIP FOR ONE YEAR FROM SUBSTANTIAL COMPLETION.
4. ALL DUCTWORK AND PIPING THAT IS EXPOSED TO VIEW SHALL BE ROUTED AS HIGH AS POSSIBLE AND TIGHT TO THE UNDERSIDE OF THE STRUCTURAL STEEL ABOVE. TAG

#
INSTALLATION TYPICAL EXHAUST GRILLE. CFM SHEET NAME:

1. CORE-DRILL OR SAW-CUT FLOOR, WALL, ROOF, ETC. AS REQUIRED FOR PIPING OR DUCTWORK AND FIRE-STOP OPENING AROUND PIPE OR DUCTWORK. VERIFY LOCATION OF STRUCTURAL BEAMS, MECHANICAL NOTES
JOISTS, ETC. BEFORE DRILLING OR CUTTING. NOTIFY ARCHITECT OF ANY DISCREPANCIES. NC NEW CONNECTION TO EXISTING.
2. WHEREVER FOUNDATION WALLS, OUTSIDE WALLS, ROOFS, ETC. ARE CUT FOR INSTALLATION OF SYSTEMS, THEY SHALL BE PATCHED TO MATCH EXISTING CONSTRUCTION AND SEALED
WEATHER-TIGHT. WORK SHALL BE PERFORMED BY CRAFTSMEN SKILLED IN THEIR RESPECTIVE TRADES.
3. ALL DUCTWORK AND PIPING SHALL BE ROUTED ABOVE THE SUSPENDED CEILING SPACE, UNLESS OTHERWISE NOTED ON PLANS.
5. ALL OUTSIDE AIR INTAKES SHALL BE A MINIMUM OF 10'-0" AWAY FROM EXHAUST DISCHARGE OPENINGS AND PLUMBING VENT STACKS OR AS REQUIRED BY LOCAL CODES.
ISSUED FINAL:05-13-2024
INSULATION
1. ALL DUCTWORK ABOVE DROP CEILING SHALL BE INSULATED WITH 1 1/2" FOIL BACK DUCT WRAP INSULATION. ALL SEAMS SHALL BE TAPED SOLID.
2. NO FLEXIBLE DUCTWORK SHALL BE USED WITH THE EXCEPTION OF DETAIL 6 ON SHEET M102. MAXIMUM FLEXIBLE DUCT LENGTH OF 5 FEET. THE CONTRACTORS ARE REQUIRED TO VISIT THE SITE AND FULLY AQUAINT
THEMSELVES WITH THE EXISTING CONDITIONS AND THE DIFFICULTIES
3. ALL SUPPLY, RETURN AND OUTSIDE AIR RECTANGULAR/ROUND DUCTWORK SHALL BE INSULATED WITH SLEEVE INSULATION. INVOLVED IN ACCOMPLISHING THE NEW WORK. PROBLEMS, DISCREPANCIES
SMOKE DETECTORS OR INFORMATION NEEDED SHALL BE SUBMITTED TO THE LANDLORD
CONSTRUCTION MANAGER IN WRITING PRIOR TO SUBMITTING A PROPOSAL.
1. PROVIDE RETURN AIR SMOKE DETECTORS IN ALL AIR DISTRIBUTION SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2000 CFM. SMOKE DETECTOR SHALL BE INSTALLED UPSTREAM OF ANY THE SUBMISSION OF PROPOSAL WILL INDICATE THAT THE CONTRACTOR HAS
FILTERS, EXHAUST AIR CONNECTIONS, OR OUTSIDE AIR CONNECTIONS. FULLY UNDERSTOOD AND HAS INCLUDED ALL COSTS FOR THIS PROJECT.
TESTING AND BALANCING
1. BALANCING CONTRACTOR SHALL BALANCE SYSTEMS TO AIR QUANTITIES SHOWN ON PLAN. BALANCING CONTRACTOR SHALL USE DUCT MOUNTED MANUAL DAMPERS FOR AIR SYSTEM BALANCING.

12800 UNIVERSITY DR. SUITE 402


1911 S FEDERAL HWY, UNIT 206
USE OF A TERMINAL DAMPER IS NOT ACCEPTABLE.
2. TESTING AND BALANCING CONTRACTOR SHALL TEST ALL HVAC EQUIPMENT TO ENSURE PROPER OPERATION, TEST ALL CONTROLS TO ENSURE PROPER OPERATION, CALIBRATION AND ADJUSTMENT
OF CONTROLS, AND TEST ECONOMIZERS TO ENSURE PROPER OPERATION.

DELRAY BEACH, FL 33483


3. THE ARCHITECT AND/OR OWNER'S REPRESENTATIVE SHALL BE NOTIFIED 48 HOURS OR MORE PRIOR TO FINAL TESTING AND BALANCING WORK SO THAT THEY AND/OR THE ENGINEER MAY BE PRESENT

POS ORDER COUNTER

FT. MEYERS, FL 33907


TO OBSERVE THIS WORK. THE BALANCING CONTRACTOR SHALL SUBMIT WRITTEN REPORTS OF ALL AIR FLOW READINGS, STATIC PRESSURES, GPM RATES, PRESSURE READINGS, TEMPERATURE

PDS ARCHITECTURE
READINGS, MOTOR AMPERAGE, ETC., TO DOCUMENT PROPERLY OPERATING AND BALANCED MECHANICAL SYSTEMS IN ALL AREAS. A COPY OF THE TEST AND BALANCE REPORT SHALL BE SUBMITTED
TO THE AUTHORITIES HAVING JURISDICTION PRIOR TO FINAL INSPECTION AND REQUESTING OCCUPANCY.

PROJECT:

CLIENT:
SHEET NUMBER:

M-100
PROJECT NUMBER: 2403062

DRAWN BY: AJK

CHECKED BY: ALG

PRELIMINARY DOCUMENTS
KEYED NOTES
1 FULL SIZE DUCT FROM RTU THROUGH ROOF
10
2 FULL SIZE DUCT FROM MUA THROUGH ROOF
3 FULL SIZE MAKEUP AIR DUCT DOWN OFF BOTTOM TO MAKEUP AIR
2"ø V PLENUM ON HOOD
9
4 FULL SIZE DOUBLE-WALL GREASE EXHAUST UP AND TRANSITION TO THIS DRAWING IS PRELIMINARY
FULL SIZE INLET OF KEF-1 UNTIL SIGNED AND SEALED BY
THE LICENSED PROFESSIONAL
5 12X12 EXHAUST AIR DUCT UP THROUGH ROOF AND TO TERMINATE WITH NOTED BELOW.
1 GOOSENECK WITH BIRDSCREEN AND BACKDRAFT DAMPER
RTU-2 PROFESSIONAL SEAL
RTU-1 6 UNDERCUT DOOR FOR AIR TRANSFER
7 EXPOSED DUCTWORK TO BE DOUBLE-WALL WITH 1/2" CODE COMPLIANT
INSULATION, PROVIDED WITH PAINT GRIP FINISH. TYPICAL ALL EXPOSED
DUCTWORK.
8 1-WAY THROW SUPPLY DIFFUSER
9 10' CLEARANCE FROM EXHAUST AND VENT FOR OA INTAKE
1 10 CONDENSER FOR WALK IN COOLER BELOW, BY OTHERS.
11 PROVIDE SINGLE VENT AND INTAKE. INSTALL AND SIZE PER
MANUFACTURER RECOMMENDATION
MUA-1 5/13/24
12 2-WAY THROW DIFFUSER
Dr. Al Gonzalez P.E.
DOTec Engineering
424 Jefferson Street
2
St. Charles, MO 63301
Ph 636-724-9872
12X12 EXHAUST AIR DUCT FROM Fx 636-724-9032
EF-1 BELOW AND SHALL
WWW.DOTECENGINEERING.COM
TERMINATE WITH GOOSENECK
WITH BIRDSCREEN [email protected]
THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE
FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE

9 FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE


PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE
CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE
NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE
REVISION OR CHANGES.

