Format No:- UGTL/CA/01
TEST REPORT
JOB ID No.: UGTL/CAC/271223/49 Date: 04-01-2025 TR NO – 2024/08/72
CLIENT : The Project Director, Product : IS: 383-2016
WAPCOS Limited, Bhubaneswar. Specification (Amendment No 2-
Name of 2019)
Contractor : Silki Construction Test Specification : Tabulated Below
K.M. Mallik Road, Lalpur,
Ranchi-834001 (Jharkhand) Seal / Stamp / : Nil
Description : 20mm coarse aggregate sample for the following test. Mark (if any)
of Sample (s)
Name of Work:- Construction of 120 seated ST Hostel at Thakurmunda Sample received on : 01-01-2025
Govt. High School at Thakurmunda Mayurbhanj. Sample tested on : 03-01-2025
Test : Aggregate Impact Value,
Parameters
This is to certify that the above sample (S) has/have been tested with the following results
COARSE AGGREGATE PHYSICAL PROPERTIS:-
S. No. Parameters Results Req, as per IS:383-2016 Test Method
30% Max for wearing
1. Aggregate Impact Value (%) 16.81 surface Concrete & 45% IS:2386 (P-4)-1963,
Max for other Concrete Reaf:2021
Aggregate impact value (Dry) IS: 2386- Part 1V : 2386- 2021)
Wt. of Metal Passing AIV% Average AIV
Trial Wt. of Oven Dried 2.36mm Sieve (gms) %
No. Metal Taken(gms)
1 341 60.3 17.68
2 355 56.4 15.89 16.81
3 349 58.9 16.88
1. The test report relates to the Sample(s) submitted by Customer.
2. Liability for return of sample(s) ceases after fifteen days unless otherwise advised by concerned authority.
3. The reproduction of the report except in full is invalid without written approval of the laboratory management.
4. The test result referred in certificate are based on observations measurements under the stated environmental
………conditions.
5. The test Report cannot be used as an evidence in the court of Law, without written
permission of the ….. laboratory.
. Authorized Signatory
*** END OF REPORT***