GEKO DG - Fault Alarm Lists & Their Meanings

The document provides a comprehensive list of operating, warning, and fault messages for the Geko DG system, including their causes and removal actions. It details various alarm numbers associated with specific issues such as emergency stops, oil pressure, temperature, and fuel levels. Additionally, it includes a list of alarms and their meanings, categorized by initial and fault alarms.

Uploaded by

Subas Shrestha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views2 pages

GEKO DG - Fault Alarm Lists & Their Meanings

The document provides a comprehensive list of operating, warning, and fault messages for the Geko DG system, including their causes and removal actions. It details various alarm numbers associated with specific issues such as emergency stops, oil pressure, temperature, and fuel levels. Additionally, it includes a list of alarms and their meanings, categorized by initial and fault alarms.

Uploaded by

Subas Shrestha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Geko DG - Operating/warning/fault messages

Picture Description Cause / removal Fault Alarm Number


Emergency stop Emergency
activated stop 100

Safety message Optional monitoring e.g.


canopy / door 318
surveillance

Engine oil pressure too Wire break of the oil


low pressure sensor 602

Engine temperature too overburdened


high Too high environment 301 / 701
temperature
incoming / outgoing air
blocked

Water in the fuel filter drain the fuel filter 214 / 614

Battery voltage too 211 / 611 – Low


high / to low charge 212 / 612 - High

Fuel reserve Check the fuel level 203 / 603


Refill if necessary

External Fuel reserve


level Refill if necessary

Starter blocked 314 / 714


displayed time to protect
against overloading

Service interval Perform the appropriate


Service 101

Insulation control
the Customers 300 / 700

the internal wiring

Frequency lower limit 316 / 716


exceeded. power generator.

Frequency upper limit


exceeded. power generator. 315 / 715
Voltage lower limit 305 / 705
exceeded. power generator.

Voltage upper limit


exceeded. power generator. 308 / 708
Check the Generator
controller.
Current limit exceeded
power generator. 311 / 711

GEKO DG – List of Alarms & their Meanings


S. No Initial Warning Fault Meaning
Alarm Alarm
1 100 Emergency STOP
2 101 Maintenance / Servicing Required
3 102 GSM Module
4 200 600 Low Oil Pressure
5 201 601 High Oil Temperature
6 202 602 Low Oil Level
7 203 603 Low fuel Level
8 204 604 Fuel Temperature High
9 205 605 Battery Charge Indicator
10 206 606 High Battery Temperature
11 207 607 High Ambient Temperature
12 208 608 Cooling water Temperature
13 209 609 Cylinder Head Temperature
14 210 610 Exhaust Temperature
15 211 611 Battery Low
16 212 612 Battery High
17 213 613 Coolant Level Low
18 214 614 Water in the Fuel
19 215 615 Fuel Loss
20 216 616 Engine Temperature Fault
21 300 700 Insulation Monitoring
22 301 701 High Temperature of Generator
23 302 702 Overload in L1
24 303 703 Overload in L2
25 304 704 Overload in L3
26 305 705 Voltage L1 violation – Minimum
27 306 706 Voltage L2 violation – Minimum
28 307 707 Voltage L3 violation – Minimum
29 308 708 Voltage L1 violation – Maximum
30 309 709 Voltage L2 violation – Maximum
31 310 710 Voltage L3 violation – Maximum
32 311 711 Current L1 Violation - Maximum
33 312 712 Current L2 Violation – Maximum
34 313 713 Current L3 Violation - Maximum
35 314 714 Starter is Interlock
36 315 715 Frequency High
37 316 716 Frequency Low
38 317 717 Unbalanced Load
39 318 718 Safety loop activated