KEF-1 Digitally signed by Ildefonso


Gonzalez
DN:
[email protected],
CN=Ildefonso Gonzalez,
Ildefonso Gonzalez OU=CEO/President, O=DOTec
Corp, L=Saint Charles,
9 S=Missouri, C=US
Date: 2024.05.13
14:59:23-05'00'

2"ø V

DESCRIPTION
ROOF PLAN
2
1/4" = 1'-0"

RESTROOM WALK-IN-COOLER
6
104 103
E1

DATE
S4 50 CFM
6
40 CFM

S1 6"ø
S4

#
6"x6"

6"ø
10"ø

275 CFM 40 CFM E1 SHEET NAME:

50 CFM HVAC
S1
8"ø

S1 R1 RESTROOM 6"x6"
275 CFM
12"x12"

275 CFM 2200 CFM


T
105 8 S2 R2
7
750 CFM 1750 CFM
24"ø

28"x10" 20"x10" ISSUED FINAL:05-13-2024


1
1

28"x10"

SERVICE
6"x6"
20"ø

101 2 S2
S1 710 CFM
12 S3
7 275 CFM
12"x12"

20"x10"

260 CFM
EF-1

12800 UNIVERSITY DR. SUITE 402


KITCHEN

1911 S FEDERAL HWY, UNIT 206


18"x14"

S1
275 CFM 102
6"x6"
10"ø

DELRAY BEACH, FL 33483


12"ø DINING

POS ORDER COUNTER

FT. MEYERS, FL 33907


PDS ARCHITECTURE
S1 100 3 S2
275 CFM 5 710 CFM
3
S1
275 CFM

PROJECT:
16"ø 7 12"x12"

CLIENT:
HD-1 4 11
10"ø

S1 S1 12 3
SHEET NUMBER:
275 CFM 275 CFM
S3
S3
265 CFM
50 CFM
M-101
PROJECT NUMBER: 2403062

DRAWN BY: AJK

DUCT PLAN CHECKED BY: ALG


1
1/4" = 1'-0" PRELIMINARY DOCUMENTS
EXHAUST FANS AIR DEVICE TYPE SCHEDULE
PLAN S.P. (IN AIRFLOW PLAN MODULE SIZE FRAME/
SERVICE BASIS OF DESIGN MODEL NO. POWER SONES NOTES BASIS OF DESIGN MODEL NOTES
MARK WC) (CFM) MARK (NECK SIZE) MOUNT
KEF-1 HOOD CAPTIVEAIR AH-DU180HFA 1.400 2,615 208-3-60 // 1.5 HP 16.7 1,4
S1 TITUS 300RL (12X8) D 1,3
EF-1 GENERAL CAPTIVEAIR AH-SIF9DD 0.100 150 208-1-60 // 0.166 HP 5.8 2,3,4
S2 TITUS PAS 24X24 (14"Ø) L 1,2,4
S3 TITUS PAS 24X24 (10"Ø) L 1,2,4
NOTES:
S4 TITUS PAS 12X12 (6"Ø) G 1,2,4 THIS DRAWING IS PRELIMINARY
FAN TO BE INSTALLED IN ON ROOF AND CONTROLLED VIA KITCHEN HOOD OPERATION. COORDINATE WITH UNTIL SIGNED AND SEALED BY
1 R1 TITUS 350RL 30X30 D 4,5,6
HOOD IN FIELD THE LICENSED PROFESSIONAL
R2 TITUS PAR 24X24 (22X22) L 4,5,6 NOTED BELOW.
2 FAN TO BE INSTALLED ABOVE CEILING. FAN TO BE OPERATIONAL WHEN SPACE IS OCCUPIED.
E1 TITUS PAR 12X12 (6X6) L 4,5,6 PROFESSIONAL SEAL
3 TERMINATE THROUGH GOOSENECK WITH BUGSCREEN AND BACKDRAFT DAMPER.
FRAME/MOUNT LEGEND:
4 EQUALS BY PANASONIC, GREENHECK OR LOREN COOK ACCEPTABLE.
D DIRECT MOUNT TO DUCT
FOR QUESTIONS CALL THE ADVANCED HOODS SYSTEMS, LLC F FLUSH IN FLOOR
REGION 140 G GYPSUM (DRYWALL) CEILING
PHONE: 407-269-4813
EMAIL: [email protected] L LAY-IN CEILING
REFERENCE PROJECT QDOBA DELRAY WEST
S SPECIALTY SURFACE. COORDINATE WITH G.C.
V VERTICAL SURFACE (WALL, DOOR, ETC.)

NOTES: 5/13/24
1 PROVIDE WITH 4-WAY AND/OR HORIZONTAL THROW UNLESS NOTED OTHERWISE.
Dr. Al Gonzalez P.E.
2 ALL TAKEOFFS TO AIR DEVICES SHALL HAVE SPIN-IN FITTING AND TO BE THE SIZE OF THE NECK OF
DOTec Engineering
AIR DEVICE
3 PROVIDE WITH ADJUSTABLE AIR SCOOP AND BALANCING DAMPER. 424 Jefferson Street
4 PROVIDE INSULATED BACKS ON ALL DIFFUSERS. St. Charles, MO 63301
5 PROVIDE BALANCING DAMPER AT NECK OF AIR DEVICE. Ph 636-724-9872
6 PAINT INSIDE OF RETURN AIR PLENUM FLAT BLACK. Fx 636-724-9032
WWW.DOTECENGINEERING.COM
7 COORDINATE WITH G.C./ARCHITECT/OWNER FOR COLOR/FINISH. [email protected]
THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE
FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE

MAKEUP AIR UNIT


FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE
PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE
CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE

COOLING PERFORMANCE FAN POWER CONDENSER POWER NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE

UNIT
REVISION OR CHANGES.

PLAN MARK BASIS OF DESIGN MODEL NO. MIN AIR DESIGN E.S.P. SONES NOTESGonzalez
Digitally signed by Ildefonso
ENTERING TEMP LEAVING TEMP TOTAL/SENSIBLE WEIGHT
FLOW AIR FLOW (IN WC) V-P-F MCA//MOP QTY V-P-F MCA//MOP (LBS) DN:
(DB/WB °F) (DB/WB °F) CAPACITY (MBH) [email protected],
(CFM) (CFM) Ildefonso Gonzalez
CN=Ildefonso Gonzalez,
OU=CEO/President, O=DOTec
MUA-1 CAPTIVEAIR AH-A1-15D-MPU 1,800 2,100 0.55 90/78 76.3/70.8 60.0/30.5 208-3-60 7.7//15 2 208-3-60 11.2//20 1076 28.7 1 Corp, L=Saint Charles,
S=Missouri, C=US
Date: 2024.05.13

NOTES:
14:59:29-05'00'

FOR QUESTIONS CALL THE ADVANCED HOODS SYSTEMS, LLC


1 CONTROLS TO BE TIED INTO HOOD OPERATION, COORDINATE WITH MANUFACTURER REGION 140
PHONE: 407-269-4813
EMAIL: [email protected]
REFERENCE PROJECT QDOBA DELRAY WEST

