Potterton Precision Install
Potterton Precision Install
Condensing
Central Heating
Boiler
Precision
www.britishgas.co.uk
The Health & Safety Executive operates the ‘Gas Safe Register’,
a self-certification scheme for gas heating appliances.
Installers are required to carry out installation, commissioning and servicing work
in accordance with the Benchmark Code of Practice which is available from the
Heating and Hotwater Industry Council who manage and promote the Scheme.
Visit www.centralheating.co.uk for more information.
0086
ISO 9001
FM 00866
2
Installer Notification Guidelines
Choose Building
Regulations Notification
Route
3
Legislation
IMPORTANT - Installation, Commissioning, Service & Repair This company declares that no substances harmful
to health are contained in the appliance or used
This appliance must be installed in accordance with the manufacturer’s instructions and during appliance manufacture.
the regulations in force. Read the instructions fully before installing or using the
appliance. The appliance is suitable only for installation in GB and IE
and should be installed in accordance with the rules in
In GB, this must be carried out by a competent person as stated in the Gas Safety force, and only used in a suitably ventilated location.
(Installation & Use) Regulations.
In GB, the installation must be carried out by a Gas Safe
Registered Installer. It must be carried out in accordance
Definition of competence: A person who works for a Gas Safe registered company with the relevant requirements of the:
and holding current certificates in the relevant ACS modules, is deemed competent. • Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic
Regulations (Northern Ireland).
Gas Installations”. • The Water Fittings Regulations or Water Byelaws in
Scotland.
NOTE: The addition of anything that may interfere with the normal operation of the • The Current I.E.E. Wiring Regulations.
appliance without express written permission from the manufacturer or his agent could
Where no specific instructions are given, reference should
invalidate the appliance warranty. In GB this could also infringe the Gas Safety
be made to the relevant British Standard Code of Practice.
(Installation and Use) Regulations.
In IE, the installation must be carried out by a competent
Warning - Check the information on the data plate is compatible with local supply Person and installed in accordance with the current edition
conditions. of I.S. 813 ‘Domestic Gas Installations’, the current Building
Regulations and reference should be made to the current
ETCI rules for electrical installation.
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency)
Codes of Practice, most recent version should be used
Regulations 1993 No 3083” and is deemed to meet the requirements of Directive
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with
In GB the following Codes of Practice apply:
liquid or gaseous fuels:- Standard Scope
BS 6891 Gas Installation.
BS 5546 Installation of hot water supplies for domestic
Type test for purpose of Regulation 5 certified by: purposes.
Notified Body 0087. BS EN 12828 Heating systems in buildings.
BS EN 14336 Installation & commissioning of water based
heating systems.
Product/Production certified by: BS 6798 Installation of gas fired hot water boilers.
BS 5440 Part 1 Flues.
Notified Body 0086. BS 5440 Part 2 Ventilation.
BS 7074 Expansion vessels and ancillary equipment for
sealed water systems.
For GB/IE only. BS 7593 Treatment of water in domestic hot water
central heating systems.
4
Safe Manual Handling
General
The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.
Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and
hands. Health & Safety is the responsibility of EVERYONE.
There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.
Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.
Preparation
Co-ordinate movements - know where, and when, you are both going.
Minimise the number of times needed to move the boiler - plan ahead.
Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special
care on ladders/into lofts.
Technique
When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and
sideways and keep the load as close to your body as possible.
Where possible transport the boiler using a sack truck or other suitable trolley.
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary.
See section 8.3 of these instructions for recommended lift points.
Remember
The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.
If at any time when installing the boiler you feel that you may have injured yourself STOP !!
DO NOT ‘work through’ the pain - you may cause further injury.
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!
5
Contents
Section Page
1.0 Introduction 7
10.0 Installation 30
11.0 Electrical 36
Benchmark Checklist 58
6
1.0 Introduction
1.1 Description
7
2.0 General Layout
1. Wall Plate
2. Flue Elbow
3. Heat Exchanger
4. Burner
5. Air Box
6. Fan Protection Thermostat
15 14 8. Condensate Trap
2 9. PCB Housing Assembly
10. Gas Tap
11. Gas / Air Ratio Valve
12. Flow Pipe Connection
1
13. Return Pipe Connection
14. Flow Temperature Safety Thermostat - Black
15. Flow Temperature Thermistor - Red
3
16. Flow Switch (dry fire protection)
12
4 17
Fig. 3
7
11
Fig. 4 Fig. 6
10
8
Mains On.
3.0 Appliance Operation
3.1
Flow NO
temperature less
than set point ?
1. Switched Live On: When the switched live switches
on if the flow temperature is less than the set point
then pump overrun occurs. When the switched live
YES switches on if the flow temperature is greater than the
set point then pump overrun occurs.
10 second
Pump On.
2. Pump On: The pump is on while the fan, spark
generator and gas valve are off. After 10 seconds if the
flow switch has made then fan pre-purge occurs. After
10 seconds if the flow switch has not made then anti-
NO
Flow switch made ? cycle occurs.
