Manual VER-I RISH_PFC8 (2)

The Power Factor Controller RISH PFC 8 is designed for indoor use and operates within a voltage range of 30-550V, featuring a user-friendly interface with a menu-driven display. It includes various settings for capacitor management, alarm outputs for fault detection, and options for advanced configurations such as Modbus and Real Time Clock. The manual provides detailed instructions on installation, operation, and troubleshooting for optimal performance and safety.

Uploaded by

Don Ronald
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views

Manual VER-I RISH_PFC8 (2)

The Power Factor Controller RISH PFC 8 is designed for indoor use and operates within a voltage range of 30-550V, featuring a user-friendly interface with a menu-driven display. It includes various settings for capacitor management, alarm outputs for fault detection, and options for advanced configurations such as Modbus and Real Time Clock. The manual provides detailed instructions on installation, operation, and troubleshooting for optimal performance and safety.

Uploaded by

Don Ronald
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 88

Power Factor Controller

RISH PFC 8

96 x 96

Operation Manual

Version I-7/19
!
CAUTIONS:

1. High voltage !

2. This controller may only be used indoor !

3. Make sure that the discharge time set in controller matches capacitor
discharge time !

Version I-7/19
CONTENTS

Section 1 General

Section 2 Mechanical dimensions and panel cut out

Section 3 Installation and connection of the controller

3.1 Alarm output / Error messages

Section 4 Terminal details


4.1 96 x 96 4 relay model
4.2 96 x 96 6/8 relay model, MODBUS model

Section 5 Front screen

Section 6 Front screen capacitor symbols

Section 7 Keyboard

Section 8 Display of various electrical parameters

Section 9 Display operations

Section 10 Basic settings

2
Section 11 Advanced settings
11.1 System setup
11.2 Manual setup
11.3 Alarm setup
11.4 Reset values
11.5 Modbus setup
11.6 Display setup
11.7 Change password

Section 12 Service mode

Section 13 Technical data

Section 14 Factory default setting

Section 15 Operating diagram


Section1 General
The power factor controller is a modern control device of innovative
design with a variety of functions.It is designed for a measuring voltage
of 30...550V (L-N) or (L-L) and a auxillary supply voltage of 110 to 550
VAC.
It features a user interface with a menu-driven display in plain text for
maximum ease of operation. Straight forward symbols and alphanumeric
displays combine maximum ease of handling with convenient presentation of
results.
Display of various grid parameters, storage of various values and a test run
option make it easy to analyse errors and monitor the system.

Main features:

R 1.Autoinitialisation function that detects connected capacitor kvar,


R connected number of capacitor banks,input phase correction angle,
R input voltage connection VLL-VLN
2.Various capacitor kvar selection option -
Direct value (Individual capacitor kvar),
Control series (programming of capacitor kvar ratio),
Auto detected capacitor kvar
3.4/6/8 switching outputs
R 4.Complete menu-guided operation and User interface
R 5.Illuminated graphic display with 2 x 16 characters
R 6.Four-quadrant operation
R 7.RTC option with last three fault logs
R 8.Display of various line parameters (V, I, F, Q, P, S...)
R 9.Monitoring of the individual capacitor kvar
R 10.Storage of maximum values, minimum values of line-parameter,
R switching-operation values as well as of the turn-on times of
R individual capacitor
R 11.Programming of output
Programming of output as Auto,fixed and faulty. This option used
for skipping step from switching for PF correction
R 12.Manual control
R Manual control allows switching of capacitor and contactor
R thus used for diagnosis purpose
R 13.Error detection for various states and interference-message
R output Test run of PFC system with error analysis
14.Recall function of recorded values
R 15.True RMS measurement upto 31st harmonics
R 16.Display of individual voltage and current harmonics upto 31st
R 17.Display of voltage and current total harmonics distortion
R 18.Display and monitoring of temperature

PFC Configurations

Output relay 4 relays outputs, 1 alarm relay


Options 6 relay outputs, 1 alarm relay
8 relays outputs, 1 alarm relay

Option RS485 Optional Interface RS 485 output

Option RTC Optional Real Time Clock.


Section 2 Mechanical Dimensions :

96 model Without Add On card (Relay + Modbus)


96 mm 51 mm

96 mm

59 mm
PFC 96 model With Add On card (Relay + Modbus)
96 mm 51 mm
96 mm

75 mm
Panel Cutout for PFC 96 size model
92 mm + 0.8mm

92 mm + 0.8mm
Optional Pluggable Module (Relay + Modbus)

Insert The ADD on


assembly here and fit
the assembly with
screws.
Section 3 Installation and connection of the controller
The controller is designed to be incorporated into the front panel of a PFC-
cabinet. It requires a panel cutout of 92 x 92. The controller is inserted from
the front and it gets fitted into panel with help of self clicking & if required
swivel screw can be used.The controller should be installed by qualified
technicians and must be operated in accordance with the specified safety
regulations.
Mounting of the controller is featured with easy “Clip- in” mounting. Push the
meter in panel slot, it will click fit into panel with the four integral retention
clips on two sides of meter. If required, additional support is provided with
swivel screws as shown in Fig. 1
Before the controller is connected up, all leads and cables must be checked to
ensure that no current is flowing through them. Care should be taken to
ensure that the measuring voltage and current are in the correct phase
position. The connection should be set up as shown in Fig. 2. The specified
safety regulations must be observed.
The auxilliary supply voltage is 110 to 550 VAC / DC
The measuring voltage may lie in the range from 30-550 VAC and can be
connected as L-N or L-L. after voltage and current connections enter CT
primary and secondary.
Now as per site conditions Phase correction angle,voltage
type,Capacitor bank KVAr ,Number of capacitor banks parameters can
be set OR Auto initialisation can be carried out to detect above parameters.
Auto-initialisation function designed to works in most of practical load
conditions and system networks. Refer Auto initialisation notes for detail.
if any ambiguty found in system values during or after autoinitilisation then
settings for above can be done in basic settings and advanced system
settings.
Easy Clip in
Mounting

Swivel Screw

Fig 1: Installation
3.1 Alarm output / error messages
The alarm contact is open in normal operation and closed in the event of a
fault. The relevant fault is simultaneously shown on the display in plain text.
The following fault messages are displayed:
UNDERVOLTAGE Display and relay output
OVERVOLTAGE Display and relay output
UNDER FREQUENCY Display and relay output
OVER FREQUENCY Display and relay output
UNDER CURRENT Display and relay output
OVER CURRENT Display and relay output
VOLTAGE HARMONICS Display and relay output
CURRENT HARMONICS Display and relay output
OVER TEMPERATURE Display and relay output
OUT OF BANK Display and relay output
OVER COMPENSATION Display and relay output
PFC 96X96 Electrical Connection

Aux- Input Input current


Voltage Voltage
k l
R
L
Y O
B A
D
N

Contactor1
Breaker

Coil
T 2A

T 2A

T 6A
Capacitor bank1

(1) (2) (4) (5) (6) (7) NO COM COM C 1 C2 C3 C 4

AUX VL - VL‘ IL - IL‘ ALARM


(110-550) (30-550) (1A / 5A)
VAC (VLN/VLL)

RS-485
(B) (A) (G)
Power factor controller

COM C5 C6 C7 C8

Fig 2: Connection Diagram


Section 4 Rear side Terminals
4.1 Without Add on Card (Relay + Modbus)

Aux Supply Measurement Measurement


(110 to 550 Voltage Current
VAC) (30 to 550 VAC) (1 / 5 Amp)

1 2 3 4 5 6 7

L N NC VL VL‘ IL IL‘

ALARM
COM C1 C2 C3 C4
NO COM

Common (Relay 1 to 4)
Incoming phase
Potential Free
Potential Free supply for
Relay Contacts
Alarm Contact contactors.
4.2 With Add on Card (Relay + Modbus)

Aux Supply Measurement Measurement


(110 to 550 Voltage Current
VAC) (30 to 550 VAC) (1 / 5 Amp)

1 2 3 4 5 6 7

L N NC VL VL‘ IL IL‘

B A G
COM C5 C6 C7 C8
RS 485

ALARM
COM C1 C2 C3 C4
NO COM

Common (Relay 1 to 8)
Incoming phase
Potential Free
Potential Free supply for
Relay Contacts
Alarm Contact contactors.
Section 5 Front Screen
PF 0.990 IND

Bank 1 upto banks configured

First line indicates the PF value, inductive / capacitive PF.


“PF = 0.999” indicates the overall PF of the system.
“IND” or “CAP” indicates inductive or capacitive respectively.
‘-’ sign to power factor indicates change in qudrant operation
Maximum 8 banks available with PFC 96
Meter toggles between PF screen, Fault status screen ( if any fault exist ).