DESCRIPTION
PACKAGE UNIT
COOLING PERFORMANCE HEATING PERFORMANCE POWER
PLAN MARK BASIS OF DESIGN SERVICE MODEL NO. SUPPLY OUTDOOR E.S.P. EER/SEER TOTAL/ FITLER TYPE CONTROL TYPE SHIPPING NOTES
EAT (DEG F) LAT (DEG F) AMBIENT ELECTRIC NG INPUT NG OUPUT
AIR (CFM) AIR (CFM) (IN WC) SENSIBLE V-P-F MCA//MOP WEIGHT
DB/WB DB/WB AIR (DEG F) HEAT (KW) (CFH) (MBH)
(MBH) (LBS)
RTU-2 CAPTIVEAIR KITCHEN AHRTU1-E.102-15-7.5T 2,250 500 0.55 11.0/15.1 87.2/57.1 83.6/79.4 53.4/53.4 95 7 --- --- MERV 8 7-DAY T-STAT 208-3-60 34.3 // 40 1,300 1,2,4,5,6,7
RTU-1 CAPTIVEAIR DINING AHRTU2-E.152-18-10T 2,200 800 1 10.8/14.5 125.5/77.2 83.6/79.4 53.5/53.5 95 9 --- --- MERV 8 7-DAY T-STAT 208-3-60 66 // 80 1,915 1,2,4,5,6,7

NOTES:
1 CONTROLS TO BE TIED INTO HOOD OPERATION, COORDINATE WITH MANUFACTURER
2 PROVIDE CODE REQUIRED SMOKE DETECTOR IN ROOFTOP UNIT RETURN DUCT

DATE
3 PROVIDE WITH 14" ROOF CURB FOR INSTALLATION. FOR QUESTIONS CALL THE ADVANCED HOODS SYSTEMS, LLC
4 PROVIDE WITH ENTHALPY ECONOMIZER. REGION 140
PHONE: 407-269-4813
5 PROVIDE WITH FACTORY SUPPLIED, FIELD INSTALLED, POWERED CONVENIENCE OUTLET. EMAIL: [email protected]

#
6 PROVIDE WITH NON-FUSED DISCONNECT SWITCH. REFERENCE PROJECT QDOBA DELRAY WEST
SHEET NAME:
7 RUN CONDENSATE LINE TO NEAREST ROOF DRAIN / SCUPPER - VERIFY LOCATION. MECHANICAL
8 PROVIDE WITH DEHUMIDIFICATION COIL OPTION AND FACTORY CONTROLS. SCHEDULES
9 EXISTING EQUIPMENT TO BE SERVICED AND RETURNED TO DUTY. REFER TO SERVICE NOTES INCLUDED IN PROJECT DOCUMENTS.
10 PROVIDE WITH 14" ROOF CURB ADAPTER FOR INSTALLATION OVER EXISTING ROOF PENETRATIONS.

ISSUED FINAL:05-13-2024

12800 UNIVERSITY DR. SUITE 402


1911 S FEDERAL HWY, UNIT 206
DELRAY BEACH, FL 33483
POS ORDER COUNTER

FT. MEYERS, FL 33907


PDS ARCHITECTURE
PROJECT:

CLIENT:
SHEET NUMBER:

M-102
PROJECT NUMBER: 2403062

DRAWN BY: AJK

CHECKED BY: ALG

PRELIMINARY DOCUMENTS
800 OA 500 OA 2100 OA
(RTU-1) (RTU-2) (MUA-1)

NOTE:
4" ANGLE SHALL OVERLAP MAIN ROOF RAFTER BY 1"
MINIMUM; WELD TO FLANGE EDGE OF BEAM BELOW
ALL ROOF MOUNTED ANGEL WITH 1 /4" FILLET WELD AS SHOWN 2615 EA
FROM HD-1
HVAC EQUIPMENT (KEF-1)
2200 RA 3000 SA 1750 RA 2250 SA
CCA WOOD (DINING) (DINING) (KITCHEN) (KITCHEN)
THIS DRAWING IS PRELIMINARY
BLOCKING (3) #14 SCREWS SHALL BE USED AT EACH SIDE OF UNTIL SIGNED AND SEALED BY
THE LICENSED PROFESSIONAL
THE UNIT CURB FLANGE ATTACHING THE UNIT TO 150 EA
CAP FLASHING FROM RESTROOMS NOTED BELOW.
THE ROOF CURB ON ALL FOUR SIDES OF UNIT
(EF-1)
PROFESSIONAL SEAL
PREFABRICATED CURB
AIR BALANCE
4" CANT STRIP RTU-1 +800 OA
RTU-2 +500 OA
WOOD BLOCKING MUA-1 +2100 OA
KEF-1 -2615 EA
EF-1 -150 EA
EXISTING MEMBRANE ROOF SYSTEM PRESSURIZATION +635 CFM
INSTALL NEW 4" X 1 / 4" ANGLE BUILDING IS POSITIVE
REPAIR ROOF IRON AROUND INSIDE OF CURB
INSULATION ON TOP OF BAR-JOIST
WHERE DISTURBED WHERE UNIT CROSS' JOISTS AIR BALANCE
1 5/13/24
1/4" = 1'-0"
1" OVERLAP Dr. Al Gonzalez P.E.
1/4" FILLET WELD
DOTec Engineering
BELOW ANGLE
REMOVABLE CAP 424 Jefferson Street
St. Charles, MO 63301
TEE OPEN Ph 636-724-9872
EXISTING STEEL ROOF DECK DRAIN PAN
AT TOP TO Fx 636-724-9032
ATMOSPHERE WWW.DOTECENGINEERING.COM
SEE ARCHITECTURAL DRAWINGS [email protected]
FOR ROOF CURB DETAILS THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE
STATIC LOOP FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE
FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE
PER MFG SPEC PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE
SCH 40 PVC PIPE CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE
DRAIN PITCHED TO NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE
REVISION OR CHANGES.
GUTTER OR DRAIN Digitally signed by Ildefonso
Gonzalez
DN:
CONDENSATE DRAIN PIPING SHALL BE SCHEDULE 40 PVC PIPE WITH SOLVENT [email protected],
CN=Ildefonso Gonzalez,
JOINTS, PIPE SHALL BE THE FULL SIZE OF THE DRAIN PORT SIZE OF THE
Ildefonso Gonzalez OU=CEO/President, O=DOTec
EQUIPMENT BEING INSTALLED . Corp, L=Saint Charles,
S=Missouri, C=US
Date: 2024.05.13
CONDENSATE DRAINS SHALL BE ROUTED A MINIMUM OF 4'-0" AWAY FROM 14:59:35-05'00'

UNIT ON LOWER SLOPED SIDE OF ROOF

HVAC CURB SUPPORT DETAIL CONDENSATE DRAIN DETAIL


5 2
12" = 1'-0" 12" = 1'-0"

DESCRIPTION
ROOFTOP HVAC UNIT

ROOF

RETURN
AIR

DATE
HVAC UNIT EMERGENCY DUCT
SHUTDOWN WIRING SUPPLY AIR
DUCT

#
FIRE ALARM SHEET NAME:
ZONE WIRING
MECHANICAL DETAILS

IONIZATION SMOKE SUSPENDED CEILING ISSUED FINAL:05-13-2024


DETECTOR W/ DUAL
REMOTE ALARM CONTACTS & REMOTE
INDICATION STATION INDICATOR LIGHT
WITH LIGHT
DUCT MOUNTED SMOKE DETECTOR
DETAIL
3
12" = 1'-0"

SUPPLY/RETURN DUCT SUPPORT 1" X18GA.