5 second
8. Anti-cycle: The pump, fan, spark generator and gas
Fan Post Purge.
valve are off. After 3 minutes if the flow temperature is
less than the set point then pump on occurs. After 3
minutes if the flow temperature is greater than the set
point then pump overrun occurs.
YES All TRVs
shut down ?
9. Ignition Lockout: The pump, fan, spark generator
and gas valve are off. The boiler can only be reset by
manually using the reset button.
NO
1 minute
Pump Overrun.
3 minute
Anti-cycle.
9
4.0 Technical Data
Appliance Type C13 C33 C53 Max Gas Rate (2H - G20 - 20mbar) Electrical Supply 230V~ 50Hz
(After 10 Mins) (Appliance must be connected to an
Appliance Category CAT I 2H Setting 1 2 3 4 5 earthed supply)
m3/hr 1.34 1.64 1.94 2.31 2.95
Heat Input (Q)(Gross) Max Min Power Consumption 80W
Setting 1 kW 13.34 10.2 Injector (Natural Gas)
6.5mm Diameter External Fuse Rating 3A
Setting 2 kW 16.88 10.2
Setting 3 kW 20.18 10.2 Nox Class 5
Internal Fuse Rating (BS 4265)
Setting 4 kW 24.50 10.2 Horizontal Fuse 3.15 AT (PCB)
Setting 5 kW 33.76 10.2 Flue Terminal Diameter 110mm
Dimensions Projection 150mm Electrical Protection IPX2
Heat Output (P)
Connections
(Non Condensing 70° C Mean Water Temp) Water Content
Max Min Gas Supply - 1
/2in BSPT
Central Heating Flow - 22mm litres 2.6
Setting 1 kW 11.82 9.14 Central Heating Return - 22mm pints 4.6
Setting 2 kW 15.24 9.14 Condensate Drain - 1 in BSP
Static Head
Setting 3 kW 17.81 9.14
Outercase Dimensions max 30 metres (100 ft)
Setting 4 kW 22.00 9.14 Overall Height Inc Flue Elbow - 750mm min 1 metre (3.25 ft)
Setting 5 kW 30.18 9.14 Casing Height - 600mm
Casing Width - 390mm Low Head 0.2m (8 in) min
Heat Output (P) Casing Depth - 280mm
(Condensing 40° C Mean Water Temp) System Detail
Max Min Clearances fully pumped open vented & sealed systems
(For unventilated compartments see Section 7.2)
Setting 1 kW 12.81 10.1 Gas Connection
Setting 2 kW 16.49 10.1 Both Sides 5mm Min G1/2” B.S.P. Thread
Above Casing 200mm Min
Setting 3 kW 19.27 10.1
Below Casing 50mm Min Controls
Setting 4 kW 23.8 10.1 Front (For Servicing) 500mm Min boiler thermostat, safety thermostat,
Setting 5 kW 32.61 10.1 Front (In Operation) 5mm Min flow switch, electronic flame sensing,
temperature protection thermostat &
Weights kg condensate blockage sensor
NOTE: The boiler is delivered at Setting 3.
Packaged Boiler Carton 36.2
If a greater or lesser output is required
Packaged Flue Kit 3.6
refer to the output setting procedure on Inlet Pressure at Gas Valve (Natural Gas)
Installation Lift Weight 26.0
the boiler front panel. The electrical supply Min 18.1 mbar
MUST BE ISOLATED before doing this, CO/CO2 Ratio Up to a maximum Max 22.5 mbar
and it must only be done by a competent of 0.004
registered person. (see Section 12.1)
CO2 Level 9% ± 1%
Flow Temperature (adjustable)
SEDBUK Declaration 55° C to 78° C (± 5° C)
Setting 1 - The efficiency is 90.5% Recommended System
NOTE: All data in this section are nominal values
Setting 2 - The efficiency is 91.3% and subject to normal production tolerances Temperature Drop
Setting 3 - The efficiency is 90.4% Condensing 20°C 36°F
Setting 4 - The efficiency is 90.9%
Setting 5 - The efficiency is 90.9%
Hydraulic Resistance Chart
This value is used in the UK Government’s Standard
220 91
Assessment Procedure (SAP) for energy rating of
200 83
Pressure Drop (mbar)
0 10 20 30 40
Water Flow Rate (litres/min)
10
5.0 Dimensions and Fixings
DIMENSIONS
E A 600mm
At Least 1.5°
B 280mm
C 390mm
A
D 150mm Ø Min.
E 162.5mm
F 96mm
B
360° Orientation
D C
The 1.5° fall provided by the elbow
is to allow condensate to run back to
the boiler, for disposal through the
Tube Ø 110mm condensate discharge pipe.
Fig. 7
11
6.0 System Details
12
Copper 6.0 System Details
Copper 0.5m
0.5m
Flow
Boiler 6.3 Pipework
Return
Copper
1. The sizes of flow and return pipes from the boiler should
1m
be determined by normal methods, according to the
Fig. 9 requirements of the system. The connections on the boiler
are 22mm.
Return
6.4 Low Head Installation
6.5 Pump
Fig. 11 If Conditions Require,
This System Possible 1. Providing that the cold feed and open vent pipe are
positioned correctly (e.g. the system is not prone to
pumping over, air entrainment etc.) the pump may be fitted
22mm
200mm on the primary return pipe.
