26spa6 1si
26spa6 1si
Installation Instructions
NOTE: For use with R-454B indoor units only. Read the entire instruction manual before starting installation.
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 death. WARNING signifies hazards which could result in personal
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 injury or death. CAUTION is used to identify unsafe practices which
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 may result in minor personal injury or product and property damage.
Check Equipment and Job Site . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 NOTE is used to highlight suggestions which will result in enhanced
Install on a Solid, Level Mounting Pad . . . . . . . . . . . . . . . . . . . . . 2 installation, reliability, or operation.
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Operating Ambient. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 ! WARNING
Make Piping Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mandatory Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 ELECTRICAL SHOCK HAZARD
Make Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Failure to follow this warning could result in personal injury or death.
Compressor Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Before installing, modifying, or servicing system, main electrical
Install Electrical Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 disconnect switch must be in the OFF position. There may be more than
1 disconnect switch. Lock out and tag switch with a suitable warning
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
label.
Check Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Final Checks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Repairing Refrigerant Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 ! WARNING
SAFETY CONSIDERATIONS EXPLOSION HAZARD
Failure to follow this warning could result in death,
IMPORTANT: This appliance shall only be installed by EPA qualified
serious personal injury, and/or property damage.
personnel having appropriate certification. This appliance is not
intended for use by persons (including children) with reduced physical, Never use air or any gas containing oxygen for leak
sensory or mental capabilities or lack of experience and knowledge, testing or operating refrigerant compressors. Never
unless they have been given supervision or instruction concerning use of allow compressor suction pressure to operate in a
the appliance by a person responsible for their safety. vacuum with service valves closed. See service
manual for pump-down instructions.
Improper installation, adjustment, alteration, service, maintenance, or
use can cause explosion, fire, electrical shock, or other conditions which
may cause death, personal injury, or property damage. Consult a GENERAL
qualified installer, service agency, or your distributor or branch for NOTE: In some cases noise in the living area has been traced to gas
information or assistance. The qualified installer or agency must use pulsations from improper installation of equipment.
factory-authorized kits or accessories when modifying this product. 1. Roof mounted units exposed to winds may require wind baffles.
Refer to the individual instructions packaged with the kits or accessories
when installing. 2. Locate unit away from windows, patios, decks, etc. where unit
operation sound may disturb customer.
Follow all safety codes. Wear safety glasses, protective clothing, and
work gloves. Use quenching cloth for brazing operations. Have a dry 3. Ensure that vapor and liquid tube diameters are appropriate for unit
powder or CO2 fire extinguisher available. Read these instructions capacity.
thoroughly and follow all warnings or cautions included in literature and 4. Run refrigerant tubes with no bends with centerline bend radius less
attached to the unit. Consult local building codes and current editions of than 2.5 times the external pipe diameter.
the National Electrical Code (NEC) NFPA 70. In Canada, refer to 5. Leave some slack between structure and unit to absorb vibration.
current editions of the Canadian electrical code CSA 22.1.
6. When passing refrigerant tubes through the wall, seal opening with
Proper tools should be used that are designed for the refrigerant of the
unit being installed. For A2L refrigerants, non-sparking tools are RTV or other pliable silicon-based caulk. (See Fig. 1.)
required. A refrigerant detector should be used prior to and during the 7. Avoid direct tubing contact with water pipes, duct work, floor
installation process to check for leaks. Open flames or other ignition joists, wall studs, floors, and walls.
sources should not be present except during brazing. Brazing should 8. Do not suspend refrigerant tubing from joists and studs with a rigid
only take place on refrigerant tubes that are open to the atmosphere or wire or strap which comes in direct contact with tubing (see Fig. 1).
have been properly evacuated.
9. Ensure that tubing insulation is pliable and completely surrounds
Recognize safety information. This is the safety-alert symbol When vapor tube.
you see this symbol on the unit and in instructions or manuals, be alert to 10. When necessary, use hanger straps which are 1 in. (25 mm) wide
the potential for personal injury.
and conform to shape of tubing insulation. (See Fig. 1.)
Understand these signal words; DANGER, WARNING, and CAUTION.
These words are used with the safety-alert symbol. DANGER identifies 11. Isolate hanger straps from insulation by using metal sleeves bent to
the most serious hazards which will result in severe personal injury or conform to shape of insulation.
26SPA6: Installation Instructions
12. Provision shall be made for expansion and contraction of long runs contains information needed to properly install unit. Check rating plate
of piping. to be sure unit matches job specifications.
