URS Attachment AHU
URS Attachment AHU
Puducherry
Attachment# 1
1.0 Environment
This section gives a brief summary of the layout and physical condition of the proposed site of the AHU
system. This includes (but not limited to), the data sheet of the room where proposed equipment is to be
placed with proposed placement drawing showing room dimensions, design of rooms to be maintained by
the AHU system, drain locations, access route from outside, AHU supply/return grill locations, utility point
locations, etc.
S.No Parameter Specifications/Dimension
.
Area name Length Width Height Area Volume ACPH
m m m m2 m3
Men Entry 2.02 4.85 NLT 20
1.02 1.98 2.4
Air Lock sqm m3
1. Details of area to be Decartoning 16.18 38.83 NLT 20
3.54 4.57 2.4
supplied Room sqm m3
14.24 34.18 NLT 20
RM Day 3.11 4.58 2.4
m3
Store sqm
3. No. of air changes per Should be NMT 20 Nos. / Hour for the Class of area ISO 8 at rest condition.
hour in cubicle
Should be NMT 50 Nos. / Hour for the Class of area ISO 7 at rest condition.
Should be NMT 100 Nos. / Hour for the Class of area ISO 6 at rest condition.
Qright Pharma Private Limited
Puducherry
4. Particulate matter Should meet the specifications of Class ISO 8 / Grade D area,
count
Class ISO 7 / Grade C area and Class ISO 6 / Grade B area.
Should meet the specifications of Class ISO 8 / Grade D, Class ISO 7 / Grade
C and Class ISO 6 / Grade B.
5. Microbial load
Qright Pharma Private Limited
Puducherry
Recovery for
7. Should be achieved within 30 minutes.
temperature and RH
The smoke should be diffused uniformly at supply air location to room and
8.
Air flow pattern
pass through return location. Also smoke should be passed from positive
pressure area to negative pressure area.
Parameters Specifications
Filter Type Sliding, Box type Filter
MOC Frame / 0.1 mm GI / HDPE/Synthetic Fiber
MOC Media
Filter Size / 610 H x 610 W x 48 D 610 H x 305 Wx48 D mm
Qty mm / 1 No. / 1 No.
Eff:90% @ 10µm Eff:90% @ 10µm
Pre Filter :(F5)
9. Filter Detail Parameters Specifications
Filter Type Bag filter Box type
MOC Frame / 0.1 mm GI / HDPE/Synthetic Fiber
MOC Media
Filter Size / 610 H x 610 W x 300 D 305 Hx 610 Wx300 D mm
Qty mm /1 No. / 1 No.
Eff:95% @ 5µm Eff:95% @ 5µm
Fine Filter :( F7)
Parameters Specifications
Filter Type Flange type Filter
MOC Frame / 0.1 mm GI / Synthetic Fiber
MOC Media
Filter Size / 610 H x 610 W x 300 D 610 H x 305 Wx300 D mm
Qty mm /1 No. / 1 No.
Eff:97% @ 3µm Eff:97% @ 3µm
10. Electrical motor for Type: 3 phase induction motor. Motor should be compatible to run with VFD.
main supply blower Motor should be flame proof.
11. Valve control Controller and sensor should be provided after coil or in the area for actuation
of chilled water control valve.
Isolation valve should be provided at chilled water inlet and outlet.
Two ways balancing cum control valve for chilled water and three ways for hot
water should be provided.
12. Valves and strainers Strainer should be provided at chilled water inlet line.
Pressure gauge isolation valve should be provided.
a. Return air ducting:
Thickness: 0.6mm. Non soldered.
G.I. Sheet metal ducting – Prefabricated ducts 24G (0.6MM)/ 22G (0.8MM)/
20G (1.0MM).
Insulation:
MOC:
Nitrile rubber / closed cell polyethylene elastomeric foam insulation with
13. Ducting aluminum foil.
Thickness : 9mm
Insulation:
MOC:
Nitrile rubber / closed cell polyethylene elastomeric foam insulation with
aluminum foil.