Feed & Vent
Min Pipe
Air
Separator
Boiler Pump
Flow
Return
Fig. 12
Alternative Low Head Installation
13
230V Key to colours
50Hz b - Blue
L N E
g/y
b Y Plan
br - Brown
6.0 System Details
w Diverter
Cylinder Valve w - White
Stat gr
o - Orange
1
6.6 System Controls
Room
o gr - Grey
Stat g/y - Green/Yellow
C 2 This boiler does not require a bypass.
Boiler This boiler does not require a permanent live.
L E N P/F The pump only needs wiring directly to the boiler for
fully TRV’d systems.
i) Y Plan, Room Thermostat System, CH Interlocked By Room Thermostat 1. To comply with Part L1 of the Building Regulations the
At least the Radiator(s) near the Room Thermostat not TRV’d heating system into which the boiler is installed should
Pump run from Switched Live include the following:
By-pass permitted but not required for Part L1 compliance
a) zone controls
gr b) timing controls
230V b
c) boiler control interlocks
gr
50Hz
L N E Motor Motor
b br 2. Such a system needs to be fully pumped and must
provide independent temperature and time control to
br S Plan o g/y S Plan
g/y Valve Valve both the heating and hot water circuits and have a boiler
Room Cylinder o interlock.
Stat Stat
3. The boiler should be controlled so that it operates on
Boiler
L E N P/F
demand only. Where it is proposed to effect control by
thermostatic radiator valves, a room thermostat (or
other device such as a flow switch - a flow switch is
Timer integral to this boiler) should also be provided to switch
L off the boiler when there is no demand for heating or
N
Pump hot water.
CH on NE L
HW on
4. The interlock for the CH circuit can be provided by
ii) S Plan, Room Thermostat System, CH Interlocked By Room Thermostat either a Room Thermostat or a fully TRV’d system with
At least the Radiator(s) near the Room Thermostat not TRV’d the pump wired back to the boiler without a bypass.
Pump run from Switched Live
By-pass permitted but not required for Part L1 compliance
Connection diagrams for both options for Y and S plan
systems are shown.
230V
50Hz gr
L N E b Y Plan 230V b
gr
g/y
w Diverter 50Hz
L N E
Cylinder Valve b
Motor Motor
gr br
Stat
1 o S Plan o g/y S Plan
g/y Valve Valve
C 2 br Cylinder o
Stat
Boiler
L E N P/F
Boiler
L E N P/F
Timer
L Timer
N
CH on NE L Pump L
HW on N
CH on NE L Pump
HW off
HW on
14
6.0 System Details
3 Litre
Top Up Bottle
Air
Vent
(if required) 6.7 Sealed Systems (Fig. 13)
Temporary
Cold CH
Hose
Mains Return
Fig. 14
Inlet
15
7.0 Site Requirements
7.1 Location
Zone 0
2. If the boiler is sited in an unheated enclosure then it is
recommended to incorporate an appropriate device for
0.6 m
frost protection in the system controls.
Window
Recess
3. If the boiler is fitted in a room containing a bath or
Zone 2
shower it MUST NOT BE fitted in zone 0, 1 or 2, ONLY
within the shaded area (Figs. A & B shows zone
dimensions for a bathtub. For other examples refer to
the Current I.E.E. Wiring Regulations) reference must be
Fig. A made to the relevant requirements.
In GB Only
In GB this is the current I.E.E. Wiring Regulations and
Building Regulations.
In IE reference should be made to the current edition of
I.S. 813 “Domestic Gas Installations” and the current
ETCI rules.
16
5mm Min 390mm 5mm Min
7.0 Site Requirements
17
Examples are shown of the following methods of termination:-
i) to an internal soil & vent pipe
ii) via an internal discharge branch (e.g. sink waste) downstream of the trap 7.0 Site Requirements
iii) to a drain or gully
iv) to a purpose made soakaway
v) pumped into an internal discharge branch (e.g. sink waste) downstream of the trap 7.6 Condensate Drain
vi) pumped into an external soil & vent pipe
vii) to a drain or gully with extended external run & trace heating FAILURE TO INSTALL THE CONDENSATE DISCHARGE
PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE
OPERATION OF THE BOILER.
It is strongly recommended to discharge internally into the household
drainage system. If connecting to a rain water drain, that drain MUST CAREFUL CONSIDERATION MUST BE GIVEN TO THE
discharge into a foul drain. POSSIBILITY OF THE PIPEWORK BEING SUBJECT TO
21.5mm 32mm Insulation FREEZING CONDITIONS AND APPROPRIATE
MEASURES TAKEN TO PREVENT BLOCKAGE.
CORRECT INSTALLATION IN ACCORDANCE WITH
THIS SECTION WILL CONSIDERABLY MINIMISE THE
LIKELIHOOD OF BLOCKAGE AND SUBSEQUENT
BOILER LOCK-OUT.
i) Termination to an internal soil and
vent pipe A CONDENSATE DISCHARGE PUMP AND PIPE ‘TRACE
HEATING’ ARE AVAILABLE AS ACCESSORIES - see
paragraphs 7.7.12 to 7.715 for further details.