UNDERCURRENT
- - - - - - - -

Fault status screen represent one out of following status :


UNDERVOLTAGE
OVERVOLTAGE
UNDER FREQUENCY
OVER FREQUENCY
UNDER CURRENT
OVER CURRENT
OVER HARMONICS VOLTAGE
OVER HARMONICS CURRENT
OVER TEMPERATURE
OUT OF BANK
OVER COMPENSATION
Section 6 Front Screen capacitor symbols
PF 0.990 IND
M X D

Bank 1 Upto Banks configured

Label M in second line of display signifies that controller is in manual mode


screen

Power Factor at Load sensing CT is 0.990 IND (Inductive).


(‘CAP’ defines Capacitive).
change in quadrant is indicated by minus sign appearing in-front of power
factor value.

Total number of banks configured 8


Capacitor bank 1 is declared as fixed and is in ON condition.
Capacitor bank 2 is in ON condition (Auto mode).
Capacitor bank 3 is in Auto mode, OFF state and can be switched ON
Capacitor bank 4 is declared as faulty so in OFF condition.
Capacitor bank 5 is in ON condition (Auto mode).
Capacitor bank 6 is in discharging state.
Capacitor bank 7,8 is in ON condition (Auto mode).

if any faults is existing then PF and alternately fault screen appears on LCD.
Section 7 Keyboard

Keyboard with soft touch keys are provided on the front fascia
of the controller. The various keys are:-

MENU Key. Pressing menu key will enter


into program mode menu OR to return
M to previous menu / submenu / Return to
main PF screen.
This key is denoted as M key in manual.

UP Key. Used to scroll up the menu


screen and submenu screen,Increment
values when entering numbers.
This key is denoted as U key in manual.

DOWN Key. Used to scroll down the


menu and submenu screen, decrement
values when entering numbers.
This key is denoted as D key in manual.
ENTER key. Used for entering a
submenu or for confirming changes of
entered values.
This key is denoted as E key in manual.

15
Section 8 Display of various electrical parameters:

Values of various electrical parameters can be viewed by using


UP / Down keys.

SYS PF, BANK STATUS, It shows System PF value, system


bank status, system fault status.
FAULT STATUS

LINE VOLTAGE It shows phase RMS voltage value

LINE CURRENT It shows phase RMS current value


UP KEY

DOWN REACTIVE POWER


KEY
It shows system power
ACTIVE POWER parameters
system KVAR, KW, and KVA

APPARENT POWER

It shows KVar value to be


Diff. to PF
compensated.
LINE FREQUENCY It shows phase Frequency value
It shows Total Harmonics
distortion for system Voltage,
V-THD I-THD
current.
It shows individual Voltage,
current harmonics upto 31st.
INDIVIDUAL V,I HARMONICS
Use of enter key on this screen
and then up down key used for
viewing values
kWh IMPORT It shows system active import
energy.

It shows system active export


UP KEY kWh EXPORT
energy.
DOWN
KEY kVARh IND It shows inductive reactive
energy.

kVARh Cap It shows capacitive reactive


energy.

kVAh It shows system Apparent energy.

AMPERE DEMAND It shows system Ampere demand.


ACT IVE DEMAND IMPORT It shows system active import
demand power value.

ACT IVE DEMAND EXPORT It shows system active export


demand power value.

It shows system apparent


APPERANT DEMAND
demand power value.
It shows Approximate ambient
TEMPERATURE temperature of surrounding /
UP KEY panel.
It shows Run hour in hour
DOWN RUN H OUR [HH.MM]
minute format.
KEY
It shows On hour (unit is
ON H OUR [HH.MM] powered) in hour minute
format.
Shows current time & date that
TIME : 04 : 25 is set on internal Real Time
DATE : 04 / 11 / 18
Clock.(This screen will be
displayed if optional RTC module
is present)
It shows power failure count value
PD COUNT: 99
with last time date stamp
12:06 04 / 11 / 18 Note : -If controller having RTC
then only date & time stamp
available else only PD count shown
SYSTEM FAULTS-1 It shows system present faults.

UP KEY
SYSTEM FAULTS-2
It shows system present faults.
DOWN
KEY

SYSTEM WARNING It shows system warning.

Section 9 Display Operations

PFC normally shows default screen of power factor, by using up / down key
scrolling is possible for various system measured parameters.
Pressing menu key on other than default screen will show default screen first.
use Up/ Down key to scroll measurement parameter. Auto scroll of display parameter
with fixed scrolling time can also be enabled.
Upon pressing menu key on default screen will show three main menus
namely Basic Setting, Advanced Setting, Service Modes.
Further navigation to settings is possible by using Up / Down key.
Enter key enables scrolling for various menu option and also, editing of
parameters.
Section 10 BASIC SETTINGS
Press ENTER key to enter into Basic setting.
ENTER PASSWORD : Password protection can be
enabled to prevent unauthorised access to basic
ENTER PASSWORD
setting’s sub-menues, by default password is set to
0000.
APFC allows user to set password in range 0000 to
9999. Password protection is enabled by selecting a
four digit number other than 0000.
Password Setting:
To change password please refer section 11.7

CT PRIMARY :This parameter allows user to set


Current transformer’s primary value. Value is settable
from 0001 to 9999 Amp.
CT PRIMARY
Press ENTER key to edit CT PRIMARY value.
Pressing UP or DOWN key will increment or decrement
digit value. Then pressing ENTER key will advance to next
digit & confirm newly changed values.

CT SECONDARY : This parameter allows user to set


Current transformer’s secondary value. Value can be
set as 1 or 5 Amp.
CT SECONDARY Press ENTER key to edit CT SECONDARY value.
Pressing UP or DOWN key will increment or decrement
digit value. Then press ENTER key to confirm newly
changed values.
Auto init : Enables auto initilization function
selecting YES option starts auto detection process

Proper CT primary and secondary should be set before starting


auto init
AUTO INIT Auto initialization detects voltage connection type LN or LL ,
system correction angle between inputs , carries out test run to
detect capacitor KVAr and also detect number of connected
capacitors. if undercurrent fault is present during auto init then
auto init function gets aborted.
To successfully detect system type (LN,LL) voltage should be in
range of 180V.to 550V, if 220/230/240 VLN system then system
connection can be automatically detected ,if any other voltage ex.
110 VLL controller prompts to select connection type.
To successfully detect phase correction angle PF should be in
range of 0.600 inductive to 0.999 inductive.
auto init starts with switch off all capacitors and after discharge
time complete, phase correction angle and type is evaluated and
shown on LCD, then capacitor KVAr detection starts, detected
KVAr is displayed on LCD and these values can also be seen in
service mode menu.
system type (LN or LL) detected get overwritten to present value
whereas system angle stored in separate location (not
overwritten).
if any discrepancy found in system type ,correction user can
change to old values by appropriate settings in basic settings
menu.if any capacitor detected 0 KVAr then that output marked
as faulty and neglected in correction algorithm if any discrepancy
found in KVAr detected or number of banks then appropriate
settings to be carried out in basic settings.
SYSTEM NOMINAL VOLTAGE :This is the system rated
SYS NOM VOLTAGE
voltage with respect to which the fault limits
are defined. Value is settable from 50 to 550 VAC.
Press ENTER key to edit system nominal value.
Pressing UP or DOWN key will increment or decrement
digit value. Then pressing ENTER key will advance to
next digit & confirm newly changed values.
CAPACITOR KVAr: Assigns Capacitor KVAr for outputs.
CAPACITOR KVAr following 3 option possible
1.AUTO DETECTED: KVAr measured by auto-
Initialisation function
2.DIRECT Kvar: Individual capacitor KVAr can be
programmed independent of other capacitor banks
3.CONTROL SERIES. Predefined sequence is Ratio of
capacitor KVAr with reference to first step
This option gets changed to AUTO DETECTED upon
successful auto-initialisation for automatic
operation avoiding manual interferance
Press ENTER key to edit Capacitor KVAr selection option
Pressing UP or DOWN key will scroll available options
Then pressing ENTER key confirms the option
PHASE CORR. ANGLE
PHASE CORRECTION ANGLE: Selects phase correction
angle for inputs applied.
1 AUTO DETECTED: phase correction angle as
detected by auto-initialisation function
2. USER SETTINGS: use correction angle as set in
system setup menu of input current and voltage
( refer Network table on Pg 30 )
This option gets changed to AUTO DETECTED upon
successful auto-initialisation.
Control Series: Control series is predefined sequence is
CONTROL SER. ratio of capacitor KVAr with respect to first capacitor KVAr.
there are 20 predefined control series any control series
can be selected
Pressing UP or DOWN key will increment or decrement
control series number. Then pressing ENTER key will
confirm newly changed values
Control series1:1,1,1,1,1,1,1,1
Control series2:1,2,2,2,2,2,2,2
Control series3:1,2,3,3,3,3,3,3
Control series4:1,2,3,4,4,4,4,4
Control series5:1,2,4,4,4,4,4,4
Control series6:1,2,3,6,6,6,6,6
Control series7:1,2,4,8,8,8,8,8
Control series8:1,1,1,1,2,2,2,2
Control series9:1,1,1,1,1,6,6,6
Control series10:1,1,2,2,2,2,2,2
Control series11:1,1,2,2,2,4,4,4
Control series12:1,1,2,2,4,4,4,4
Control series13:1,1,1,2,2,2,2,2
Control series14:1,1,2,3,3,3,3,3
Control series15:1,1,2,4,4,4,4,4
Control series16:1,1,2,4,8,8,8,8
Control series17:1,2,2,3,3,3,3,3
Control series18:1,2,3,4,4,8,8,8
Control series19:1,2,2,4,4,4,4,4
Control series20:1,2,2,2,4,4,4,4
If connected capacitor kVAr to output relays not suitable for
any of above control series then direct kvar option can be
selected so that any value of capacitor kVAr can be set
CAP.BANKS IN USE :
CAP BANKS IN USE
There are 3 models with 4 / 6 / 8 relay options. user
can set banks from 1 to n
( n = 4,6,8 )as per ordered device.
if CAPACITOR KVAr option set as [AUTO DETECTED]
then this option not available since number of banks
are detected automatically.
Press ENTER key to edit bank kVAr values.
Pressing UP or DOWN key will increment or decrement
digit value. Then pressing ENTER key will advance to
next digit & confirm newly changed values.

