Letter of Conformity for Grid Support
Interactive Inverter
UL STANDARD No. 1741-THIRD EDITION SUPPLEMENT SA
Reference Certificate: 70043714 Master Contract: 203213
Project: 80158407 Date Issued: 2023-02-17
Issued to: Fronius International GmbH
Guenter Fronius Strasse 1
Wels-Thalheim, 4600
AUSTRIA
The products listed below have been found to comply with the applicable
requirements of UL 1741- Third Edition (Rev. September 28, 2021)
Supplement SA - GRID SUPPORT UTILITY INTERACTIVE INVERTERS
AND CONVERTERS.
Thian (Peter) Lim
Issued by:
Thian (Peter) Lim
Transformerless Special Purpose Grid Support Interactive Inverter, Models Fronius Primo 10.0-1 208-240,
Fronius Primo 11.4-1 208-240, Fronius Primo 12.5-1 208-240, and Fronius Primo 15.0-1 208-240, permanently
connected.
For details related to rating, reference should be made to the CSA Certification Record, the Descriptive Report or
Annex A Ratings for Certificate of Conformance.
APPLICABLE REQUIREMENTS
*UL Std No. 1741- Third Edition - Inverters, Converters, Controllers and Interconnection System Equipment
For Use With Distributed Energy Sources (Rev. September 28, 2021)
*Note: Conformity to UL 1741-Third Edition (Rev. September 28, 2021) includes compliance with applicable
requirements of UL1741 Supplement SA 8 to SA 15 - GRID SUPPORT UTILITY INTERACTIVE INVERTERS
AND CONVERTERS, California Rule 21(SRDs), Hawaiian Electric Co. Rule 14, Hawaiian Electric Co. SRD-
UL-1741-SA-V1.0, IEEE 1547:2003, IEEE 1547a and IEEE 1547.1:2005
DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved. Page 1
Reference Certificate: 70043714 Master Contract: 203213
Project: 80158407 Date Issued: 2023-02-17
Supplement to Letter of Conformity for Grid Support Interactive Inverter
Firmware Revision:
Fronius Primo 15.0-1 208-240 (representative of series)
Product Tested
Device
Device Software Version (release date) Device Checksum
Manufacturer/Type
V0.3.7.0 (07/14/2015) 033D2FB7BE
3E4429E74E
4B9B77DB18
25A1F7162B
V0.3.8.2 (10/09/2015) DAEC969571
B126D12202
800383CC19
ReCerbo (U2 on 6A0D971C36
ReCerbo) V0.3.10.2 (05/04/2016) B5754C2321
ST Microelectronics /
283AA8E595
STM32F437IIH6
90C8889239
(U2)
3F26194BCB
0xE3492C0519
0xAE4F1889BC
V0.3.14.9 (2020-06-18)
0x7AC2223564
0xDBD515D7FA
0x42C2680BD0
0xDA43B99DD2
V0.3.25.0 (2020-11-30)
0xEE36096821
0xEF8FE850F1
PS1 – Roach (U4 on V0.18.8.3 (08/21/2015) 0x7d2799ea
ROACH03) ST Microelectronics / V0.18.16.3 (10/14/2015) 0xc182aa5f
STM32F405ZG (U4) V0.18.46.3 (29/03/2016) 0x66FFBF09
Alterative:
V0.18.50.3 (26/07/2016) 0x04c39395
ST Microelectronics /
STM32F407XX(U4) V0.26.16.0 (10/07/2017/ 0x5dca92ea
V1.5.1.1 (2021-02-11) 0xffc6b806
V0.6.18.4 (08/21/2015) 0xea600a4
V0.6.26.4 (10/09/2015) 0xeca75edd
PS2 – Guard (U7 on
V0.6.32.4 (07/04/2016) 0x2283EDD6
PRIMOFIL15) ST Microelectronics / V0.6.34.4 (10/06/2016) 0x3a229e91
STM32F415VG (U7)
V0.10.7.0 (05/09/2017) 0x998c8938
V0.10.9.0 (10/11/2017) 0xab23f31a
V0.11.8.1 (2021-03-09) 0xea584008
DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved. Page 2
Reference Certificate: 70043714 Master Contract: 203213
Project: 80158407 Date Issued: 2023-02-17
Tests were performed on model Fronius Primo 15.0-1 208-240 (representative of series), at Fronius International
GmbH, Guenter Fronius Strasse 1, Wels-Thalheim, 4600 Austria under the CSA SMTC program.
