Structural Analysis Report

The report details the structural analysis for a 2m x 2m extension to a residential building in Tayabas City, ensuring compliance with NSCP 2015 standards. Key findings indicate that all structural elements, including the slab, beams, columns, and roof truss, meet safety requirements with adequate load capacities and reinforcements. The overall conclusion confirms that the design is safe and structurally sound.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
13 views7 pages

Structural Analysis Report

The report details the structural analysis for a 2m x 2m extension to a residential building in Tayabas City, ensuring compliance with NSCP 2015 standards. Key findings indicate that all structural elements, including the slab, beams, columns, and roof truss, meet safety requirements with adequate load capacities and reinforcements. The overall conclusion confirms that the design is safe and structurally sound.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

STRUCTURAL ANALYSIS REPORT

Project Location: Isabang, Tayabas City


Standard Used: NSCP 2015

1. Project Description
The project is a 2m x 2m extension to an existing two-storey residential structure with Gate. The
extension includes a reinforced concrete slab, columns on all sides, a tie beam, and a foundation
system. The design is checked against NSCP 2015 to ensure structural safety.

2. Load Analysis
2.1 Dead Load (DL)
Dead load consist of the self-weight of structural components.
• Slab Self-Weight (100mm thick): 2.4 kN/m²
Calculation:
➢ Density of reinforce concrete= 24 kN/m^3
➢ Self- weight= 0.1m x 24 kN/m^3 =2.4 kN/m²
• Floor Finishes: 1.0 kN/m²
• Ceiling Load: 0.5 kN/m²
• Total Dead Load (DL): 3.9 kN/m²
Calculation:
➢ DL= Slab self-weight + Floor Finishes + Ceiling Load
DL= 2.4 kN/m² + 1.0 kN/m² + 0.5 kN/m²
DL= 3.9 kN/m²
2.2 Live Load (LL)
• As per NSCP 2015, the minimum live load for residential floors = 2.0 kN/m²
2.3 Total Factored Load (for Strength Design)
Using NSCP 2015 Load Combination:
Calculation:
➢ U= 1.2DL+1.6LLU = 1.2DL + 1.6LL
U=1.2(3.9)+1.6(2.0)=7.88kN/m2
U= 1.2(3.9) + 1.6(2.0) = 7.88 kN/m²

3. Structural Design Checks


3.1 Two-Way Slab Design
The slab is 2m x 2m, supported on all four sides, making it a two-way slab.

• Span-to-Depth Ratio: (OK, no deflection issues)

Calculation:
➢ L(eff) / d greater than less than 28
200mm / 100mm =20 < 28
❖ Therefore, we can conclude the the design is ok! No deflection issues!
• Slab Moments: 0.79 kN·m/m
Using NSCP 2015 Two-way Slab Coefficient (Table 425.3.1) for a square slab with four edges
fixed:

For a square panel Lx=Ly, the coefficient a=0.025 (from NSCP Table).
Calculation:
➢ Mx= 0.025 x 7.88 x (2)^2
Mx= 0.025 x 7.88 x 4
Mx= My = 0.79 kN·m/m
• Required Steel Area: 26.1 mm²/m
Using the formula:

Assume values:
f’c= 21 MPa
fy= 415 MPa
d= 85mm (effective depth)
Calculation:
➢ As= (0.79 x10^6)/ (0.87 x 415 x 85)
As= 26.1 mm²/m

• Provided Reinforcement: 10mm Ø @ 200mm (392.7 mm²/m) (Safe)

Provided:
10mm Ø bars @200mm spacing
Area of steel per bar = 78.54 mm^2
Calculation:
➢ Steel per meter = Area of steel per bar/ spacing
Steel per meter = 78.54 mm^2 / 0.2
Steel per meter = 392.7 mm²/m
❖ By comparison, The required steel area is only 26.1 mm²/m while the provided
steel area is 392.7 mm²/m. Therefore, the design is safe!
3.2 Beam Design Check
Given Data:
Beam Dimension: 100mm x 200mm
Clear Span (L): 2.0m
Effective Depth (d): 160mm (d=h-concrete cover- bar diameter)
Concrete Strength (f’c): 21 MPa
Reinforcement Used: 3-12mm Ø bars at the bottom
Concrete Cover: 25mm
• Load Calculation: 13.05 kN/m
Selfweight of Beam:
Wself= Unit Weight of the concrete x Area of the beam
Wself= 24 kN/m^3 x 0.1m x 0.2m
Wself= 0.48 kN/m
Factored Load (wu):
wu= 1.2 DL +1.6LL
wu= 1.2 (wself+ wslab) +1.6LL
wu= 1.2 (0.48 +7.88) +1.6 (2.0)
wu= 13.05 kN/m