Thickness : 9 mm
All duct joints should be filled with sealant for zero leakages.
Volume control dampers should be used for the better air control.
14. Duct leakages Should be less than 3 % of total volume handled by system.
VFD for supply
15. Suitable capacity of VFD to be provided.
blower
AHU cum dehumidifier should be operational through auto / manual switch
16. Operational feature and also compatible to run with VFD and BMS.
17. Fresh air Minimum 10%
18. Relief air Not more than ____NA______%
(if applicable) Not Applicable
All the filter banks, blower section, coil section should be facilitate with the
19 Filter section provision for the measurement of the differential pressure across the filters.
Low leakage aerofoil dampers should be provided.
Individual damper should be provided for supply, return, fresh air, relief air,
reactivation air etc.
20. Damper section Size:
Fresh air inlet damper: 215H x 215L mm 1no.
Return air damper : 650Hx 315 L mm no.1
Supply air outlet damper : 450Hx 315 L mm no.1
3.0 Instrumentation Requirements:
This section mentions in brief the minimum requirement for measuring instrumentation for controlling
and monitoring of process parameters. e.g. magnehelic gauge / manometer and etc.
S. No. Parameter Specifications
1. Differential magnehelic Magnehelic manometer should be provided across HEPA / Fine filter
gauge / manometer if bank. Manometer should have proper zero setting.
applicable. For room : 0 to 100 mm of WC
For AHU cum dehumidifier: 0 to 50 mm of WC.
1. Performance of the system The system is intended to be operated regularly 24 hours, 7 days per
according to operation. week.
2. Cleaning requirements Easy accessible for cleaning of parts and should be provided with
quick fixing arrangement.
5.0 Capacity:
S.No. Parameter Specifications
3000 CFM
1.
Capacity
Exhaust CFM: 90%
Required fresh air CFM: 10 %
6.0 Automation and Safety Features: The minimum required as well as desired automation and safety
features (alarms, interlocking, etc.) are listed in this section.
S.No. Parameter Specifications
Noise level Should be not more than 80 Db in 01 meter distance.
1.
Safety guards Safety guards should be provided to all moving parts.
2.
Limit switch Blower plenum should have limit switch which can switch OFF the
3.
blower when plenum door is opened.
Earthing connections Proper earthing to be provided.
4.
View lamp and view window FLP / NFLP view lamp should be provided in blower section with
5.
view glass on panel.
Indicator lamp Indication lamp for the process air blower, reactivation blower, bed
6.
motor, heater bank should be provided (If applicable).
Smoke detector Smoke detector should be provided in the return air duct of AHU
7.
(If applicable)
Emergency stop The system shall have an emergency stop mechanism
10.
Power failure and recovery The equipment should not function in case of power failure and starts
11.
only after operator intervention.
7.0 System Boundaries: Nil
Qright Pharma Private Limited
Puducherry
4. Damper Aluminium
5.
1. NA NA
1. Design Specification
Qright Pharma Private Limited
Puducherry
2. Functional Specification
5. Instrument Listing
6. Control Schematics
7. Control panel assembly drawings
8. Machine Assembly Drawings
9. Bill of Material
10. Operator, Maintenance and Service Manual
11. Spare Parts List
12. MOC certificates
13. Calibration certificates of instruments
14. Test certificates of components/test devices
15. Weld certificates (if any)
16. ‘As-built’ P&ID
17. Isometric drawing (if any)
18. Electrical drawings
19. Component Cut Sheets (optional)
22.
Manufacture’s Quality Certificate
Qright Pharma Private Limited
Puducherry
23. Service and support details
24. Purchase order copy
25. Operation handbook
26. Calibration instructions
27. Maintenance instructions
28. Other (Specify)
Prepared by Approved by
Sign and Date: Sign and Date: