0% found this document useful (0 votes)
22 views

Spec MAX3100

The MAX 3100 Series is a multifunction power meter capable of measuring over 60 parameters, including voltage, current, and power, with options for advanced features like harmonic analysis and data storage. It supports various communication protocols, including RS-485 and Ethernet, and complies with multiple international standards for safety and accuracy. The device is designed for flexible installation and can operate as a standalone data acquisition module or integrated with its LCD front panel.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views

Spec MAX3100

The MAX 3100 Series is a multifunction power meter capable of measuring over 60 parameters, including voltage, current, and power, with options for advanced features like harmonic analysis and data storage. It supports various communication protocols, including RS-485 and Ethernet, and complies with multiple international standards for safety and accuracy. The device is designed for flexible installation and can operate as a standalone data acquisition module or integrated with its LCD front panel.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

MAX 3100 Series

MaxSave
Multifunction Power Meter

MAX 3100 SERIES


Product Profile
MAX3100 is a powerful multifunction power meter that can measure more than 60 parameters such as U,I,P,
Q, cos o ,F, kWh, kvarh, etc. The standard MAX3100 has RS-485 communication protocol, 2 energy pulse outputs
(active and reactive each) functions. With optional module, MAX3100 can perform more functions as harmonic
analysis, 8 digital signal inputs, 4 programmable relay outputs, 4 programmable analog outputs (0-5V or 4-20mA).
data storage. Profibus communication, Ethemet metworking capabilities.
Applying modular design. MAX 3100 works flexibly to suit customers'needs. MAX 3100 LCD front panel and
main unit can be connected or separated; the main unit alone can work as a data acquisition module.
MAX3100 fulfills ass the important requirement of IEC60687(GB/T17883-1999),C1268(GN/T17882-1999), IEC
61000-4-30, GB/T 14549-1993, IEC688-1992,GB/T13850-1998.
Measured scope : Single phase, 3P3W system.

EMC and other safety standard


IEC61000-4-2 : 1995 (GB/T17626.2-1998) IEC61000-4-4 : 1995 (GB/T17626.4 -1998)
IEC61000-4-8 : 1995 (GB/T17626.8-1998) IEC61010-1 : 1990 (GB/T4793.1-1995)

Functions Description
Phase Voltage Phase Voltage, average phase Voltage
Line Voltage Line Voltage, average line Voltage
Current Phase Current, average phase Current, zero sequence Current
Active Power Phase active Power, 3 phase active total power
Real time Reactive Power Phase reactive Power, 3 phase reactive total Power
measurement Apparent Power Phase apparent Power, 3 phase apparent total Power
Power 4 quadrant Power 4 quadrant
Frequency System frequency
Power Factor Phase Power factor, 3 phase total Power factor

Demand statistic Demand 3 phase active/reactive demand Power, demand apparent Power

Active Energy Imported, exported and net acive energy, 1 channel active energy pulse output

Main Energy Reading Reactive energy Imported,exported and net reactive energy,1 channel reactive energy pulse output

unit Multi tariff billing Multi tariff setup


Time Display Real time display Year/month/day/hour/minute/second
Data communication RS-485 communication 1 Modbus-RTU protocol

Remote signal 8 Channels Status detecion, SOE event record


input module
Relay output 4 channels programmable Programmable over/under limit value for real time measurement, Volt-

module overlimit/underlimit alarm age/Current unbalanced ratio,demand value,harmonics, remote signal.