CAP.[01] POWER
CAP.[01] POWER : user can program bank KVAr
values in range 1 to 255 KVAr. Increments in steps of
0.5 KVAr.
if [CONTROL SER.] option is selected then only 1st
capacitor KVAr power need to set. next capacitor
KVAr sets automaticaly
Ex if control series is 3 and CAP[01] set 5KVAr then
Capacitor1 KVAr is 5 x 1 = 5 KVAr
Capacitor2 KVAr is 5 x 2 = 10 KVAr
Capacitor3 KVAr is 5 x 3 = 15 KVAr
For [DIRECT KVAr] option all capacitor KVAr need to
be entered in subsequent settings.
For [AUTO DETECTED] option capacitor KVAr
CAP.[n] POWER automatically detected and set.
Press ENTER key to edit Capacitor KVAr power
Pressing UP or DOWN key will increment or decrement
digit value.Then pressing ENTER key will confirm newly
changed values.
Section 11 ADVANCED SETTINGS
Press ENTER key to enter into Advance setting.

ENTER PASSWORD : Password protection can be


ENTER PASSWORD enabled to prevent unauthorised access to advanced
setting’s sub-menues, by default password is set to
0001.
PFC allows user to set password in range 0000 to
9999.Password protection is enabled by selecting a
four digit number other than 0000.
Password Setting:
To change password please refer section 11.7
Section 11.1 : SYSTEM SETUP
This menu allows user to set one out of several system
SYSTEM SETUP
related setup parameters.
Press ENTER key to enter into system setup sub menus.
Pressing UP or DOWN key will scroll through submenus.

TARGET PF :This parameter is the target power factor of


system. Value is settable from 0.8 INDUCTIVE to 0.8
TARGET PF CAPACITIVE.
Press ENTER key to edit target PF.
Pressing UP or DOWN key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed values.

SWITCH IN TIME :This parameter is the SWITCH-IN time


SWITCH-IN-TIME
of individual capacitor bank. Switch in time Value is
settable from 10 to 1800 Sec.
Press ENTER key to edit switch in time value.
Pressing UP or DOWN key will increment or decrement digit
value resp. Then pressing ENTER key will advance to next
digit & confirm newly changed values.
SWITCH OFF TIME :This parameter is the SWITCH-
SWITCH-OFF-TIME OFF time of individual capacitor bank. Switch off time
Value is settable from 10 to 1800 Sec.
Press ENTER key to edit Switch off time value.
Pressing UP or DOWN key will increment or decrement
digit value resp. Then pressing ENTER key will advance
to next digit & confirm newly changed values.

DISCHARGE TIME :This parameter is the discharge


DISCHARGE TIME
time of individual capacitor bank. discharge time Value
is settable from 60 to 1800 Sec.
Press ENTER key to edit discharge time value.
Pressing UP or DOWN key will increment or decrement
digit value resp. Then pressing ENTER key will advance to
next digit & confirm newly changed values.

THRESHOLD : Threshold for switching ON / OFF next


THRESHOLD
stage. It should not be change in normal case
Threshold value is editable in range 30 to 100%.
Press ENTER key to edit threshold value.
Pressing UP or DOWN key will increment or
decrement digit value resp. Then pressing ENTER key
will advance to next digit & confirm newly changed
values.
SWITCHING OPERATION WARNING COUNT : After
an output has performed this number of switching
operations a warning message is displayed.
SWITCHING OPERATION
WARNING COUNT switching operation warning count is editable in
range 10000 to 255000.
Warning will disappear if user resets switching
operation count.

Press ENTER key to edit switching operation count.


Pressing UP or DOWN key will increment or
decrement digit value resp. Then pressing ENTER key
will advance to next digit & confirm newly changed
values.

Capacitor Health Check : The kvar of the particular


capacitor bank is calculated during each switching
operation and compared with stage output of
CAP HEALTH CHECK capacitor. If the result value is below 80% and
above 70 % of nominal value for a particular bank
warning will be displayed & if it goes below 70% of
nominal value that particular bank will get block.
user can enable or disable this feature. The
number of attempts for checking bank value are
programable, refer “cap test attempt” count.
Press ENTER key to edit cap health check.
Press UP or DOWN key to get available options (yes
/no) resp. Then pressing ENTER key will confirm
newly changed options.
CAPACITOR TEST ATTEMPTS COUNT :
This parameter is programable in range 5 to 9.
CAPACITOR TEST
when at least this number of successive
ATTEMPTS COUNT
measurement is resulted in fault in the capacitor
power, Capacitor fault message will appear on
display.

Press ENTER key to edit capacitor test attempt count.


Pressing UP or DOWN key will increment or
decrement digit value resp. Then pressing ENTER key
will advance to next digit & confirm newly changed
values.
SYSTEM FREQUENCY :
SYSTEM FREQUENCY
This parameter is settable as 50 or 60 Hz.

Press ENTER key to edit parameter.


Pressing UP or DOWN key will increment or
decrement digit value resp. Then pressing ENTER key
will advance to next digit & confirm newly changed
values.
SYSTEM TYPE :
SYSTEM TYPE
This parameter is settable as 1 phase or 3 phase.
for 3 phase option all powers get multiplied by 3

Press ENTER key to edit parameter.


Press UP or DOWN key to get available options (1PH
/3PH) resp. Then pressing ENTER key will confirm
newly changed option.
INPUT PHASE CURRENT / VOLTAGE :
This parameters are used for phase correction
INPUT PHASE CURRENT between voltage and current in the measuring
system.
Theses settings are applicable if PHASE CORR.
ANGLE option in basic settings is set as
INPUT PHASE VOLTAGE [USER SETTINGS]
first set phase input current then accordingly in
next menu set phase voltage as per network
connection. Refer below table for configuration.
Use UP or DOWN key to scroll options and use
ENTER key to confirm selection
Note : This setting is not applicable if
PHASE CORR. ANGLE set as [AUTO DETECTED]

Network table
PHASE CURRENT PHASE VOLTAGE
IL1 L1 - N - 0
IL1 L1 - L2 - 30
IL1 ( k <- > l ) L2 - N - 60
IL1 L3 - L2 - 90
IL1 L3 - N - 120
IL1 L3 - L1 - 150
IL1 ( k <- > l ) L1 - N - 180
IL1 ( k <- > l ) L1 - L2 - 210
IL1 L1 - N - 240
IL1( k <- > l ) L3 - L2 - 270
IL1 ( k <- > l ) L3 - N - 300
IL1 ( k <- > l ) L3 - L1 - 330
PHASE CURRENT PHASE VOLTAGE
IL2 L2 - N - 0
IL2 L2 - L3 - 30
IL2 ( k <- > l ) L3 - N - 60
IL2 L1 - L3 - 90
IL2 L1 - N - 120
IL2 L1 - L2 - 150
IL2 ( k <- > l ) L2 - N - 180
IL2 ( k <- > l ) L2 - L3 - 210
IL2 L3 - N - 240
IL2 ( k <- > l ) L1 - L3 - 270
IL2 ( k <- > l) L1 - N - 300
IL2 ( k <- > l ) L1 - L2 - 330

PHASE CURRENT PHASE VOLTAGE


IL3 L3 - N - 0
IL3 L3 - L1 - 30
IL3 ( k <- > l ) L1 - N - 60
IL3 L2 - L1 - 90
IL3 L2 - N - 120
IL3 L2 - L3 - 150
IL3 ( k <- > l ) L3 - N - 180
IL3 ( k <- > l ) L3 - L1 - 210
IL3 L1 - N - 240
IL3 ( k <- > l ) L2 - L1 - 270
IL3 ( k <- > l ) L2 - N - 300
IL3 ( k <- > l ) L2 - L3 - 330
DEMAND INTEGRATION TIME :
This parameter is used to set the period over which
current and power readings are to be integrated.
The Unit of displayed values is minutes. time is
DEMAND INT. TIME settable as 8,15,20,30 minutes resp.
Press ENTER key to edit parameter.
Pressing UP or DOWN key will increment or
decrement digit value resp. Then pressing ENTER key
will advance to next digit & confirm newly changed
values.

