California State Approval Drawings Full

The document outlines the general notes and requirements for a construction project, including compliance with various California building codes and plumbing standards. It specifies fire blocking locations, plumbing fixture standards, smoke and carbon monoxide alarm installations, and site drainage provisions. Additionally, it details the project description, including the construction of a new detached 1-bedroom ADU in the rear yard, along with various structural and safety requirements.

Uploaded by

sajjad.khan.emon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
73 views9 pages

California State Approval Drawings Full

The document outlines the general notes and requirements for a construction project, including compliance with various California building codes and plumbing standards. It specifies fire blocking locations, plumbing fixture standards, smoke and carbon monoxide alarm installations, and site drainage provisions. Additionally, it details the project description, including the construction of a new detached 1-bedroom ADU in the rear yard, along with various structural and safety requirements.

Uploaded by

sajjad.khan.emon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

GENERAL NOTES DRAWING LIST NOTE:

PLANS TO COMPLY WITH THE FOLLOWING CODES A-1 TITLE BLOCK/SITE/ROOF Fire blocking must be provided in accordance with Section R302.11 of CRC at the following locations:
 In concealed spaces of stud walls and partitions, including furred spaces, at the ceiling and floor levels.
2022 CALIFORNIA BUILDING CODE, 2022 CALIFORNIA ELECTRICAL CODE, 2022 CALIFORNIA MECHANICAL CODE
2022 CALIFORNIA PLUMBING CODE, 2022 CALIFORNIA ENERGY CODE, 2022 CALIFORNIA FIRE CODE
A-2 EXISTING/NEW PLANS  In concealed spaces of stud walls and partitions, including furred spaces, at 10-foot intervals along the length of the wall.
 At all interconnections between concealed vertical and horizontal spaces such as occur at soffits, drop ceilings and cove ceilings.
THE PLUMBING FIXTURES AND PLUMBING FITTING SHALL MEET THE STANDARDS NOTED BELOW: T-1 TITLE 24 PROPERTY LINE: 64.98'
A) WATER CLOSET= 1.28 GALLONS PER FLUSH MAX.
B) SHOWER HEAD= 1.8 GPM MAX.
S-1 STRUCTURAL NOTES

7' - 0"
C) LAVATORY FAUCETS= 1.2 GPM MAX.
D) SINK FAUCETS= 1.8 GPM MAX" TITLE 24, CBC, CPC.
E) URINALS= 0.125 GALLON/FLUSH S-2 FOUNDATION/FRAMING
PROVIDE ULTRA FLUSH WATER CLOSETS FOR ALL NEW CONSTRUCTION. EXISTING SHOWER HEADS AND TOILETS MUST BE
ADAPTED FOR LOW WATER CONSUMPTION.
S-3 ROOF FRAMING
SITE DRAINAGE: SHOW ON PLANS HOW CONCENTRATED DRAINAGE IS BEING CONVEYED TO THE STREET VIA NON-EROSIVE S-4 STRUCTURAL DETAILS
DEVICES ZonouZ deZine

AUTOMATIC GARAGE DOOR OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE WITH UL 235.
S-5 STRUCTURAL DETAILS (N) 1-STORY 15560 Rockfield Blvd Unit 212, Irvine, CA 92618 949-880-7146

THESE DRAWINGS, SPECIFICATIONS, IDEAS AND


AN APPROVED SMOKE ALARMS SHALL BE INSTALLED IN EACH SLEEPING ROOM & HALLWAY OR AREA GIVING ACCESS TO A S-6 STRUCTURAL DETAILS ADU ARRANGEMENTS PRESENTED THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF ZONOUZ INC, NO PART
SLEEPING ROOM, AND ON EACH STORY AND BASEMENT FOR DWELLINGS WITH MORE THAN ONE STORY. SMOKE ALARMS
SHALL BE INTERCONNECTED SO THAT ACTUATION OF ONE ALARM WILL ACTIVATE ALL ALARMS WITHIN THE DWELLING. THE THEREOF SHALL BE COPIED, DISCLOSED TO OTHERS
NEW CONSTRUCTION SMOKE ALARMS SHALL RECEIVE THEIR PRIMARY SOURCE OF POWER FROM THE BUILDING WIRING OR USED IN CONNECTION WITH ANY PROJECT OTHER
AND SHALL BE EQUIPPED WITH BATTERY BACK UP AND LOW BATTERY SIGNAL. THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE
UP BEEN PREPARED AND DEVELOPED WITHOUT THE
FOR EXISTING POOL ON SITE PROVIDE ANTI-ENTRAPMENT COVER MEETING THE CURRENT ASTM or ASME IS REQUIRED FOR WRITTEN CONSENT OF ZONOUZ INC.
THE SUCTION OUTLETS OF THE SWIMMING POOL, TODDLER POOL AND SPA FOR SINGLE FAMILY DWELLINGS PER THE VISUAL CONTACT WITH THESE DRAWINGS OR
ASSEMBLY BILL No.2977 SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE
(E) LANDSCAPE EVIDENCE OF ACCEPTANCE OF THESE RESTRICTIONS.
THE PROJECT CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT ADJACENT PROPERTIES, WORKERS,
AND THE OTHER PERSONS DURING THE EXCAVATION AND SITE PREPARATION OPERATIONS. KEY NOTES
PROVIDE ANTI-GRAFFITI FINISH AT FIRST 9' FEET MEASURED FROM GRADE, AT EXTERIOR WALLS & DOORS.

PROVIDE RAIN GUTTERS AND CONVEY RAIN WATER TO THE STREET 5' - 6"

IF ADVERSE SOIL CONDITIONS ARE ENCOUNTERED, A SOILS INVESTIGATION REPORT MAY BE REQUIRED

PRIOR TO ANY CONSTRUCTION OPERATIONS, A LICENSED TESTING LABORATORY SHALL DETERMINE WHETHER THE
EXISTING FOUNDATION IS POST-TENSIONED AND PROVIDE DOCUMENTATION OF SAME TO THE CITY OF LOS ANGELES. IF
POST TENSION STRANDS EXIST THE PROJECT CONTRACTOR SHALL SUBMIT A REVISED FOUNDATION PLAN SHOWING
ANCHOR AND TENDON LOCATIONS AND OBTAIN A FIELD REVISION TO THE BUILDING PERMIT

AN APPROVED CARBON MONOXIDE ALARMS SHALL BE INSTALLED DWELLING UNITS IN SLEEPING UNITS WITHIN WHICH FUEL- ATTIC VENT CALC.

PROPERTY LINE: 110.0'

PROPERTY LINE: 120.0'


BURNING APPLIANCES ARE INSTALLED AND IN DWELLING UNITS THAT HAVE ATTACHED GARAGES. CARBON MONOXIDE
ALARMS SHALL BE PROVIDED OUTSIDE OF EACH SEPARATE DWELLING UNIT SLEEPING AREA IN THE IMMEDIATE VICINITY OF ATTIC AREA= 200 sq. ft.
THE BEDROOMS ON EVERY LEVEL OF A DWELLING UNIT INCLUDING BASEMENTS

PROVIDE EMERGENCY EXIT DOOR OR WINDOW FROM BASEMENT AND/ OR SLEEPING ROOM(S). NET CLEAR WINDOW ATTIC VENT REQUIRED: 192 sq. in.

19' - 9"
OPENING AREA SHALL BE NOT LESS THAN 5.7 SQ.FT. (821 SQ. IN.). MIN. NET WINDOW OPENING HEIGHT DIMENSION, 24"
CLEAR; MIN. NET OPENING WIDTH DIMENSION, 20" CLEAR. FINISHED SILL HEIGHT MAX. 44" ABOVE FLOOR." CBC 310.4 SCOPE OF WORK 200 /150 = 1.33 sq. ft.
1.33 X 144 = 192 sq. in.
WATER HEATER MUST BE STRAPPED TO WALL." SEC. 507.3, CPC
NEW DETACHED 1-BEDROOM
A COPY OF THE EVALUATION REPORT AND/OR CONDITIONS OF LISTING SHALL BE MADE AVAILABLE AT THE JOB SITE
ADU IN REAR YARD. 796 SQ.FT. PROVIDED : 226 sq.in.
AN APPROVED SEISMIC GAS SHUTOFF VALVE WILL BE INSTALLED ON THE FUEL GAS LINE ON THE DOWN STREAMS SIDE OF
THE UTILITY METER AND BE RIGIDLY CONNECTED TO THE EXTERIOR OF THE BUILDING OR STRUCTURE CONTAINING THE (2)16"x14" GABLE= 226 sq. in.
FUEL GAS PIPING." (PER ORDINANCE 171,874-FOR WORK OVER $10,000.)

