BMS I/O LIST FOR FUEL SYSTEM
HW -03 Project: System:01
Relay Output from Fuel System Control Panel to the BMS
S.NO. DESCRIPTION AI AO DI DO
A Fuel Transfer Pump
1 Pump Start/Stop Status 2
2 Pump Run/Trip Status 2
3 Pump Auto Manual Switch Status 2
B Level Switch
1 High-High Level Status 1
2 High Level Status 1
3 Low Level Status 1
4 Low-Low Level Status 1
C Leak Detection
1 Leak Status 1
D Solenoid Valve
1 Open Status 1
2 Close Status 1
E Buildings Fire Alarm Integration with the Fuel System Control Panel
1 Fire alarm Status 1
TOTAL IO POINTS 14
PLC Output from Fuel Polishing System Control Panel to the BMS
S.NO. DESCRIPTION AI AO DI DO
A Fuel Polishing System
1 Fuel Leak alarm Status 1
2 Water in bowl Status 1
3 Pressure Alarm to change the Secondary Filter Status 1
4 Vacuum Alarm to change the Primary filter Status 1
5 Motor Overload Status 1
6 External Shutdown Status 1
TOTAL IO POINTS 6