ENERGY UPDATE RATE :


ENERGY UPDATE RATE
This parameter allows user to enter energy update
rate in min. Time is settable in range 1 to 60 min
resp.

Press ENTER key to edit parameter.


Pressing UP or DOWN key will increment or
decrement digit value resp. Then pressing ENTER key
will advance to next digit & confirm newly changed
values.

ENERGY UNIT :
ENERGY UNIT
This parameter allows user to set energy in terms
of Wh / kWh / MWh as per the requirement. Same
is applicable to all types of energy.
Press ENTER key to edit parameter.
Pressing UP or DOWN key will scroll between the
available options. Then pressing ENTER key will
confirm the newly selected option.

ENERGY OVERFLOW COUNT :


ENERGY OVERFLOW This parameter is used for setting maximum
COUNT
energy count after which energy will roll over to
zero depending on setting of Wh, KWh & MWh.
Count is settable in range 7 to 9.

Press ENTER key to edit parameter.


Pressing UP or DOWN key will increment or
decrement digit value resp. Then pressing ENTER key
will advance to next digit & confirm newly changed
values.

RTC DATE, TIME


RTC DATE , TIME Date: Allows user to set date.
Time: Allows user to set the time.

Press ENTER key to edit parameter.


Pressing UP or DOWN key will increment or
decrement digit value resp. Then pressing ENTER key
will advance to next digit & confirm newly changed
values.
Note: (optional menu displayed when RTC module is
present)
DEFAULT SYSTEM VALUES :
This menu allows user to reset PFC to factory
default setting.(Refer section 14 )
DEFAULT SYSTEM VALUES Press ENTER key to edit parameter.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.
During factory reset meter will display “WAIT”
message on second row then PFC will reset to factory
default settings.

Note : - Resetting to factory default setting APFC will


initialize Energy, Demand counters and
resets Min / max values.

MAX SWITCH POWER :


This menu allows user to set maximum capacitor
bank kVAr switching value.
MAX SWITCH POWER The settable range is from minimum set capacitor
bank value upto the sum of total capacitor banks
values.
Increments in steps of minimum capacitor bank
value.

Press ENTER key to edit parameter.


Press UP or DOWN key to increments OR decrements
max switching power in steps of minimum bank kVAr
value. Then press ENTER key to confirm newly
changed max switching power.
Section 11.2 :MANUAL SETUP :
This menu allows user to test or set the bank
MANAUL SETUP operating mode.
BANK ON / OFF MANUALLY :
This menu allows user to ON / OFF banks set in Auto
mode only.
Press ENTER key to ON/OFF Bank manually.
Press UP or DOWN key to get available options as ON /
MANUAL BANK
OPERATION OFF. Then press ENTER to ON / OFF bank manually.
Note : PFC allows to ON / OFF Banks set in Auto
mode only. If fault is present PFC does not allow to
ON/OFF Banks manually. On exit from manual mode all
the banks enter into Auto mode.

BANKS FUNCTION :
SET BANK FUNCTION AS
This parameter allows to set individual bank
AUTO / FIXED / FAULTY
operating mode.
Press ENTER key to edit parameter.
Press UP or DOWN key to get available options as
AUTO / FIXED / OFF. Then press ENTER to confirm
individual bank operating mode.
Auto : Automatic Operation
It is displayed as capacitor symbol if connected.
Fixed : - It is displayed as capacitor symbol with
underline. Fixed Capacitor Banks are continuously
connected except in fault condition.
Off : - It is displayed as cross symbol. The capacitor
banks are permanently disconnected.
Section 11.3 :ALARM SETUP :
This menu allows user to set one out of several alarm
ALARM SETUP
related parameters.
Press ENTER key to enter into alarm setup sub menues.
Pressing UP or DOWN key will scroll through submenus.

UNDER -VOLTAGE
UNDER VOLTAGE : It is for Under voltage protection
when phase voltage goes below the set threshold value.

Press ENTER key to enter into under voltage sub setup.


Pressing UP or DOWN key will scroll through submenus.

TRIGGER VALUE : Value is settable from 75 to 90% of


TRIGGER VALUE
system nominal voltage value.
( 75 TO 99 % )

Press ENTER key to edit trigger value.


Pressing UP or DOWN key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
RELAY ACTIVATION
confirm newly changed values.

RELAY ACTIVATION : APFC unit allows to activate /


deactivate assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.
Note 1: - If fault occurs PFC will Switch off all banks
including fixed banks one after the other with a delay of
1second between the banks when fault occurs.
Note 2: - Relay will reset at 3% of voltage nominal value
plus trip value.
Reset point is factory set, not editable.

OVER VOLTAGE : It is for over voltage protection against


OVER VOLTAGE
over voltage condition in phase.

Press ENTER key to enter into over voltage sub setup.


Pressing UP or DOWN key will scroll through submenus.

TRIGGER VALUE : Value is settable from 105 to 115% of


system nominal voltage value.
TRIGGER VALUE Press ENTER key to edit trigger value.
( 105 TO 115 % ) Pressing UP or DOWN key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed values.
RELAY ACTIVATION : APFC unit allows to activate /
RELAY ACTIVATION
deactivate assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.
Note : - 1. If fault occurs APFC will Switch off all banks
including fixed banks one after the other with a delay of
1sec between the banks when fault occurs.
2.Relay will reset if system voltage is trip value setting
minus 2% of voltage nominal value. Reset point is factory
set, not editable.
FREQUENCY FAULT : It is for frequency protection against
FREQUENCY FAULT
frequency condition in phase.

Press ENTER key to enter into under frequency sub setup.


Pressing UP or DOWN key will scroll through submenus.

TRIGGER VALUE : Value is settable from 2 to 10% of


system frequency value.
TRIGGER VALUE
( 2 - 10 % ) Press ENTER key to edit trigger value.
Pressing UP or DOWN key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed values.

RELAY ACTIVATION : PFC unit allows to activate /


deactivate assigned relay.
RELAY ACTIVATION
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.

Note : -
1. Frequency fault will occur at nominal frequency minus or
plus of trigger point of nominal frequency.
2. If fault occurs PFC will Switch off all banks including fixed
banks one after the other with a delay of 1sec between the
banks when fault occurs.
3.Relay will reset at 1% of Nominal frequency value plus OR
minus trip value resp. Reset point is factory set, not
editable.
UNDER CURRENT : It is for under current protection
UNDER CURRENT
against under current condition in phase.

Press ENTER key to enter into under current sub setup.


Pressing UP or DOWN key will scroll through submenus.

TRIGGER VALUE : Value is settable from 1 to 3% of CT


Primary. For example if CT ratio is 500/1A & trigger value
is set as 1%, then under current fault will activate if load
current falls below 1% of CT Primary.
TRIGGER VALUE

(1 - 3 %)
Press ENTER key to edit trigger value.
Pressing UP or DOWN key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed values.

RELAY ACTIVATION : PFC unit allows to activate /


RELAY ACTIVATION deactivate assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.

Note : - 1. If fault occurs PFC will Switch off all banks


including fixed banks one after the other with a delay of
1sec between the banks when fault occurs.
2.Relay will reset at Trip value plus 1% of CT Primary. Reset
point is factory set, not editable.
OVER CURRENT : It is for over current protection against
OVER CURRENT
over current condition in phase.

Press ENTER key to enter into over current sub setup.


Pressing UP or DOWN key will scroll through submenus.

TRIGGER VALUE : Value is settable from 60 to 120%. For


example if CT ratio is 500/1A & trigger value is set as
110%, then Over current fault will activate if load
current exceeds 550A.
TRIGGER VALUE

( 60 - 120 % ) Press ENTER key to edit trigger value.