PROVIDE 70 INCH HIGH NON-ABSORBENT WALL ADJACENT TO SHOWER AND APROVED SHATTER- RESISTANT MATERIALS
FOR SHOWER ENCLOSURE." 91.807.1.3, 91.2406.4(5), 91.1115B.9.6,7,8 NOTES:
-ATTIC VENTS PROTECTED BY
ALL DIAPHRAGM AND SHEAR WALL NAILING SHALL UTILIZE COMMON NAILS OR GALVANIZED BOX
(E) 1-STORY S.F.D 1/4" CORROSION RESISTANT METAL MESH
-ATTIC ACCESS THROUGH (N)
VICINITY MAP NO WWORK INSIDE THE HOUSE
1400 BEECHWOOD AVE

(E) CONCERET
BLOCK MAP LEGAL DESCRIPTION DRIVEWAY
(E) LANDSCAPE
2 % DRAINAGE

2 % DRAINAGE
TO STREET

TO STREET
Site Address 1400 BEECHWOOD AVE
ZIP Code
PIN Number
Lot/Parcel Area (Calculated) 9,822 (sq ft)
Thomas Brothers Grid
Assessor Parcel No. (APN) 284-121-17
Tract TR 3385

3' - 0"
Map Reference
Block None PROPERTY LINE: 54.75'
Lot 16
Arb (Lot Cut Reference) None

5' - 0"
1400 BEECHWOOD AVE Map Sheet
30' - 0"

Engineer of Record Signature

RESIDENCE
PROJECT DESCRIPTION RFA SUMMARY BEECHWOOD AVE
TOTAL LOT AREA 9,822 sq.ft. 1400 BEECHWOOD AVE
EXISTING LIVING AREA 1,288 sq.ft. FULLERTON, CA 92835
NEW A.D.U 796 sq.ft.
TITLE BLOCK/SITE
TOTAL LIVING AREA 2,084 sq.ft.
CONSTRUCTION TYPE Roof
VB 1 Project number AZ170802
1/8" = 1'-0"
ZONE R-1 Date 7/13/2023 9:52:34 AM
Drawn by A.Z.
# OF STORIES 1
LOT COVERAGE: Checked by Checker
SPRINKLER NO
(E) LIVING SPACE: 1288 SQ.FT
(N) ADU
LOT:
796 SQ.FT.
9,822 SQ.FT.
A-1 PAGE 1 OF 10

Scale 1/8" = 1'-0"


2084/9822=0.21
7 A-2
(N) ROOF
A-2 Door Schedule
2
Roof
15' - 6 15/32" Mark Width Height Description Comments Count
22' - 0"

5' - 9 1/2"
1' - 7" 1' - 7"
303 6' - 0" 6' - 6" Double-Flush 1
305 2' - 8" 6' - 8" Single-Flush 1
306 2' - 8" 6' - 8" Single-Flush 1
307 2' - 8" 6' - 8" Single-Flush 1
Top Plate

6' - 0"
119 9' - 9" 309 2' - 8" 6' - 8" Single-Flush 1
(N) BEDROOM
310 2' - 8" 6' - 8" Single-Flush 1
F TEMPERED
(N) STUCCO
TO MATCH
Window Schedule

8' - 0"
115 305 EXISTING
ZonouZ deZine
Clear Opening Coun
15560 Rockfield Blvd Unit 212, Irvine, CA 92618 949-880-7146

SD
Type Mark Width Height Comments t THESE DRAWINGS, SPECIFICATIONS, IDEAS AND
ARRANGEMENTS PRESENTED THEREBY ARE AND SHALL

5' - 7"
REMAIN THE PROPERTY OF ZONOUZ INC, NO PART
115 6' - 0" 5' - 0" 2 THEREOF SHALL BE COPIED, DISCLOSED TO OTHERS
Finish Floor OR USED IN CONNECTION WITH ANY PROJECT OTHER

1' - 9"
1' - 9" 118 4' - 0" 3' - 0" 1 THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE
Natural Grade BEEN PREPARED AND DEVELOPED WITHOUT THE
309 306
GFI 119 3' - 0" 3' - 0" 2 WRITTEN CONSENT OF ZONOUZ INC.
0' - 0" 123 6' - 0" 2' - 0" 2 VISUAL CONTACT WITH THESE DRAWINGS OR
F SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE
8 307 Elevation 1 - a 124 5' - 0" 4' - 0" 1
SD (N) PWD
119 2 EVIDENCE OF ACCEPTANCE OF THESE RESTRICTIONS.
A-2 1/4" = 1'-0" 165 5' - 0" 2' - 0" 1

5' - 10"
UP 303 (N) CLOSET (N)
310 STACKABLE
A-2 3 LAUNDRY
(N) ROOF KEYNOTES
CM DIRECT VENT Roof
GFI GFI TO OUTSIDE 5 A-2 15' - 6 15/32" 1) AN APPROVED SMOKE ALARMS SHALL BE
INSTALLED IN EACH SLEEPING ROOM & HALLWAY OR
GFI

GFI
AREA GIVING ACCESS TO A SLEEPING ROOM, AND ON

5' - 9 1/2"
GFI
EACH STORY AND BASEMENT FOR DWELLINGS WITH

ROOF MATERIAL: MORE THAN ONE STORY. SMOKE ALARMS SHALL BE


INTERCONNECTED SO THAT ACTIVATION OF ONE
ALARM WILL ACTIVATE ALL ALARMS WITHIN THE
123 123

Top Plate
MANUFACTURER: GAF DWELLING. THE NEW CONSTRUCTION SMOKE ALARMS
SHALL RECEIVE THEIR PRIMARY SOURCE OF POWER

FIBERGLASS ASPHALT SHINGLE


115 FROM THE BUILDING WIRING AND SHALL BE EQUIPPED
(N) 16"14" GABLE
9' - 9" WITH BATTERY BACK UP AND LOW BATTERY SIGNAL.
TEMPERED

GFI
GFI
LISTED CLASS A FIRE 2) AN APPROVED CARBON MONOXIDE ALARMS SHALL
BE INSTALLED DWELLING UNITS IN SLEEPING UNITS

APPROVED - ESR-1475 SRI=16


WITHIN WHICH FUEL-BURNING APPLIANCES ARE

8' - 0"
115 115

17' - 9"
(N) STUCCO INSTALLED AND IN DWELLING UNITS THAT HAVE
118 303 TO MATCH ATTACHED GARAGES. CARBON MONOXIDE ALARMS
TEMPERED EXISTING SHALL BE PROVIDED OUTSIDE OF EACH SEPARATE
(N) LIVING/DINING AREA (N) KITCHEN DWELLING UNIT SLEEPING AREA IN THE IMMEDIATE
GFI

VICINITY OF THE BEDROOMS ON EVERY LEVEL OF A


DWELLING UNIT INCLUDING BASEMENTS.
Finish Floor 3) FANS SHALL BE ENERGY STAR COMPLIANT AND BE

1' - 9"
1' - 9" DUCTED TO TERMINATE TO THE OUTSIDE OF THE
GFI

BUILDING. FANS, NOT FUNCTIONING AS A


Natural Grade COMPONENT OF A WHOLE HOUSE VENTILATION
0' - 0" SYSTEM, MUST BE CONTROLLED BY A HUMIDITY
CONTROL
GFI

Elevation 2 - a
3
1/4" = 1'-0" LEGEND

SD SMOKE DETECTOR SEE KEYNOTE 1


124

(N) ROOF Roof CM CARBON MONOXIDE SEE KEYNOTE 2


15' - 6 15/32" MECH. VENT SEE KEYNOTE 3
4 F

5' - 9 1/2"
LIGHT FIXTURE HIGH EFFICIENCY
A-2
ELECTRICAL OUTLET
New First Floor 165
1 ELECTRICAL SWITCH
1/4" = 1'-0"
Top Plate Top Plate
9' - 9" 9' - 9"
(N) TOP (N)R30 (N) 2X4 STUD
PLATE @ 16" O.C.

(N) STUCCO 124


0' - 4" NEW WALL
8' - 0"

TO MATCH
EXISTING
3' - 6"

(N) R19. (N) F.J. (N) R15 EXISTING WALL

Finish Floor Finish Floor


1' - 9"

1' - 9" 1' - 9"


Natural Grade Natural Grade
0' - 0" 0' - 0"
(N) FOOTING
Elevation 3 - a
4
1/4" = 1'-0"
Section 4
8
1/4" = 1'-0"

3D View 2 (N) ROOF


6 (E) ROOF
Roof Roof
15' - 6 15/32" 15' - 6 15/32"
5' - 9 1/2"

(N)R30
(N) R.R

Top Plate Top Plate


(N) 16"14" GABLE
9' - 9" 9' - 9"
(N) TOP (N) C.J.
PLATE Engineer of Record Signature

(N) R15
RESIDENCE
8' - 0"

(N) STUCCO 118 119 119


TO MATCH
EXISTING (N) 2X4 STUD
@ 16" O.C.
(N) F.J. (N) R19.
1400 BEECHWOOD AVE
FULLERTON, CA 92835
Finish Floor Finish Floor
PROPOSED PLAN
1' - 9"

1' - 9" 1' - 9"


Natural Grade Natural Grade
0' - 0" 0' - 0" Project number AZ170802
(N) FOOTING (N) FOOTING
Elevation 4 - a Date 7/13/2023 9:52:39 AM
5
1/4" = 1'-0" Drawn by A.Z.
Checked by Checker

7
Section 3
1/4" = 1'-0" A-2
Scale 1/4" = 1'-0"
ZonouZ deZine
15560 Rockfield Blvd Unit 212, Irvine, CA 92618 949-880-7146

THESE DRAWINGS, SPECIFICATIONS, IDEAS AND


ARRANGEMENTS PRESENTED THEREBY ARE AND SHALL
REMAIN THE PROPERTY OF ZONOUZ INC, NO PART
THEREOF SHALL BE COPIED, DISCLOSED TO OTHERS
OR USED IN CONNECTION WITH ANY PROJECT OTHER
THAN THE SPECIFIC PROJECT FOR WHICH THEY HAVE
BEEN PREPARED AND DEVELOPED WITHOUT THE
WRITTEN CONSENT OF ZONOUZ INC.
VISUAL CONTACT WITH THESE DRAWINGS OR
SPECIFICATIONS SHALL CONSTITUTE CONCLUSIVE
EVIDENCE OF ACCEPTANCE OF THESE RESTRICTIONS.

