Basics of Hart Communicator
Posted on : February 13, 2018 By Areej
Instrumentation Instrumentation Tools
Introduction
HART is a master-slave communication protocol , which means that during normal operation, each slave
Bagging machines
Compatible with virtually all types of bags and
products
Premier Tech Open
https://automationforum.co/basics-hart-communicator/ 1/6
2/18/2020 Basics of Hart Communicator – Instrumentation and Control Engineering
x
INSTRUMENTATION PROCESS CONTROL AUTOMATION ANIMATION CALIBRATION ELECTRICAL QUIZ TOOLS VALVES
Corrugated Pipe Price List x
ANALYTICAL INSTRUMENTATION High strength,
ANDROID TOOLS High VIBRATION
quality. MEASUREMENT PLC HOW TO
Double Wall Corrugated Pipes | Best Quality
and Best Price for Contact Kuzeyboru. Buy
Now
kuzeyborugroup.com
OPEN
Innovation, precision, durability
made in Germany by Form + Test
Ad
(field device) communication is initiated by a master communication device. Two masters can connect to each
HART loop. The primary master is generally a distributed control system (DCS), programmable logic controller (PLC),
or a personal computer (PC). The secondary master can be a handheld terminal or another PC. Slave devices include
transmitters, actuators, and controllers that respond to commands from the primary or secondary master.in this
session we are going to discuss about Basics of Hart Communicator
THEORY
The HART Communicator is a menu driven system. Each screen provides a menu of options that can be selected
as outlined above, or provides direction for input of data, warnings, messages, or other instructions.
When the HART Communicator is turned on, one of two menus will appear.
If the HART Communicator is connected to an operating loop, the communicator will find the device and display
the Online Menu (see below).
If it is not connected to a loop, the communicator will indicate that no device was found. When you press OK
(F4), it will display the Main menu.
The Main Menu provides the following options:
Offline–saves or retrieves transmitter configuration information.
Online–connects the communicator to a compatible device
Frequency Device–The Frequency Device option displays the frequency output and corresponding pressure
output of current-to-pressure transmitters.
Utility–The Utility option provides access to the contrast control for the HART Communicator LCD screen and
to the auto poll setting used in multidrop applications.
https://automationforum.co/basics-hart-communicator/ 2/6
2/18/2020 Basics of Hart Communicator – Instrumentation and Control Engineering
Once selecting a main menu option, the HART Communicator provides the information you need to complete x
INSTRUMENTATION PROCESS CONTROL AUTOMATION ANIMATION CALIBRATION ELECTRICAL QUIZ TOOLS VALVES
the operation. x
The Online Menu can be selected from the main menu as outlined above, or it may appear automatically if the
ANALYTICAL INSTRUMENTATION ANDROID TOOLS VIBRATION MEASUREMENT PLC HOW TO
HART Communicator is connected to an active loop and can detect an operating transmitter.
On-line mode is used for direct evaluation of a particular meter, reconfiguration, changing parameters,
maintenance, and other functions.
The keys of the HART Communicator include action, function, and alphanumeric and shift keys.
Action Keys
ON/OFF Key Use this key to power the HART Communicator.
When the communicator is turned on, it searches for a transmitter on the 4–20 mA loop.
If a device is not found, the communicator displays the message, “No Device Found. Press OK.”
If a HART-compatible device is found, the communicator displays the Online Menu with device ID and tag
Directional Keys
Use these keys to move the cursor up, down, left, or right.
The right arrow key also selects menu options, and the left arrow key returns to the previous menu.
HOT Key
Use this key to quickly access important, user-selectable options when connected to a HART-compatible device.
Pressing the Hot Key turns the HART Communicator on and displays the Hot Key Menu.
See Customizing the Hot Key Menu in the HART Communicator manual for more information
Use the four software-defined function keys, located below the LCD, to perform software functions. On any Search
given menu, the label appearing above a function key indicates the function of that key for the current menu.
As you move among menus, different function key labels appear over the four keys. Search … S
For example, In menus providing access to on-line help, the label may appear above the F1 key. Simply press
the key to activate the function.
POPULAR POST
In menus providing access to the On-line Menu, the label may appear above the F3 key. Simply press the key to
activate the function. Basic troubleshooting of Electrical
components in MCC/Electrical
Alphanumeric and Shift Keys Control Panel/Switch Gear
March 30, 2014 15 Comments
The alphanumeric keys perform two functions: the fast selection of menu options and data entry.
What is the difference between
control panel and MCC?
May 26, 2011 12 Comments
P&ID (Piping and instrument
diagram) & PFD (Process flow
diagram).
December 11, 2010
12 Comments
What is a control panel?. What are
the components in a control panel?
March 14, 2011 11 Comments
https://automationforum.co/basics-hart-communicator/ 3/6
2/18/2020 Basics of Hart Communicator – Instrumentation and Control Engineering
,
x
INSTRUMENTATION PROCESS CONTROL AUTOMATION ANIMATION CALIBRATION ELECTRICAL QUIZ TOOLS VALVES
Basic Concept of PLC (Programmable x
logic controllers).