Pressing UP or DOWN key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed values.

RELAY ACTIVATION : PFC unit allows to activate /


RELAYACTIVATION deactivate assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.

Note : - 1. If fault occurs PFC will Switch off all banks


including fixed banks one after the other with a delay of
1sec between the banks when fault occurs.
2.Relay will reset at Trip value minus 1% of CT Primary.
Reset point is factory set, not editable.
VOLTAGE THD : When voltage THD is more
VOLTAGE THD
than set limit then PFC will operate alarm relay

Press ENTER key to enter into voltage THD sub setup.


Pressing UP or DOWN key will scroll through submenus.

TRIGGER VALUE : Value is settable from 1 to 25%.


TRIGGER VALUE

( 1 - 25 % )
Press ENTER key to edit trigger value.
Pressing UP or DOWN key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed values.

RELAY ACTIVATION : APFC unit allows to activate /


RELAY ACTIVATION deactivate assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.

Note : - 1. If fault occurs PFC will Switch off all banks


including fixed banks one after the other with a delay of
1second.
2.Relay will reset at set trigger value of voltage THD minus
5%.
Reset point is factory set, not editable.
CURRENT THD : When current THD is more
CURRENT THD
than set limit then PF controller will operate relay

Press ENTER key to enter into current THD sub setup.


Pressing UP or DOWN key will scroll through submenus.

TRIGGER VALUE : Value is settable from 1 to 99%.


TRIGGER VALUE
( 1 - 99 % )
Press ENTER key to edit trigger value.
Pressing UP or DOWN key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed values.

RELAY ACTIVATION : PFC allows to activate / deactivate


RELAY ACTIVATION assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.

Note : - 1. If fault occurs APFC will Switch off all banks


including fixed banks one after the other with a delay of
1second
2.Relay will reset at set current THD minus 5%.
Reset point is factory set, not editable.
Temperature : When cabinet temperature exceeds above
TEMPERATURE the 55 deg celsius PFC displays warning message and if
temperature exceeds above 60 deg celsius PFC
disconnects all the capacitor banks and activates the
relay if enabled.

RELAY ACTIVATION : PFC allows to activate / deactivate


RELAY ACTIVATION assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.

Note : - 1. If fault occurs PFC will Switch off all banks


including fixed banks one after the other with a delay of
1sec between the banks when fault occurs.

2. When temperature regains below the 55 deg celcius the


alarm relay gets deactivated and banks switching takes as
per requirement

3. The temperature limit of 55 and 60 deg celcius is factory


set and not editable.
OVER COMPENSATION : In Auto mode if all banks are
OVER COMPENSATION
ON (except Fixed banks) and if Diff. to PF exceeds
threshold of lower bank KVAr value PFC will activate
relay if enabled.
Press ENTER key to enter into over compensation sub
setup.
Pressing UP or DOWN key will scroll through submenus.

RELAY ACTIVATION : PFC allows to activate /


RELAY ACTIVATION deactivate assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.

Note : - 1. Relay will reset if Diff. to PF goes below


threshold of lower bank kvar value.

OUT OF BANKS : In Auto mode if all banks are ON


OUT OFF BANKS
and still target PF is not achieved PFC will operate
relay if activated.
Press ENTER key to enter into OUT OF BANK sub setup.
Pressing UP or DOWN key will scroll through submenus.

RELAY ACTIVATION : PFC allows user to activate /


RELAY ACTIVATION
deactivate assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.
Note : - Relay will reset if target PF is achieved.

BATT. LOW FAULT : - (* Applicable for RTC module.)


BATT. LOW FAULT If the internal Lithium coin Battery Voltage drops down,
APFC will show “BAT” (low RTC battery) message on the
system warning screen (Display Parameters) until the
battery is replaced by a new healthy battery. It is
essential to have the battery operational to maintain the
Real Time Clock and Calendar information specifically
during supply power down condition.
User can enable / disable battery low fault message.
Press ENTER key to edit option.
Press UP or DOWN key to get available options (Yes / No).
Then press ENTER key to confirm newly changed option.

BANK SWITCHING COUNT WARNING : -IF count crosses


BANK SWITCHING the set Capacitor switching count APFC gives warning
COUNT WARNING only on display. If user resets the count that particular
bank warning will disappear. By default warning is
enabled.

BANK HEALTH WARNING : -The kvar value of the


BANK HEALTH
particular capacitor bank is calculated during each
WARNING switching operation and compared with set bank value of
capacitor. If the result is below the 80% of set bank value
health warning will be displayed.
Section 11.4 : RESET VALUES :
This menu allows user to reset one out of several
parameters.
RESET VALUES
Press ENTER key to enter into reset values sub menus.
Pressing UP or DOWN key will scroll through submenus.
RESET ENERGY : Press ENTER key to reset all energy
RESET ENERGY related parameters.
After resetting PFC will show “DONE” message on display.

RESET DEMAND : Press ENTER key to reset all demand


RESET DEMAND related parameters.
After resetting PFC will show “DONE” message on display.

RESET MINIMUM PARAMETERS : Pressing ENTER key will


reset minimum voltage, current, frequency, temperature
RESET MIN PARA
parameters.
After resetting PFC will show “DONE” message on display.

RESET MAXIMUM PARAMETERS : Pressing ENTER key will


RESET MAX PARA reset maximum voltage, current, frequency, temperature
voltage THD, current THD, import power, export power,
capacitive power, inductive power, apparent power
parameters.
After resetting PFC will show “DONE” message on display.

RESET ON - RUN HOUR : Press ENTER key to reset run


RESET ON-RUN
HOUR hour, on hour.
After resetting PFC will show “DONE” message on display.
RESET INTERRUPT : Press ENTER key to reset
RESET INTERRUPT power down interrupt count.
After resetting PFC will show “DONE” message on
display.
RESET BANK SWITCHING COUNT : Press ENTER
RESET BANK SW ITCHING
key to entered into submenus. Then press UP or
COUNT ( INDIVIDUAL / ALL ) DOWN key get available options. Then pressed
ENTER key to reset individual, all bank switching
count.
After resetting PFC will show “DONE” message on
display.
RESET BANK OPERATION TIME : Press ENTER key
RESET BANK OPERATION to entered into submenus.. Then press UP or DOWN
TIME ( INDIVIDUAL / ALL ) key get available options. Then pressed ENTER key
to reset individual, all bank operation count.
After resetting PFC will show “DONE” message on
display.
Section 11.5 : MODBUS SETUP :
This menu allows user to set modbus related setup.
MODBUS SETUP
Press ENTER key to enter into modbus setup sub menus.
Pressing UP or DOWN key will scroll through submenus.

BAUD RATE : Press ENTER key to edit baud rate.


Press UP or DOWN key to get available options. Then
BAUD RATE
pressing ENTER key will confirm newly changed values.
Value are settable as 4.8k, 9.8k, 19.2k, 38.4k, 57.6kpbs.

PARITY : Press ENTER key to edit parity.


PARITY
Press UP or DOWN key to get available options. Then
pressing ENTER key will confirm newly changed parity.
parity are settable as none, even, odd.

STOP BITS : Press ENTER key to edit stop bits.


STOP BITS
Press UP or DOWN key to get available options. Then
pressing ENTER key will confirm newly changed values.
stop bits are settable as 1 or 2.

DEVICE ADDRESS : It allows to set RS 485 address for


DEVICE ADDRESS PFC.
Address are settable in range 1 to 247.
Press ENTER key to edit device address.
Pressing UP or DOWN key will increment or decrement
digit value resp. Then pressing ENTER key will advance to
next digit & confirm newly changed values.
Section 11.6 : DISPLAY SETUP :
This menu allows user to set display related submenus.
DISPLAY SETUP
Press ENTER key to enter into display setup sub menues.
Pressing UP or DOWN key will scroll through submenus.

LCD BACKLIGHT : PFC allows to ON / OFF LCD backlight.


LCD BACKLIGHT
If backlight is set to off mode, APFC unit will switch off
backlight after 30 Sec. During editing period backlight
will get switch on & remained ON for next 30 Sec.

AUTOSCROLL: APFC unit allows to enable / disable screen


AUTOSCROLL
scrolling.Press ENTER key to edit autoscroll mode.
Press UP or DOWN key to get available options. Then
pressing ENTER key will confirm newly changed autoscroll

CONTRAST: APFC unit allows to set LCD contrast. It is


CONTRAST settable in range 1 to 9.
Press ENTER key to edit LCD contrast.
Pressing UP or DOWN key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed contrast.
Section 11.7 :CHANGE PASSWORDS:
To change Basic setting’s password and Advanced
CHANGE PASSWORD setting’s password enter correct password of
Advanced Setting.
After entering Advanced Setting’s correct password,
PFC enters into advanced setting’s sub-menues.
Pressing UP or DOWN key will scroll through Advanced
setting’s sub-menues. Select “CHANGE PASSWORDS”
sub-menu, Press ENTER key to enter into Change
Password’s sub menus. Pressing UP or DOWN key will
scroll through Basic password, Advanced Password
menu.