KEYNOTES

Engineer of Record Signature

RESIDENCE

1400 BEECHWOOD AVE


FULLERTON, CA 92835
TITLE 24
Project number AZ170802
Date 7/13/2023 9:52:39 AM
Drawn by Author
Checked by Checker

T-1
Scale
GENERAL STRUCTURALSTEEL

1. DESIGN CODE DATA FOUNDATION 1. STRUCTURAL STEEL SHALL BE:


2022 CALIFORNIA BUILDING CODE W SHAPES ASTM A992
2022 CALIFORNIA RESIDENTIAL CODE 1. ALLOWABLE SOIL BEARING = 1,500 PSF FOR STRIP FOOTINGS (PRESUMPTIVE) OTHER SHAPES, PLATES, AND BARS ASTM 36
NSD - 2018: NATIONAL DESIGN SPECIFICATION FOR WOOD CONTRUCTION 2. GRADE AREAS IN ACCORDANCE WITH THE ELEVATIONS AND GRADES SHOWN ON THE SITE DRAWINGS AND AS TUBES ASTM A500, GRADE B
ASCE 7-16: MINIMUM DESIGN LOADFS FOR BUILDINGS AND OTHER STRUCTURES PIPES ASTM A53, GRADE B
REUIRED FOR DRAINAGE.
2. ALL BOLTS, NUTS, AND WASHERS SHALL CONFORM WITH ASTM A307 UNLESS OTHERWISE NOTED.
ACI 318-11: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY 3. ALL SLAB GRADE AREAS SHALL BE PROOF ROLLED. ALL SOFT SPOTS SHALL BE REMOVED AND REPLACED WITH
3. ALL HIGH-STRENGTH BOLTS SHALL CONFORM WITH ASTM A490 UNLESS OTHERWISE NOTED.
ANSI/ AFPA NS-2005: NATIONAL DESIGN SPECIFICATION FOR WOOD STRUCTURES COMPACTABLE FILL.
4. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE AISC 'SPECIFICATIONS ’ FOR DESIGN,
ACI 530-16/ ASCE 5-16/ TMS 402-16: BUILDING CODE REQUIREMENTS AND SPECIFICATION 4. SLAB ON GRADE TO BE CONSTRUCTED ON A MINIMUM OF 6" OF COMPACTED GRANULAR FILL. FABRICATION, AND ERECTION OF STRUCTURAL STEEL AND FRAMING.
FOR MASONRY STRUCTURES

1400 BEECHWOOD AVE FULLERTON, CA 92835


5. ALL FILL MATERIAL USED IN GRADING OPERATIONS SHALL CONSIST OF EARTH, WHICH IS FREE OF DDEBRIS, BOULDERS 5. WELDING SHALL CONFORM WITH THE LATEST EDITION OF THE AWS SPECIFICATIONS. USE E70
OR ORGANIC MATERIAL. FILL SHALL BE PLACED IN MAXIMUM OF 12" LIFTS AND COMPACTED TO 35% OF MODIFIED ELECTRODES.
2. BUILDING OCCUPANCY CATEGORY = II (PER ASCE 7-16 TABLE 1-1) PROCTOR MAXIMUM DRY DENSITY. 6. STEELWORK EXPOSED TO WEATHER TO BE EITHER HOT-DIPPED GALVANIZED TO MEET THE
6. ALL FOOTINGS SHALL BEAR ON UNDISTURBED SOIL OR COMPACTED FILL HAVING A MINIMUM ALLOWABLE BEARING REOUIREMENTS OF ASTM A153, OR PAINTED AS SPECIFIED BELOW.
3. DESIGN LOADS: a. PAINT SPECIFICATION BASED ON EXTERIOR EXPOSURE AND COASTAL ENVIRONMENT.
CAPACITY AS INDICATED ABOVE.
b. SHOP PRIMER: TNEMEC SERIES 90-97 TNEME-ZINC, 2.5 TO 3.5 MILS.
7. THE ENGINEER SHALL BE NOTIFIED IF ACTUAL FIELD CONDITIONS DO NOT MEET BEARING REQUIREMENTS OR IF
A. DEAD LOADS: c. FIELD INTERMEDIATE: TNEMEC SERIES 66 OR 69 HI-BUILD EPOXOLINE, 4.0 TO 6.0 MILS.
QUESTIONABLE SOIL CONDITIONS ARE DISCOVERED INCLUDING BUT NOT LIMITED TO PEAT AND OTHER HIGH ORGANIC
d. FIELD FINISH: TNEMEC SERIES 73, 74 OR 75 ENDURA-SHIELD, 3.0 TO 5.0 MILS. COLOR PER
SOILS. OWNERS SPECIFICATION.
WALL 12 PSF
e. ALTERNATIVES TO THE SPECIFIED PAINT SYSTEM WILL BE CONSIDERED UPON SUBMISSION OF
DECK 10 PSF CONCRETE CONSTRUCTION MANUFACTURE'S DOCUMENTS AND APPROVAL BY OWNER.
FLOOR 20 PSF 7. THE CONTRACTOR IS TO FIELD LOCATE BOLT POSITIONS FOR BASE PLATES, ANCHOR PLATES, ETC.
ROOF 17 PSF 1. ALL CONCRETE DESIGN AND CONSTRUCTION SHALL CONFORM WITH THE LOCAL BUILDING CODE REQUIREMENTS AND TO BE ATTACHED TO EXISTING CONCRETE, AND INCLUDE ON THE SHOP DRAWING DETAILS.
THOSE OF THE LATEST EDITION OF THE FOLLOWING STANDARDS. ACI 318, ACI 315, ACI 301 AND ACI 307.
B. LIVE LOADS: 2. ALL CONCRETE UNLESS SPECIFICALLY NOTED SHALL BE NORMAL WEIGHT (145 PCF)
3. THE COMPRESSIVE STRENGTH OF ALL GROUT USED TO PROVIDE LEVEL BEARING OF COLUMN BASE PLATES SHALL MEET
WALL 0 PSF
OR EXCEED THE COMPRESSIVE STRENGTH OF THE SUPPORTING CONCRETE MEMBER.
DECK 60 PSF
4. CONCRETE REINFORCING SHALL HAVE THE FOLLOWING MINIMUM PROTECTIVE COVER
FLOOR 40 PSF
ROOF 20 PSF
CONCRETE CAST AGAINST EARTH 3"
CONCRETE EXPOSED TO EARTH OR WEATHER
C. WIND DESIGN CRITERIA
#6 THROUGH #18 BARS 2" SUBJECT PROPERTY

RESIDENCE
#5 BAR AND SMALLER 1-1/2"
WIND SPEED: 95 MPH
EXPOSURE: "C"
CONCRETE WITH INTERIOR EXPOSURE
ENCLOSURE CLASSIFICATION ENCLOSED
SLABS, WALLS, JOISTS
Kz: 0.85
#14 AND #18 BARS 1-1/2"
I: 1.0
#11 BAR AND SMALLER 3/4"
Kzt 1.0
BASE VELOCITY PRESSURE 16.69 PSF
5. UNLESS NOTED OTHERWISE ON THE DRAWINGS ALL REINFORCING SHALL BE LAPPED TO DEVELOP ITS
D. SEISMIC DESIGN CRITERIA CAPACITY AS FOLLOWS.
SITE CLASS: D (DEFAULT)
BAR SIZES STANDARD TOP BAR "B" SPLICE HOOK
SPECTRAL RESPONSE PARAMETERS Sms: 2.742
SEISMIC DESIGN CATEGORY: D #3 13" 16" 16" 6"
IMPORTANCE FACTOR Ie: 1 #4 20" 24" 24" 6"
RESPONSE MODIFICATION FACTOR R: 6.5 #5 28" 44" 44" 10"
SEISMIC RESPONSE COEFFICIENT Cs: 0.15 #6 36" 60" 60" 12"
#7 52" 82" 82" 14"
MAXIMUM ALLOWABLE DEFLECTION CRITERIA: MULTIPLY LAP LENGTHS BY 1.3 FOR TOP BAR CONDITIONS, TOP BARS ARE HORIZONTAL BARS WITH 12" OR
MORE OF CONCRETE BELOW
ROOF: L/360 LIVE; L/240 TOTAL LOAD 6. SLAB ON GRADRE SHALL HAVE A CLASS "A" TOLERANCE
FLOORS: L/480 LIVE LOAD; L/360 TOTAL LOAD (WOOD I-JISTS ONLY) 7. A 6-MIL. (MIN) POLYETHYLENE VAPOR BARRIER WITH JOINTS LAPPED NOT LESS THAT 6" SHALL BE PLACED
FLOORS: L/360 LIVE LOAD; L/240 TOTAL LOAD BETWEEN THE SAND BASE AND THE CONCRETE FLOOR.
VERTICAL WINDOW SUPPORT; L/1000 LIVE LOAD 8. CALCIUM CHLORIDE AND OR ADMIXTURES CONTAINING CALCIUM CHLORIDE SHALL NOT BE USED.
EXTERIOR WALL SYSTEMS ; L/600 WIND LOAD 9. ALL CONCRETE SUBJECT TO EXTERIOR EXPOSURE SHALL BE AIR ENTRAINED TO 6% AND A MAXIMUM 1"
AGGREGATE
4. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF CONSTRUCTION LOAD 10. PLACING OF CONCRETE SHALL BE DONE IN CONFORMANCE WITH ACI-306 FOR COLD WEATHER AND
IMPOSED UPON OR EXISTING STRUCTURAL FRAMING. CONSTRUCTION LOADS SHALL NOT EXCEED ACI-305 FOR HOT WEATHER.
THE DESIGN CAPACITY OF THE FRAMING AT THE TIME THE LOADS ARE IPMOSED.