50mm
per me The condensate discharge pipe MUST NOT RISE at any
tre of
2.5° M pipe ru point along its length. There MUST be a fall of AT LEAST
inimum n
fall 2.5° (50mm per metre) along the entire run EXCEPT when
employing a suitable condensate pump in basement and
cellar or similar applications.
450mm min*
The boiler condensate trap incorporates a seal of 75mm,
*450mm is applicable to properties therefore it is unnecessary to install an air break and trap in
up to 3 storeys. the discharge pipework.
For multi-storey building installations
consult BS 6798. 1. The condensate outlet will accept 21.5mm (3/4in) plastic
Boiler overflow pipe. It is strongly recommended that this discharges
ii) External termination via internal discharge branch
internally into the household drainage system.
e.g sink waste - downstream*
Where this is not possible, discharge into an outside drain is
Sink 50mm
per me permissible providing every possible precaution is taken to
tre of
pipe ru Pipe must terminate above prevent freezing.
2.5° M n
inimum water level but below
fall
surrounding surface. Cut 2. Ensure the discharge of condensate complies with any
end at 45° national or local regulations in force. BS 6798 & Part H1 of the
Building Regulations give further detailed guidance.
*It is NOT RECOMMENDED 3. The discharge pipe should be run in a proprietary drain pipe
to connect upstream of the material e.g. PVC, PVC-U, ABS, PVC-C or PP.
sink or other waste water
receptacle ! 4. Metal pipework is NOT suitable for use in condensate
discharge systems.
Boiler
iii) Termination to a drain or gully 5. The pipe should be a minimum of 21.5mm diameter and
must be supported using suitably spaced clips of the correct
Pipe must terminate above
design to prevent sagging.
50mm water level but below
per me surrounding surface. Cut
tre of 6. It is advisable that the full length of condensate pipe is run
pipe ru end at 45°
2.5° M n internally and preferably be less than 3 metres.
inimum
fall
7. Internal runs greater than 3 metres or runs in cold areas
should use 32mm waste pipe.
Basement or similar
(heated)
vii) to a drain or gully with extended
Boiler external run & trace heating
50mm
per me
tre of
pipe ru
2.5° M n Pipe must terminate above
inimum water level but below
fall
surrounding surface. Cut
end at 45°
19
Terminal Position with Minimum Distance (Fig. 17) mm
Aa Directly below an opening, air brick, opening 7.0 Site Requirements
windows, etc. 300
Ba Above an opening, air brick, opening window etc. 300
Ca Horizontally to an opening, air brick, opening window etc. 300 7.7 Flue
Db Below gutters, soil pipes or drain pipes. 25 (75)
Eb Below eaves. 25 (200) NOTE: Due to the high efficiency of the boiler a plume of
Fb Below balconies or car port roof. 25 (200) water vapour will be discharged from the flue. This should
Gb From a vertical drain pipe or soil pipe. 25 (150) be taken into account when siting the flue terminal.
Hb From an internal (i) or external (ii) corner. (i) 25 (300) (ii) 115
1. The following guidelines indicate the general requirements
I Above ground, roof or balcony level. 300
for siting balanced flue terminals. For GB recommendations are
J From a surface or boundary line facing a terminal. 600 given in BS 5440 Pt.1. For IE recommendations are given in the
K From a terminal facing a terminal (Horizontal flue). 1200 current edition of I.S. 813 “Domestic Gas Installations”.
From a terminal facing a terminal (Vertical flue). 600
L From an opening in carport (e.g. door, window) 2. If the terminal discharges onto a pathway or passageway,
into the dwelling. 1200 check that combustion products will not cause a nuisance and
M Vertically from a terminal on the same wall. 1500 that the terminal will not obstruct the passageway.
N Horizontally from a terminal on the same wall. 300
R From adjacent wall to flue (vertical only). 300 3. Take into consideration the effect the plume of vapour may
S From an adjacent opening window (vertical only). 1000
have on neighbours when siting the flue.
T Adjacent to windows or openings on pitched and flat roofs. 600 4. Adjacent surfaces close to the flue terminal may need
Table. 2 U Below windows or openings on pitched roofs. 2000 protection from the effects of condensation. Alternatively a flue
deflector kit (part no. 248167) is available.
aIn addition, the terminal should be no nearer than 150 mm to an opening in the
building fabric formed for the purpose of accommodating a built-in element such as 5. For installation of the flue into an internal corner at the
a window frame. See B.S.5440-1. 25mm dimension the flue deflector kit (part no. 248167) must
b Only ONE 25mm clearance is allowed per installation. If one of the dimensions be fitted.
D, E, F, G or H is 25mm then the remainder MUST be as shown in brackets, in 6. * Reduction to the boundary is possible down to 25mm but
accordance with B.S.5440-1. the Flue Deflector Kit (part no. 248167) must be fitted.
IMPORTANT:
• Under car ports we recommend the use of the plume
displacement kit.
• The terminal position must ensure the safe and
nuisance - free dispersal of combustion products.