12800 UNIVERSITY DR. SUITE 402


1911 S FEDERAL HWY, UNIT 206
SHEET METAL BANDING MOUNTED TO STRUCTURE
WITH (4) #8 SHEET METAL SCREWS

DELRAY BEACH, FL 33483


POS ORDER COUNTER

FT. MEYERS, FL 33907


PDS ARCHITECTURE
INSULATE SUPPLY/RETURN CEILING GRID
W/ 1-1/2" FOIL BACKED
FIBERGLASS DUCT WRAP
TAPE ALL SEAMS SOLID

PROJECT:
SUPPLY/RETURN DUCT SEE PLAN FOR SIZE

CLIENT:
DUCT SUPPORT DETAIL
4
12" = 1'-0" SHEET NUMBER:

M-103
PROJECT NUMBER: 2403062

DRAWN BY: AJK

CHECKED BY: ALG

PRELIMINARY DOCUMENTS
PLUMBING NOTES PLUMBING FIXTURE AND CONNECTION SCHEDULE
NOTE DESCRIPTION
FIXTURE WASTE (SAN) CW (DW) SIZE HW (DH) SIZE DESCRIPTION (PROVIDE CARRIERS, STOP VALVES, P-TRAPS, ADA INSULATION AS
SUPPLY PIPING TYPE TRAP SIZE (IN) VENT SIZE (IN) EQUAL TO MANUFACTURER NAME/MODEL NUMBER
TAG SIZE (IN) (IN) (IN) APPLICABLE)
1. AT THE POINTS OF INTERCONNECTION BETWEEN THE HOT AND COLD
WATER SUPPLY PIPING SYSTEMS AND THE INDIVIDUAL FIXTURES,
APPLIANCES OR DEVICES, PROVISIONS SHALL BE MADE TO PREVENT WATER HEATER(S) SHALL BE INTERNALLY MOUNTED, COMMERCIAL CONDENSING, MULTIPLE
UNDESIRED FLOW BETWEEN SUCH PIPING SYSTEMS. TANKLESS WATER POINT-OF-USE, GAS FIRED, DIRECT VENT, WATER HEATER(S) DESIGN CERTIFIED TO THE ANSI
WH-1 3/4 3/4 RINNAI CU199iN
2. LAVATORY FAUCETS SHALL BE OF THE METERING TYPE WHEN LOCATED IN HEATER Z21.10.3 STANDARD FOR GAS FIRED WATER HEATERS.
THE FOLLOWING PUBLIC RESTROOMS THIS DRAWING IS PRELIMINARY
2.1. IN ALL OCCUPANCIES IN RESTROOMS THAT HAVE SIX OR MORE UNTIL SIGNED AND SEALED BY
LAVATORIES. REDUCED PRESSURE THE LICENSED PROFESSIONAL
METERED LEAK DETECTION, EPOXY COATED STAINLESS STEEL TRIM, BRONZE BALL-TYPE TEST NOTED BELOW.
BFP-2 BACKFLOW 4 AMES / WATTS / ZURN 5000CIV / 5000CIV / 375ASTDA
2.2. INSCHOOL OCCUPANCIES IN STUDENT-USE RESTROOMS. COCKS, 175 PSI RATED
PREVENTOR PROFESSIONAL SEAL
2.3. IN ASSEMBLY OCCUPANCIES IN ALL CUSTOMER OR PUBLIC-USE
RESTRROMS FLOOR DRAIN ROUND ADJUSTABLE, CAST OR DUCTILE IRON, MEDIUM DUTY NICKEL BRONZE STRAINER, TRAP
FD-1 PER PLANS FULL SIZE JR SMITH / ZURN 2010 / Z415-SZ1
(GENERAL) PRIMER CONNECTION, NO HUB.
3. THE FIXTURE SUPPLY PIPE SHALL TERMINATE NOT MORE THAN 36 INCHES
FROM THE POINT OF CONNECTION TO THE FIXTURE. A REDUCED SIZE FLOOR DRAIN ROUND ADJUSTABLE, CAST OR DUCTILE IRON, MEDIUM DUTY NICKEL BRONZE STRAINER, TRAP
FD-1 PER PLANS FULL SIZE JR SMITH / ZURN AS REQUIRED
FLEXIBLE WATER CONNECTOR INSTALLED BETWEEN THE SUPPLY PIPE AND (COOLER) PRIMER CONNECTION, NO HUB. PROVIDE FUNNEL PER MANUFACTURER GUIDANCE
THE FIXTURE SHALL BE OF AN APPROVED TYPE. THE SUPPLY PIPE SHALL SODA
EXTEND TO THE FLOOR OR WALL ADJACENT TO THE FIXTURE. SD
DISPENSER
4. WHERE WATER PRESSURE WITHIN A BUILDING EXCEEDS 80 PSI STATIC, AN FS-1 FLOOR SINK
APPROVED WATER PRESSURE REDUCING VALVA CONFORMING TO ASSE WHITE 21"x18" SURFACEMOUNTED VITREOUS CHINA, 3-HOLE, ADA COMPLIANT.
1003 OR CSA B356 WITH STRAINER SHALL BE INSTALLED TO REDUCE THE LAV-1 LAVATORY 1-1/2 1-1/2 1-1/2 1/2 1/2 KOHLER K-2032
COORDINATE FAUCET WITH OWNER REP. MANUAL FAUCET
5/13/24
PRESSURE IN THE WATER DISTRIBUTION PIPING TO NOT GREATER THAN 80
PSI STATIC. 24X24 TERRAZON MOP BASIN W/DROP FRONT AND SS CURBS. PROVIDE FIAT MODEL 830-AA Dr. Al Gonzalez P.E.
4.1. THE PRESSURE REDUCING VALVE SHALL BE DESIGNED TO REMAIN OPEN TO
MS-1 MOP BASIN 1/2/1900 1-1/2 3/4 3/4 FIAT / TERRAZZO-WARE MSB 2424 / TDF-24 SINK FAUCET, CHROME PLATED, VACUUM BREAKERINTEGRAL STOPS, PAIL HOOK, WALL DOTec Engineering
PERMIT UNINTERRUPTED WATER FLOW IN CASE OF VALVE FAILURE. BRACE, 3/4 INCH HOSE THREAD. PROVIDE HOSE AND MOP WALL BRACKETS. 424 Jefferson Street
5. A WATER HAMMER ARRESTOR SHALL BE INSTALLED WHERE QUICK CLOSING SINK, KITCHEN, 18 GA STAINLESS STEEL, SINGLE 18 x 18 x 12 INCH BOWL SINK. INCLUDE CHICAGO FAUCETS St. Charles, MO 63301
2BS 1-1/2 1-1/2 1-1/2 1/2 1/2 STEELTON 522CS118NFW
VALVES AND METALLIC PIPING ARE USED. NOT REQUIRED WHERE PLASTIC FOOD PREP W4W-GN1AE35-317AB, 1.5 GPM FAUCET WITH 4" CENTERS AND 3-1/2" GOOSENECK SPOUT. Ph 636-724-9872
PIPE IS USED FOR WATER DISTRIBUTION PIPING. SINK, KITCHEN, 18 GA STAINLESS STEEL WALL MOUNTED SINGLE 12 x 16 x 4 INCH BOWL SINK WITH Fx 636-724-9032
SK-1 1-1/2 1-1/2 1-1/2 1/2 1/2 REGENCY 600HS12
6. PIPE AND PIPE FITTINGS, INCLUDING VALVES AND FAUCETS, UTILIZED IN HAND SINK GOOSENECK FAUCET INCLUDED. WWW.DOTECENGINEERING.COM
THE WATER SUPPLY SYSTEM SHALL HAVE NOT MORE THAN 8-PERCENT TP-1 TRAP PRIMER 1/2 ZURN ZN415-4NH-6B-P [email protected]
LEAD CONTENT. WALL HUNG, SYPHON JET, WHITE VITREOUS CHINA, 1.28 GPF WITH ELONGATED BOWL AND
THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE

