Drawing Portion of IRSEM-20

The document provides detailed specifications and reinforcement details for the construction of RCC cable markers, including dimensions and materials required. It outlines the engraving and painting requirements for the markers, as well as the concrete mix specifications for installation. Additionally, it specifies the placement intervals for the cable markers in different sections.

Uploaded by

Ashish Gupta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views1 page

Drawing Portion of IRSEM-20

The document provides detailed specifications and reinforcement details for the construction of RCC cable markers, including dimensions and materials required. It outlines the engraving and painting requirements for the markers, as well as the concrete mix specifications for installation. Additionally, it specifies the placement intervals for the cable markers in different sections.

Uploaded by

Ashish Gupta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Drg.No.

15-D1
DRAWING FOR RCC CABLE MARKER
REINFORCEMENT DETAILS FOR RCC CABLE MARKER

70 6 MM DIA. M.S.ROD 1 No. OF LENGTH


1650 MM APPROXIMATELY BENT AT
300 IR 70
50
THE TOP AS SHOWN IN THE SKECH.
100 3D VIEW
50 TOP VIEW
SIG. 70 250
40 150
50

200 500

6 MM DIA. M.S. TIE ROD 2 Nos. 250


OF LENGTH 250 MM.
450 300 50
50
80 200 300
200
100 8 MM DIA. M.S. ROD 1 No. OF LENGTH
800 MM APPROXIMATELY 250
6 MM DIA. M.S. ROD OF 500
150 LENGTH 450 MM 50
50
1 VERTICAL MS RODS OF 8 MM Dia.,
50 50 150 MM HEIGHT : 08 NUMBERS
100 100 2 HORIZONTAL MS RINGS (350 x 350)
500 OF 8 MM Dia. : 01 NUMBERS

200
CONCRETE SKIRTING FOR PLACING ON CABLE MARKER
50

50
IR 300

SIG
200 100

50
350
600
200

150
500
64 150
300
NOTE:-

NOTE:- 1. ALL DIMENSIONS ARE IN MILLI METER.


1. ALL DIMENSIONS ARE IN MM. 2. PAINTED WHITE LETTERS ON RED BACK GROUND
2. CABLE MARKER SHALL BE ENGRAVED WITH IR SIG / IR QUAD / IR OFC AS THE CASE MAY BE OF 2.8" (70 MM) HEIGHT.
3. FOUNDATION CONCRETE OF 300 MM FROM THE BASE OF THE
3. CABLE MARKERS SHALL BE PAINTED IN RED COLOR PAINT FOR SIGNALLING CABLES
MARKER SHALL BE DONE AT SITE AT ALL PLACES WITH MIX 1:3:5.
ENGRAVED LETTERS SHALL BE PAINTED IN WHITE COLOR CEMENT PAINT.
4. COMPONENT CONCRETE SHALL BE OF M25 MIX AND WIRE
4. AFTER PLACING PRECAST RCC SKIRTING ON THE PRECAST RCC MARKER AS SHOWN, GAP
BETWEEN THE CABLE MARKER AND SKIRTING SHALL BE FILLED WITH RICH MORTAR. MESH OF 1.5 MM THICK MESS SHALL BE USED.
5. THE PROPORTION FOR CEMENT, SAND & JELLY SHALL BE 1:2:4 WITH 6 MM TO 10 MM GRANITE METAL. 5. THE ENGRAVING OF "RLY" & "SIG" SHALL BE DONE ON BOTH SIDES
6. FOR MILD STEEL THE SPECIFICATION IS IS:432. OF THE MARKER AND ENGRAVED SIDE SHALL BE PLACED
7. CABLE MARKERS SHALL BE PLACED AT AN INTERVAL OF 20 M WITH IN STATION SECTION AND 50 M IN BLOCK SECTION PARALLEL TO THE LENGTH OF CABLE ROUTE.
FOR GUIDANCE ONLY.
FOR GUIDANCE

Page 13 of 104