5. THE STRUCTURE IS DESIGN TO FUNCTION AS A UNIT UPON COMPLETION. THE CONTRACTOR IS WOOD CONSTRUCTION
RESPONSIBLE FOR THE DESIGNING AND FURNISHING ALL TEMPORARY BRACING AND OR SUPPORT
DIMENSION LUMBER
THAT MAY BE REQUIRED AS THE RESULT OF THE CONTRACTOR'S CONSTRUCTION METJODS AND OR
SEQUENCES. THE STRUCTURAL ENGINEER ASSUMES NO LIABLITY FOR THE STRUCTURE DURING 1. ALL DIMENSION LUMBER NOMINAL 2" THICK AND 4-8" WIDE SHALL BE #2 DF OR EQUAL.
CONSTRUCTION. 2. LAMINATED VENNER LUMBER (LVL) TO BE 2.0E AND Fb = 2,600 PSI OR GREATER.
3. NOT USED
6. THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS OF CONSTRUCTIONS AND ALL 4. NOT USED
JOB SITE SAFETY. 5. SILLS AND MENBERS EXPOSED DIRECTLY TO MOISTURE OR IN DIRECT CONTACT WITH CONCRETE OR (BOISE VERSA - STUD
1.7/2650 OR APPROVED EQUAL
7. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO THE START OF 6. PLYWOOD SHALL CONFORM TO THE LATEST EDITION OF U.S PRODUICT STANDARD PS-I. INSTALL IN STAGGERED PATTERN. STAMP
CONSTRUCTION - RESOLVE ANY DISCREPANCY WITH ARCHITECTS DO NOT SCALE DRAWINGS. NAIL AS REQUIRED FOR DIAPHRAGM ACTION. PROJECT ADDRESS:
7. SHEAR PLATE AND SPLIT RING FASTENERS SHALL BE TECO OR APPROVED EQUAL. 1400 BEECHWOOD AVE FULLERTON, CA 92835
8. NAILS SHALL BE STRONGHOLD, GALVANIZED COMMON NAILS OF THE SIZES INDICATED, EXCEPT THAT GALVANIZED SISING
8. STRUCTURAL DRAWINGS ARE INTENDED TO BE USED WITH ARCHITECTURAL , MECHANICAL,
NAILS SHALL BE USED FOR THE ATTATCHMENT OF EXTERIOR PLYWOOD SIDEING
ELECTRICAL, CIVIL AND OTHER DESIGN CONSULTANTS CRAWINGS. ANY APPARENT DESCRIPANCIES, 9. ALL BOLTS AND LAG SCREWS SHALL BE AMERICAN STANDARD MANUFACTURE. DRAWING INDEX
LIMITATIONS OR CONCERNS RESULTING FROM THIS COORDINATION SHOULD BE RESOLVE WITH THE 10. BOLT HOLES IN WOOD SHALL BE DRILLED 1/16" MAXIMUM OVERSIZES. HOLES FOR SCREWS AND LAG SCREWS SHALL BE
ARCHITECT IMMEDIATELY. FIRST BORED FOR THE SAME DEPTH AND DIAMETER OF THE SHANK. THEN THE REMAINDER OCCUPIED BY THE THREADED SHEET NUMBER SHEET NAME
S1.0 GENERAL NOTES
PORTION SHALL BE BORED NOT LARGER IN DIAMTER THAN THE ROOT OF THE THREAD. ALL SCREWS SHALL BE SCREWED, NOT
S2.0 FOUNDATION & 1ST FLOOR FRAMING PLAN
9. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO DRIVEN INTO PLACE.
S3.0 ROOF PLAN
CONSTRUCTING. NOTIFY THE OWNERS REPRESENTATIVE OF ANY DISCREPANCY IMMEDIATELY. 11. PROVIDE WASHERS UNDER ALL NUTS AND HEADS OF BOLTS AND LAG SCREWS. WASHERS SHALL BE EITHER ROUND MALLEABLE S4.0 DETAILS 1
IRON OR SQUARE CUT STEEL WASHERS 1/4" THICK x 3 FASTENER DIAMETERS S5.0 DETAILS 2
THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL BUILDING MATERIALS AND 12. WHEREVER NECESSARY TO CUT OR DRILL TREATED LUMBER, TREAT THE CUT OR BORED SURFACES WITH TWO HEAVY COATS OF S6.0 DETAILS 3
COMPONENTS. COMPONENT LOCATIONS ARE SHOWN FOR DESIGN INTENT, NOT EXACT LOCATION, THE SAME PRESERVATIVE AS USED IN THE ORIGINAL TREATMENT. S7.0 COVERED PATIO DETAIL 1
13. PROVIDE SOLID BLOCKING AT MID-SPAN OF ALL SAWN JOISTS AND STUDS EXCEEDING 10 FOOT SPAN AND AT 10 FOOT S8.0 COVERED PATIO DETAIL 2 PROJECT #: 2023
SPECIFICALLY. INDEPENDENT PREPARED SHOP DRAWINGS ARE REQUIRED OF ALL TRADES FOR
MAXIMUM CENTER.
COORDINATION AND BEST PRACTICE. ERRORS OR OMISSIONS IN INSTALLATION DUE TO THE DRAWN BY: HOANG LUAN
14. MEMBERS BEARING ON CONCRETE OR MASONRY WALLS SHALL HAVE A 1/2" AIR SPACE AROUND SIDES AND END OF BEAM
CONTRACTORS FAILURE TO COORDINATE THE WORK WILL BE THE SOLE RESPONSIBILITY OF THE 15. DESIGN FABRICATION AND CONSTRUCTION SHALL CONFORM TO THE "NATIONAL DESIGN SPECIFICATION" FOR WOOD
CONTRACTOR. CONSTRUCTION" CURRENT EDITION AS RECCOMENDED BY THE NATIONAL LUMBER MANUFACTURERS ASSOCIATION.
16. NOT USED.
MATERIAL SPECIFICATIONS 17. SET ALL JOISTS WITH CROWN UP.
18. WALL SHEATHING SHALL BE NAILED AS INDICATED ON DRAWINGS. ALL PANEL EDGES SHALL BE BACKED WITH 2x OR WIDER Revision Schedule
CONCRETE FRAMING
19. PLYWOOD SHEATHING TO BE GRADED APA STRUCTURAL 1. Number Description Date
FOOTING AND FOUNDATION WALLS 3,000 PSI @ 28 DAYS 20. ALL BOLTS, LAG SCREEWS, SCREWS NAD NAILS SHALL HAVE A HOT DIP GALVANIZED FINISH
SLAB ON GRADE 3,000 PSI @ 28 DAYS 21. SIMPSON STRONG TIE CONNECTORS ARTE SPECIFICALLY REQUIRED TO MEET STRUCTURAL CALCULATIONS OF PLAN, BEFORE
ALL OTHER CIP CONCRETE NOT NOTED 3,000 PSI @ 28 DAYS SUBSTITUTING ANOTHER BRAND, CONFIRM LOAD CAPACITY BASED ON RELIABLE PUBLISHED TESTING DATA OR CALCULATIONS.
CONCRETE REINFORCING STEEL 60 KSI. ASTM A615 THE ENGINEER OF RECORD IS REQUIRED TO EVALUATE AND GIVE WRITTEN APPROVAL FOR SUBSTITUTION PRIOR TO
WELDED WIRE REINFORCEMENT 65KSI, A185 INSTALLATION.
ANCHOR RODS ASTM F1554 (SEE SCHEDULE FOR GRADE) 22. ALL SIMPSON CONNNECTORS SHALL BE ZMAX (G185) HOT-DIP GALVANIZED (HDG).
ADHESIVE ANCHORS SET-XP® HIGH-STRENGTH EPOXY ADHESIVE
INJECTION ADHESIVE OR EQUAL VERTICAL STRUCTURAL PANEL SHEATHING NOTES (WOOD FRAMING)

MECHANICAL ANCHORS HILTI KWIK BOLTS III OR EQUAL 1. FASTENERS SHALL NOT BE LOCATED LESS THAN 3" FROM THE EDGE OF THE PANEL
POWDER DRIVEN FASTENERS HILTI DS OR EQUAL 2. FASTENERS SAHLL BE DRIVEN FLUSH WITH SURFACE OR SHEATHING SHEET NAME
3. FASTENERS SHALL BE SUFFICIENT LENGHT TO ENSURE PENETRATION INTO FRAMING MEMBERS BY AT LEAST 1 1/2"
2x10 AND SMALLER SF NO.2 OR BETTER 4. FRAMING MEMBERS SHALL BE MINIMUM 2" NOMINAL IN THE DIMENSION TO WHICH THE STRUCTURAL PANEL IS ATTACHED
MINIMIM DESIGN VALUES
Fb 875 PSI WOOD SHEATHING ROOF
Ft 450 PSI
Fv 135 PSI 1. PANEL ROOF SHEATHING SHALL BE 5/8" APA EXPOSURE 1, RATED SHEATHING WITH 48/24 SPAN RATING. (U.N.O) GENERAL
Fg 425 PSI 2. NOT USED
FcII 1,150 PSI 3. FASTENERS SHALL BE A MINIMIM 8d BOX NAIL (0.113") RING SHANK FOR ROOF
NOTE
E 1,400,000 PSI 4. ROOF PANEL SHEATHING SHALL BE CONTINOUS OVER 2 OR MORE SUPPORTS (MINIMUM)
Emin 510,000 PSI 5. ROOF PANEL SHEATHING SHALL BE ORIENTED WITH THE STRENGTH ZXIS PERPENDICULAR TO THE SUPPORTS
6. ROOF SHEATHING, SPACE NAILS @ 6" O.C ALONG INTERMEDIATED FRAMING MEMBERS. (FIELD OF PANEL) SPACE NAILS @ 3"
MICROLLAM® LVL BEAMS (LVL) O.C AT ALL PANEL EDGES.
MINIMUM DESIGN VALUES 7. EACH PANEL SHALL BE IDENTIFIED WITH THE GRADE TRADEMARK OF THE AMERICAN PLYWOOD ASSOCIATION AND SHALL
Fb 2,600 PSI
SHEET NUMBER
MEET THE REQUIREMENTS OF PRODUCT STANDARD (PSI) APPLICATION AND NAILING OF PLYWOOD SHALL BE IN ACCORDANCE
E 2,000,000 PSI WITH THE RECCOMENDATION OF THE AMERICANPLYWOOD ASSOCIATION AND TABLE 2304.9.1 " FASTENING SCHEDULE" OF
THE INTERNATIONAL BUILDING CODE UNLESS OTHER REQUREMENTS NOTED ON THE PLAN ARE MORE STRICT

S1.0
LEGEND

WALL ABOVE FRAMING PLAN

B A B A WALL BELOW FRAMING PLAN

2
S4.0 FLOOR SHEATHING: 3 4" T&G APA RATED

S .W

ST

1400 BEECHWOOD AVE FULLERTON, CA 92835


. PO
SHEATHING GLUED & NAILED w/10d @6"o.c.

