General Rules:: Software Family: Software Release: Parameters Descriptor (E2)

The document outlines the specifications and parameters for the XC600 software family, including CRC calculation, baud rate, and data format. It details the analog and digital input reading functions, including register addresses, gain, offset, and units for various probe values and set points. Additionally, it provides examples of how to send and receive data using Modbus RTU protocol for different measurement types and settings.

Uploaded by

lucas.en93
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views3 pages

General Rules:: Software Family: Software Release: Parameters Descriptor (E2)

The document outlines the specifications and parameters for the XC600 software family, including CRC calculation, baud rate, and data format. It details the analog and digital input reading functions, including register addresses, gain, offset, and units for various probe values and set points. Additionally, it provides examples of how to send and receive data using Modbus RTU protocol for different measurement types and settings.

Uploaded by

lucas.en93
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

SOFTWARE FAMILY:

SOFTWARE RELEASE: PARAMETERS DESCRIPTOR(E2):


XC600,
3.0 1.2
03
Revision:
0.2 2014/09/12

GENERAL RULES:
CRC calculation: standard modbus RTU CRC

Baudrate 9600
Data Lenght 8
Parity none
Stop bit 1
Minimum TimeOut 60ms

ANALOG INPUT

Reading function code: 0x 03

The data received must be added to "Offset" and then multiplied by "Gain".
The result can have "Dec" decimal digit

Example:
sent ADDR+FUNCTION CODE + 01000001+CRC
received ADDR+030202B9+CRC
where
0x02B9 = 697(dec) (697 + 0 )* 0.1 = 69.7 °C Probe value P1_C

sent ADDR+FUNCTION CODE + 01010001+CRC


received ADDR+03020222+CRC
where
0x0222 = 546(dec) (546 + 0 )* 0.1 = 54.6 bar Probe value P1_bar

HEX HEX HEX HEX


Name Read Register Num. Elements Read Write Register Num. Elements Write Gain Dec Offset Unit Byte ORDER Format R/W
Probe value P1_C 0100 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
Probe value P1_F 0100 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
Probe value P1_bar 0101 0001 \ \ 0,1 1 0 bar H-L 16 bit Signed R
Probe value P1_PSI/PA 0101 0001 \ \ 1 0 0 PSI H-L 16 bit Signed R
Probe value P2_C 0102 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
Probe value P2_F 0102 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
Probe value P2_bar 0103 0001 \ \ 0,1 1 0 bar H-L 16 bit Signed R
Probe value P2_PSI/PA 0103 0001 \ \ 1 0 0 PSI H-L 16 bit Signed R
Probe value P3_C 0104 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
Probe value P3_F 0104 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
Probe value P3_bar 0105 0001 \ \ 0,1 1 0 bar H-L 16 bit Signed R
Probe value P3_PSI/PA 0105 0001 \ \ 1 0 0 PSI H-L 16 bit Signed R
Probe value P4_C 0106 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
Probe value P4_F 0106 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
Probe value P4_bar 0107 0001 \ \ 0,1 1 0 bar H-L 16 bit Signed R
Probe value P4_PSI/PA 0107 0001 \ \ 1 0 0 PSI H-L 16 bit Signed R
Pb Compr circuit1_C/bar 0108 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
Pb Compr circuit1_F/PSI/PA 0108 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
R
Operat.Set Compr circuit1_C/bar 0109 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed
Operat.Set Compr
R
circuit1_F/PSI/PA 0109 0001 \ \ 1 0 0 °F H-L 16 bit Signed
Pb Compr circuit2_C/bar 010B 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
Pb Compr circuit2_F/PSI/PA 010B 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
R
Operat.Set Compr circuit2_C/bar 010C 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed
Operat.Set Compr
R
circuit2_F/PSI/PA 010C 0001 \ \ 1 0 0 °F H-L 16 bit Signed
Pb fan ciruit_C/bar 010E 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
Pb fan ciruit_F/PSI/PA 010E 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
Operat.Set fan circuit_C/bar 010F 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
R
Operat.Set fan circuit_F/PSI/PA 010F 0001 \ \ 1 0 0 °F H-L 16 bit Signed
R
Aver T/P in DGS regulation_C/bar 0111 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed
Aver T/P in DGS
R
regulation_F/PSI/PA 0111 0001 \ \ 1 0 0 °F H-L 16 bit Signed
PWM Triac DGT percentage 0112 0001 \ \ 1 0 0 % H-L 16 bit Signed R
AO1 Percentage 0113 0001 \ \ 1 0 0 % H-L 16 bit Signed R
AO2 Percentage 0114 0001 \ \ 1 0 0 % H-L 16 bit Signed R
High circuit1 HAL_C/bar 0601 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
High circuit1 HAL_F/PSI/PA 0601 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
Low circuit1 LAL_C/bar 0602 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
Low circuit1 LAL_F/PSI/PA 0602 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
High circuit2 2HAL_C/bar 0604 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
High circuit2 2HAL_F/PSI/PA 0604 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
Low circuit2 2LAL_C/bar 0605 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
Low circuit2 2LAL_F/PSI/PA 0605 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
High set fan HAF_C/bar 0607 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
High set fan HAF_F/PSI/PA 0607 0001 \ \ 1 0 0 °F H-L 16 bit Signed R
Low set fan LAF_C/bar 0608 0001 \ \ 0,1 1 0 °C H-L 16 bit Signed R
Low set fan LAF_F/PSI/PA 0608 0001 \ \ 1 0 0 °F H-L 16 bit Signed R