ANALYTICAL INSTRUMENTATION ANDROID TOOLS VIBRATION MEASUREMENT PLC HOW TO September 23, 2012
7 Comments
Data Entry
Some menus require data entry. Use the alphanumeric and shift keys to enter all alphanumeric information into
the HART Communicator. If we press an alphanumeric key alone from within an edit menu, the bold character
in the center of the key appears. These large characters include the numbers 0 through 9, the decimal point (.), Corrugated Pipe Price Lis
and the dash symbol (—).
To enter an alphabetic character, first press the shift key that corresponds to the position of the letter you High strength, High quality.
want on the alphanumeric Then press the alphanumeric key. Double Wall Corrugated Pipes | Best Quali
and Best Price for Contact Kuzeyboru. Buy
For example, to enter the letter R, first press the right shift key, then the “6” key (see Figure). Do not press Now
these keys simultaneously, but one after the other. kuzeyborugroup.com
Hart Communicator Connections OPEN
Categories
Analytical Instrumentation
Android Tools
Animation
Automation
Calibration
The HART Communicator Model 275 / 375 can interface with a transmitter from the control room, the Communication
instrument site, or any wiring termination point in the loop through the rear connection panel as shown in
Figure Control System
To communicate, connect the HART Communicator in parallel with the instrument or load resistor. The
control valve
connections are non-polarized.
Avoid contact with leads and terminals.
DCS
The HART Communicator needs a minimum of 250 ohms resistance in the loop to function properly. The HART
Communicator does not measure loop current directly. Displacement Measurement
Benefits outlined in this section include: ebooks
Improved plant operations Electrical
Operational flexibility
Flow Measurement
Instrumentation investment protection
Digital communication
How to
for know more about how to calibrate transmitters with hart communicator click the link belowCalibration procedure
of DPT transmitter
Humidity measurement
Instrumentation
Instrumentation Questions
https://automationforum.co/basics-hart-communicator/ 4/6
2/18/2020 Basics of Hart Communicator – Instrumentation and Control Engineering
Areej Instrumentation Tools x
INSTRUMENTATION PROCESS CONTROL AUTOMATION ANIMATION CALIBRATION ELECTRICAL QUIZ TOOLS VALVES
-- News Reporter
interview questions
ANALYTICAL INSTRUMENTATION ANDROID TOOLS VIBRATION MEASUREMENT PLC HOW TO
Level Measurement
P&ID
PLC
pressure
Basics of Vortex flowmeter BASIC CONTROL PRINCIPLES Pressure Measurement
Process Control
Temperature Measurement
Leave a Reply
temprature
You must be logged in to post a comment.
Tools
Uncategorized
Sponsored Content Valves
Vibration Measurement
whatis
Amazon Echo Show 8 launched in India: Nubia's 80W fast charging tech teased,
Check out price, features, release date could arrive on upcoming Red Magic 5G
India Today India Today
Recommended by
Corrugated Pipes Here
A Century for Service Life
Corrugated Pipes With Best Price and Best Quality Contact
Kuzeyboru to buy.
kuzeyborugroup.com
OPEN
https://automationforum.co/basics-hart-communicator/ 5/6
2/18/2020 Basics of Hart Communicator – Instrumentation and Control Engineering
report this ad
x
INSTRUMENTATION PROCESS CONTROL AUTOMATION ANIMATION CALIBRATION ELECTRICAL QUIZ TOOLS VALVES
Facebook Twitter Linkedin youtube Instagram
ANALYTICAL INSTRUMENTATION
ANDROID TOOLS
VIBRATION MEASUREMENT PLC HOW
TO
Like us on facebook Tweet us on twitter Join us on Linkedin Subscribe us on youtube Join us on instagram
Recent Post Random Post Recent Comments Quizzes
How to select an 4-20mA Analog Inputs MOHAMMED-ECE on Documents Instrumentation - Control Sys
actuator for valve? from Transmitters and drawings, which is essential for
Flow Measurement
No comment
measuring instrumentation engineer.
No comment Instrumentation - Quiz
MOHAMMED-ECE on What are the
what is an isolation Temperature Measurement
differences between circuit breaker
transformer and what How a SCADA works?
are its advantages And Functions of SCADA and fuse ? Instrumentation Basics
No comment No comment MOHAMMED-ECE on E Calibration Measurement
book:Instrumentation construction
How to do Megger Overview of pressure Level Measurement
engineering.
test/insulation measurement
Instrumentation Quiz - Powe
resistance for younik on Types of Valve
No comment
transformer? Generation
shepeerd siame on Level
No comment Different methods of Transmitter Calibration – Zero
temperature
Suppression and Zero elevation
Why transformer testing measurement
is needed and how to do No comment
the maintenance of a
transformer
What is a deluge valve ?
No comment
No comment
What is a piezoelectric
transducer and how
does it work
No comment
Copyright © 2018 Automationforum Designed & Developed by Automatio
https://automationforum.co/basics-hart-communicator/ 6/6