BMS Upper Computer Guidance V219 - 241228 - 055244
BMS Upper Computer Guidance V219 - 241228 - 055244
Figure 3-2
Figure 3-3
4. Communication Port Configuration
1) Port number (the upper computer will automatically identify the USB to 485 serial port
number)
2) Baud rate : 19200
See Figure 4-1
3) Click Connect
See Figure 4-2
Figure 4-1
Figure 4-2
After successful connection, the upper computer displays the battery data.
See Figure 4-3
Figure 7.1
Figure 7.2
Figure 7.3
Figure 7.4(other manufacturer information)
8. Display Interface Introduction
After successful connection, the red box below is the display Interface Introduction
See Figure 8-1
Detailed introduction see Table 8-1
Figure 8-1
Voltage difference
Voltage
between the max voltage
difference
and min voltage
Charge current
Or
Current
Discharge current
(negative value)
Upload
Remain_ parameter-Num59
Current battery capacity
capacity can set current
capacity
Actual capacity after full
Total_capacity
battery
Remain_capacity/Tota
SOC State of charge
l_capacity*100%
Upload
Nominal_
Rate capacity. parameter-Num58
capacity
can set capacity
The number of cycles
will be increased by
one when the
Battery_cycles Cycle number
cumulative discharge
capacity reaches 80%
of the full capacity
When there is no
Port voltage. external connection,
Bus voltage Detection of external the bus voltage is
voltage equal to the total
battery voltage
Green: switch
Discharge Discharge switch connected
switch indicator Gray: switch
disconnected
Green: switch
connected
Charge switch Charge switch indicator
Gray: switch
disconnected
Green:switch
Current limit Current limit switch connected
switch indicator Gray:switch
disconnected
Green:switch
Temperature Temperature control connected
control switch switch indicator Gray:switch
disconnected
Warn and BMS warning and protect
Protect display area
Table 8-1
9. Parallel Mode
1) Parallel pack selection
When several batteries(max to 16) are combined, ensure that the corresponding address dialed
by the BMS is consistent with the address set (pack x)by the upper computer(click the pack
number to light up or greyed the icon).
See Figure 9-1
2) When confirming the number of parallel machines, click connect to upper computer and
select Cycle Refresh. The upper computer can see the number of parallel machines and pack
refresh data
See Figure 9-2
3) On the upper computer interface, you can click Multiple to see each group of PACK data
See Figure 9-3
Figure 9-1
In figure 9-1, there are 2 pack icons display in the pack frame, this means there are 3 packs in
parallel status. Only the slave pack can be displayed in the pack frame.
Figure 9-2
Figure 9-3
10. Firmware update
10.1 Open Firmware Update (BMS boot state)
10.2 Use USB to 485 communication line, select the corresponding port, select the baud rate of
19200, and click Open.
10.3 Select folder— —Jump out of corresponding box— —choice the target program( This
program. ehex format)
10.4 Click download and the progress bar will appear (When you report an error, try pressing
the reset button or downloading it several times)
10.5 after the program upgrade OK, prompt download successful proof that the program
upgrade OK.
Note: This upgrade software can also be upgraded according to the corresponding address.
If the address of BMS is consistent with the address of Pack number, it can be upgraded.
Figure 11-2
Click STOP to stop record.
Figure 11-3
Click RUN to record again.
Click Clear to empty the record frame.
Click Save to export the record document.