0% found this document useful (0 votes)
39 views2 pages

Saudi Arabia - Pad - 300 1000kVA - 11-13,8kV 231V

This document details HV/LV three-phase distribution transformers available in Saudi Arabia, with power ratings from 300 to 1000 kVA and voltage specifications of 11-13.8kV/231V. The transformers meet IEC standards and include various fittings such as tap changers, bushings, and indicators. Additionally, it provides electrical characteristics, dimensions, and contact information for the manufacturer, Matelec Group.

Uploaded by

Raymond Sakr
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views2 pages

Saudi Arabia - Pad - 300 1000kVA - 11-13,8kV 231V

This document details HV/LV three-phase distribution transformers available in Saudi Arabia, with power ratings from 300 to 1000 kVA and voltage specifications of 11-13.8kV/231V. The transformers meet IEC standards and include various fittings such as tap changers, bushings, and indicators. Additionally, it provides electrical characteristics, dimensions, and contact information for the manufacturer, Matelec Group.

Uploaded by

Raymond Sakr
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

HV/LV three phase distribution transformers

KINGDOM of SAUDI ARABIA - Pad mounted

From 300 to 1000 kVA


11-13.8kV/231V

General description Fittings


This range of transformers satisfies the requirements of IEC Each transformer is equipped with :
publications 60076 with SEC specifications 51-SDMS-01. • 1 x five positions regulating off-circuit tap changer
The transformers comply with the following specifications: • 1 x coupling off-circuit changer in the case of dual primary
• Indoor installation • 3 x HV porcelain bushings
• Maximum ambient temperature : 55°C • 4 x LV bus bars with copper conductor
• Top oil temperature rise : 45°C • 2 x lifting lugs
• Average winding temperature rise : 50°C • 1 x rating plate
• Cooling is implemented with natural circulation (ONAN) of • 1 x thermometer with maxima indicator on the cover
mineral oil and air • 1 x oil level indicator on the cover
• Hermetically sealed, with gas cushion • 1 x pressure relief device 0.3 bar
• Cover bolted on corrugated tank • 1 x oil draining valve 1”
• Color : Gray RAL 7033 • 2 x earthling terminal studs M10
Other requirements can be provided upon request. • 4 x bidirectional rollers Ø = 125mm
• 1 x air-insulated LV cable box
• 1 x air-insulated HV cable box
Other fittings can be provided upon request.

ELECTRICAL CHARACTERISTICS
Rated Power (kVA) 300 500 1000
Rated Voltage (kV/V) Dual primary 11-13.8kV/231V.
Secondary voltage is at no-load.
Highest Voltage (kV) 17.5
Tappings (%) ±2.5% ±5% for 13.8kV and ±3.13% ±6.273% for 11kV
Vector Group Dyn11 (Delta; Star with Neutral brought out)
Frequency (Hz) 60
Impedance voltage at 75°C (%) 4 5 6
Losses (W) No-Load 520 750 1100
Load (75°C) 3180 4700 8800
Voltage Drop at Full load(%) cosØ=1 1.13 1.06 1.06
cosØ=0.8 3.19 3.76 4.35
Efficiency at Full load cosØ=1 98.78 98.92 99.02
cosØ=0.8 98.48 98.66 98.78
Efficiency at 75% load cosØ=1 98.98 99.10 99.20
cosØ=0.8 98.73 98.88 99.00
Other ratings, losses and impedance voltages can be provided upon request.

SAUDI MATELEC FOR INDUSTRIES


MATELEC GROUP
Head Office Dabab Street, Dabab Bldg - 3rd floor - Office No 10
Ghorfine - Amchit - P.O.Box: 12 Jbeil - Lebanon P.O. Box: 52114 - Riyadh 11563
Tel: (961) 9 620 920 - Fax: (961) 9 620 934 / 5 Riyadh - Kingdom of Saudi Arabia
E-mail: [email protected] Tel: (966) 11 4029909 - Fax: (966) 11 4024280
www.matelecgroup.com E-mail: [email protected]
HV/LV three phase distribution transformers
KINGDOM of SAUDI ARABIA - Pad mounted

From 300 to 1000 kVA


11-13.8kV/231V
12 10 6 5 13

1
4
2 3

14

18
15
A
B

16

8
17
7

11

G H

C Nº DESCRIPTION

1 Corrugated refrigeration panels


2 Rating plate
3 HV porcelain bushings
E E
4 LV bus bars
20 5 Tap changer
19 9 6 Coupling changer (in case of double primary)
7 2 earthling terminal studs M10
D

8 Oil draining Valve 1"


9 Oil filling plug 1”
10 Lifting lugs
11 Bidirectional rollers
12 Thermometer with maxima indicator
13 Oil level indicator
14 LV cable box
F F F
15 LV cables rubber gaskets
16 LV cable clamps
17 LV cable support
18 MV cable box
19 Pressure releif device 0.3 bar
20 Tap changer caution plate
APPROXIMATE WEIGHT AND OVERALL DIMENSIONS
Power LV HV LV HV Height Cover Length Width Oil Total
Bushing Bushing Cable Cable Height Weight Weight
Box Box -A- -B- -C- -D- -E- -F- -G- -H-
kVA mm mm mm mm mm mm mm mm Kg Kg
300 1/1250 17.5/250 LVCB17 MVCB26 1405 1265 1500 1280 230 180 750 600 365 1595
(item 1) (item 26)
500 1/1250 17.5/250 LVCB17 MVCB26 1460 1320 1650 1270 230 180 750 600 410 1895
(item 1) (item 26)
1000 1/2500 17.5/250 LVCB18 MVCB26 1675 1535 1850 1450 230 180 750 600 615 3080
(item 3) (item 26)
For bushings and cable boxes items, refer to tables 2 and 3 in our general transformers catalogue.
The values contained in this document can be changed without prior notice.
Exact values will be supplied upon order confirmation. Ref. PDS KSA 03 - 08/14
All rights reserved, Matelec Group, 2014.