.PO

S. W
HDU5 HDU5

ST
AT EDGE AND 10d @12"o.c. AT FIELD (NO
6 22' BLKG REQ'D), SEE 4/S6.0

1 1 ROOF SHEATHING:1 2" APA RATED


SHEATHING NAILED w/10d @6"o.c. AT EDGE
AND 10d @12"o.c. AT FIELD (NO BLKG
REQ'D), SEE 4/S6.0

# **.*' "#" DENOTES SHEAR WALL TYPE & EDGE


NAIL SPACING AND "**.*"" DENOTES
MINIMUM SHEAR WALL LENGTH. SEE
SHEET 9/S5.0 FOR SHEAR WALL
SCHEDULE. SEE DETAIL 4/S6.0 FOR
SHEAR WALL FRAMING AND TYP.
PENETRATIONS IN SHEAR WALL

13'
6
"####" DENOTES SHEAR WALL HOLDOWN
#### TYPE. SEE TYPICAL DETAIL 6/S5.0 FOR
INFO AND MIN. END POST SIZE

RESIDENCE
18'-8''
2
S4.0 SEE DETAIL 6/S5.0 FOR SHEAR WALL
POST. SHEAR WALL POST ABOVE &

A& T
OS
S.W (2) 2x12 FLOOR JOIST @12"O.C. BELOW WILL BE FRAMED PER DETAIL

B
.P
S.W
.PO 8/S6.0
ST

HDU5
10" SEE DETAIL 6/S5.0 FOR SHEAR WALL POST
SIZE

T
OS
.P
S.W
DENOTES SIMPSON HANGER PER
SCHEDULE 7/S6.0, U.O.N.
2
7'-0"

S4.0

ST
.PO
S.W
HDU5 DENOTES SIMPSON CONCEALED
FLANGE HANGER PER SCHEDULE 7/S6.0,
U.O.N.

2 2
SEE HEADER SCHEDULE ON 11/S6.0 FOR
HEADER SIZES, UNLESS NOTED ON
PLAN.

ST
.PO
HDU5

S.W
CONCRETE FOUNDATION PER PLAN

NOTE: CONTRACTOR TO VERIFY ALL EXISTING FRAMING. NOTIFY


ENGINEER-OF-RECORD- IF EXISTING FRAMING CONDITIONS IN THE FIELD ARE
DIFFERENT THAN SHOWN ON PLAN

18'-2''

18'-2''
STAMP

6
(2) 2x12 FLOOR JOIST @12"O.C.

6
2 2
S4.0 S4.0

PROJECT #: 2023
2
S4.0 DRAWN BY: HOANG LUAN

Revision Schedule
3 3
Number Description Date
6 22'

S.W
ST

HDU5 HDU5
.PO

.PO
S.W

ST
FOUNDATION PLAN 1ST FLOOR FRAMING PLAN SHEET NAME
1 SCALE: 3/8"=1'-0" 2 SCALE: 3/8"=1'-0"

FOUNDATION &
1ST FLOOR
FRAMING PLAN

SHEET NUMBER

S2.0
LEGEND

WALL ABOVE FRAMING PLAN

B A WALL BELOW FRAMING PLAN


6
S4.0
2x12 RAFTER FLOOR SHEATHING: 3 4" T&G APA RATED

1400 BEECHWOOD AVE FULLERTON, CA 92835


@16"O.C. SHEATHING GLUED & NAILED w/10d @6"o.c.
AT EDGE AND 10d @12"o.c. AT FIELD (NO
BLKG REQ'D), SEE 4/S6.0

2x12 P.T.

2x12 P.T.
. 1
P.T ROOF SHEATHING:1 2" APA RATED

2x
12
2

3'-0"
1 SHEATHING NAILED w/10d @6"o.c. AT EDGE
2x

P .T.
AND 10d @12"o.c. AT FIELD (NO BLKG
2x12 P.T. 2x12 P.T. REQ'D), SEE 4/S6.0
(2) 2x12 P.T.

3 piece(s) 2 x 6 SP No.2
# **.*' "#" DENOTES SHEAR WALL TYPE & EDGE
NAIL SPACING AND "**.*"" DENOTES
MINIMUM SHEAR WALL LENGTH. SEE
SHEET 9/S5.0 FOR SHEAR WALL
SCHEDULE. SEE DETAIL 4/S6.0 FOR
SHEAR WALL FRAMING AND TYP.

3 piece(s) 2 x 10 SP No.2
PENETRATIONS IN SHEAR WALL
3 piece(s) 2 x 6 SP No.2

"####" DENOTES SHEAR WALL HOLDOWN


#### TYPE. SEE TYPICAL DETAIL 6/S5.0 FOR
INFO AND MIN. END POST SIZE

RESIDENCE
2x8 CEILING JOIST SEE DETAIL 6/S5.0 FOR SHEAR WALL
@16"O.C. POST. SHEAR WALL POST ABOVE &

A& T
OS
BELOW WILL BE FRAMED PER DETAIL

B
.P
S.W
8/S6.0

3 piece(s) 2 x 6 SP No.2 3 piece(s) 2 x 6 SP No.2 SEE DETAIL 6/S5.0 FOR SHEAR WALL POST
SIZE

T
OS
.P
3 piece(s) 2 x 6 SP No.2

S.W
3 piece(s) 2 x 6 SP No.2
3 piece(s) 2 x 10 SP No.2
DENOTES SIMPSON HANGER PER
2x8 CEILING JOIST 2x8 CEILING JOIST SCHEDULE 7/S6.0, U.O.N.

3 piece(s) 2 x 6 SP No.2
@16"O.C. @16"O.C.

DENOTES SIMPSON CONCEALED


FLANGE HANGER PER SCHEDULE 7/S6.0,
U.O.N.

2
SEE HEADER SCHEDULE ON 11/S6.0 FOR
HEADER SIZES, UNLESS NOTED ON
PLAN.

2x12 RAFTER @16"O.C. 5


S4.0 CONCRETE FOUNDATION PER PLAN
3 piece(s) 2 x 10 SP No.2

NOTE: CONTRACTOR TO VERIFY ALL EXISTING FRAMING. NOTIFY


ENGINEER-OF-RECORD- IF EXISTING FRAMING CONDITIONS IN THE FIELD ARE
DIFFERENT THAN SHOWN ON PLAN

3 piece(s) 2 x 6 SP No.2
STAMP

PROJECT #: 2023

DRAWN BY: HOANG LUAN


(2) 2x12 P.T.

2x12 P.T. 2x12 P.T.


Revision Schedule
3'-0"

.T.
2x12 P.T.

2x12 P.T.
2x
P

1
12

2P
2x 3

.T.
3 piece(s) 2 x 10 SP No.2 Number Description Date

2x12 RAFTER
@16"O.C.

ROOF PLAN SHEET NAME


3 SCALE: 3/8"=1'-0"

ROOF PLAN

SHEET NUMBER

S3.0
A

TOP RAIL
RAILING POST 4x4 WOOD 2X4 RAILING POST 4x4

TOP RAIL 2X STUD WALL W/


1 CONCRETE SLAB-ON-GRADE
WOOD 2X4 2'' G.B. (SEE PLAN)

WOOD 2X2 @5'' W/ 6X6-1.4X1.4 WWF ON


2X P.T.PL. W/ CONC. NAILS 6mm MIN. VAPOR BARRIER (STEGO WRAP OR
O.C. COMPACTED FILL
TO FASTEN TO CONC. W/ EQUIVALENT) AT INTERIOR CONDITIONS,
RAILING POST 4x4 5 S.A.D.
8'' DIA x 10'' A.B. @ 2' - 0'' O.C. MAX.

1400 BEECHWOOD AVE FULLERTON, CA 92835


BOTTOM RAIL
WOOD 2X2 @5''
WOOD 2X4

4"
O.C.

4"
BOTTOM RAIL
WOOD 2X4

Finish Floor

8"
1' - 9"
SEE ARCH 1"

111 2"
L 3''x3''x41'' (5'' LONG) W/

SEE ARCH
5 (1) 85'' ø EPOXY SET BOLTS

2"
8'' THRU BOLT

11 1
@6'' 0.C. - STAGGERED (MIN. 6'' EMBED.)

4"
SCREW TO STAIR STRINGER (2) # 4 CONT. REBAR UNDIS. SOIL 4" MIN. OPEN GRADED ROCK
2X6 P.T. OR COMPOSITE 1'-4"
CAPILLARY BREAK (3 4" DRAIN
DECKING PER OWNER/BLDR W/ (4) # 41'' WOOD SCREWS
ROCK)
2X6 P.T.
Natural Grade
0' - 0"
2 piece (s) 2x12 P.T.

