Easergy MiCOM P445
Fast Multifunction Distance Protection Relay
P445/EN PC/E62
Software Version J6
Hardware Suffix L
IEC61850 Edition 2
Issue Date 01/2017
Protocol Implementation Conformance Statement (PICS)
Note The technical manual for this device gives instructions for its installation, commissioning, and
operation. However, the manual cannot cover all conceivable circumstances or include detailed
information on all topics. In the event of questions or specific problems, do not take any action
without proper authorization. Contact the appropriate Schneider Electric technical sales office
and request the necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of
Schneider Electric including settlements of warranties, result solely from the applicable
purchase contract, which is not affected by the contents of the technical manual.
This device MUST NOT be modified. If any modification is made without the express permission
of Schneider Electric, it will invalidate the warranty, and may render the product unsafe.
Easergy MiCOM and the Schneider Electric logo and any alternative version thereof are trademarks and
service marks of Schneider Electric.
All trade names or trademarks mentioned herein whether registered or not, are the property of their owners.
This manual is provided for informational use only and is subject to change without notice.
© 2017, Schneider Electric. All rights reserved.
MiCOM P445 Protocol Implementation Conformance
Statement (PICS)
PROTOCOL IMPLEMENTATION
CONFORMANCE STATEMENT
(PICS)
P445/EN PC/E62 – IEC61850 Edition 2 Page-1
Protocol Implementation Conformance MiCOM P445
Statement (PICS)
Date (month/year): 01/2017
Products covered by this This chapter covers the specific versions of the MiCOM products listed below. This includes
chapter: only the following combinations of Software Version and Hardware Suffix.
Hardware suffix: L
Software version: J6
Connection diagrams: This includes a list of the Connection Diagrams for the Products covered by this document.
10P445xx (xx = 01 to 04)
Page-2 P445/EN PC/E62 – IEC61850 Edition 2
Contents Protocol Implementation Conformance
Statement (PICS)
CONTENTS
Page-
1 Introduction 5
2 ACSI Basic Conformance Statement 6
3 ACSI Models Conformance Statement 7
4 ACSI Service Conformance Statement 9
TABLES
Page-
Table 1 - Basic Conformance Statement 6
Table 2 - ACSI Models Conformance Statement 8
Table 3 - ACSI Service Conformance Statement 11
P445/EN PC/E62 – IEC61850 Edition 2 Page-3
Protocol Implementation Conformance Tables
Statement (PICS)
Notes:
Page-4 P445/EN PC/E62 – IEC61850 Edition 2
Introduction Protocol Implementation Conformance
Statement (PICS)
1 INTRODUCTION
This specification is the Protocol Implementation Conformance Statement (PICS) and
shows the Abstract Communication Service Interface (ACSI) conformance statements as
defined in Annex A of Part 7-2 of the IEC 61850 standard specifications. The following
ACSI conformance statements used to provide an overview and details about MiCOM
P445 with firmware J4.
ASCI basic conformance statement
ACSI models conformance statement
ACSI service conformance statement
The statements specify the communication features mapped to IEC 61850-8-1.
P445/EN PC/E62 – IEC61850 Edition 2 Page-5
Protocol Implementation Conformance ACSI Basic Conformance Statement
Statement (PICS)
2 ACSI BASIC CONFORMANCE STATEMENT
The basic conformance statement is defined in Table 1.
Server
Client /Subscriber Value /Comments
/Publisher
Client-Server roles
Server side (of Two-Party- Application-
B11 Y
Association)
Client side of (Two-Party- Application-
B12
Association)
SCSMs supported
B21 SCSM: IEC 61850-8-1 used Y
B22 SCSM: IEC 61850-9-1 used
B23 SCSM: IEC 61850-9-2 used
B24 SCSM: other
Generic Substation Event model (GSE)
B31 Publisher side Y
B32 Subscriber side Y
Transmission of Sampled Value Model (SVC)
B41 Publisher side
B42 Subscriber side
–
Y = Yes (supported)
N or empty = No (not supported)
Table 1 - Basic Conformance Statement
Page-6 P445/EN PC/E62 – IEC61850 Edition 2
ACSI Models Conformance Statement Protocol Implementation Conformance
Statement (PICS)
3 ACSI MODELS CONFORMANCE STATEMENT
The ACSI models conformance statement is defined in Table 2.
Client/ Server/
Value/ Comments
Subscriber Publisher
If Server or Client side (B11/12) supported
M1 Logical device Y
M2 Logical node Y
M3 Data Y
M4 Data set Y
M5 Substitution
M6 Setting group control Y
Reporting
M7 Buffered report control Y
M7-1 sequence-number Y
M7-2 report-time-stamp Y
M7-3 reason-for-inclusion Y
M7-4 data-set-name Y
M7-5 data-reference Y
M7-6 buffer-overflow Y
M7-7 entryID Y
M7-8 BufTim Y
M7-9 IntgPd Y
M7-10 GI Y
M7-11 conf-revision Y
M8 Unbuffered report control Y
M8-1 sequence-number Y
M8-2 report-time-stamp Y
M8-3 reason-for-inclusion Y
M8-4 data-set-name Y
M8-5 data-reference Y
M8-6 BufTim Y
M8-7 IntgPd Y
M8-8 GI Y
M8-9 conf-revision Y
Logging
M9 Log control
M9-1 IntgPd
M10 Log
Control
M11 Control Y
If GSE (B31/32) is supported
M12 GOOSE Y Y
M13 GSSE
If SVC (41/42) is supported
M14 Multicast SVC
P445/EN PC/E62 – IEC61850 Edition 2 Page-7
Protocol Implementation Conformance ACSI Models Conformance Statement
Statement (PICS)
Client/ Server/
Value/ Comments
Subscriber Publisher
M15 Unicast SVC
If Server or Client side (B11/12) supported
Time source with required accuracy
M16 Time Y Y
shall be available.