Top View Rear Flue
Fig. 16a
Plume
Displacement Kit
N
R D A
M C E
I I I I
S
F B
F J,K
L A
A
G H
Air Inlet
H
I
150mm
20 Fig. 17c MIN.
8.0 Flue Options
Y Concentric
The maximum equivalent lengths are 4m (horizontal) or
X
(vertical). Their lengths exclude the standard elbow and
flue/terminal assembly (horizontal) and terminal assembly
(vertical).
FLUES IN VOIDS
Consideration must be given to flue systems in voids
and the provision of adequate access for subsequent
periodic visual inspection.
NOTE: Horizontal flue pipes should always be installed with a 1.5° fall from the
terminal to allow condensate to run back to the boiler.
B
A
Y
A+B+2x45°Bends
21
Vertical Flue System
Examples (Twin Pipe) 8.0 Flue Options
Concentric
The maximum equivalent lengths are 4m (vertical). Their
Y lengths exclude the standard elbow and terminal assembly
(vertical).
X Twin Flue
The total maximum equivalent flue length is 150m.
NOTE: Each 1m of flue duct should be calculated as 2m.
22
8.0 Flue Options
M
L
J
23
8.0 Flue Options
For Vertical Flues
8.4 For Vertical Flue Systems
Vertical Flue
Adaptor
1. Undo the screws securing the blanking plate to the
boiler top panel. Discard the plate.
Gasket 2. Fix the vertical adaptor and gasket to the top panel with
the previously removed screws.
2. Fix both the air and flue adaptors with their gaskets
onto the boiler top panel. Secure with screws.
Air Duct
Adaptor
Flue Duct
Adaptor
Gasket
Gasket
24
8.0 Flue Options
m
0m The standard horizontal flue kit allows for flue lengths
80
between 270mm (105/8”) and 800mm (32”) from elbow to
m
0m terminal (Fig. 18).
27
25
9.0 Plume Displacement
Plume Outlet (‘Peak’
MUST be Uppermost)
9.1 Plume Displacement Kit (P.D.K.)
Kit No 5121371
Content of kit
1 70/110 Concentric Flue
1 1m 70 Dia Exhaust Flue Pipe
0.94 metre
2 Support Brackets
1 93° Elbow/Plume Outlet Assembly
1 Flue Trim
2 “O” Rings
1 Elbow with Gasket
28 28
9.0 Plume Displacement
26 26
Ou
Ou
24 24
Ou
Ou
tp u
tp u
tpu
tpu
22 22
9.2 Determining Permissible Lengths - P.D.K.
t Se g 5
t Se g 5
tS
tS
20 20
ett
ett
ttin
ttin
18 18
in
in
gs 1 In the graph the solid line diagonal represents the
gs 1
16 16
70Ø Exhaust (metres)
to
14 4 14
4
extensions) and the 70Ø exhaust (and any extensions or
12 12
10 10
8 8
additional bends).
6 6
24
Ou
22
t Se g 5
20
ett
18
in
16
70Ø Exhaust (metres)
14
shown to be acceptable.
4
12
10
Example 3 - Flue Lengths OK
8
In the example shown, assume that the concentric part of
6
the flue needs to be 2 metres long. Find the position of ‘2’ on
4
the horizontal axis of the graph and then project upwards to
2
the solid diagonal line. This is represented by the vertical
0
thick dotted line. Where this dotted line intersects with the
0 1 2 3 4
Concentric 70/110 Flue (metres) solid diagonal line on the graph, project across to the vertical
Example 3 axis. As can be seen this corresponds with 14 metres.
Flue Lengths - OK Therefore, the total equivalent length of the 70Ø exhaust
can be up to 14 metres. Any elbow equivalencies must be
accounted for i.e. 93° elbows are equal to 1 metre, each 45°
elbow to 0.5 metres.
70Ø Exhaust Support
Bracket
45° Elbow
Flue Length - Worked Example
X British Gas Potterton Precision - Output Setting 5
93° Elbow
Y In Fig. D opposite an additional 93° elbow and pair of 45°
elbows have been included in the 70Ø exhaust.
1 metre Extension
Also 3 straight extension pieces have been used.
27
9.0 Plume Displacement
7. Fit the boiler flue elbow to the boiler top panel, ensuring
the gasket is in place (Fig. F).
28
9.0 Plume Displacement
Plume Outlet
Elbow 9.3 General Fitting Notes - P.D.K. (cont.)
200mm Min.
Fig. I
200mm Min.
Fig. J
29
Template Literature Pack
10.0 Installation
Wall Plate
Check Site Requirements (section 7) before
commencing.
2.0
7. Ensuring the wall plate is level both horizontally and
3.0
vertically, drill and plug at least 5 securing positions at
4.0 the top and bottom through the wall plate. Utilising the
(metres)
slots available ensure the wall plate is square and secure
to the wall (Fig. 22).
Distance in metres from boiler to the wall.
For pipe lengths greater than 4m increase the off-set by 26mm
for every additional metre to maintain approx 1.5° inclination. 8. Additionally drill 2 relief holes 10mm deep in the wall
as shown on template (Fig. 22).