10"

RESIDENCE
FOOTING INTERIOR LOAD BEARING WALL FOUNDATION CONCRETE SLAB-ON-GRADE
10" (2) #5 BARS 4 SCALE: 1"=1'-0" 1 1"=SCALE: 1'-0"

DETAIL OF STAIR
7 SCALE: 1"=1'-0" SIMPSON STRONG WALL PER
PLAN

TOP RAIL TOP RAIL


WOOD 2X4 WOOD 2X4
1"

FLOOR SHEATHING PER PLAN


ROOF SHTG w/ E.N. PER E.N.
PLAN E.N.

RAILING POST 4x4 RAILING POST 4x4

2x BLKG SNUG TIGHT


BETWEEN RAFTERS 6" MIN.
3'-0"

1'-9"
WOOD 2X2 @5'' WOOD 2X2 @5'' "A35" CLIP AT SPACING
O.C. O.C. PER SHEAR WALL #4 HORIZ.
SCHEDULE BAR @12"o.c.
BOTTOM RAIL BOTTOM RAIL
WOOD 2X4 WOOD 2X4 2x12 RAFTER @16"O.C.
LINE
PLATE
#4 VERT. BAR @12"o.c.

2X6 P.T. OR COMPOSITE


DECKING PER OWNER/BLDR 18" MAX.
S.A.D. 2x FASCIA w/ (2) 16d NAILS
"A35" CLIP AT SPACING PER

1'-6"
AT EACH RAFTER
SHEAR WALL SCHEDULE H2.5A AT EA.
ROOF JOIST

2 piece (s) 2x12 P.T.

3" CLR.
2X6 P.T. 2x12 P.T.
@12'' o.c. 2'-2" STAMP
6'-0" (4) #5 BARS
T&B

SECTION A FRAMING AT ROOF RAFTERS SHEAR WALL AT FOUNDATION


8 SCALE: 1"=1'-0" 5 SCALE: 1"=1'-0" 2 SCALE: 1"=1'-0"

PROJECT #: 2023

DRAWN BY: HOANG LUAN

E.N. Revision Schedule


(N) POST PER PLAN w/ 'CB' COLUMN
2x BLKG SNUG TIGHT BASE Number Description Date
BETWEEN RAFTERS

DECKING #4 DOWEL (12"x12")


H2.5A AT EA.
@12"o.c., TYP.
ROOF JOIST

MIN.
1"
CONCRETE SLAB

LINE
PLATE

SHEET NAME

1'-6"
2x FASCIA w/ (2) 16d
HUS212-2 18" MAX. NAILS AT EACH RAFTER

S.A.D.
(2) 2x12 P.T.
2x12 RAFTER @16"O.C.
DETAILS 1

CLR.
3"
2'-0"

(3) #4 BARS EA. WAY

SHEET NUMBER

FRAMING AT ROOF RAFTERS FOOTING & POST AT FOOTING


6 SCALE: 1"=1'-0"
3 SCALE: 1"=1'-0" S4.0
HOLDOWN PER PLAN REINFORCED CONC. FOOTING OR STEM WALL

SHEATHING PER PLAN SHEATHING PER PLAN

SLAB
SHEATHING PER PLAN d lp TYP.
SILL PLATE FASTENING w/ SDS SCREWS
SILL PLATE FASTENING w/ SDS SCREWS
PER SHEAR WALL SCHEDULE
PER SHEAR WALL SCHEDULE
FLOOR SHEATHING PER PLAN
FLOOR SHEATHING PER PLAN E.N. E.N.
FLOOR SHEATHING PER PLAN E.N.

TYP.
1"
FLOOR JOIST PER PLAN 6" MIN. FLOOR JOIST PER PLAN 6" MIN.
6" MIN.
2x FULL DEPTH BLOCKING 2x FULL DEPTH BLOCKING "A35" CLIP AT SPACING PER

1400 BEECHWOOD AVE FULLERTON, CA 92835


#4 VERT. BAR @12"o.c. #4 VERT. BAR @12"o.c.
@8'-0"o.c. @8'-0"o.c. SHEAR WALL SCHEDULE #4 VERT. BAR @12"o.c. ADD'L BAR TO MATCH

30" MAX.
1

30" MAX
BEAM REINF. INTERRUPTED FOOTING BOTTOM BAR SIZE &

30" MAX
#4 HORIZ. BAR @12"o.c. #4 HORIZ. BAR @12"o.c.

MIN.
"A35" CLIP AT SPACING PER "A35" CLIP AT SPACING PER

6"
#4 HORIZ. BAR @12"o.c. 1 SPACING
SHEAR WALL SCHEDULE SHEAR WALL SCHEDULE P.T. 2x SILL PLATE w/ 5 8"Ø ANCHOR BOLT w/ 7" MIN.
P.T. 2x SILL PLATE w/ 5 8"Ø ANCHOR BOLT w/ 7" MIN. EMBED AT ANCHOR BOLT PER EMBED AT SPACING PER SHEAR WALL SCHEDULE
HOLDOWN SCHEDULE BENT BAR TO MATCH
SPACING PER SHEAR WALL SCHEDULE
℄ OF SCHEDULE 40 2d FOOTING BOTTOM BAR SIZE &
PIPE SLEEVE SPACING
1'-0" MIN.

CASE II

PER PLAN
PER PLAN

PER PLAN
(2) #5 BARS T&B (2) #5 BARS T&B
(2) #5 BARS T&B
REINFORCED CONC. FOOTING OR STEM WALL

SEE MECH. DWGS FOR LOCATION

SLAB
AND SIZE OF PIPE SLEEVES

CLR.
CLR.

3"
3"

CLR.
3"
PER PLAN PER PLAN

MIN.
D/3
PER PLAN

MAX.
A: AT WALL

D/3

D
B: AT HOLDOWN A: AT WALL

RESIDENCE
SHEAR WALL AT FOUNDATION

MIN.
D/3
5 SCALE: 1"=1'-0"
HOLDOWN PER PLAN
ADD ONE STIRRUP SAME
BEAM REINF. SIZE AS ADJACENT STIRRUPS,
SHEATHING PER PLAN 1" CLR. EA.
SIDE OF PIPE SLEEVE
℄ OF SCHEDULE 40
PIPE SLEEVE
HOLDOWN SCHEDULE AT FOUNDATION FLOOR SHEATHING PER PLAN CASE I
E.N.
CONCRETE STRENGTH (f'c = 2,500 PSI MIN.)
NOTES:
PENETRATIONS THRU STRUCTURAL MEMBERS ARE PERMITTED ONLY WITH THE REVIEW OF THE
MIN. END POST SIZE MIN. ALTERNATIVE
STEM/CURB MIN. MIN. EMBEDMENT & STRUCTURAL ENGINEER.
HOLDOWN TYPE SIMPSON ANCHOR BOLT EMBEDMENT ANCHOR BOLT
WIDTH "W" CLEARANCE "D2" (SEE NOTE 5)
2x4 WALL 2x6 WALL "D1"

HDU2 4x4 4x6 SB5 8x24 6" 1'-6" N/A SSTB24


"A35" CLIP AT SPACING PER 6" MIN. PIPE SLEEVE THOUGH
SHEAR WALL SCHEDULE
#4 VERT. BAR @12"o.c. CONCRETE FOOTING OR STEM WALL
5
1

30" MAX.
HDU4 4x4 4x6 SB 8x24 6" 1'-6" N/A N/A
#4 HORIZ. BAR @12"o.c. SCALE: 1"=1'-0"
ANCHOR BOLT PER
HDU5 4x4 4x6 SB5 8x24 6" 1'-6" N/A N/A HOLDOWN SCHEDULE

HDU8 4x6 6x6 SB7 8x24 6" (SEE NOTE 7) 1'-6" N/A N/A
(1) TYPICAL WALL STANDARD
VERTICAL BAR 90° HOOK,
HDU11 4x8 6x8 SB1x30 6" (SEE NOTE 7) 2'-0" N/A N/A STANDARD (1) TYPICAL
(#5 BAR MIN.) TYP. WALL
180° HOOK
VERTICAL BAR

PER PLAN
HDU14 4x8 6x8 PAB8 (SEE NOTE 6) N/A N/A 1'-5" N/A (#5 BAR MIN.)
(2) #5 BARS T&B
HD19 4x8 6x8 PAB9 (SEE NOTE 6) N/A N/A 1'-7" N/A
HALF TYPICAL
TYP. WALL SPACINGTO FIRST TYPICAL WALL
REINFORCING REINFORCING
VERTICAL BAR, TYP.
1. REFER TO THE PLANS FOR HOLDOWN SIZE AND HOLDOWN POST SIZES.

