WALL MOUNT HORN/STROBES FHS-340 SERIES
Features
• UL and C-UL listed
• 12 VDC with 15, 35 or 60 cd settings
• 24 VDC with 15, 35, 60, 75, 95 or 110 cd settings
• 6 distinct candela settings
• Candela selection view window
• 15/75 ADA compliant on 60cd setting
• 33 sound output settings
• Horn or chime sound output
• Pre-wire back plate
• Universal back plate mounting (single gang, double
gang, octagon, or 4” square)
• Single screw mounting
• For indoor applications
Description Engineering Specifications
The FHS-340 Horn/Strobe Series provides a wide The installer shall provide and install the FHS-340
range of candela light output options in a single selectable horn/strobe. The strobe shall have six
device. The candela settings include a 12 or 24 (6) candela settings. The candela settings shall be
volt DC operation for the 15, 35 and 60 (75 on selectable using a drum roller and shall display the
axis) candela settings and 24 volt DC operation for candela setting on the front of the device. The
the 15, 35, 60, 75, 95 and 110 candela settings. horn shall have 33 selectable settings configurable
The candela setting is displayed through the front by dip switches. The sounder shall be capable of
window and is selectable using a drum wheel. ANSI Temporal Code 3, March Time and produce
The horn settings include Temporal, Non- a chime output. The horn shall have three distinct
Temporal, March Time and a Chime sound. The volume levels. The horn/strobe shall operate at 12
horn also has Low, Mid and High volume settings or 24 VDC regulated or full wave rectified. The
for each pattern and tone. The tones include 2400 horn/strobe shall have an operating range between
Hz, Electro-Mechanical, Broadband and Chime. 8 and 33 VDC. The strobes can be synchronized
using a control panel with the Mircom sync
The voltage input can be either regulated DC or full protocol or the SDM-240 sync module. The strobe
wave rectified (FWR) 12 volt or 24 volt operation shall utilize a mounting plate that allows the
with an operating range from 8 to 33 V DC. The installer to pre-wire the mounting plate. The
strobes can be synchronized using a control panel mounting plate shall be universal and mount on a
with the Mircom (Amseco) sync protocol or an single gang, double gang, octagon or 4 inch
SDM-240 sync module. square box. The mounting plate shall be
The FHS-340 utilizes a universal mounting plate completely covered by the strobe and shall be
that will mount on a single gang, double gang, secured by a single screw. The strobe shall be UL
octagon and 4” square electrical boxes. The back listed to standard 1638, General Signaling, and
plate allows the installer to mount the plate and standard 1971, Signaling Devices for the Hearing
connect the wire connections. The strobe attaches Impaired. In addition, the strobes shall be C-UL
in a hinge fashion from the top and is secured by a listed to CAN-ULC S526. The horn shall be UL
single mounting screw. The strobe completely listed to standard 464, Audible Signaling Devices.
covers the mounting back plate, therefore it can be
mounted before other trades work is completed
and not affect the final look.
S5375
CATALOG NUMBER 5269
NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to
discontinue models.
Installation
Dimensions Light Output
Inches (mm) Light output in precentage when measured from the following directions per UL 1971.
Strobe Current Horn Dipswitch
ON
Light Max. RMS Operating Current (mA RMS) Pattern
Output 1 ON - Non-
Reg. 12 Reg. 12 Reg. 24 Reg. 24
VDC FWR VDC FWR 1 OFF - Temporal 1 2 3 4 5 6 7 8
15cd 116 152 62 99 Both 2 = OFF
35cd 209 267 102 152 1 and 2 ON = March Time
60/75cd 254 258 131 190 Tone
75cd NA NA 146 208 3 and 4 ON = 2400Hz
95cd NA NA 177 243
110cd NA NA 196 268
3 ON and 4 OFF = Electromechanical
3 and 4 OFF = Chime
3 OFF Voltage 12/24V and 4 ON = Broadband
UL Designation Regulated 12 DC/FWR Regulated 24 DC/FWR
Volume
Operating Voltage
8 - 17.5V 16 - 33V 5 and 6 ON = High
Range
5 ON and 6 OFF = Mid
Flash Rate 60 times/min.