SET POINT

Reading function code: 0x 03


Writing function code: 0x 10
The data received must be added to "Offset" and then multiplied by "Gain".
The result can have "Dec" decimal digit

Example:
sent ADDR+03010A0001+CRC
received ADDR+030202A6+CRC
where
0x02A6 = 678(dec) (678 + 0 )* 0.1 = 67.8 °C Super Set Compr circuit1_C/bar reading value

sent ADDR+10010A0001+02+01E7+CRC
received ADDR+10010A0001+CRC
where
0x01E7 = 487(dec) (487 + 0 )* 0.1 = 48.7 °C Super Set Compr circuit1_C/bar written value

HEX HEX HEX HEX


Name Read Register Num. Elements Read Write Register Num. Elements Write Gain Dec Offset Unit Byte ORDER Format R/W

Super Set Compr ciruict1_C/bar 010A 0001 010A 0001 0,1 1 0 °C H-L 16 bit Signed R/W
Super Set Compr
ciruict1_F/PSI/PA 010A 0001 010A 0001 1 0 0 °F H-L 16 bit Signed R/W

Super Set Compr ciruict2_C/bar 010D 0001 010D 0001 0,1 1 0 °C H-L 16 bit Signed R/W
Super Set Compr
ciruict2_F/PSI/PA 010D 0001 010D 0001 1 0 0 °F H-L 16 bit Signed R/W
Super Set Fan circuit_C/bar 0110 0001 0110 0001 0,1 1 0 °C H-L 16 bit Signed R/W

Super Set Fan circuit_F/PSI/PA 0110 0001 0110 0001 1 0 0 °F H-L 16 bit Signed R/W
Load1 working hours 0E00 0001 0E00 0001 1 0 0 10hours H-L 16 bit Signed R/W
Load2 working hours 0E01 0001 0E01 0001 1 0 0 10hours H-L 16 bit Signed R/W
Load3 working hours 0E02 0001 0E02 0001 1 0 0 10hours H-L 16 bit Signed R/W
Load4 working hours 0E03 0001 0E03 0001 1 0 0 10hours H-L 16 bit Signed R/W
Load5 working hours 0E04 0001 0E04 0001 1 0 0 10hours H-L 16 bit Signed R/W
Load6 working hours 0E05 0001 0E05 0001 1 0 0 10hours H-L 16 bit Signed R/W
SetPoint Comp circuit1_C/bar 03AE 0001 03AE 0001 0,1 1 0 °C H-L 16 bit Signed R/W

SetPoint Comp circuit1_F/PSI/PA 03AE 0001 03AE 0001 1 0 0 °F H-L 16 bit Signed R/W
SetPoint Comp circuit2_C/bar 03AF 0001 03AF 0001 0,1 1 0 °C H-L 16 bit Signed R/W

SetPoint Comp circuit2_F/PSI/PA 03AF 0001 03AF 0001 1 0 0 °F H-L 16 bit Signed R/W
Set Point Fan_C/bar 03B0 0001 03B0 0001 0,1 1 0 °C H-L 16 bit Signed R/W
Set Point Fan_F/PSI/PA 03B0 0001 03B0 0001 1 0 0 °F H-L 16 bit Signed R/W