6.1. PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS AND FIXTURE FITTINGS WATER CLOSET SLOAN / MANSFIELD / AMERICAN FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE
WC-1 1/4/1900 2 1 ST2459 / 1301 / Z5615-BWL OPEN SEAT. MANUAL FLUSH VALVE, ADA HEIGHT. PROVIDE CARRIER. FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE

UTILIZED TO SUPPLY WATER FOR DRINKING OR COOKING PURPOSES SHALL (ADA) STANDARD PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE
COMPLY WITH NSF 372 AND SHALL HAVE A WEIGHTED AVERAGE LEAD CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE

CONTENT OF 0.25 PERCENT OR LESS. WCO WALL CLEANOUT 1/4/1900 SIOUX CHIEF / JR SMITH 835 SERIES / 4710 ROUND WITH 873 SERIES STAINLESS STEEL CLEANOUT COVER KIT CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE
NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE
REVISION OR CHANGES.

WATER METER
7. THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, FROM THE WMT-1 2 AS DIRECTED BY OWNER
Digitally signed by Ildefonso

TESTER CONN.
Gonzalez
SOURCE OF HOT WATER TO THE FIXTURES THAT REQUIRE HOT OR DN:
[email protected],
TEMPERED WATER, SHALL NOT EXCEED 50 FEET. CN=Ildefonso Gonzalez,
PLUMBING ABBREVIATIONS Ildefonso Gonzalez
WATER DEMAND CALCULATION PLUMBING SYMBOLS OU=CEO/President, O=DOTec
8. THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND Corp, L=Saint Charles,

NONCARBONATED BEVERAGE DISPENSERS SHALL BE PROTECTED AGAINST


S=Missouri, C=US
COLD WATER Date: 2024.05.13
BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO ASSE 1022 OR QTY TOTAL TOTAL BT BATHTUB 14:59:41-05'00'
CW COLD WATER
BY AN AIR GAP. FIXTURE GPM (GPM) WSFU (WSFU) TEMPERED WATER
DW DISHWASHER
9. THE SUPPLY LINES AND FITTINGS FOR PLUMBING FIXTURES SHALL BE 2 LAVATORY 4 8 1.5 3 TEMPERED WATER RETURN ET EXPANSION TANK
FCO FLOOR CLEANOUT
INSTALLED SO AS TO PREVENT BACKFLOW. PLUMBING FIXTURE FITTINGS 2 SINK, KITCHEN, FOOD PREP 6.5 13 3 6 T TEMPERED WATER FD FLOOR DRAIN
SHALL PROVIDE BACKFLOW PROTECTION IN ACCORDANCE WITH ASME 2 SINK, KITCHEN, HAND SINK 6.5 13 3 6 HB HOSE BIBB

DESCRIPTION
A112.18.1/CSA B125.1. F FIRE LINE HW HOT WATER
1 SINK, KITCHEN 6.5 6.5 3 3 KS KITCHEN SINK
10. THE FIXTURE SUPPLY PIPE SHALL TERMINATE NOT MORE THAN 36 INCHES 2 WATER CLOSET (TANK) 9.4 18.8 5 10
SP SPRINKLER LINE LAV LAVATORY
FROM THE POINT OF CONNECTION TO THE FIXTURE. LM LAUNDRY MACHINE
1 DRINKING FOUNTAIN 1 1 0.25 0.25 SANITARY SH SHOWER
SANITARY PIPING SS SERVICE SINK
1 MOP BASIN 5.5 5.5 2.25 2.25 VENT
SS SANITARY SEWER
1. HORIZONTAL DRAINAGE PIPING SHALL BE INSTALLED IN UNIFORM
ALIGNMENT AT UNIFORM SLOPES. THE SLOPE OF A HORIZONTAL DRAINAGE NET WATER DEMANDS: 66 31 COND CONDENSATE LINE VT VENT
VTR VENT TO ROOF
PIPE SHALL BE NOT LESS THAN; WATER SERVICE MAIN DEMAND SIZE BASIS (GPM): 24 G COMPRESSED AIR WC WATER CLOSET
[PIPE SIZE (INCHES): MINIMUM SLOPE (IN/FT)] WCO WALL CLEANOUT
BALL VALVE WH WATER HEATER
2 1/2 OR LESS 1/4
3 TO 6
8 OR LARGER
1/8
1/16
HOT WATER DEMAND CALCULATION PIPING BELOW GRADE OR SLAB

QTY TOTAL TOTAL BUTTERFLY VALVE


2. THE SIZE OF THE DRAINAGE PIPING SHALL NOT BE REDUCED IN SIZE IN THE FIXTURE GPM (GPM) WSFU (WSFU) UNION
DIRECTION OF THE FLOW.
2 LAVATORY 4 8 1.5 3 GATE VALVE
3. HORIZONTAL DRAINAGE PIPES IN BUILDINGS SHALL HAVE CLEANOUTS THE CONTRACTORS ARE REQUIRED TO VISIT THE SITE AND FULLY AQUAINT
LOCATED AT INTERVALS OF NOT MORE THAN 100 FEET.
2 SINK, KITCHEN, FOOD PREP 6.5 13 3 6 THEMSELVES WITH THE EXISTING CONDITIONS AND THE DIFFICULTIES
2 SINK, KITCHEN, HAND SINK 6.5 13 3 6 INVOLVED IN ACCOMPLISHING THE NEW WORK. PROBLEMS, DISCREPANCIES

DATE
4. ONE CLEANOUT SHALL BE REQUIRED FOR EVERY FOUR HORIZONTAL OR INFORMATION NEEDED SHALL BE SUBMITTED TO THE LANDLORD
45-DEGREE CHANGES LOCATED IN SERIES. 1 SINK, KITCHEN 6.5 6.5 3 3 CONSTRUCTION MANAGER IN WRITING PRIOR TO SUBMITTING A PROPOSAL.
THE SUBMISSION OF PROPOSAL WILL INDICATE THAT THE CONTRACTOR HAS
1 MOP BASIN 5.5 5.5 2.25 2.25 FULLY UNDERSTOOD AND HAS INCLUDED ALL COSTS FOR THIS PROJECT.
NET HW DEMANDS: 46 20

#
SHEET NAME:
WATER HEATER DEMAND SIZE BASIS (GPM): 19.6
PLUMBING NOTES

SANITARY DEMAND CALCULATION


QTY FIXTURE FU TOTAL
5 FLOOR SINK 2 10
8 FLOOR DRAIN 2 16 ISSUED FINAL:05-13-2024
2 LAVATORY 1 2
2 SINK, KITCHEN, FOOD PREP 2 4
2 SINK, KITCHEN, HAND SINK 2 4
1 SINK, KITCHEN 2 2
2 WATER CLOSET (TANK) 4 8
1 DRINKING FOUNTAIN 0.5 0.5
1 MOP BASIN 2 2
NET SANITARY (FU): 48.5