The following tests were performed under the requirements of UL 1741- 3rd Edition with SUPPLEMENT SA -
GRID SUPPORT UTILITY INTERACTIVE INVERTERS AND CONVERTERS (September 28th, 2021) with
acceptable results:
General Overview of UL 1741 Evaluations:
UL 1741 3rd Edotion
With SUPPLEMENT SA - GRID SUPPORT UTILITY INTERACTIVE INVERTERS AND CONVERTERS
UL1741 – SA Applicable Requirement/Topic Comment
UL1741 - SA8 Anti-islanding Protection - Unintentional Islanding with Grid PASS
Support Functions Enabled
UL1741 - SA9 L/HVRT Low and High Voltage Ride-Through PASS
UL1741 - SA10 L/HFRT Low and High Frequency Ride-Through PASS
UL1741 - SA11 RR – Normal Ramp Rate and SS – Soft-Start Ramp Rate PASS
UL1741 - SA12 SPF – Specified Power Factor PASS
UL1741 - SA13 Volt/VAr Mode (Q(V) PASS
UL1741 - SA14 Frequency-Watt (FW) – Optional PASS
UL1741 - SA15 Volt-Watt (VW) – Optional PASS
Grid Support Interactive Inverters certified with Reactive Power Priority
Inverter Manufacturer Co New Model numbers to be li Question Question Question
mpany Name sted with CEC list[Nominal #1 (Y/N) #2 (Y/N) #3 (Y/N)
Voltage]
Fronius International GmbH Fronius Primo 10.0-1 208-240, Y Y
Fronius International GmbH Fronius Primo 11.4-1 208-240, 0 Y Y
Fronius International GmbH Fronius Primo 12.5-1 208-240 Y Y
Fronius International GmbH Fronius Primo 15.0-1 208-240 Y Y
DQD 507 Rev. 2019-04-30 © 2018 CSA Group. All rights reserved. Page 3
Reference Certificate: 70043714 Master Contract: 203213
Project: 80158407 Date Issued: 2023-02-17
Product Certification History
Project Date Description
80158407 2023-02-17 Update report 70043714 to include alternate Fuse holder, Line to ground
cap, opto isolator, PTC, alternate fan, and Current sensor with the same
form, fit and function or better specification. Due to the nature of the above
changes, no further testing is deemed necessary.
80106345 2022-03-26 Update report 70043714 to include software bugfixes and some alternative
omponents.
80048720 2020-07-20 Update report 70043714 to include new RECEBRO Firmware revision
number for the increase in initial programing initialization timing slot from
80ms to 125 ms to accommodate hardware tolerances. The change on this
parameter has no impact on grid tie and factory testing except factory
programing’s initialization timing. Therefore, no further testing is deemed
necessary.
80045323 2020-06-15 Update report 70043714 to include an alternate MCUs which is identical to
the original model STM32F405 except alternate Micro STM32F407 has two
additional features (I.e. Ethernet + camera interface which are not deployed).
Since firmware version remains the same and the hardware functional
features including form and fit are compatible, no further testing is deemed
necessary
70163420 2017-12-22 Update report 70043714 to evaluate firmware changes that address software
bugs associated with Filter stage changes issues.
70130882 2017-09-22 Update Primo Series (10KW-15KW) Report 70043714 to include new
UL1741 SA.