DIGITAL INPUT

Reading function code: 0x 01

Meaning single element


ON = 0x 0001
OFF= 0x 0000

HEX HEX
Name Read Register Num. Elements Read R/W
Safety Load 1 0204 0001 R
Safety Load 2 0205 0001 R
Safety Load 3 0206 0001 R
Safety Load 4 0207 0001 R
Safety Load 5 0208 0001 R
Safety Load 6 0209 0001 R
Invert fan(no relay) safety 020A 0001 R
Log Pressure CPR Circuit1 020B 0001 R
Log Pressure CPR Circuit2 020C 0001 R
High Pressostate(Fan circuit) 020D 0001 R
Energy Saving 020E 0001 R
Swtich OFF 020F 0001 R
Liquid level 0210 0001 R
Fan silence 0211 0001 R
External alarm 0212 0001 R

DIGITAL OUTPUT

Reading function code: 0x 01

Meaning single element


ON = 0x 0001
OFF= 0x 0000

HEX HEX
Name Read Register Num. Elements Read R/W
Compressor 1 Circuit1 022F 0001 R
Compressor 2 Circuit1 0230 0001 R
Compressor 3 Circuit1 0231 0001 R
Compressor 4 Circuit1 0232 0001 R
Compressor 5 Circuit1 0233 0001 R
Compressor 6 Circuit1 0234 0001 R
Fan 1 023B 0001 R
Fan 2 023C 0001 R
Fan 3 023D 0001 R
Fan 4 023E 0001 R
Fan 5 023F 0001 R
Fan 6 0240 0001 R
Compressor 1 Circuit2 0235 0001 R
Compressor 2 Circuit2 0236 0001 R
Compressor 3 Circuit2 0237 0001 R
Compressor 4 Circuit2 0238 0001 R
Compressor 5 Circuit2 0239 0001 R
Compressor 6 Circuit2 023A 0001 R
Digital Compressor 0241 0001 R
Step Digital Stream Compressor 0242 0001 R

Triac Digital Scroll Compressor 0243 0001 R


Inverter CPR Circuit1 0244 0001 R
Inverter CPR Circuit2 0245 0001 R
Inverter Fan 0246 0001 R
Liquid Inject 0247 0001 R
Alarm 0248 0001 R

Device Status

Reading function code: 0x 01

Meaning single element


ON = 0x 0001
OFF= 0x 0000

HEX HEX
Name Read Register Num. Elements Read R/W
On 0200 0001 R
Keyboard 0201 0001 R
Alarms muting 0202 0001 R
Energy Saving 0203 0001 R
SuperVis Set CPR Circuit 1 0249 0001 R
SuperVis Set CPR Circuit 2 024A 0001 R
SuperVis Set fan 024B 0001 R

ALARMS

Reading function code: 0x 01

Meaning single element


ON = 0x 0001
OFF= 0x 0000

HEX HEX
Name Read Register Num. Elements Read R/W
Error Pb1 0213 0001 R
Error Pb2 0214 0001 R
Error Pb3 0215 0001 R
Error Pb4 0216 0001 R
C1LA Low CPR Circuit1 0217 0001 R
C1HA High CPR Circuit1 0218 0001 R
C2LA Low CPR Circuit2 0219 0001 R
C2HA High CPR Circuit2 021A 0001 R
EA1 Load 1 Alarm 021D 0001 R
EA2 Load 2 Alarm 021E 0001 R
EA3 Load 3 Alarm 021F 0001 R
EA4 Load 4 Alarm 0220 0001 R
EA5 Load 5 Alarm 0221 0001 R
EA6 Load 6 Alarm 0222 0001 R
F-LA Low Fan Circuit 021B 0001 R
F-HA High Fan Circuit 021C 0001 R
EOL1 Low CPR Circuit1 0223 0001 R
EOL2 Low CPR Circuit2 0224 0001 R
E1L1 Low CPR Circuit1 0225 0001 R
E1L2 Low CPR Circuit2 0226 0001 R
EOH High Fan Circuit 0227 0001 R

DTL discharge DGS compressor 0228 0001 R


A5 liquid level 0229 0001 R
A12 device configuration 022A 0001 R
A13 EEPROM 022B 0001 R
A14 Maintenance 022C 0001 R
EA external alarm 022D 0001 R

INF Inverter fan (no relay) safety 022E 0001 R

COMMANDS

Writing function code: 0x 05

Meaning single element


ON = 0x FF00
OFF= 0x 0000

HEX
Name Modbus Command R/W
Device ON 0200FF00 W
Device OFF 02000000 W
Keyboard Lock 0201FF00 W
Keyboard Unlock 02010000 W
Alarm Muting 0202FF00 W
Energy Saving ON 0203FF00 W
Energy Saving OFF 02030000 W
Rst SuperVis CPR1 02490000 W
Rst SuperVis CPR2 024A0000 W
Rst SuperVis FAN 024B0000 W