12800 UNIVERSITY DR. SUITE 402


1911 S FEDERAL HWY, UNIT 206
GAS FIRED EQUIPMENT AND CONNECTION SCHEDULE

DELRAY BEACH, FL 33483


POS ORDER COUNTER

FT. MEYERS, FL 33907


GAS DEMAND, CONNECTION GAS DEMAND

PDS ARCHITECTURE
FIXTURE BASIS OF DESIGN, NAME/MODEL DESCRIPTION (PROVIDE ISOLATION VALVES, PRESSURE REGULATORS, DRIP LEGS, ETC. AS
QTY. TYPE EACH UNIT SIZE TO EACH TOTAL FOR BASIS OF DESIGN, MANUFACTURER
TAG NUMBER APPLICABLE)
(CFH) UNIT (IN) EQP. (CFH)
S36A - 6 OPEN BURNERS, CONVECTION OVEN. 35,000 BTU SPACE SAVER OVEN WITH SNAP
RG-1 1 RANGE, KITCHEN 145 3/4 145 SOUTHBEND S36A
ACTION THERMOSTAT ADJUSTABLE FOR 175°F TO 550°F
18” X 14” X 3-3/4” (45.7 X 35.6 X 9.5 CM) FRYING AREA. 119,000 BTU/HR (29,975 KCAL/HR.)

PROJECT:
FR-1 1 FRYER, KITCHEN 105 1/2 105 DEAN INDUSTRIES SR42GN

CLIENT:
(34.9 KW/HR.) INPUT PER FRYPOT MEETS HIGH PRODUCTION DEMANDS OF A VARIED MENU
18” X 14” X 3-3/4” (45.7 X 35.6 X 9.5 CM) FRYING AREA. 119,000 BTU/HR (29,975 KCAL/HR.)
CB-1 1 CHARBROILER 160 1/2 160 MONTAGUE/LEGEND UFLC-48R SHEET NUMBER:
(34.9 KW/HR.) INPUT PER FRYPOT MEETS HIGH PRODUCTION DEMANDS OF A VARIED MENU
WATER HEATER(S) SHALL BE INTERNALLY MOUNTED, COMMERCIAL CONDENSING, MULTIPLE
WH-1 2
TANKLESS WATER
200 3/4 400 RINNAI CU199iN POINT-OF-USE, GAS FIRED, DIRECT VENT, WATER HEATER(S) DESIGN CERTIFIED TO THE ANSI
P-100
HEATER
Z21.10.3 STANDARD FOR GAS FIRED WATER HEATERS. PROJECT NUMBER: 2403062

NET GAS DEMAND: 810 CFH @2 PSI VIA 1 1/2" GAS LINE TO/FROM METER DRAWN BY: ALM

CHECKED BY: ALG

PRELIMINARY DOCUMENTS
KEYED NOTES
2 1" CW FROM CITY SERVICE
3 SEE DETAIL FOR WATER HEATER CONNECTION
6 4 PROVIDE TRAP PRIMER AS REQUIRED
5 CW LINE BELOW GRADE TO METER AND BACKFLOW PREVENTER.
6 1/2" CW DOWN TO SODA DISPENSER AND TEA MAKER WITH SHUTOFF
1/2"ø CW VALVE FOR EACH PIECE OF EQUIPMENT. PROVIDE IN-LINE THIS DRAWING IS PRELIMINARY

1"ø CW
BACKFLOW PREVENTER OR VACUUM BREAKER UPSTREAM FROM UNTIL SIGNED AND SEALED BY
WC-1 THE LICENSED PROFESSIONAL
SHUTOFFS.
SD NOTED BELOW.
LAV-1
PROFESSIONAL SEAL

GENERAL NOTES

3/4"ø CW
1. PIPING RUNOUTS TO PLUMBING FIXTURES SHALL BE THE SAME SIZE AS
SCHEDULES CONNECTION SIZE UNLESS NOTES OTHERWISE.
LAV-1 WC-1 2. ALL FIXTURES TO HAVE SHUTOFF VALVES.
FS-1

3/4"ø HW

1"ø CW
2 5

5/13/24

1"ø CW
1/2"ø CW

3/4"ø HW
1"ø CW
1/2"ø HW Dr. Al Gonzalez P.E.
DOTec Engineering
424 Jefferson Street

3/4"ø HW
SK-1 St. Charles, MO 63301
SK-1 Ph 636-724-9872
Fx 636-724-9032
WWW.DOTECENGINEERING.COM
[email protected]

1"ø CW
THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE
FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE
FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE
PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE
CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE
NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE
REVISION OR CHANGES.

3/4"ø HW
4 Digitally signed by Ildefonso
Gonzalez
2BS DN:
[email protected],
CN=Ildefonso Gonzalez,
4 4 Ildefonso Gonzalez
FS-1 OU=CEO/President, O=DOTec
Corp, L=Saint Charles,
FS-1 S=Missouri, C=US
Date: 2024.05.13

3/4"ø HW
14:59:47-05'00'
FS-1 FS-1
3/4"ø HW 3

2BS
1"ø CW
MS-1 WH-1

DESCRIPTION
WH-1
3/4"ø HW

DOMESTIC WATER PLAN CW



1 3/4
1/4" = 1'-0"

1"ø
CW 3/4 CW

HW 1"ø

DATE
CW

1/2

3/4"ø CW
1"ø
W CW
1" øC 1"ø

#
CW
SHEET NAME:

1/2"ø HW
WC-1 W
WH-1 PLUMBING PLAN -
CW "øH 1"ø DOMESTIC WATER
"ø 1/2 CW 1/2"
1/2 øH WH-1
W HW

1/2"ø CW
LAV-1 3/4
HW
/2"
ø CW
1 1"ø

1/2"ø CW

1/2"ø CW
HW

1/2"ø HW
SK-1 "ø ISSUED FINAL:05-13-2024
1/2"ø CW

3/4

1/2"ø HW
3/4"ø HW
WC-1 SK-1
LAV-1 MS-1
2BS

SD 2BS

12800 UNIVERSITY DR. SUITE 402


1911 S FEDERAL HWY, UNIT 206
DELRAY BEACH, FL 33483
POS ORDER COUNTER

FT. MEYERS, FL 33907


PDS ARCHITECTURE
DOMESTIC WATER ISOMETRIC
2
NOT TO SCALE

PROJECT:

CLIENT:
SHEET NUMBER:

P-101
PROJECT NUMBER: 2403062

DRAWN BY: ALM

CHECKED BY: ALG

PRELIMINARY DOCUMENTS
KEYED NOTES
1 4" GW TO EXISTING GREASE TRAP

6-TIER 24X48
2 4" S TO CITY SERVICE

6-TIER 24X48
GENERAL NOTES

6-TIER 24X42
THIS DRAWING IS PRELIMINARY
WC-1
1. PIPING RUNOUTS TO PLUMBING FIXTURES SHALL BE THE SAME SIZE AS UNTIL SIGNED AND SEALED BY
FS-1
SD SCHEDULES CONNECTION SIZE UNLESS NOTES OTHERWISE. THE LICENSED PROFESSIONAL
2" VTR NOTED BELOW.

