Geko DG - Operating/warning/fault messages
Picture Description Cause / removal Fault Alarm Number
Emergency stop Emergency
activated stop 100
Safety message Optional monitoring e.g.
canopy / door 318
surveillance
Engine oil pressure too Wire break of the oil
low pressure sensor 602
Engine temperature too overburdened
high Too high environment 301 / 701
temperature
incoming / outgoing air
blocked
Water in the fuel filter drain the fuel filter 214 / 614
Battery voltage too 211 / 611 – Low
high / to low charge 212 / 612 - High
Fuel reserve Check the fuel level 203 / 603
Refill if necessary
External Fuel reserve
level Refill if necessary
Starter blocked 314 / 714
displayed time to protect
against overloading
Service interval Perform the appropriate
Service 101
Insulation control
the Customers 300 / 700
the internal wiring
Frequency lower limit 316 / 716
exceeded. power generator.
Frequency upper limit
exceeded. power generator. 315 / 715
Voltage lower limit 305 / 705
exceeded. power generator.
Voltage upper limit
exceeded. power generator. 308 / 708
Check the Generator
controller.
Current limit exceeded
power generator. 311 / 711
GEKO DG – List of Alarms & their Meanings
S. No Initial Warning Fault Meaning
Alarm Alarm
1 100 Emergency STOP
2 101 Maintenance / Servicing Required
3 102 GSM Module
4 200 600 Low Oil Pressure
5 201 601 High Oil Temperature
6 202 602 Low Oil Level
7 203 603 Low fuel Level
8 204 604 Fuel Temperature High
9 205 605 Battery Charge Indicator
10 206 606 High Battery Temperature
11 207 607 High Ambient Temperature
12 208 608 Cooling water Temperature
13 209 609 Cylinder Head Temperature
14 210 610 Exhaust Temperature
15 211 611 Battery Low
16 212 612 Battery High
17 213 613 Coolant Level Low
18 214 614 Water in the Fuel
19 215 615 Fuel Loss
20 216 616 Engine Temperature Fault
21 300 700 Insulation Monitoring
22 301 701 High Temperature of Generator
23 302 702 Overload in L1
24 303 703 Overload in L2
25 304 704 Overload in L3
26 305 705 Voltage L1 violation – Minimum
27 306 706 Voltage L2 violation – Minimum
28 307 707 Voltage L3 violation – Minimum
29 308 708 Voltage L1 violation – Maximum
30 309 709 Voltage L2 violation – Maximum
31 310 710 Voltage L3 violation – Maximum
32 311 711 Current L1 Violation - Maximum
33 312 712 Current L2 Violation – Maximum
34 313 713 Current L3 Violation - Maximum
35 314 714 Starter is Interlock
36 315 715 Frequency High
37 316 716 Frequency Low
38 317 717 Unbalanced Load
39 318 718 Safety loop activated