SCHEDULE OF LOADS (SINGLE PHASE, 2 WIRE, @60 HZ)
CKT NO. LOAD DESCRIPTION QTY VOLTS WATTS AMPS TRIP FRAME POLE SIZE OF WIRE
2
1 LIGHITNG OUTLET 14 230 1400 6.09 15 A 60 2 2 - 2.0 mm THW STRANDED WIRE IN 13mm Ø PVC PIPE
2 LIGHTING OUTLET 11 230 1100 4.78 15 A 60 2 2 - 2.0 mm2 THW STRANDED WIRE IN 13mm Ø PVC PIPE
3 LIGHTING OUTLET 21 230 2100 9.13 15 A 60 2 2 - 2.0 mm2 THW STRANDED WIRE IN 13mm Ø PVC PIPE
4 10 - DUPLEX CONVENIENCE OUTLET. 20 230 3600 15.65 20 A 60 2 2 - 5.5 mm2 THW STRANDED WIRE IN 20mm Ø PVC PIPE
5 10 - DUPLEX CONVENIENCE OUTLET. 20 230 3600 15.65 20 A 60 2 2 - 5.5 mm2 THW STRANDED WIRE IN 20mm Ø PVC PIPE
6 SPLIT TYPE ACU UNIT - 0.5 HP 1 230 2200 11.96 30 A 60 2 2 - 5.5 mm2 THW STRANDED WIRE IN 20mm Ø PVC PIPE
7 SPLIT TYPE ACU UNIT - 0.5 HP 1 230 2200 11.96 30 A 60 2 2 - 5.5 mm2 THW STRANDED WIRE IN 20mm Ø PVC PIPE
8 RANGE OUTLET 1 230 1000 4.35 40 A 60 2 2 - 8.0 mm2 THW STRANDED WIRE IN 20mm Ø PVC PIPE
9 REF OUTLET 1 230 1000 4.35 20 A 60 2 2 - 3.5 mm2 THW STRANDED WIRE IN 13mm Ø PVC PIPE
10 SPARE 230
11 SPARE 230
TOTAL CURRENT LOAD: 83.91
98.09 x 0.80 = 67.1304
CIRCUIT BREAKER 110 A 18200