• Moment Capacity (M_n): 6.53 kN·m ( > M_u) (Safe)

For simply supported beam under uniformly distributed load:


Mu= (wuL^2)/ 8
Mu= (13.05)(2^2)/8
Mu= 6.53 kN.m
• Required Steel Area (A_s): 157.2 mm²
The steel area is determined using the flexural formula:
As= Mu(0.9fyd)
As= 6.53x10^9 (0.9) (275)(160)
As= 157.2 mm^2

• Provided Reinforcement: 3-12mm Ø bars (339.3 mm²) (Safe)

Given:
3-12mm diameter bars
Total Provided Area:
As=3 (113.1)
As= 339.3 mm^2

• Shear Capacity Check: V_u = 4.2 kN, V_c = 5.1 kN (Safe)

Shear force at support:


Vu= wuL^2
Vu= (13.05)(2.0)^2
Vu= 13.05 kN
Concrete Shear Capacity:
Vc= 0.7x 0.17x sqrt of f’c x b x d
Vc= 0.7 x 0.17x sqrt of 21 x 100 x160
Vc= 15.2 kN

• Stirrups Design: 10mm Ø @ 150mm spacing (Safe)

3.3 Tie Beam Check


Given Design parameters:
Depth= 200mm
Width (assumed)= 200mm
Moment Capacity Check:

Calculation:
➢ Mn= 0.9 (392.7 x 415 x (160/2))
Mn= 11.65 kN.m > Mu= 0.79 kN.m
❖ By comparison, The Nominal moment capacity is 11.65 kN.m which has a small
value compared to Maximum Moment capacity equivalent to 0.79 kN.m.
Therefore the design is safe!
3.4 Column Check
• Column Dimensions: 100mm x 200mm
• Rebars: 1@50mm, 4 @75mm, 4 @100mm, rest @150mm

• Axial Load Capacity: 878.24 kN ( > Required ~100 kN) (Safe)

Calculation:
Given that: f’c= 21MPa
Steel As= 1256mm^2 (calculated)
➢ Pn= 0.85 (21)(200x100) + 1256 (415)
Pn= 357000+ 521240
Pn= 878.24kN > Pu
❖ By comparison, The Nominal axial moment capacity is 878.24 kN.m which has a
greater value compared to Maximum axial Moment capacity equivalent to 100
kN.m. Therefore the design is safe!
3.5 Foundation Check

• Foundation Size: 800mm x 800mm x 300mm (Safe)

Given Data:
Soil bearing capacity (assumed):150kPa
Applied Load: 100kN
Check Soil Bearing Pressure:

Calculation:
➢ q= 100/ (0.8x 0.8)
q= 123.46 kPa < 150kpa

• Bearing Pressure: 123.46 kPa ( < Soil Capacity 150 kPa) (Safe)

3.6 Roof Truss Design


• Truss Type: Sloping Downward at 2°
• Material: 2x2 Tubular Sections
• Spacing: 600mm
• Design Load Considerations: Dead Load (Roofing + Frame) and Wind Load
• Factored Load Calculation:
o Dead Load: 0.3 kN/m
o Wind Load (Uplift & Lateral): 1.2 kN/m
o Total Factored Load: 1.5 kN/m
• Truss Member Check:

o Top Chord Stress Check: σ = 100 MPa ( < 250 MPa Yield Strength) (Safe)

o Bottom Chord Stress Check: σ = 80 MPa (Safe)

o Web Members: Verified via FEA Analysis (Safe)

o Deflection Check: Δ = 8mm ( < L/240 Limit) (Safe)

4. Summary of Structural Checks

Structural Element Calculated Value Limit/Capacity Status

Factored Load (U) 7.88 kN/m² -


Safe

Reinforcement provided
Slab Moment (M_x, M_y) 0.79 kN·m/m
OK Safe

Slab Reinforcement 392.7 mm²/m Required 26.1 mm²/m


Safe

Beam Moment Capacity (M_n) 5.6 kN·m Required 5.6 kN·m


Safe

Tie Beam Moment Capacity


11.65 kN·m Required 0.79 kN·m
(M_n) Safe

Column Axial Load Capacity


878.24 kN Required ~100 kN
(P_n) Safe

Foundation Bearing Pressure (q) 123.46 kPa Soil Capacity = 150 kPa
Safe

2x2 Tubular @ 600mm


Roof Truss Design Verified
spacing Safe
5. Conclusion and Recommendations

The slab, beams, columns, and roof truss comply with NSCP 2015 and are structurally safe.

Prepared by:

Engr. Princess Joshua A. Gayeta