BASIC PASSWORD:
Press ENTER key to edit basic password.
BASIC PASSWORD
Pressing UP or DOWN key will increment or decrement
digit value. Then pressing ENTER key will advance to
next digit & confirm newly changed password.
To re-edit password, follow the same procedure as
mentioned.

ADVANCE PASSWORD:
Press ENTER key to edit advanced password.
ADVANCE PASSWORD Pressing UP or DOWN key will increment or decrement
digit value. Then pressing ENTER key will advance to
next digit & confirm newly changed password.
To re-edit password, follow the same procedure as
mentioned.
Section 12 : SERVICE MODE :
Press ENTER key to entered into service sub menus.
SERVICE MODE Pressing UP or DOWN key will scroll through
submenus.
The following sub menus will be available in service sub
menus : -
1. V -MIN V-MAX
2. I -MIN I -MAX
3. Frequency- MIN MAX
4. Temperature Min MAX
5. Maximum V THD I THD
6. Maximum Import Active power
7. Maximum Export Active power
8. Maximum Capacitive power
9. Maximum Inductive power
10. Maximum Apparent power
11. Maximum Import demand
12. Maximum Export demand
13. Maximum Apparent demand
14. Maximum Ampere demand
15. C1 to C8* Switching count
16. C1 to C8* Operation time
17. C1 to C8*
Auto Initialization detected capacitor KVAr value
18 TEST RUN
19.SHOW FAULT LOG

* As per configuration ( Maximum relay can be 8 )


TEST RUN:
This menu point allows the user to check the settings of the PFC controller.
After activation of the test run, PFC checks if any fault condition present then
message will be displayed as INPUT FAULT TESTRUN ABORTED
For fault condition banks are not switched ON.
PFC switches each stage on and off successively and calculates the output of
the capacitors connected (this procedure is done three times to eliminate
possible errors).
kvar of capacitor bank can be seen while test run in process.
Any discrepancies in bank parameters found are evaluated and displayed in
plain text.
The following errors can be displayed:

UNSTABLE LOAD
CHECK CAPACITOR POWER!!!
CHECK CAPACITOR COUNT ..... No capacitor detected on any of the output

Note: The results displayed are messages intended to help the user trace the
cause of the error. Final evaluation remains the responsibility of the user.
Under complicated (high load fluctuations) grid conditions, 100% error
recognition cannot be guaranteed.
Section 13 : TECHNICAL DATA :
- Large and multifunctional LCD
Display (2 × 16 characters)
- Graphic and alphanumeric
- LCD illumination
- Line voltage (V AC)
System parameters - Reactive power (VAr)
displayed - Active power (W)
- Frequency (Hz)
- Apparent power (VA)
- Line current (A)
- Temperature (°C)
- Real-time cos phi
- Diff to PF
- THD – V / THD - I in % upto 31st
- Individual Harmonics in % upto
31st for V & I
- Energy kWh (Import/ Export)
- Energy kVAh
- Energy kVARh (Ind /Cap)
- Demand kVA/Current/kW (Imp / Exp)
- Run Hour
- On Hour
- No of interruption
- RTC time.
- System Fault 1/2.
- System Warning
Alarm output - Out of Bank (Under
Compensation)
- Overcompensation
- Under Voltage
- Over Voltage
- Undercurrent
- Overcurrent
- Over temperature
- Under / Over Frequency
- Excess Harmonics ( V-THD / I- THD)

Recall recorded values - Maximum / Minimum Voltage


- Maximum / Minimum Current
- Maximum / Minimum Frequency
- Maximum Active Power (Import
/ Export)
- Maximum Apparent Power
- Maximum Capacitive Power
- Maximum Inductive Power
- Maximum Active Import Demand
- Maximum Active Export Demand
- Maximum Apparent Demand
- Maximum Ampere Demand
- Maximum / Minimum
Temperature
- Maximum THD(V/I)
- Switching count of Capacitor
- Operation time of capacitor
- Capacitor switching count exceed
the limit (OSC - Over Switching
Count)
- Capacitor kVAr value between 70
Warning Messages to 80% (CVAL)
- Ambient temperature between
55 to 60 Degree Cel. (TMP)
- RTC Battery Low (BAT)
(Only applicable for RTC module)

Weight 0.35 kg

Panel-mounted 96 × 96 × 51 mm
(Back Depth 75mm with add on
Dimensions
module)
(cut out 92 +0.8× 92+0.8 mm)

Ambient conditions
- Over-voltage class III
- Pollution degree 2
- Operating temperature –10 ... +60 °C
- Storage temperature –20 ... +65 °C
- Sensitivity to EMC IEC61326-1:2012 Table–2
- Safety guidelines IEC 61010-1:2010
- Mounting position Flush Mounting
- Humidity class 15% … 95% non-condensing
Protection class
- Front plate IP54 to IEC60529
- Rear side IP20 to IEC60529
Operation
- Auxiliary Supply voltage 110 V AC – 550 V AC
- Auxiliary Supply Frequency 40 to 70 Hz
- Auxiliary VA burden(8 Relay) < 10 VA Approx.
- Target cos phi 0.8 ind. … 0.8 cap.
- Switching On & Off 10 s … 30 min
- Discharge Time 60 s … 30 min
Control modes self-optimized intelligent control
Measurement
- Measurement voltage range 30 ... 550 V AC (L–L / L–N)
- Fundamental frequency 50 / 60 Hz
- Input voltage burden < 0.3 VA Approx.
- Measurement current (CT) x/5 and x/1 Ampere onsite programmable
- Minimum measuring current 1 mA
- Maximum current 6 A (sinusoidal)
- Input current burden < 0.25 VA Approx.
Accuracy Current, voltage: 0.5% of nominal value
Active, Apparent, Reactive power: 1% of
nominal value
Active Energy : 1%
Apparent Energy : 1%
Reactive Energy : 2%
THD : ± 4%
Switching outputs
Relay outputs
- Number of outputs 6/8/12 steps available
- Switching voltage/Power Max. 250 VAC / 1000W
Alarm relay Potential-free contact
(Max. 250 VAC / 1000W)
Section 14 : FACTORY DEFAULT SETTING :

Description Default value

System Nominal Voltage 240 VLN

CT Primary 1000 Amp

CT Seconadry 5 Amp

System frequency 50 Hz

System type 3 Phase

PHASE I (refer flow chart) IL 1


PHASE V (refer flow chart) VL 1 - N - 00
Demand integration time 8 Min

Energy unit kWh, KVArh, KVAh

Energy Rate 1 Min

Energy Overflow Count 8

Node address 1

Rs485 setup code 9600, none, 2

PHASE CORR. ANGLE USER SETTINGS

CAPACITOR KVAr DIRECT KVAr


Section 14 : FACTORY DEFAULT SETTING :
Basic Password 0000
Advanced Password 0001