13. Piping and fittings shall be protected as far as possible against Install on a Solid, Level Mounting Pad
adverse environmental effects. For example, the accumulation of If conditions or local codes require the unit be attached to pad, tie down
dirt and debris. bolts should be used and fastened through knockouts provided in unit
14. Piping should be installed to reduce the likelihood of hydraulic base pan. Refer to unit mounting pattern in Fig. 2 to determine base pan
shock damaging the system. size and knockout hole location.
15. Certified piping and components must be used in order to protect For hurricane tie downs, contact local distributor for details and PE
against corrosion. (Professional Engineer) certification, if required.
16. Flexible pipe elements shall be protected against mechanical
damage, excessive stress by torsion, or other forces. They should be
checked for mechanical damage annually.
17. Piping material, routing, and installation shall include protection
from physical damage in operation and service, and be in
compliance with the national and local codes and standards of the
installation site.
18. When setting up refrigerant piping, precautions shall be taken to
avoid excessive vibration or pulsation
OUTDOOR WALL INDOOR WALL
CAULK
LIQUID TUBE
31–1/2 X 31–1/2
JOIST 9–1/8 (231.8) 6–9/16 (166.7) 24–11/16 (627.1)
(800.1 X 800.1)
HANGER STRAP
(AROUND SUCTION 35 X 35
TUBE ONLY) INSULATION 9–1/8 (231.8) 6–9/16 (166.7) 28–7/16 (722.3)
(889 X 889)
SUCTION TUBE
A05177
Fig. 2 – Tiedown Knockout Locations
On rooftop applications, mount on level platform or frame. Place unit
above a load-bearing wall and isolate unit and tubing set from structure.
Arrange supporting members to adequately support unit and minimize
1” (25.4 mm) transmission of vibration to building. Consult local codes governing
MIN LIQUID TUBE rooftop applications.
SUSPENSION Roof mounted units exposed to winds may require wind baffles.. Consult
A07588 the Application Guideline and Service Manual - Residential Split
Fig. 1 – Connecting Tubing Installation
System Air Conditioners and Heat Pumps for wind baffle construction.
INSTALLATION NOTE: Unit must be level to within ±2° (±3/8 in./ft.±9.5 mm/m) per
compressor manufacturer specifications.
IMPORTANT: Effective January 1, 2023, all split system and packaged
air conditioners must be installed pursuant to applicable regional Clearance Requirements
efficiency standards issued by the Department of Energy. When installing, allow sufficient space for airflow clearance, wiring,
refrigerant piping, and service. Allow 24 in. (610 mm) clearance to
! CAUTION service end of unit and 48 in. (1219 mm) above unit. For proper airflow,
a 6-in. (152 mm) clearance on 1 side of unit and 12-in. (305 mm) on all
CUT HAZARD remaining sides must be maintained. Maintain a distance of 24 in. (610
mm) between units or 18 in. (457 mm) if no overhang within 12 ft. (3.67
Failure to follow this caution may result in personal injury. m) Position so water, snow, or ice from roof or eaves cannot fall directly
Sheet metal parts may have sharp edges or burrs. Use care and wear on unit.
appropriate protective clothing and gloves when handling parts. NOTE: 18” (457 mm) clearance option described above is approved for
outdoor units with wire grille coil guard only. Units with louver panels
Check Equipment and Job Site require 24” (610 mm) between units.
On rooftop applications, locate unit at least 6 in. (152 mm) above roof
Unpack Unit
surface.
Move to final location. Remove carton taking care not to damage unit.
Operating Ambient
Inspect Equipment
The minimum outdoor operating ambient in cooling mode without
File claim with shipping company prior to installation if shipment is accessory is 55°F (13°C).
damaged or incomplete. Locate unit rating plate on unit corner panel. It
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
26SPA6: Installation Instructions
Outdoor units may be connected to indoor section using accessory If using brazing connections, use a properly sized swedge tool to create a
tubing package or field-supplied refrigerant grade tubing of correct size swedge (bell) on one of the two copper tubes being connected.
and condition. Rated tubing diameters shown in Table 1 are
Alternatively, a copper coupling can be used which will require two
recommended up to 80 ft. (24 m). See Product Data for acceptable
alternate vapor diameters and associated capacity losses. For tubing braze joints instead of one.
requirements beyond 80 ft. (24 m), substantial capacity and performance Clean line set tube ends with emery cloth or steel brush. Remove any grit
losses can occur. Following the recommendations in the Residential or debris.