CLR.
2. FOR HOLD DOWN ASSEMBLIES, USE SIMPSON HOLDOWNS OR APPROVED EQUAL END

3"
3. BOLTS THROUGH FLOOR AND EMBEDDED IN FOUNDATION SHALL BE F1154 STEEL, GRADE A36, ALL THREAD.
PER PLAN
4. HOLDOWNS SHALL NOT BE SUBSTITUTED FOR SILL PLATE ANCHOR BOLTS
5. EMBEDMENT PER MANUFACTURER'S REQUIREMENTS CORNER
6. USE STANDARD STEEL FOR THE SIMPSON PRE-ASSEMBLED ANCHOR BOLTS AND OVERSIZE PENETRATION IN P.T. SILL PLATE 1 4"
7. MAXIMUM STEM/CURB HEIGHT EQUALS 111 4"
8. HOLDOWN ANCHOR BOLT NUT SHOULD BE FINGER TIGHT PLUS 1 3 T0 1 2 TURN WITH HAND WRENCH. B: AT HOLDOWN PLAN VIEW OF CONCRETE FOOTINGS STAMP
2 SCALE: 1"=1'-0"

HOLDOWN ANCHORAGE AT FOUNDATION SHEAR WALL AT FOUNDATION DEVELOPMENT LENGTH AND LAP SPLICE (Ld)
6 SCALE: 1"=1'-0" 4 SCALE: 1"=1'-0"
SCHEDULE (INCHES) CLASS B
CONCRETE COMPRESSIVE STRENGTH (PSI)
SHEAR WALL SCHEDULE: SIZE LOCATION
2,500 3,000 4,000 5,000 6,000

5
HORIZ. TOP BAR 41 38 33 29 27
WALL STUDS P.T. 3x SILL DBL. 2x TOP PLATE 8"Ø #4
2x SOLE PLATE TO SOLID SAWN ALL OTHER BARS 32 29 25 23 21
PLATE TO CONNECTION TO THREADED
TYPE
"APA RATED"
10d EDGE
& BLOCKING
CONCRETE
RIM/BLOCKING OR LSL RIM/BLOCKING RODS HORIZ. TOP BAR 51 47 41 36 33
PROJECT #: 2023
1
2" WALL AT ALLOWABLE #5
PER NAIL RIM/BLOCKIN STEEL BEAM
SHEATHING ABUTTING SHEAR (PLF) ALL OTHER BARS 39 36 31 28 26
PLAN SPACING G JOIST "LTP4" OR SDS1 4"x6" TO SOLE DRAWN BY: HOANG LUAN
STRUCT 1 PANEL 5
8"ØANCHOR 1
SDS 4"x6" WOOD MIN. WIDTH "A35" CLIPS WOOD PLATE/TOP
EDGES BOLTS SCREWS U.O.N.
U.O.N. SCREWS PLATE
Ld PER SCHED.
MAX. SLOPE IF
6 ONE SIDE 6"o.c. 2x 48"o.c. 16d NAILS @6"o.c. 112" 16"o.c. 8"o.c. 16"o.c. 340
6 REQUIRED Revision Schedule
1
4 ONE SIDE 4"o.c. 2x 32"o.c. 8"o.c. 112" 12"o.c. 8"o.c. 16"o.c. 510 Number Description Date
3x OR DBL.
B: LAP SPLICE
3 ONE SIDE 3"o.c. 32"o.c. 6"o.c. 112" 8"o.c. 6"o.c. 16"o.c. 665
2x Ldh = 22 x d, TYP. Ldh = 22 x d, TYP.
CRITICAL SECTION CRITICAL SECTION
24 x d FOR 24 x d FOR
3x OR DBL. 1
2 ONE SIDE 2"o.c. 16"o.c. 6"o.c. 3 2" 8"o.c. 6o.c. 16"o.c. 870 f'c < 2,500 PSI f'c < 2,500 PSI
2x

3x OR DBL.
4-4 DOUBLE SIDED 4"o.c. 16"o.c. 6"o.c. 312" 6"o.c. 6"o.c. 16"o.c. 1020
2x
6d FOR #8 & SMALLER 6d FOR #8 & SMALLER

12d
3x OR DBL. 8d FOR #9 & LARGER 8d FOR #9 & LARGER
3-3 DOUBLE SIDED 3"o.c 16"o.c. 4"o.c. 312" 5"o.c. 4"o.c. 8"o.c. 1330
2x
4d OR 21 2" MIN. SHEET NAME
3x OR DBL. A34 clips
2-2 DOUBLE SIDED 2"o.c. 8"o.c. 3"o.c. 312" 3"o.c. 8"o.c. 1740
2x @4"o.c. 90° HOOK 180° HOOK
A: STANDARD HOOK
NOTES: (THIS SCHEDULE IS BASED ON AWC SDPWS-2015 TABLE 4.3A)
1. USE COMMON OR GALVANIZED BOX NAILS FOR ALL NAILING. 10d COMMON NAIL SHALL HAVE .148" DIAMETER AND 16d COMMON NAIL SHALL HAVE .162" DIAMETER. 10d GALVANIZED BOX NAIL SHALL NOTES:
HAVE .128" DIAMETER AND 16d GALVANIZED BOX NAIL SHALL HAVE .135" DIAMETER. NAILS SHALL HAVE 11 2" MIN. PENETRATION INTO FRAMING MEMBER OR BLOCKING. 1. d = REBAR DIAMETER.
2. LAP SPLICE LENGTHS ARE BASED ON 60 KSI REBAR YIELD STRENGTH AND NORMAL CONCRETE
DETAILS 2
2. THIS SCHEDULE SHALL APPLY TO NAILING AT ALL STUDS, WALL SHEATHING JOINTS, TOP PLATES, SILL PLATES, SOLE PLATES, RIMS, AND BLOCKING.
3. NAILING AT INTERMEDIATE MEMBERS (FIELD NAILING) SHALL BE 10d NAIL @12"o.c. WEIGHT.
4. WALL SHEATHING SHALL BE APPLIED OVER STUDS SPACED AT 16"o.c. 3. TOP BAR IS A HORIZONTAL BAR (OTHER THAN IN WALLS) PLACED WITH MORE THAN 12" OF FRESH
5. ALL SILL FASTENING TO CONCRETE SHALL HAVE AS A MINIMUM 5 8"Ø ANCHOR BOLTS w/SIMPSON H.D.G. BPS5 8-6 (BPS 5 8-3 AT 2x4 WALLS) BEARING PLATE WASHER OR EQUIVALENT. BEARING PLATE CONCRETE CAST BELOW BARS.
SHALL EXTEND TO WITHIN 1 2" OF THE EDGE OF THE SILL PLATE ON THE SIDE(S) WITH SHEATHING. ANCHOR BOLTS SHALL BE EMBEDDED 7" MIN. IN CONCRETE WALL OR FOUNDATION. 4. LAP SPLICE LENGTHS ARE BASED ON MINIMUM CLEAR COVER GREATER THAN ONE BAR DIAMETER
6. NAILS PENETRATING PRESSURE TREATED WOOD SHALL BE HOT-DIPPED GALVANIZED PER ASTM A153, CLASS D. AND MINIMUM CLEAR SPACING GREATER THAN TWO BAR DIAMETERS.
7. DBL. 2x STUDS AT ABUTTING PANEL EDGES SHALL BE FASTENED TOGETHER w/ 16d NAILS AT EDGE NAIL SPACING. 5. IF EITHER REQUIREMENT IN NOTE 4 IS NOT SATISFIED, INCREASE LAP SPLICE LENGTH BY 50%. SHEET NUMBER
8. NAILING SPACED AT 3"o.c. OR LESS SHALL BE STAGGERED 1 2" MIN. AND INSTALLED 3 8" MIN. FROM EDGE OF WALL SHEATHING AND STUD.

SHEAR WALL SCHEDULE REBAR DEVELOPMENT LENGTHS


7 SCALE: 1"=1'-0" 3 SCALE: 1"=1'-0"
S5.0
DOUBLE TOP PLATE HEADER ABOVE OPENING PER SCHEDULE
w/ "A34" CLIP EACH SIDE AT 2x4 WALL AND
"A35" CLIP EACH SIDE AT 2x6 WALL, JOIST AND BEAM HANGER SCHEDULE
UNLESS OTHERWISE NOTED ON PLAN.

FACE MOUNT TOP FLANGE CONCEALED FLANGE


JOIST / BEAM
PAIR OF SIMPSON "A34" CLIPS TOP HANGER HANGER HANGER
AND BOTTOM TYP. AT EXTERIOR
WALL 2x6 HU26 HU26TF HUC26 4'-0" MIN. LAP SP2 Stud-Plate Ties
EA. STUD
S.A.D. FOR (3) 20d NAILS AT EACH END AT EXTERIOR 16-16d NAILS STAGGERED
2x12 HU212 HU212TF LUC210Z
OPENING SIZE WALL AND (2) 16d NAILS AT INTERIOR
WALL
(2) 2x12 LUS210-2 - -
10'-0" MAX.

KING STUD TYP. DOUBLE KING


AT WIDTH>6'-0" AT EXTERIOR WALL 3x6 HU36 HU36TF HUC36

1400 BEECHWOOD AVE FULLERTON, CA 92835


STUD TYP. AND AT WIDTH>8'-0" AT INTERIOR
WALL 4x6 HU46 HU46TF HUC46
2-2X TOP PLATES PLATE JOINTS TO
STUDS BE ALIGNED OVER
CRIPPLE STUD TYP. DOUBLE CRIPPLE 4x8 HU48 HUS48TF HUC48
FRAMING AT EDGE NAILING (E.N.) STUDS (TYP.)
AT WIDTH>4'-0" AT EXTERIOR WALL
WINDOW AND AT 4x10 HUS410 HUS410TF HUCQ410-SDS 2x4 (FLAT) EDGE BLKG.
WIDTH>6'-0" AT INTERIOR WALL BOUNDARY NAILING (B.N.) AT
WHERE REQUIRED SEE PLAN STUDS
PERIMETER, SAME AS EDGE
4x12 HU412 HUS412TF HUCQ412-SDS NAILING, U.O.N. 2X BOTTOM
WINDOW SILL PLATE, PER SCHEDULE PLATES
EDGE OF SHEET, TYP
w/ "A34" CLIP EACH END AT 2x4 WALL
AND "A35" CLIP EACH END AT 2x6 31 2"x91 2" LSL/PSL HHUS410 BA3.56/9.5 HUCQ410-SDS
FIELD NAILING (F.N.)
WALL
SILL OR SOLE PLATE "WIDTH" OF OPENING 31 2"x117 8" LSL/PSL HHUS410 BA3.56/11.88 HUCQ412-SDS 4'-0"x8'-0" SHEATHING WITH FACE GRAIN
PERPENDICULAR TO JOISTS, PLACE IN A STAGGERED FLOOR OR ROOF JOISTS BELOW