Fig. 21
8. Loosely route the condensate discharge pipe to the
lower left hand side of the wall plate.
Relief Holes
Wall Plate
Fig. 22
30
10.0 Installation
Fig. 22a
Internal Polystyrene
Packaging Piece
Outercase
Br
it
is
h
G
as
Fig. 23
31
10.0 Installation
Wall Plate
Fig. 24
10.4 Making the Water Connections
Return Pipe Connection (Fig. 25)
Suggested Lifting 1. The boiler has two side water connections which are
Points shown as labelled FLOW and RETURN. The front connection is the
shaded area flow pipe and the rear threaded connection is the return.
32
10.0 Installation
Wall Thickness
HORIZONTAL FLUE
33
10.0 Installation
Inner Flue Support Bracket 6. Ensure the inner flue support bracket is positioned in
the flue (Fig. 28).
7. Engage the flue into the flue elbow using soap solution
to ease the engagement ensuring the flue is assembled as
shown (Fig. 29). Rear Flue Only:- Take the tape supplied
Fig. 28 in the kit and wrap around the joint between the flue and
the elbow (Fig. 29a).
11. Make good between the wall and air duct outside the
Tape (Rear Flue Only) building ensuring the 1.5° drop between the terminal and
elbow.
Fig. 30
Flue Trim
Fig. 29
34
10.0 Installation
2. Undo the two screws securing the cable clamp and place
to one side (Fig. 31).
4. Lay the cable through the cable clamp to gauge the length
of cable required when it is connected to the 4-way
terminal block.
Fig. 31
Cable Clamp
Fig. 33
35
11.0 Electrical
op
PCB g
op
w g br
b bk r w
r
pu b
pu b r
gy br b y bk
r op
gy Flow
Overheat
g/y g/y Thermostat
Output br Gas
Selector g/y Valve
b w
CH 325 Vdc Flame Spark
Flow DC Fan bk Detection Electrode
Switch bk Electrode
L N Optional
Flow Pump
Thermistor Feed
Fan g/y
Overheat Condensate
Thermostat Trap
b - Blue r - Red
bk - Black g - Green
w - White g/y- Green/Yellow
br - Brown op - Opaque
gy - Grey y - Yellow
pu - Purple
36
11.0 Electrical
pu
pu
b
b
Optional
Output
Pump
Selector
Feed N
L
Flow
Thermistor
y b br
r
g/y
r
b
y
br g/y
Spark
CH Electrode
Flow Switch b
gy Flame
Detection
Electrode
gy
br
br
Main
PCB
w
Layout of PCB Pins
op Condensate Trap
w
br g
r bk
b
Gas Valve
w r
g/y bk
bk Fan Overheat
Thermostat
Fan bk
Flow Overheat
Thermostat
Wiring Key
b - Blue
bk - Black
br - Brown
r - Red
w - White
g/y - Green/Yellow
g - Green
gy - Grey
op - Opaque
y - Yellow
pu - Purple
37
12.0 Commissioning the Boiler
8. Having checked:
• That the boiler has been installed in accordance
with these instructions.
DO NOT check gas pressure here • The integrity of the flue system and the flue seals.
• The integrity of the boiler combustion circuit and
the relevant seals.
OUT
38
12.0 Commissioning the Boiler
Perform Flue Integrity
Visual Check
Examine all flue joints for 12.2 Checking the Combustion
soundness and ensure the
system is adequately 1. This procedure is mandatory in GB from April 2014. It is
supported. strongly recommended to perform the procedure before that
date.
No Is flue system OK ? Yes Set Boiler to Maximum Rate* *To operate at Maximum Rate
Allow the combustion to Ensure all external controls are
stabilise. Do not insert probe calling for heat, that the system
to avoid ‘flooding’ the analyser. is cold and the boiler control
Rectify all faults knob is turned fully clockwise.
If necessary call
0844 871 1555 for advice.
The appliance MUST NOT be Check CO & Combustion
commissioned until all Ratio at Maximum Rate
problems are resolved. Whilst the boiler is still
operating at maximum insert
the analyser probe into the
flue gas test point, allowing the
reading to stabilise.
40
13.0 Fitting the Outer Case
Bri
For IE, it is necessary to complete a “Declaration of
tish
Fig. 37
s
Position of Badge
41
14.0 Servicing the Boiler
5. Remove the cap from the flue sampling point, insert the
analyser probe and obtain the CO/CO2 ratio. This must be
less than 0.004.
42
14.0 Servicing the Boiler
6. Remove the outercase and lower door panel (see Fitting the
Outercase, Section 13.0).
7. Release the four 1/4 turn screws securing the air box door
panel and remove the door (Fig. 39).
43
14.0 Servicing the Boiler
Injector Pipe e) Remove the gas injector pipe from the gas valve
(push-fit) (Fig. 42).
12. Check the CO/CO2 ratio and CO2 level at the flue
Combustion sampling point (Fig.41a) is as quoted in Section 4.0,
Box Base
‘Technical Data’.
Heat Exchanger
Support Bracket 13. If the ratio or level is greater than that quoted
telephone the Technical Enquiries for further advice.
