0% found this document useful (0 votes)
77 views3 pages

Topsolar PV ZZ-F H1Z2Z2-K Specs

The TOPSOLAR PV ZZ-F / H1Z2Z2-K is a TÜV & EN certified solar PV string cable designed for connecting photovoltaic panels, featuring a flexible tinned copper conductor and low smoke zero halogen (LSZH) rubber insulation. It is suitable for various environmental conditions, with excellent chemical resistance and a maximum service temperature of 120ºC. The cable is available in multiple cross-sections and has an estimated lifetime of 30 years.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views3 pages

Topsolar PV ZZ-F H1Z2Z2-K Specs

The TOPSOLAR PV ZZ-F / H1Z2Z2-K is a TÜV & EN certified solar PV string cable designed for connecting photovoltaic panels, featuring a flexible tinned copper conductor and low smoke zero halogen (LSZH) rubber insulation. It is suitable for various environmental conditions, with excellent chemical resistance and a maximum service temperature of 120ºC. The cable is available in multiple cross-sections and has an estimated lifetime of 30 years.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

TOPSOLAR PV ZZ-F / H1Z2Z2-K

TOPSOLAR PV
ZZ-F / H1Z2Z2-K
TÜV & EN solar PV string cable.
EN 50618/ TÜV 2Pfg 1169-08 / UTE C 32-502

DESIGN

Conductor
Class 5 (flexible) tinned copper, based on EN 60228 and IEC 60228. Dca
Insulation
Low smoke zero halogen (LSZH) rubber.

Outer sheath
Low smoke zero halogen (LSZH) rubber, red or black colour.

APPLICATIONS
String cable TopSolar ZZ-F / H1Z2Z2-K is a solar PV cable, TÜV & EN certified, specia-
lly designed for the connection of photovoltaic panels. This versatile single-conductor
cable is designed to meet the varying needs of the solar industry. Higly flexible cable,

SOLAR CABLES
compatible with all major connectors. Suitable for wet, damp and humid locations.

www.topcable.com 121
TOPSOLAR PV ZZ-F / H1Z2Z2-K

CHARACTERISTICS

Electrical performance Mechanical performance


LOW VOLTAGE 1,5/1,5 1kV · (1,8) kV DC. Minimum bending radius: x3 cable diameter.
Impact resistance: AG2 Medium severity.

Standard
EN 50618/ TÜV 2Pfg 1169-08 / UTE C 32-502. Chemical performance
Chemical & Oil resistance: Excellent.
Grease & mineral oils resistance: Excellent.
Approvals
CE
TÜV UV UV Resistant
EN UV Resistant based on EN 50618 and TÜV 2Pfg 1169-08.
RoHS

Water performance
Dca
Water presence: AD8 submerged.

Thermal performance
Maximum service temperature: 120ºC.
Life Estimated Lifetime
Estimated lifetime 30 years based on UNE-EN 60216-2.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC.

Other
Fire performance
Meter by meter marking.
Flame non-propagation based on UNE-EN 60332-1 and
IEC 60332-1.
LSZH (Low Smoke Zero Halogen) based on UNE-EN Installation conditions
60754-1 and IEC 60754-1. Open Air.
Low smoke emission based on UNE-EN 61034 and IEC Buried.
61034: Light transmittance > 60%
Low corrosive gases emission based on UNE-EN 60754-2
Applications
and IEC 60754-2.
Reaction to fire CPR: Dca , according to EN 50575. Solar PV installations - string cable.

122 Top Cable


TOPSOLAR PV ZZ-F / H1Z2Z2-K

DIMENSIONS
Cross Diameter Weight Open Inst. on Inst. Voltage
section Air surface adjoining drop
(mm2) (mm2) (Kg/km) (A) (A) to surface (V/A · km)
(A)
1 x 2,5 4,8 42 41 39 33 23,0
1x4 5,3 57 55 52 44 14,3
1x6 5,9 76 70 67 57 9,49
1 x 10 7,0 120 98 93 79 5,46
1 x 16 8,2 179 132 125 107 3,47
1 x 25 10,8 294 176 167 142 2,23
1 x 35 11,9 390 218 207 176 1,58

SOLAR CABLES

Maximum current capacity according to IEC 60364-5-52.


For other installation conditions, please refer to correction factors in the appendix to this catalogue.
See more technical data on the particular cable specification and on its Declaration of Performance (DoP)
Top Cable reserves the right to carry out any modification to the data sheets whatsoever without giving
previous notice.

For more information please contact [email protected]

www.topcable.com 123