NOTES: 6x10 OR 51 4"x91 2" PSL HGUS5.50/10 GLTV5.59 HUCQ610-SDS JOINT PATTERN, TYP. U.O.N.
MAX. WIDTH MIN. HEADER SIZE MIN. WINDOW SILL PLATE SIZE
CONNECTIONS, SP1 Stud-Plate Ties
OF
2x4 STUD WALL 2x6 STUD WALL 2x4 STUD WALL 2x6 STUD WALL HEADER AND SILL 6x12 OR 51 4"x117 8" PSL HGUS5.50/12 GLTV5.511 HUCQ612-SDS EA. STUD
OPENING
PLATE SIZES ON NOTE:
3'-6" 4x6 6x6 2x4 2x6 THIS DETAIL APPLY APPLIES TO FULL LENGTH OF WALL U.O.N. AND ALL THE WAY ACROSS BLDG ALONG LINE OF WALL AND OVER OPENINGS SUCH AS
1
TO ALL OPENINGS 7"x9 2" PSL HHUS7.25/10 GLTV49.5-2 HUC410-2
6'-0" 4x8 6x6 2-2x4 2-2x6 DOORS AND WINDOWS.
UNLESS NOTED
8'-0" 4x10 6x8 3-2x4 2-2x6
OTHERWISE. 7"x117 8" PSL HHUS7.25/10 GLTV411.88-2 HUC412-2
OVER 8' PER PLAN PER PLAN PER PLAN PER PLAN

RESIDENCE
TYPICAL OPENING IN STUD WALL NOTE:
TYPICAL HORIZONTAL DIAPHRAGMS TOP & BOTTOM PLATE SPLICE
11 SCALE: N.T.S.
1. USE JOIST AND BEAM HANGERS PER SCHEDULE, U.O.N. ON PLANS OR DETAILS
2. FOR BUILT-UP MEMBERS, USE HANGERS PER BEAM OF EQUIVALENT WIDTH
3. USE FACE MOUNTED HANGER WHENEVER POSSIBLE, SUBSTITUTE WITH TOP FLANGE HANGER AS NECESSARY
4 SCALE: N.T.S. 1 SCALE: N.T.S.
AT CONTRACTOR'S OPTION, U.O.N.
4. USE CONCEALED FLANGE HANGERS ONLY WHERE INDICATED ON PLANS
5. HANGERS PRODUCED BY SIMPSON STRONG-TIE, U.O.N., OR EQUIVALENT APPROVED BY STRUCTURAL
ENGINEER OF RECORD.
6. FOLLOW MANUFACTURER'S INSTALLATION INSTRUCTIONS
7. PROVIDE MAXIMUM FASTENERS LISTED BY MANUFACTURER
8. CONTACT STRUCTURAL ENGINEER OF RECORD FOR BEAM SIZES NOT SHOWN

NO HOLES WITHIN END MIDDLE 1 3 OF CLEAR SPAN


1
3 OF CLEAR SPAN TWICE THE LARGEST TYPICAL JOIST & BEAM
HOLE DIAMETER
MIN. HOLE HANGER SCHEDULE
CLEARANCE 7 SCALE: N.T.S.
D/3

9" MAX.
PIPE OR CONDUIT SILL PLATE
DEPTH
D/3

"D"

D/3 MAX. 6" MIN


NOTCH
D/3

D
MAX. HOLE DIAMETER: ALLOWABLE SP2 Stud-Plate
13 4"Ø AT D < 71 2" HOLE ZONE Ties EA. STUD
NOTE: 2"Ø AT D = 71 2" OR GREATER
1. ROUND HOLES ONLY.
2. NOTCHES NOT PERMITTED IN THE TOP OR BOTTOM EDGE. DRILL 1 2"Ø HOLES AT EACH ADD'L A.B. EACH SIDE WHEN
3. HOLES AND NOTCHES NOT PERMITTED IN CANTILEVERS. CORNER BEFORE NOTCHING CONDUIT IS MORE THAN D/3
4. HOLES AND NOTCHES NOT PERMITTED WHERE DEPTH IS 5" OR LESS. SIMPSON (ST2215) MIN. OR AS
5. ALLOWABLE HOLE ZONE SHOWN IS SUITABLE FOR BEAMS WITH UNIFORM LOADS ONLY, CONTACT THE NOTED ON FRAMING PLANS
STRUCTURAL ENGINEER FOR BEAMS SUPPORTING POSTS AND BEAMS.

HOLES & NOTCHES IN LSL/LVL/PSL HOLES & NOTCHES IN SILL PLATES


12 SCALE: 1"=1'-0"
8 SCALE: N.T.S.
WIDTH WIDTH
NOTCHES WITHIN END NO NOTCHES WITHIN MIDDLE 1 3
1
3 OF CLEAR SPAN OF CLEAR SPAN
D
STAMP
STUD WIDTH MIN.

BORED HOLES:
MAX.

MAX.
SPACE HOLES

MIN.
MIN. HOLE
D/4

D/6

2"
MAX. DIAMETER
BORED HOLES: SPACING
60% OF WIDTH
MAX. DIAMETER

D/3
40% OF WIDTH
SPACE HOLES/NOTCHES

DEPTH
D/3

"D"
STUD WIDTH MIN.

45°

5 5
8"
MIN. 8" MIN.

D/3
EDGE EDGE
DISTANCE DISTANCE
MIN.
2"

MAX. HOLE DIAMETER:


NOTCHES: D ALLOWABLE
D/3 AT 2x JOISTS
MAX. DEPTH MIN. HOLE
D/4 (2 2" MAX.) AT 4x OR GREATER ZONE
1 HOLE
25% OF WIDTH SPACING JOISTS
5 5
8" MIN. 8" MIN.
NOTE:
EDGE EDGE
1. HOLES AND NOTCHES NOT PERMITTED IN THE BOTTOM EDGE.
PROJECT #: 2023
DISTANCE DISTANCE 2. HOLES AND NOTCHES NOT PERMITTED WHERE DEPTH IS 5" OR LESS.
3. APPLY PRESERVATIVE TO HOLES IN PRESSURE TREATED WOOD. DRAWN BY: HOANG LUAN

INTERIOR EXTERIOR WALLS HOLES & NOTCHES IN


NON-BEARING WALLS AND BEARING WALLS SAWN LUMBER JOISTS Revision Schedule
NOTE: 9 SCALE: N.T.S.
Number Description Date
PORTION OF STUD REMAINING AT NOTCHES OR HOLES SHALL BE SOUND WOOD WITHOUT EXCESSIVE
STRENGTH-REDUCING PROPERTIES SUCH AS KNOTS, BREAKS, SPLITS, EXCESSIVE SLOPE OF GRAIN, ETC. 1 1
2" 2"
SP1 Stud-Plate
HOLES & NOTCHES IN STUDS 3
8"
3
8"
3
8"
3
8" Ties EA. STUD
13 SCALE: N.T.S.
SPACING PER
SHEAR WALL
SCHED
NAIL

WHERE SILL PLATE IS DRILLED OR NOTCHED SHEET NAME


9" MAX.
6" MIN.

MORE THAN 1 3 PLATE WIDTH, INSTALL


ANCHOR BOLT EACH SIDE
EDGE NAILING

1'-0"
NOTES:

E.N. AT STUD EACH


ANCHOR BOLT SIZE &

SIDE OF OPENING
1. ALL NAILS SHALL HAVE A MINIMUM EDGE DISTANCE OF 3 8" FOR STUD AND SHEARWAL SHEATHING.
9" MAX.
6" MIN.

SPACING PER PLANS &


DETAILS 2. PROVIDE STUD OR BLOCKING AT ALL JOIST UNLESS NOTED OTHERWISE. SEE SHEARWALL SCHEDULE FOR ADDITIONAL REQUIREMENTS.
SILL PLATE
3. PROVIDE EDGE NAILING AT ALL POSTS, ENDS OF WALLS AND EDGES OF ALL OPENINGS FULL HEIGHT. DETAILS 3
PANEL JOINT SPACING 1 8" 4. LONG LENGTH OF ALL SHEATHING PANELS SHALL RUN PARALLEL TO STUDS, UNLESS OTHERWISE APPROVED BY THE ENGINEER. STUDS EACH SIDE
MIN. 5. SEE SHEARWALL SCHEDULE FOR NAILING REQUIREMENTS AT PANEL EDGES.
SPLICE

1'-0"
1
2 2" MIN.
6. VERTICAL JOINTS OF SHEATHING PANELS SHALL BE STAGGERED.
STUD OR BLKG 7. NO OPENINGS IN SHEAR WALL PANELS ARE ALLOWED UNLESS SPECIFICALLY SHOWN ON THE STRUCTURAL PLANS.
8. NOTIFY ENGINEER OF RECORD IF B/D MORE THAN 2.
NOTE: 6"x6" OPENING OR LESS
9" MAX. 9" MAX. 9" MAX. USE 3x STUD & BLKG AT ALL PANEL EDGES AND STAGGER EDGE NAILING WHEN EDGE NAILING IS SPACED AT IN SHEAR WALL SHEET NUMBER
6" MIN. 6" MIN. 6" MIN. 2"o.c. OR LESS SHEATHING
C: DETAIL
SILL PLATE BOLTING STAGGERED PANEL EDGE NAILING TYPICAL SHEAR WALL FRAMING
14 SCALE: N.T.S. 10 SCALE: 1"=1'-0" 6 SCALE: 1"=1'-0"
S6.0