Piping and Long Line Guideline will reduce these losses. Refer to Connect vapor tube to fitting on outdoor unit vapor service valves (see
Table 1 for field tubing diameters. Refer to the Product Data for Table 1). Connect liquid tubing to adapter tube on liquid service valve.
accessory requirements.
Use refrigerant grade tubing.
There are no buried-line applications greater than 36-in. (914 mm)
Apply heat absorbing paste or heat sink product between service valve
allowed.
and joint. Wrap service valves with a heat sinking material such as a wet
If refrigerant tubes or indoor coil are exposed to atmosphere, they must
cloth.
be evacuated to 500 microns to eliminate contamination and moisture in
the system. After wrapping service valve with a wet cloth, tubing set can be brazed
to service valve using either silver bearing or non–silver bearing brazing
Refrigerant pipe should be installed with the minimum length possible
material. Do not use soft solder (materials which melt below
and practical for the application. Piping should be protected from
800°F/427°C). Braze joints using a Sil-Fos or Phos-copper alloy.
physical damage in operation and in service and be in compliance with
national and local codes such as ASRHAE 15, ASHRAE 15.2, IAPMO. Consult local code requirements.
Uniform Mechanical Code, ICC International Mechanical Code, or CSA Some outdoor units contain a mechanical fitting at the liquid distributor.
B52. When piping is installed through studs in a wall, steel plates should This connection is not field serviceable and should not be disturbed.
be used for protection with a minimum thickness of 16 gauge. For Vapor Service Valve, remove valve core from schrader port on
Service Valve BEFORE brazing. This helps prevent overheating and
All field joints shall be accessible for inspection prior to being covered
damage to valve seals (refer to Fig. 3). Replace valve core when brazing
or enclosed.
is completed.
Outdoor Unit Connected to Factory Approved R-454B
Indoor Unit
When outdoor unit is connected to factory–approved R-454B indoor
unit, outdoor unit contains approximate system refrigerant charge for
operation with AHRI rated indoor unit when connected by 15 ft. (5 m) of
field–supplied or factory accessory tubing and factory supplied filter
drier. For all sizes, adjust charge by adding or removing 0.6 oz/ft of 3/8
liquid line above or below 15 ft. (5 m) respectively.
A14236
Connect vapor and liquid tubes to fittings on vapor and liquid service Fig. 3 – Vapor Service Valve
valves (see Table 1). Use refrigerant grade tubing.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
26SPA6: Installation Instructions
! WARNING
FIRE HAZARD
Failure to following this warning could result in personal injury, death
and/or property damage.
Refrigerant and oil mixture could ignite and burn as it escapes and
contacts brazing torch. Make sure the refrigerant charge is properly A05178
removed from both the high and low sides of the system before brazing Fig. 4 – Liquid Line Filter Drier
any component or lines. Evacuate Refrigerant Tubing and Indoor Coil
! CAUTION
! CAUTION UNIT DAMAGE HAZARD
BURN HAZARD Failure to follow this caution may result in equipment damage or
Failure to follow this caution may result in personal injury improper operation.
Components will be HOT after brazing. Wear appropriate personal Never use the system compressor as a vacuum pump.
protective equipment and allow to cool before handling parts and
equipment. Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate triple
Table 1 – Refrigerant Connections and Recommended Liquid and evacuation method may be used (see triple evacuation procedure in
Vapor Tube Diameters (In.) service manual). Always break a vacuum with dry nitrogen.
LIQUID* RATED VAPOR*
Leak Check
UNIT SIZE Connection The deep vacuum method requires a vacuum pump capable of pulling a
Tube Diameter Tube Diameter
Diameter vacuum of 500 microns and a vacuum gauge capable of accurately
18 3/8 3/4 5/8 measuring this vacuum depth. The deep vacuum method is the most
24, 30 3/8 3/4 3/4 positive way of assuring a system is free of air and liquid water. A tight
36, 42, 48 3/8 7/8 7/8 dry system will hold a vacuum of 1000 microns after approximately 7
60 3/8 7/8 1-1/8
minutes. See Fig. 5
*.Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance
data when using different size and length linesets.
Notes:
1.Do not apply capillary tube indoor coils to these units.
2.For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 35
ft.(11 m) vertical differential 250 ft. (76.2 m) Total Equivalent Length, refer to the
Residential Piping and Long Line Guideline – Air Conditioners and Heat Pumps using
Puron Advance™ refrigerant.