6-TIER 24X54
LAV-1
PROFESSIONAL SEAL
FD-1
FD-2
2"ø V
FD-1

6-TIER 24X48
6-TIER 24X60
WC-1 2BS
LAV-1 FS-1

1 1/2"ø V FD-1
5/13/24

3"ø S
FD-1
4"ø S
Dr. Al Gonzalez P.E.
4"ø S DOTec Engineering
4"ø S 424 Jefferson Street
SK-1
St. Charles, MO 63301
Ph 636-724-9872
1 SK-1 Fx 636-724-9032

24X42
4"ø GW
4"ø GW 4"ø GW WWW.DOTECENGINEERING.COM
[email protected]
THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE
2"ø GW FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE

1 1/4"ø V
2"ø GW 2"ø GW FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE
2"ø GW FD-1
PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
2 CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE
CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE
NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE
FD-1 REVISION OR CHANGES.
FD-1
Digitally signed by Ildefonso
Gonzalez

4"ø GW

2"ø V
DN:
[email protected],
2BS CN=Ildefonso Gonzalez,
4"ø S Ildefonso Gonzalez
FS-1 OU=CEO/President, O=DOTec

1 1/2"ø V
Corp, L=Saint Charles,
FS-1 S=Missouri, C=US
Date: 2024.05.13
4"ø GW 4"ø GW

2"ø GW
14:59:53-05'00'

FS-1 FS-1 2BS


WH-1

2 1/2"ø V
3"ø GW 2"ø GW

DESCRIPTION
2"ø V 2"ø V

4"ø GW

2"ø V
WH-1
FD-1 MS-1
2 1/2"ø V 2 1/2"ø V

2"ø V
2"ø V
2 1/2"ø V WCO 2-1/2'' VTR

V
2"ø

SANITARY SEWER PLAN 2"ø


1 V
1/4" = 1'-0"

øV
/2"
11
WC-1

DATE
FD-2

2"ø V

2"ø V
1 1/2"ø V

2"ø V
11

1 1/4"ø V
1 1/2"ø V
2"ø
2BS /4" V
øV

#
WH-1
SHEET NAME:
FD-1
øS

1 1/2"ø V
2" 2"ø PLUMBING PLAN -
FS-1 V
LAV-1 SK-1 SANITARY SEWER
SK-1 V WH-1
FD-1 21
FD-1 /2" "ø
1/2

1 1/4"ø V

2"ø V
øV
øV

1 1/2"ø V
2
FD-1 /2" 11

1 1/2"ø V
11

2"ø V
/2"
øV FD-1
3"ø 2"ø GW 2BS

1 1/2"ø V
S V
/2 "ø
21 ISSUED FINAL:05-13-2024
LAV-1 2"ø 2BS
WC-1 GW 4"ø GW

2"ø V
1 1/2"ø GW
SD 2"ø
4" øS 2"ø GW
S 3"ø 4"ø GW FD-1
4"ø W MS-1
S GW øG

2"ø GW
2"ø W 2"
11 S 11 4" øG 2"ø GW
FS-1 /2" /2"
øS øG
W FD-1 FS-1
S 4"ø GW 4"ø GW
4"ø 2"ø S

4"ø GW
FS-1 GW

2"ø V
FD-1 3"ø GW
4"ø 3"ø
FS-1 GW 4"ø WCO
4"ø V
S øS "ø GW
1/4 3"ø GW

12800 UNIVERSITY DR. SUITE 402


4" 11
1 /2"

1911 S FEDERAL HWY, UNIT 206


2"ø GW ø V

4"ø GW
4"ø 1 1/4"ø V
GW
GW

DELRAY BEACH, FL 33483


4"ø W 4"ø V
øG 2"ø

POS ORDER COUNTER


S 4"

FT. MEYERS, FL 33907


PDS ARCHITECTURE
4"ø GW
V
2"ø

4" GW TO EXISTING
GREASE TRAP
S
4"ø

PROJECT:

CLIENT:
GW
4"ø SHEET NUMBER:

SANITARY SEWER ISOMETRIC


2
NOT TO SCALE P-102
4" S TO CITY SERVICE
PROJECT NUMBER: 2403062

DRAWN BY: ALM

CHECKED BY: ALG

PRELIMINARY DOCUMENTS
KEYED NOTES
1 1 1/2'' NATURAL GAS LINE COMING IN FROM GAS METER
2 GAS PIPING FOR HOOD SHALL HAVE ACCESSIBLE MANUAL VALVE
AND EMERGENCY SHUT-OFF VALVE. ALL GAS PIPING FOR HOOD AND
UNDER HOOD SHALL BE EXPOSED

6-TIER 24X48
3 PROVIDE 3/4" GAS TAP WITH SHUTOFF VALVE FOR FUTURE USE.
THIS DRAWING IS PRELIMINARY
UNTIL SIGNED AND SEALED BY
GENERAL NOTES THE LICENSED PROFESSIONAL

6-TIER 24X48
NOTED BELOW.
1. PIPING RUNOUTS TO PLUMBING FIXTURES SHALL BE THE SAME SIZE AS

6-TIER 24X42
PROFESSIONAL SEAL
SCHEDULES CONNECTION SIZE UNLESS NOTES OTHERWISE.

6-TIER 24X54
6-TIER 24X48
6-TIER 24X60
5/13/24
Dr. Al Gonzalez P.E.
DOTec Engineering
424 Jefferson Street
St. Charles, MO 63301
Ph 636-724-9872
1 1/2'' GAS LINE
FROM GAS METER
Fx 636-724-9032
WWW.DOTECENGINEERING.COM
[email protected]
THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE
FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE

24X42
FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE
PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR
2"ø G 1 CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE
CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE
NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE
REVISION OR CHANGES.
2"ø G
Digitally signed by Ildefonso
Gonzalez
DN:
[email protected],
CN=Ildefonso Gonzalez,
Ildefonso Gonzalez OU=CEO/President, O=DOTec
3 Corp, L=Saint Charles,
S=Missouri, C=US

2"ø G
Date: 2024.05.13
14:59:59-05'00'

2"ø G
WH-1

DESCRIPTION
2 1 1/2"ø G

1"ø G
RG-1

WH-1 1 1/2"ø G

3/4"ø G
3/4"ø G 1"ø G
FR-1
WH-1 WH-1

1"ø G

GAS PLAN 3/4"ø G


1
1/4" = 1'-0" 3/4" G TAP WITH

DATE
SHUTOFF VALVE
FOR FUTURE USE 3/4"ø G

#
3/4
"ø SHEET NAME:

1 1/2"ø G
G
PLUMBING PLAN - GAS
3/4
"ø ACCESSIBLE
G
MANUAL AND
EMERGENCY
SHUTOFF VALVE

3/4"ø G
ISSUED FINAL:05-13-2024
CB-1

3/4"ø G
RG-1

FR-1

12800 UNIVERSITY DR. SUITE 402


1911 S FEDERAL HWY, UNIT 206
DELRAY BEACH, FL 33483
POS ORDER COUNTER

FT. MEYERS, FL 33907


PDS ARCHITECTURE
PROJECT:

CLIENT:
GAS ISOMETRIC
2
NOT TO SCALE
SHEET NUMBER:

P-103
PROJECT NUMBER: 2403062

DRAWN BY: ALM

CHECKED BY: ALG

PRELIMINARY DOCUMENTS
TURN-DOWN LEAD FLASHING
SEALANT BEAD
CONNECT TO VENT THROUGH ROOF INTO TOP OF VENT PIPE
STAINLESS STEEL PIPE CLAMP
CEILNG CLEAN
MOLDED PIPE BOOT FURNISHED SHEET LEAD FLASHING BOOT OUT
BY ROOFING CONTR. MIN. 4 LB./S.F. AND 24'' SQ. FLOOR