5 and 6 OFF = Low
Sync Module (SDM-240) N/A Available
7 and 8 ON = Horn/strobe on 2 wires
Operating Temperature
Indoor model: 32°F to 120°F (0°C to 49°C) 7 and 8 OFF = Horn and strobe on 4 wires
Range
CAT. 5269
NOT TO BE USED FOR INSTALLATION PURPOSES. page 2 of 4
Specifications
Non-Temporal Horn Current
dBA Anechoic
dBA Reverberant
Max. RMS Operating Current Ratings per
Ratings per UL464
(mA RMS Current) CAN/ULC S525
Pattern Volume (dBA @ 10 ft.)
(dBA @ 10 ft.)
Reg 12 Reg 12 Reg 24 Reg 24 Reg 12 Reg 24 Reg 12 Reg 24
VDC FWR VDC FWR VDC/FWR VDC/FWR VDC/FWR VDC/FWR
High 119 161 87 179 87 87 99 100
2400 Hz Mid 44 76 28 96 82 82 94 96
Low 30 51 18 71 79 80 92 92
High 118 149 81 176 86 87 100 100
Electro-Mechanical Mid 43 72 26 102 82 84 96 97
Low 27 44 16 66 79 80 93 93
High 146 152 78 183 86 86 101 102
Broadband Mid 41 68 26 91 81 82 96 98
Low 28 45 16 72 77 79 94 95
High 27 30 21 40 70 70 86 86
Chime Mid 11 13 8 13 62 62 79 80
Low 9 8 7 9 58 57 75 75
Temporal Horn Current
dBA Anechoic
dBA Reverberant
Max. RMS Operating Current Ratings per
Ratings per UL464
(mA RMS Current) CAN/ULC S525
Pattern Volume (dBA @ 10 ft.)
(dBA @ 10 ft.)
Reg 12 Reg 12 Reg 24 Reg 24 Reg 12 Reg 24 Reg 12 Reg 24
VDC FWR VDC FWR VDC/FWR VDC/FWR VDC/FWR VDC/FWR
High 124 158 87 196 82 82 100 100
2400 Hz Mid 46 69 30 91 77 79 95 96
Low 30 48 18 60 74 75 92 92
High 114 154 80 194 83 82 100 101
Electro-Mechanical Mid 42 64 27 89 78 80 95 96
Low 28 45 16 62 75 76 93 93
Broadband High 151 149 80 197 82 82 101 102
Mid 45 65 26 86 77 78 97 98
Low 30 47 16 58 75 76 94 95
High 29 30 21 35 68 70 86 86
Chime Mid 10 12 9 14 61 61 79 79
Low 9 9 8 10 55 55 75 76
March Time Horn Current
dBA Anechoic
dBA Reverberant
Ratings per
Max. RMS Current (mA RMS Current) Ratings per UL464
CAN/ULC S525
Pattern Volume (dBA @ 10 ft.)
(dBA @ 10 ft.)
Reg 12 Reg 12 Reg 24 Reg 24 Reg 12 Reg 24 Reg 12 Reg 24
VDC FWR VDC FWR VDC/FWR VDC/FWR VDC/FWR VDC/FWR
High 121 151 92 190 83 84 99 100
2400 Hz Mid 47 67 31 80 79 81 95 96
Low 36 50 19 65 76 77 92 92
High 114 147 86 183 83 83 100 100
Electro-Mechanical Mid 42 62 27 72 80 81 95 96
Low 30 51 19 62 77 77 92 93
High 153 125 77 185 83 84 101 102
Broadband Mid 42 73 28 90 79 80 97 98
Low 29 50 16 58 76 77 94 95
NOT TO BE USED FOR INSTALLATION PURPOSES.
CAT. 5269 page 3 of 4
Wiring Diagram
Ordering Information
Model Number Description
FHS-340R Wall Mount Horn/Strobe, Red
FHS-340W Wall Mount Horn/Strobe, White
Canada Fax Toll Free: (888) 660-4113
25 Interchange Way
Vaughan, Ontario L4K 5W3 Distributed by: CAT. 5269
Telephone: (905) 660-4655 Fax: Rev. 0
(905) 660-4113
U.S.A.
Web page: http://www.mircom.com Email:
NOT TO BE USED FOR INSTALLATION PURPOSES.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: (888) 660-4655