3.For alternate liquid line options, see Product Data or Residential Piping and Long Line
Application Guideline
Mechanical Line Set Connections
A95424
If using mechanical or crimp-type line set connections, follow crimp tool Fig. 5 – Deep Vacuum Graph
manufacturer's instructions. Mechanical fittings are only permitted if Mandatory Requirements
approved for field installation by the supplier.
Pressure Proof Check
NOTE: Failure of the fittings or failure of the equipment due to use of
mechanical fittings would not be covered under the equipment limited Refrigerant tubes and indoor coil should be pressure tested with an inert
warranty. gas such as nitrogen. Pressurize the system with the inert gas to the Low
Install Liquid-Line Filter Drier Indoor Side Test Pressure listed on the outdoor unit rating plate.
Refer to Fig. 4 and install filter drier as follows: 1. Pform a pressure check of the unit with a nitrogen charge of about
200psi.
! CAUTION 2. The Nitrogen holding charge must NOT decrease in pressure for 1
hour, as indicated by the test gauge. The measuring test gauge
UNIT DAMAGE HAZARD resolution not exceeding 5% of the holding charge.
Failure to follow this caution may result in equipment damage or
improper operation.
1. Installation of filter drier in liquid line is required.
! WARNING
2. Filter drier must be wrapped in a heat-sinking material such as a wet EXPLOSION HAZARD
cloth while brazing. Failure to follow this warning could result in death,
serious personal injury and/or property damage.
1. Braze 5-in. liquid tube to the indoor coil. Never exceed the test pressures listed on the rating
2. Wrap filter drier with damp cloth. plate when pressure testing an outdoor unit.
3. Braze filter drier to above 5-in. (127 mm) liquid tube. Flow arrow
must point towards indoor coil.
4. Connect and braze liquid refrigerant tube to the filter drier.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
26SPA6: Installation Instructions
! WARNING
FIRE HAZARD
Failure to following this warning could result in personal injury, death
and/or property damage.
DO NOT USE FLAMES OR IGNITION SOURCES TO LEAK
CHECK.
! WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
The unit cabinet must have an uninterrupted or unbroken ground to
minimize personal injury if an electrical fault should occur. The ground
may consist of electrical wire or metal conduit when installed in
accordance with existing electrical codes.
A0240284/A97368
Fig. 7 – Generic Wiring Diagrams (See Thermostat Installation
Instruction for specific unit combinations)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
5
26SPA6: Installation Instructions
! WARNING
PERSONAL INJURY AND/OR PROPERTY DAMAGE
HAZARD
Failure to follow this warning could result in personal injury and/or
property damage.
For continued performance, reliability, and safety, the only approved
accessories and replacement parts are those specified by the equipment
manufacturer. The use of non-manufacturer approved parts and
accessories could invalidate the equipment limited warranty and result
in fire risk, equipment malfunction, and failure.
Please review manufacturer's instructions and replacement part catalogs
available from your equipment supplier.
Start-Up
! CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage.
Federal regulations require that you do not vent refrigerant to the
atmosphere. Recover during system repair or final unit disposal.
! CAUTION
UNIT OPERATION AND SAFETY HAZARD
HK32EA013
Fig. 8 – InteliSense™ Control Board Failure to follow this caution may result in personal injury, equipment
For more information, refer to the thermostat advanced installation and damage or improper operation.
configuration instructions found at: • Do not overcharge system with refrigerant.
Carrier.HVACPartners.com/InteliSense or, by scanning this QR Code: • Do not operate unit in a vacuum or at negative pressure.
• Compressor dome temperatures may be hot.
! CAUTION
NOTE: A new thermostat will show up in connected portal 24 hours PERSONAL INJURY HAZARD
after field installation so field gauges are needed for install. Failure to follow this caution may result in personal injury.
NOTE: The outdoor temperature sensor does not show up on this new Wear safety glasses, protective clothing, and gloves when handling
thermostat display so it should not be used for troubleshooting or refrigerant and observe the following:
charging.
• Front seating service valves are equipped with Schrader valves.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
26SPA6: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
26SPA6: Installation Instructions
Training
My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses. We
believe in providing high quality learning experiences both online and in the classroom.
Access My Learning Center with your HVACpartners credentials at www.mlctraining.com. Please contact us at [email protected] with
questions.
© 2024 Carrier. All rights reserved. Edition Date: 06/24 Catalog No: 26SPA6-1SI
Replaces:New
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
8