Autoscroll OFF
Backlite ON/OFF ON
Contrast level 5

Target power factor 0.995 Ind

Banks in use 4
Maximum Switching Power 25 kVAr

Capacitor bank 1 kvar 25

Capacitor bank 2 kvar 25

Capacitor bank 3 kvar 25

Capacitor bank 4 kvar 25

AUTO INIT NO
CONTROL SERIES 1

Depending on model number of capacitor bank count changes max is 8


Description Default value

Bank switching Threshold 66%

Capacitor switch in time 40 Sec

Capacitor switch off time 40 Sec

Capacitor discharge time 60 Sec

Capcitor bank 1 (Auto/Fixed/Faulty) Auto

Capcitor bank 2 (Auto/Fixed/Faulty) Auto

Capcitor bank 3 (Auto/Fixed/Faulty) Auto

Capcitor bank 4 (Auto/Fixed/Faulty) Auto

C-health test (enable/disable) Disable

Switch_operation_warning 50000

C Health test count 5


Fault Description Default
Enable Parameter (*) Enable
Trip Value 85%
Under Voltage 5 Sec
Trip Delay (*)
Hysteresis (*) 3%
Relay Yes
Enable Parameter (*) Enable
Trip Value 110%
Over Voltage Trip Delay (*) 5 Sec
Hysteresis (*) 2%
Relay Yes
Enable Parameter Disable
Trip Value 6%
Under Frequency
Trip Delay (*) 5 Sec
Hysteresis (*) 1%
Relay No
Enable Parameter Disable
Trip Value 6%
Over Frequency
Trip Delay (*) 5 Sec
Hysteresis (*) 1%
Relay No
*Note : - Parameters are not editable, Factory set.
Fault Description Default
Enable Parameter (*) Enable
Trip Value 2%
Under Current
Trip Delay (*) 5 Sec
Hysteresis (*) 1%
Relay Yes
Enable Parameter (*) Enable
Trip Value 110%
Over Current Trip Delay (*) 5 Sec
Hysteresis (*) 1%
Relay Yes
Enable Parameter (*) Enable
Trip Value 7%
V THD
Trip Delay (*) 30 Sec
Hysteresis (*) 2%
Relay Yes
Enable Parameter (*) Enable
Trip Value 50%
I THD
Trip Delay (*) 30 Sec
Hysteresis (*) 45%
Relay Yes
*Note : - Parameters are not editable, Factory set.
Fault Description Default
Enable Parameter (*) Enable
Trip Value (*) 60 Degree
Temperature
Trip Delay (*) 10 Sec
Hysteresis (*) 55 Degree
Relay Yes
Enable Parameter (*) Enable
Out Of bank Trip Delay (*) 10 Sec
Relay Yes
Enable Parameter (*) Enable
OverCompensation Trip Delay (*) 10 Sec
Relay Yes

*Note : - Parameters are not editable, Factory set.


Section 15 : OPERATING DIAGRAM :

Menu Key (M)

Enter Key (E)

Up Key (U)

Down Key (D)

MENU KEY PRESS

G H

D U

DISPLAY
M E
PARAMETER BASICSETTINGS
BASIC SETTING BASIC SUB MENU

D U
M E
DISPLAY ADVANCE SETTING ADVANCE SUB
PARAMETER
ADVANCE
MENU

D U

DISPLAY
M E
PARAMETER SERVICEMODE
SERVICE MODE SERVICE SUB MENU

G H
BASIC SUBMENU

Note -
EDIT ENTER PASSWORD
- 0000
IF CAPACITOR KVAR OPTION IS CONTROL
SERIES THEN ONLY FIRST CAPACITOR BANK
KVAR NEED TO SET.
No
PASSWORD CORRECT

IF CAPACITOR KVAR OPTION SELECTED AS


J
YES
K DIRECT KVR THEN ALL BANK KVAR NEED TO
D OR U D U SET
E M
EDIT CT PRIMARY
IF CAPACITOR KVAR OPTION SELECTED AS
D OR U D U AUTO DETECTED THEN BANK IN USE OPTION ,
E M
EDIT CT SECONDARY CAPACITOR KVAR SET OPTION DISAPPEAR
D OR U D U AND SETTING IS NOT REQUIRED BECAUSE
E M VALUES ARE SELECTED FROM
EDIT AUTO INIT
AUTO INITIALISATION FUNCTION.
D OR U D U
E M
EDIT SYS NOM VOLTAGE

D OR U D U BASIC SETTING
E M
CAPACITOR KVAr
EDIT

D OR U D U
E M UPON SUCCESSFUL AUTO-INITLISATION THE CAPACITOR
PHASE CORR. ANGLE
EDIT
KVAR OPTION GETS CHANGE TO AUTO DETECTED
D U AND PHASE CORRECTION ANGLE OPTION GETS
H
NO
AUTO DETECTED OPTION
NO
CONTROL SERIES OPTION
CHANGED TO AUTO DETECTED.
THIS IS DONE TO MINIMISE MANUAL INTERVENTION
YES YES AND ALLOW FULLY AUTOMATIC OPERATION OF
J , K CONTROL SER. POWER FACTOR CORRECTION.
H
D OR U D U
M
EDIT CAP. BANKS IN USE
E
D OR U D U
E M
EDIT CAP [n] POWER

D U
J K
ADVANCE SUB MENU

D OR U

EDIT ENTER PASSWORD - 0001

NO
PASSWORD CORRECT?

L N

D U
E M
SYSTEM SUB SETUP SYSTEM SETUP

D U
E M
MANUALSUB SETUP MANUAL SETUP

D U
E M
ALARM SUB SETUP ALARM SETUP

D U
E M
RESET SUB SETUP RESET VALUES ADVANCE SETTING

D U
E M
MODBUS SUB SETUP MODBUS SETUP

D U
E M
DISPLAY SUB SETUP DISPLAY SETUP

D U
CHANGE PASSWORD
E M
CHANGE PASSWORDS
SUB SETUP

L N
SYSTEM SUB SETUP

O P

D OR U D U
E M
EDIT TARGET PF

D OR U D U
E M
EDIT SWITCH-IN-TIME

D OR U D U
E M
EDIT SWITCH OFF TIME

D OR U D U
E M
EDIT DISCHARGE TIME

D OR U D U
E M
EDIT THRESHOLD

D OR U D U
E SWITCHING OPERATION M
EDIT SYSTEM SETUP
WARNING COUNT

D OR U D U
E M
EDIT CAP.HEALTHCHECK

D OR U
D U
E CAPACITOR TEST M
EDIT
ATTEMPTS COUNT

D U
D OR U
E M
EDIT SYSTEM FREQUENCY

D OR U D U
E M
EDIT SYSTEM TYPE

D U
Q R
Q R

D OR U D U
E M
EDIT * INPUT PHASE CURRENT

D OR U D U
E M
EDIT * INPUT PHASE VOLTAGE

D OR U D U

EDIT
E ENERGY DEMAND M
INTEGRATION TIME

D OR U D U
EDIT
E M
ENERGY UPDATE RATE

D OR U D U
E M
EDIT ENERGY UNIT SYSTEM SETUP

D OR U
D U

EDIT
E ENERGY OVERFLOW M
COUNT

D OR U D U
E M
EDIT #RTC DATE, TIME

D U
D OR U
E M
EDIT DEFAULT SYSTEM VALUES

D OR U D U
E M
EDIT MAX SWITCH POWER

Note : - # RTC menu will be shown only when RTC


module is present
O P *Note: - Refer Network Table
Network Table :-
PHASE CURRENT PHASE VOLTAGE
IL1 L1 - N - 0
IL1 L1 - L2 - 30
IL1 ( k <- > l ) L2 - N - 60
IL1 L3 - L2 - 90
IL1 L3 - N - 120
IL1 L3 - L1 - 150
IL1 ( k <- > l ) L1 - N - 180
IL1 ( k <- > l ) L1 - L2 - 210
IL1 L1 - N - 240
IL1( k <- > l ) L3 - L2 - 270
IL1 ( k <- > l ) L3 - N - 300
IL1 ( k <- > l ) L3 - L1 - 330
PHASE CURRENT PHASE VOLTAGE
IL2 L2 - N - 0
IL2 L2 - L3 - 30
IL2 ( k <- > l ) L3 - N - 60
IL2 L1 - L3 - 90
IL2 L1 - N - 120
IL2 L1 - L2 - 150
IL2 ( k <- > l ) L2 - N - 180
IL2 ( k <- > l ) L2 - L3 - 210
IL2 L3 - N - 240
IL2 ( k <- > l ) L1 - L3 - 270
IL2 ( k <- > l) L1 - N - 300
IL2 ( k <- > l ) L1 - L2 - 330
PHASE CURRENT PHASE VOLTAGE
IL3 L3 - N - 0
IL3 L3 - L1 - 30
IL3 ( k <- > l ) L1 - N - 60
IL3 L2 - L1 - 90
IL3 L2 - N - 120
IL3 L2 - L3 - 150
IL3 ( k <- > l ) L3 - N - 180
IL3 ( k <- > l ) L3 - L1 - 210
IL3 L1 - N - 240
IL3 ( k <- > l ) L2 - L1 - 270
IL3 ( k <- > l ) L2 - N - 300
IL3 ( k <- > l ) L2 - L3 - 330
MANUAL SUB-MENU

a b
D U
D OR U
E BANK
BANKONON
/ OFF
/ OFF
M MANUAL SETUP
EDIT
Edit ( MANUALLY )
( MANUALLY )

MANUAL SETUP
D U
D OR U

E SET BANK
BANKS OPERATE
FUNCTIONS AS M
EDIT
Edit MODE
AUTO / FIXED / FAULTY
(AUTO/FIXED/FAULTY)

a b

NOTE -

if CAPACITOR KVAR OPTION in basic settings is selected as DIRECT


KVAR or CONTROL SERIES then manual switching of bank and setting
bank mode menu is available
if CAPACITOR KVAR OPTION is selected as AUTO DETECTED then
modes of all capacitor banks are evaluated in auto initialization function,
and bank operate mode menu is not available.
ALARM SUB MENU