THIS DRAWING IS PRELIMINARY


12'' BUILT-UP ROOFING UNTIL SIGNED AND SEALED BY
MEMBRANE ROOFING
THE LICENSED PROFESSIONAL
NOTED BELOW.
2" VENT UP IN WALL
PROFESSIONAL SEAL

PLUG

ROOF CONSTRUCTION CUT OPENING OR SLEEVE


ROOF CONSTRUCTION 5/13/24
FCO DETAIL
1
NOT TO SCALE Dr. Al Gonzalez P.E.
DOTec Engineering
VENT STACK 424 Jefferson Street
INCREASER IF REQ'D. St. Charles, MO 63301
Ph 636-724-9872
FLOOR Fx 636-724-9032
DRAIN WWW.DOTECENGINEERING.COM
2" 2" 2" STRAINER [email protected]
2" DRAIN PIPING & FITTINGS 2" LEVER ACTION DRAINS
THE PROFESSIONAL ENGINEER WAIVES ANY AND ALL
FURNISHED & INSTALLED BY INSTALLED BY PLUMBING CTR.
FINISHED
RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE

PLUMBER CTR. (TYP.) CERAMIC TILE AND SETTING FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND
DESIGN INTENT THEY CONVEY, OR FOR PROBLEMS WHICH ARISE

CAST SPLIT RINGS ON REAR LEGS ROOF VENT DETAIL FLOOR BED
FROM OTHER'S FAILURE TO OBTAIN AND OR/ FOLLOW THE

4
PROFESSIONAL ENGINEER GUIDANCE WITH RESPECT TO ANY
ANCHORED TO WALL (TYP. 2) SURFACE ERRORS, OMISSIONS, INCONSISTENCIES, AMBIGUITIES, OR

BY PLUMBING CONTRACTOR.
NOT TO SCALE SLOPE TO DRAIN CONFLICTS WHICH ARE ALLEGED. BUILDINGS TO BE
CONSTRUCTED IN FULL CONFORMANCE WITH ALL APPLICABLE
CODES AND RESTRICTIONS. PROFESSIONAL ENGINEER TO BE

FLOOR WATERPROOF NOTIFIED PRIOR TO CONSTRUCTION IN THE EVENT OF CODE


REVISION OR CHANGES.

2" MEMBRANE Digitally signed by Ildefonso


Gonzalez
FS-1 DN:
FLOOR SINK WITH SEDIMENT BUCKET AND 1/2 GRATE SEE [email protected],
CN=Ildefonso Gonzalez,
FLOOR PLANS FOR LOCATION. SEE FIXTURE SCHEDULE 6" Ildefonso Gonzalez OU=CEO/President, O=DOTec
Corp, L=Saint Charles,
3" 'P' TRAP S=Missouri, C=US
3" May extend as a Date: 2024.05.13

waste or vent CONCRETE 15:00:06-05'00'

FLOOR SLAB
MULTI-BASIN WASTE DETAIL Chrome Wallcover
Wall CLAMP
7 and Screw INTO DRAIN COLLAR
NOT TO SCALE
Plugged Tee With

DESCRIPTION
Cleanout
DRAIN BODY POURED
LEAD AND OAKUM IN PLACE
OR NEOPRENE GASKET

1'-0"
Floor Line

FLOOR DRAIN IN OPEN AREA


FLOOR DRAIN DETAIL
Balance of Piping 2
NOT TO SCALE
1/8 C.I. Bend Same as Cleanout
to grade

BUILDING
ROOF
Wall Cleanout Diagram (WCO)
WALL CLEANOUT DETAIL
5
NOT TO SCALE SAW-CUT AND REMOVE EXISTING

DATE
CEILING CONCRETE FLOOR SLAB AND
PATCH TO MATCH EXISTING
REPLACE ANY EXISTING VAPOR
MINIMUM 3/8" IRON DOWELS 4" EMBEDMENT OR DRAINAGE BARRIERS AND

#
WITH EPOXY CEMENT ANCHOR AND 10" SEAL TO EXISTING BARRIER SHEET NAME:

WATER HEATERS TO BE MOUNTED PROJECTION AT 12" ON CENTER PLUMBING PLUMBING


ON EXTERIOR WALL. PROTECT DETAILS
EQUIPMENT AND COMBUSTION
FLUE/VENT FROM WEATHER FINAL BACKFILL SHALL BE
ENTRAINMENT. SUITABLE MATERIAL EXCAVATED
FROM THE TRENCH OR PIT-RUN
MIN. 6'' GRANULAR FILL, 1-1/2''Ø SAND AND GRAVEL
Finish Grade
16" Conc. Pad Brass Cleanout Plug TO NO. 200 SIEVE IN SIZE
Trowel Smooth & Edge W/Counter Sunk Head ISSUED FINAL:05-13-2024

INITIAL BACKFILL SHALL BE NATURAL


WH-1 WH-1
4'' SAND WHICH PASSES THRU A 3/8''
SIEVE AND CONTAINS NO SILT, CLAY
OR OTHER ORGANIC MATERIAL
1" CW

Long Radius Long Radius


C.I. Bend C.I. Bend TYPICAL UNDERGROUND
BEDDING MATERIAL SHALL BE
3/4" GAS

3/4" GAS

PIPING IN TRENCH
1/2" SAN

1/2" SAN
3/4" HW

3/4" HW
3/4" CW

3/4" CW

C.I. Waste Line C.I. Waste Line CRUSHED STONE, 1/2''Ø TO NO. 200
THE SUB-GRADE SHALL BE UNDISTURBED SIEVE IN SIZE
EARTH OF SUITABLE MATERIAL TO

12800 UNIVERSITY DR. SUITE 402


Waste Line Waste Line

1911 S FEDERAL HWY, UNIT 206


SUPPORT GENERAL CONSTRUCTION OR WIDTH OF TRENCH AT TOP OF PIPE
1" CW 3/4" CW SHALL BE COMPACTED THUS OR SHALL BE SHALL BE 4 X DIAMETER PLUS 8'' AND
REMOVED AND REPLACED WITH BEDDING WIDTH AT TOP OF TRENCH SHALL BE

DELRAY BEACH, FL 33483


3/4" HW
3/4" HW Two-Way Cleanout MATERIAL CONTRACTOR'S RESPONSIBILITY

POS ORDER COUNTER

FT. MEYERS, FL 33907


To Grade Diagram (GCO)

PDS ARCHITECTURE
1/2" SAN
NOTE:
FINISHED 1. LOCAL AND STATE AUTHORITIES HAVING JURISDICTION SHALL APPROVE THIS OR
3/4" HW

FLOOR EQUIPMENT DISCHARGE TO GRADE. TWO-WAY CLEANOUT DETAIL OTHER INSTALLATION.


TERMINATE DRIP AND RELIEF LEGS NO 6
NOT TO SCALE
LESS THAN 8" ABOVE GRADE. TERMINATE
LEGS WITH MALE CONNECTION FOR 3/4"
HOSE FOR SERVICE.

PROJECT:

CLIENT:
WATER HEATER - INSTANTANEOUS PIPE TRENCH DETAIL
8 3
NOT TO SCALE NOT TO SCALE SHEET NUMBER:

P-105
PROJECT NUMBER: 2403062

DRAWN BY: ALM

CHECKED BY: ALG

PRELIMINARY DOCUMENTS