Combustion Box Base 14. Complete the relevant Service Interval Record
Securing Screws section of the Benchmark Commissioning Checklist at
Burner Securing
Screws Fig. 44 the rear of this publication and then hand it back to the
user.
44
15.0 Changing Components
Electrical Connections 4. Place a tube on the drain point to drain water away
from electrics. Turn anticlockwise to open (Fig. 45).
Safety
Thermostat The thermistor, safety thermostat, interface PCB and
the flow switch can be accessed after removal of the
outer case.
Fig. 46
15.2 Flow Temperature Thermistor and
Safety Thermostat (Fig. 46)
Clip
15.4 PCB (Figs. 48 & 49)
PCB Housing Securing 3. Fit the new PCB Housing Assembly and reassemble
Screw in reverse order.
46
15.0 Changing Components
Earth 1. Loosen the screw holding the injector pipe into the
venturi.
Protection
Sensor
Venturi
Electrical Connections
Fig. 52
Electrical Connection
Wing Nuts 47
15.0 Changing Components
Injector Pipe
15.8 Gas Valve (Fig. 53)
Boiler Side 6. Remove the two gas valve securing screws from
inside the air box holding the gas valve.
Gas Tap 10. Fit the new gas valve and reassemble in reverse
order.
Fig. 53 Electrical Plug
NOTE: Check for gas tightness after replacing gas
valve.
11. Check the CO/CO2 ratio and CO2 level at the flue
sampling point (Fig.41a) is as quoted in Section 4.0,
‘Technical Data’.
48
15.0 Changing Components
Combustion Box
The burner and heat exchanger can be changed after
Door Panel
removal of the combustion box door. To change the
heat exchanger, the fan and burner must be removed
first (see section 15.6 and 15.10).
Flow
Switch 15.11 Heat Exchanger
Fig. 56
1. Drain the boiler (see section 15.1 paragraph 2 & 3).
Securing Screws
2. Remove all components in the base of the airbox.
Heat Exchanger
Assembly
Fig. 59
49
15.0 Changing Components
Central Insulation Panel 4. Pull the central insulation panel down from the centre of
the heat exchanger and remove the lower insulation pad.
Upper Insulation
Pad 5. Fit the new insulation pad and reassemble in reverse
order.
Lower Insulation
Pad
15.13 Heat Exchanger Upper Insulation Pad (Fig. 60)
2. Note the position of the control knob. Pull the knob off
the Selector Switch. Ease the bracket to the right and
forwards, disengaging the keyhole slot from the locating
Output Selector
screw.
Switch Cover
Output Selector
3. Slacken the locknut holding the Output Selector Switch to
Switch & Bracket
the mounting bracket, remove the Switch and disconnect
the electrical plug.
5. Secure the new Selector Switch with the locknut and refit
the knob. Engage the keyhole slot in the bracket over the
screw on the boiler.
50 Label
16.0 Short Parts List
A B C
Key G.C. Description Manufacturers
No. No. Part No.
D PCB 5129147
E Fan 5109925
E
F Gas Valve 241900
51
High
17.0 Fault Finding
Reset
Lockout Boiler On Mains On General Fault Finding should only be carried out by
LED Light LED Light LED Light someone who is appropriately qualified.
(Red) (Green) (Green)
Lights
Off Off Off Go to Electrical Supply
YES
section of the fault finding
instructions. Lights
ON
On Flash On YES Go to Thermistor section
of the fault finding
instructions.
Lights ON
Go to Dry-Fire Provider.
On Flash Flash
YES
section of the fault finding
instructions. LV Wiring Harness or
ON Lights
Output Selector Switch
On On On YES Ensure 8-way PCB connector
securely pushed in. If fault
Lights ON persists replace selector switch
On Off On YES or wiring harness.
Go to Ignition Lockout section
of the fault finding instructions.
ON Lights
Flash On Flash YES PCB Fault
Replace PCB.
Lights ON
Flash Off On Go to Overheat Lockout
YES
section of the fault finding
instructions.
ON Lights
On On Flash YES PCB Fault
Replace PCB.
Lights ON
Flash Flash On Go to Fan Lockout
YES
section of the fault finding
instructions.
ON
Lights
Flash On On YES PCB Fault
Replace PCB.
ON
52
Lights 17.0 Fault Finding
Off Off Off
ELECTRICAL SUPPLY
ON
No Switched Live to
NO boiler. Check Systems
240V at A ?
Controls and System
Wiring.
YES
NO A
Check wiring from
240V at B ?
terminal block to PCB.
YES
L N Optional
Pump
Live
Check for shorts on
NO
pump, fan & gas valve.
PCB fuse OK ?
Replace if shorted &
replace fuse.
YES
Replace PCB.
B
Fuse
53
Lights 17.0 Fault Finding
On Flash Flash
DRY-FIRE
ON
Are YES
Flow & Return reversed ? Swop Flow & Return.
NO E
Is the NO
Fill system with water and
system full of water ?
bleed out all air.
L N Optional
Pump Replace PCB.
