SCHEDULE OF LOADS (SINGLE PHASE, 2 WIRE, @60 HZ)
CIRCUIT NO. DESCRIPTION NO. OF OUTLET VOLTS WATTS AMPS CIRCUIT BREAKER SIZE OF WIRE SIZE OF CONDUIT
1 LIGHITNG OUTLET 18 230 1800 7.826 15 A 2 mm2 THW STRANDED WIRE 13mm Ø PVC PIPE
2 LIGHTING OUTLET 8 230 800 3.478 15 A 2 mm2 THW STRANDED WIRE 13mm Ø PVC PIPE
3 DUPLEX CONVENIENCE OUTLET. 11 230 3960 17.22 30 A 3.5 mm2 THW STRANDED WIRE 13mm Ø PVC PIPE
4 DUPLEX CONVENIENCE OUTLET. 11 230 3960 17.22 30 A 3.5 mm2 THW STRANDED WIRE 20mm Ø PVC PIPE
5 ACU OUTLET 1 230 746 4.054 30 A 5.5 mm2 THW STRANDED WIRE 20mm Ø PVC PIPE
6 ACU OUTLET 1 230 1492 8.109 30 A 5.5 mm2 THW STRANDED WIRE 20mm Ø PVC PIPE
7 RANGE OUTLET 1 230 8000 34.78 60 A 8 mm2 THW STRANDED WIRE 20mm Ø PVC PIPE
8 STOVE OUTLET 1 230 1100 4.783 40 A 5.5 mm2 THW STRANDED WIRE 20mm Ø PVC PIPE
9 REF OUTLET 1 230 2000 8.696 30 A 5.5 mm2 THW STRANDED WIRE 20mm Ø PVC PIPE
10 WATER HEATER OUTLET 1 230 2500 13.59 30 A 5.5 mm2 THW STRANDED WIRE 13mm Ø PVC PIPE
11 SPARE
12 SPARE
TOTAL CURRENT LOAD: 114.6
114.6 x 0.80 = 91.68
CIRCUIT BREAKER 125 A