L K
D U
E M
SUB MENU #1 UNDERVOLTAGE

D U
E M
SUBMENU#2 OVER VOLTAGE

D U
E M
SUBMENU #3 FREQUENCY FAULT

D U
E M
SUB MENU#4 UNDER CURRENT

D U
M
E
SUBMENU #5 OVER CURRENT

D U
E M
SUB MENU#6 VOLTAGE THD ALARM SETUP

D U
E M
SUBMENU #7 CURRENT THD

D U
E M
SUB MENU #8 TEMPERATURE

D U
E M
SUBMENU#9 OVERCOMPENSATION

D U
E M
SUB MENU#10 OUT OF BANKS

D U
E M
SUBMENU #11 *BATT.LOWFAULT

*Note : Only applicable for RTC


L K module.
SUB MENU #1

a b

D OR U
E BANK ON / OFF M MANUAL SETUP
TRIGGER VALUE
EDIT
Edit ( 75 - 90) ) %
( MANUALLY

UNDER VOLTAGE
D OR U D U
E M
EDIT RELAY ACTIVATION

a b

SUB MENU #2

c d

D OR U
E BANK ON / OFF M MANUAL SETUP
TRIGGER VALUE
EDIT
Edit ( 105 - 115
( MANUALLY ) )%

OVER VOLTAGE
D OR U D U
E M
EDIT RELAY ACTIVATION

c d
SUB MENU #3

c d

D OR U
E BANK ON / OFF M MANUAL SETUP
TRIGGER VALUE
EDIT
Edit ( 2 - 10 ) )%
( MANUALLY

FREQUENCY.FAULT
D OR U D U
E M
EDIT RELAY ACTIVATION

c d

SUB MENU #4

e f

D OR U
E BANK ON / OFF M MANUAL SETUP
TRIGGER VALUE
EDIT
Edit ( 1 - 3 ) %)
( MANUALLY

UNDER CURRENT
D OR U D U
E M
EDIT RELAY ACTIVATION

e f
SUB MENU #5

c d

D OR U
E BANK ON / OFF M MANUAL SETUP
TRIGGER VALUE
EDIT
Edit ( 60 - 120) ) %
( MANUALLY

OVER CURRENT
D OR U D U
E M
EDIT RELAY ACTIVATION

c d

SUB MENU #6

e f

D OR U
E BANK ON / OFF M MANUAL SETUP
TRIGGER VALUE
EDIT
Edit ( 1 - 25 ) )%
( MANUALLY

VOLTAGE-THD
D OR U D U
E M
EDIT RELAY ACTIVATION

e f
SUB MENU #7

c d

D OR U
E BANK ON / OFF M MANUAL SETUP
TRIGGER VALUE
EDIT
Edit ( 1 - 99 ) %
( MANUALLY )

CURRENT-THD
D OR U D U
E M
EDIT RELAY ACTIVATION

c d

SUB MENU #8

D OR U
E M
EDIT RELAY ACTIVATION TEMPERATURE
SUB MENU #9

D OR U
E M
EDIT RELAY ACTIVATION OVER-COMPENSATION

SUB MENU #10

D OR U
E M
EDIT RELAY ACTIVATION OUT OF BANK

SUB MENU #11

D OR U
E M
EDIT ACTIVATE WARNING BAT LOW WARNING
RESET SUB MENU

L K
D U
E M
DONE RESET ENERGY

D U
E M
DONE RESET DEMAND

D U
E M
DONE RESET MIN PARA

D U
E M
DONE RESET MAX PARA

D U
M
DONE
E
RESET ON-RUN HOUR

D U
E M
DONE RESET PD INTERRUPT RESET VALUES

D U

E RESET BANK
SWITCHING COUNT M
DONE
( INDIVIDUAL / ALL )

D U

E RESET BANK
DONE M
OPERATION TIME
( INDIVIDUAL / ALL )

D U

E M
DONE RESET FAULT LOGS

L K
MODBUS-SETUP

O P

D OR U D U
E M
EDIT SELECT BAUD RATE

D OR U D U
E M
EDIT PARITY

MODBUS-SETUP
D OR U D U
E M
EDIT STOP BITS

D OR U D U
E M
EDIT DEVICE ADDRESS

D OR U D U
O P

DISPLAY-SETUP

A B

D OR U D U
E M
EDIT LCD BACKLIT

D OR U D U
E M
EDIT AUTO SCROLL DISPLAY-SETUP

D OR U D U
E M
EDIT CONTRAST

D OR U D U
A B
CHANGE PASSWORD-SETUP

A B

D OR U D U
E M
EDIT BASIC PASSWORD

D OR U D U CHANGE PASSWORD SETUP


E M
EDIT ADVANCED PASSWORD

D OR U D U
A B
C F
D U
M
MAX ACTIVE POWER EXPORT DEMAND

D U
M
MAX APPARENT POWER DEMAND

D U
M
MAX AMPERE DEMAND

D U
M
BANK SWITCHING COUNT
(1- NUMBER OF CAP. BANKS)

D U
M
BANK OPERATION TIME
(1- NUMBER OF CAP.BANKS)
SERVICE MODE

D U
M
CAPACITOR KVAr POWER
(1- NUMBER OF CAP. BANKS)

D U
M
TEST RUN

D U
M
VIEW FAULT LOG

D U
L K
SERVICE SUB MENU

L K
D U
M
VOLTAGE MIN MAX

D U
M
CURRENT MIN MAX

D U
M
FREQUENCY MIN MAX

D U
M
TEMPERATURE MIN MAX

D U
M
MAX V-THD I-THD

D U
M
MAX IMPORT ACTIVE POWER SERVICE MODE

D U
M
MAX EXPORT ACTIVE POWER

D U
M
MAX REACTIVE CAP. POWER

D U
M
MAX REACTIVE IND. POWER

D U
M
MAX APPARENT POWER

D U
M
MAX ACTIVE POWER IMPORT DEMAND

C F
VIEW FAULT LOG

L K
D U
E M
SUB MENU#1 UNDERVOLTAGE

D U
E M
SUBMENU#2 OVER VOLTAGE

D U
E M
SUBMENU #3 FREQUENCY FAULT *

D U
E M
SUB MENU#4 UNDER CURRENT

D U
M
E
SUBMENU #5 OVER CURRENT

D U
E M
SUB MENU#6 VOLTAGE THD VIEW FAULT LOG

D U
E M
SUBMENU #7 CURRENT THD

D U
E M
SUB MENU #8 TEMPERATURE

D U
E M
SUBMENU#9 OVERCOMPENSATION

D U
E M
SUB MENU#10 OUT OF BANKS

D U
E M
SUBMENU #11 POWER DOWN COUNT

L K * FREQUENCY FAULT IF ENABLED


THEN ONLY CAN BE SEEN
VIEW FAULT LOG
SUB MENU #1-11

M
FAULT LOG COUNT SUB MENU #1-11
LOG1 DATE TIME ^

FAULT LOG COUNT


LOG2 DATE TIME ^

FAULT LOG COUNT ^ TIME DATE ONLY FOR RTC MODEL


LOG3 DATE TIME ^
DISPLAY PARAMETERS

L K
D U
M
MAIN SCREEN SYS PF / FAULT / BANK STATUS

D U
M
LINE VOLTAGE

D U
M
LINE CURRENT

D U
M
REACTIVE POWER

D U
M
ACTIVE POWER

D U
M
APPARENT POWER MAIN PF SCREEN
D U
M
DIFF. TO POWER FACTOR KVAr

D U
M
LINE FREQUENCY

D U
M
V- THD I-THD

D U
M
INDIVIDUAL. V[1-31] I[1-31] HARMONICS #

D U
M
KWH IMPORT

#Note : Use Enter key at individual harmonics screen then


C F
Press UP OR DOWN key to get next harmonics number
use Menu key to exit
C F
D U
M
KWH EXPORT

D U
M
kVARh INDUCTIVE

D U
M
kVARh CAPACITIVE

D U
M
kVAh

D U
M
AMPERE DEMAND

D U
M
ACTIVE POWER DEMAND IMPORT MAIN PF SCREEN
D U
M
ACTIVE POWER DEMAND EXPORT

D U
M
APPARENT POWER DEMAND

D U
M
TEMPERATURE

D U
M
RUN HOUR [HH:MM]

D U
M
ON HOUR [HH:MM]

X Y
X Y
D U
M
TIME AND DATE ^

D U
M
POWER DOWN COUNT AND TIME,DATE ^

D U
M
SYSTEM FAULTS-1

D U MAIN PF SCREEN
M
SYSTEM FAULTS-2

D U
M
SYSTEM WARNING

L K

^Note : - Only applicable for RTC module

Version I-7/19
Version I-7/19