Live
YES
YES
Turn Turn
NO NO mains off, unplug
Is the mains off & on. After 5 sec, is 7-way connector to PCB.
pump running ? there 240V Is there continuity between
F and G ?
at E?
YES NO
Unplug
5-way PCB
YES
connector. Is there continuity
Replace PCB.
between H (run pump from
switched live) ?
H
G
Viewed from
Wire Entry end
NO
7-way Connector
F
Disconnect YES
Flow Switch Inline
connector. With pump running is
Wires from inline
there continuity across flow connector to PCB faulty.
switch ?
L N Optional
NO Pump
Live
Remove NO
flow switch from boiler. Is there a NO
Is there a physical blockage to blockage in the system ? Replace Flow Switch.
the paddle within the
flow switch ?
YES YES
54
Lights 17.0 Fault Finding
On Off On
IGNITION LOCKOUT
ON
I
Is NO
Check isolation valve and
there gas at gas valve inlet ?
gas supply. J
5-way Connector
YES
Remove
Reset Lockout. NO 5-way connector YES
Is there gas flow from gas valve. Is there 240 Replace Gas Valve.
(check at meter) ? Vdc between I & J
during ignition ?
YES NO
Remove
the larger or the
Is NO Lead from PCB to Gas
Remove Gas Valve & check two 6-way PCB connectors.
there at least NO Is there continuity from I to L
inlet filter for blockage. Valve faulty.
18mbar dynamic at gas valve Otherwise incorrect gas supply & from J to K ?
inlet ? to boiler.
YES
Replace PCB.
YES
Is
Condensate Trap
YES
Clear blockage and dry
blocked or water on sensors. K
terminals ?
L
NO
6-way Connector
Is
YES Replace spark or flame
spark or flame detection detection probe and
probe damaged ? gaskets.
NO
Is NO
spark gap between 3 and Set spark gap to 3.5mm.
4mm ?
YES
Is
wiring from PCB YES Is the NO
to spark probe & flame burner blocked or Replace PCB.
detection probe OK ? damaged ?
NO YES
55
Lights 17.0 Fault Finding
Flash Off On
OVERHEAT LOCKOUT
ON
Disconnect
NO
black stat on flow pipe.
When flow < 60° C is there Replace Stat.
continuity across stat ?
YES
Reconnect stat. NO
Disconnect fan stat.
When fan temp < 60° C Replace Stat.
is there continuity
across stat ?
YES
Reconnect stat.
NO M
Disconnect the larger of Wiring from PCB to
the 6-way PCB connectors.
thermostats faulty.
Is there continuity
across M ?
Disconnect
thermistor NO
(red sensor on flow pipe). Replace thermistor.
Is resistance between
0.5kΩ & 20kΩ ?
YES
Is
combustion chamber YES Replace combustion
door seal damaged or not in chamber door seal & trim
seal.
place ?
NO
Replace PCB.
56
Lights 17.0 Fault Finding
Flash Flash On
FAN LOCKOUT
Fan PCB
Connection Connection
Unplug
3-way PCB connector NO
N O
& unplug fan. Is there Rectify wiring.
continuity from N to O &
Q
from P to Q ?
P
YES
Fan PCB
Connection Connection
Unplug
the smaller of the NO
6-way PCB connector. Is there
Rectify wiring.
continuity from R to S & from T
R
to U & from
T S
V to W ? V U
W
YES
Viewed from
Wire Entry end
Replace fan.
Lights
On Flash On
THERMISTOR
ON
Unplug
thermistor, NO
Is thermistor resistance between Replace thermistor.
0.5kΩ & 20kΩ ?
D
YES
Plug in
thermistor, leave NO
8-way connector unplugged. Wiring from PCB to
Is resistance at D between thermistor faulty. Viewed from
0.5kΩ & 20kΩ ? Wire Entry end
YES
Replace PCB.
57
GAS BOILER SYSTEM COMMISSIONING CHECKLIST
This Commissioning Checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating
compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the
warranty. This does not affect the customer’s statutory rights.
ALL SYSTEMS
’s instructions Yes
What system cleaner was used?
What inhibitor was used? Quantity litres
Yes No
ALL INSTALLATIONS
At max. rate: CO ppm AND CO/CO² Ratio
Record the following:
At min. rate: (where possible) CO ppm AND CO/CO² Ratio
The heating and hot water system complies with the appropriate Building Regulations Yes
The boiler and associated products have been installed and commissioned in accordance with the manufacturer’s instructions Yes
The operation of the boiler and system controls have been demonstrated to and understood by the customer Yes
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
*All installations in England and Wales must be to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance will then be issued to the customer.
58
© Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
SERVICE RECORD
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
Signature Signature
Signature Signature
Signature Signature
Signature Signature
Signature Signature
*All installations in England and Wales must be to Local Authority Building Control (LABC) either directly or through a
Competent Persons Scheme. A Building Regulations Compliance will then be issued to the customer.
59
© Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
All descriptions and illustrations provided in this leaflet have been carefully
prepared but we reserve the right to make changes and improvements in
our products which may affect the accuracy of the information contained in
this leaflet. All goods are sold subject to our standard Conditions of Sale
which are available on request.
7209192 - 06 (1/14)