M17 File Transfer Y
M18 Application association Y
M19 GOOSE Control Block Y Y
M20 Sampled Value Control Block
Y = service is supported
N or empty = service is not supported
Table 2 - ACSI Models Conformance Statement
Page-8 P445/EN PC/E62 – IEC61850 Edition 2
ACSI Service Conformance Statement Protocol Implementation Conformance
Statement (PICS)
4 ACSI SERVICE CONFORMANCE STATEMENT
The ACSI service conformance statement is defined in Table 3 (depending on the statements in Table 1).
Services AA:TP/MC Client (C) Server (S) Comments
Server
S1 GetServerDirectory TP Y
Application association
S2 Associate Y
S3 Abort Y
S4 Release Y
Logical device
S5 GetLogicalDeviceDirectory TP Y
Logical node
S6 GetLogicalNodeDirectory TP Y
S7 GetAllDataValues TP Y
Data
S8 GetDataValues TP Y
S9 SetDataValues TP Y
S10 GetDataDirectory TP Y
S11 GetDataDefinition TP Y
Data set
S12 GetDataSetValues TP Y
S13 SetDataSetValues TP
S14 CreateDataSet TP
S15 DeleteDataSet TP
S16 GetDataSetDirectory TP Y
Substitution
S17 SetDataValues TP
Setting group control
S18 SelectActiveSG TP Y
S19 SelectEditSG TP
S20 SetSGValues TP
S21 ConfirmEditSGValues TP
S22 GetSGValues TP
S23 GetSGCBValues TP Y
Reporting
Buffered Report Control Block (BRCB)
S24 Report TP Y
S24-1 data-change (dchg) Y
S24-2 quality-change (qchg) Y
S24-3 data-update (dupd)
S25 GetBRCBValues TP Y
S26 SetBRCBValues TP Y
Unbuffered Report Control Block (URCB)
S27 Report TP Y
S27-1 data-change (dchg) Y
P445/EN PC/E62 – IEC61850 Edition 2 Page-9
Protocol Implementation Conformance ACSI Service Conformance Statement
Statement (PICS)
Services AA:TP/MC Client (C) Server (S) Comments
S27-2 quality-change (qchg) Y
S27-3 data-update (dupd)
S28 GetURCBValues TP Y
S29 SetURCBValues TP Y
Logging
Log Control Block
S30 GetLCBValues TP
S31 SetLCBValues TP
Log
S32 QueryLogByTime TP
S33 QueryLogByEntry TP
S34 GetLogStatusValues TP
Generic substation event model (GSE)
GOOSE-CONTROL-BLOCK
IED supports GOOSE
S35 SendGOOSEMessage MC Y
Publisher and Subscriber.
S36 GetGoReference TP
S37 GetGOOSEElementNumber TP
S38 GetGoCBValues TP Y
S39 SetGoCBValues TP Y
GSSE-CONTROL-BLOCK
S40 SendGSSEMessage MC
S41 GetReference TP
S42 GetGSSEElementNumber TP
S43 GetGsCBValues TP
S44 SetGsCBValues TP
Transmission of sampled value model (SVC)
Multicast SVC
S45 SendMSVMessage MC
S46 GetMSVCBValues TP
S47 SetMSVCBValues TP
Unicast SVC
S48 SendUSVMessage TP
S49 GetUSVCBValues TP
S50 SetUSVCBValues TP
Control
S51 Select Y
S52 SelectWithValue TP Y
S53 Cancel TP Y
S54 Operate TP Y
Command-
S55 TP Y
Termination
S56 TimeActivated-Operate TP
File transfer
S57 GetFile TP Y
Page-10 P445/EN PC/E62 – IEC61850 Edition 2
ACSI Service Conformance Statement Protocol Implementation Conformance
Statement (PICS)
Services AA:TP/MC Client (C) Server (S) Comments
S58 SetFile TP
Only from /COMTRADE/
operation may be
S59 DeleteFile TP Y
performed on .cfg and
.dat files.
S60 GetFileAttributeValues TP Y
GetServerDirectory
S61 TP Y
(FILE-SYSTEM)
Time
nearest negative power of
T1 Time resolution of internal clock 10 10
2 in seconds
T2 Time accuracy of internal clock T0
1ms 1ms T1
T2
T3
T4
T5
Supported TimeStamp nearest value of 2 ** -n in
T3 - 10 10
resolution seconds
Table 3 - ACSI Service Conformance Statement
AA: Application Association type
MC: Multicast (for GOOSE and SMV)
MMS: Manufacturing Message Specification
TP: Two part (for MMS)
P445/EN PC/E62 – IEC61850 Edition 2 Page-11
Protocol Implementation Conformance ACSI Service Conformance Statement
Statement (PICS)
Notes:
Page-12 P445/EN PC/E62 – IEC61850 Edition 2
Customer Care Centre
http://www.schneider-electric.com/ccc
2017 Schneider Electric. All rights reserved.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publisher: Schneider Electric
Publication: Easergy MiCOM P445/EN PC/E62 Fast Multifunction Distance Protection Relay Software Version: J6
Hardware Suffix: L IEC61850 Edition: 2
01/2017