The overlimit/underlimit command can be read thru com. Port
Analog output module 4 channels programmable 4 - 20mA or 0-5V
Data storage Store real time measured value in cycle, Voltage/Current.
module unbalanced ratio, demand value, harmonics, remote signal.
Storage capacity : 8GB
Total harmonic distortion 3 phase, single phase, neutral line
for Voltage/Current
optional Harmonic Even/odd harmonic distortion Harmonic distortion ( 2nd to 63rd)
Module analysis Fundermental Voltage/Current Magnitude, phase angle
module Fundermental active/reactive power
Harmonics, individual Magnitude, phase angle
Current K factor
Profibus
communication module 1 channal Profibus protocol
Ethernet 10M/100M adaptable
networking TCP/IP com. Protocol
communication 1 channal
module Visit Webpage, send email periodically,and send event record information
Measurement Accuracy
Parameters Display Direction
Voltage 0~9999.9KV Class0.2
Current 0~9999.9KV Class0.2
Power factor -1~+1 Directional Class 1
Frequency 45 ~ 65Hz 0.01Hz
Active Power -999999 ~ 999999MW Directional Class0.5
Reactive Power -999999 ~ 999999Mvar Directional Class0.5
Apparent Power -999999 ~ 999999MVA Class0.5
Active Demand -999999 ~ 999999MW Class 1
Reactive Demand -999999 ~ 999999MVar Class0.5
Active Energy 0 ~ 999999999MWh Directional Class0.5
Reactive Energy 0 ~ 999999999Mvarh Directional Class 1
Phase Angle 0.0. ~ 359.9 . Directional Class 2
Curren total harmonic % 0 ~ 100% Class 2
Voltage total harmonic % 0 ~ 100% Class 2
Technical Specification
Input Current Profibus com.module (optional)
Input Current: 0~5A (Current value can be set up) No. of channels
Measurement scope : 0.5%~120%In Communication protocol Profibus-DP protocol
Overload capacity : 2Xrated continuously, 100A/1s non continuously Ethernet networking module (optional)
Power consumption: ≤0.2VA per phase No.of channels: 1Chanel 10M/100M adaptive
Voltage Input Communication protocol TCP/IP protocol
Input Voltage: 0~400VAC (L-N),0~690VAC (L-L) Other parameters
(Voltage value can be set up) Auxiliary Power 85~265VAC/DC (standard)
System frequency: 45~65Hz 24~80VAC/DC (optional)

Measurement scope: 3%~120%Un Display module LCD Display 76mmx66mm


Overload Capacity: 2Xrated continuous,2500V/1s non continuous luminosity con be adjusted

Power consumption: ≤ 0.5VA per phase Storage Capacity 2GB


Switch Status (Optional) Temp.drifting factor <100PPM/. C
Input Chaneles 8 channels Withstand Voltage(input against output) 2500V/1min
Input Type Dry contact Total power consumption <8VA
Contact Capacity 2500VAC Operation temperature -20. C ~ 60. C
Relay output (optional) Storage temperature -40. C ~ 85. C
Output Chanels 4 Channels programmable Operation humidity 5~95%RH
Output Type Mechanic contact, constant on output Pollution Class Class 2
Contact Capacity 5A/250VAC Material of Housing Flammability acc.to UL94V0
Analog output (optional) Dimensional Size:Front panel+main unit, 96x99x78mm,
No.of outputs 4 Chanels programmable front+main+optional module 96x99x121mm
Output signal 4 ~ 20mA or 0~5V Dimensional Size:Main unit 92x112x74mm
Response time ≤ 400ms main + module 92x112x114mm
Pulse output (standard) Dimensional Size:Front panel 96x99x41mm
No.of outputs 2 channels (active/reactive energy each) Installation Size:Front panel+main unit 91x91mm
Serial com.port (standard) (+module)
No.of outputs 1 RS-485 port
Communication protocol Modbus-RTU protocol
Baud rate 2400/4800/9600/19200/38400bps Connection and Installation
I. Integrated Front panel + main unit (+module) connection ______Default type
MAX3100 inteqrated connection is mainly for panel installation.
II. Main unit (+module) connection______no display, for data acquisition purpose
MAX3100 con transmit the measured parameters thru com. Port to other device. This installation unit
can be installed on 35mm rail or bolted in the cainet.
III. Front panel and main unit(+module)separated connection ____customized installation
The front panel can be installed on the front panel of cabinet; the main unit can be installed on 35mm
DIN rail or bolted in the cabinet. These two are connected by wire (length of wire is 0.5/1/1.5/2m).
Customized length of wired is offered.