0% found this document useful (0 votes)
250 views11 pages

Regulación SUN2000-330KTL-H1 de Factor de Potencia, Q, P, Arranque, Parada, Ramp

The document provides a detailed description of the Huawei SUN2000-330KTL-H1 inverter, including its technical specifications, control settings for active and reactive power, and fault ride through capabilities. It outlines the inverter's ability to manage power output and maintain grid stability through various control modes. Additionally, it includes schematic diagrams and capability curves to illustrate the inverter's functions and performance characteristics.

Uploaded by

Jesus Ortiz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
250 views11 pages

Regulación SUN2000-330KTL-H1 de Factor de Potencia, Q, P, Arranque, Parada, Ramp

The document provides a detailed description of the Huawei SUN2000-330KTL-H1 inverter, including its technical specifications, control settings for active and reactive power, and fault ride through capabilities. It outlines the inverter's ability to manage power output and maintain grid stability through various control modes. Additionally, it includes schematic diagrams and capability curves to illustrate the inverter's functions and performance characteristics.

Uploaded by

Jesus Ortiz
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

FusionSolar Smart PV Solution

SUN2000-330KTL-H1
Grid Code Functions Description

Huawei Technologies Co., Ltd.

Version Author Date Details


01 Huawei 03/28/2023

The information in this document may contain predictive statements including, without limitation, statements regarding the future financial
and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual results and
developments to differ materially from those expressed or implied in the predictive statements. Therefore, such information is provided for
reference purpose only and constitutes neither an offer nor an acceptance. Huawei may change the information at any time without notice.
FusionSolar Smart PV Solution - Technical Specifications Huawei Confidential

Contents
1. Product Datasheet ................................................................................................... 1

2. Schematic Diagram ................................................................................................. 2

3. Capability Curve ..................................................................................................... 3

4. Control Settings ....................................................................................................... 4


4.1 Active Power Control ......................................................................... 4
4.2 Reactive Power Control ..................................................................... 5
4.3 Fault Ride Through (FRT) Capability ............................................. 7
FusionSolar Smart PV Solution - Technical Specifications Huawei Confidential

1. Product Datasheet

Table 1: SUN2000-330KTL-H1 datasheet.

2023-3-30 Huawei confidential information Page 1


FusionSolar Smart PV Solution - Technical Specifications Huawei Confidential

2. Schematic Diagram

Figure 1: Inverter schematic diagram.

2023-3-30 Huawei confidential information Page 2


FusionSolar Smart PV Solution - Technical Specifications Huawei Confidential

3. Capability Curve

Figure 2: PQ curve of SUN2000-330KTL-H1.

Figure 3: Power de-rating curve with ambient temperature of SUN2000-330KTL-H1.

2023-3-30 Huawei confidential information


FusionSolar Smart PV Solution - Technical Specifications Huawei Confidential

4. Control Settings

4.1 Active Power Control

SUN2000-330KTL-H1 is able to control the active power injected into the grid. The
maximum output power of the inverter can be set by the HMI (APP or monitoring
system) through the following two methods.

a) Fixed Active Power Value Pref Control


Pref range: 0 ~ Pmax

b) Active power setting percentage


Range: (0%~100%)*Pmax

Another purpose of output power control is to control the frequency of the grid. If there
is an increase of the grid frequency (more generation than consumption), the inverter
will reduce the power contribution to the grid, as illustrated in Figure 4.

Figure 4: Power-frequency control mode.

2023-3-30 Huawei confidential information


FusionSolar Smart PV Solution - Technical Specifications Huawei Confidential

4.2 Reactive Power Control

The inverter output reactive power can also be set through HMI (APP or monitoring
system). The inverter will keep the power factor equal to 1 by default. There are four
ways to set the inverter reactive power:

a) Mode 1: Constant Reactive Power


The reactive set point is obtained from the fixed reference value (Qref).
Qref range: -0.6*Smax ~ 0.6*Smax

b) Mode 2: Constant Power Factor


The reactive set point is obtained from the reference value of the fixed power
factor (cosφref).
Adjustable Power factor range: ±1

c) Mode 3: Q-U Curve Control


Q range: -0.6*Smax ~ 0.6*Smax
U range: 0.8*Un ~ 1.15*Un
Description: The inverter can respond according to a pre-defined Q-U curve.
The customer is allowed to customize a Q-U curve with 2 ~ 10 points, and the
inverter can respond accordingly. The following figure presents one example.
Q/SAmax

B
0.31

Inductive
Lagging

0.98 1 1.02 1.04 1.06 U/Uc

-0.31 A

Figure 5: Example of Q-U curve control.

2023-3-30 Huawei confidential information


FusionSolar Smart PV Solution - Technical Specifications Huawei Confidential

d) Mode 4: PF-P Curve Control


Power factor range: ±1
Active power range: (0%~100%)*Pmax
Description: The inverter can also be controlled through a pre-defined PF-P
Curve (2 ~ 10 points). The inverter can respond according to the set point, as
shown in Figure 6.

PF (cosφ)
Over-excited

1
0.2 0.5 1 P/Pn
Under-excited

0.9

Figure 6: Example of PF-P curve control.

2023-3-30 Huawei confidential information


FusionSolar Smart PV Solution - Technical Specifications Huawei Confidential

4.3 Fault Ride Through (FRT) Capability

SUN2000-330KTL-H1 inverter monitors the frequency and voltage values of the


interconnection point (POI) of the PV power station. These values are processed to
determine the grid-connected state (frequency crossing or voltage crossing mode).
Once the voltage and frequency is deviated from the normal range, the protection relay
will operate to disconnect the inverter from the grid.

The frequency protection function has two limits for the maximum frequency and three
for the minimum frequency. These points define a ‘No-trip’ Zone for the inverter, as
shown in Figure 7. In this ‘No-trip’ Zone (Zone A), SUN2000-330KTL-H1 inverter is
able to continuously operate without disconnection.

f (pu)

Zone B
fmax2

fmax1
Zone A

tfmax2 tfmax1
tfmin3 tfmin2 tfmin1 t
fmin1

fmin2

fmin3 Zone B

Figure 7: Frequency Fault Ride Through Curve.

2023-3-30 Huawei confidential information


FusionSolar Smart PV Solution - Technical Specifications Huawei Confidential

The voltage protection function has two limits for the maximum voltage and another
four for the minimum voltage. These points define a ‘No-trip’ Zone for the inverter, as
shown in Figure 8. In this ‘No-trip’ Zone (Zone A), SUN2000-330KTL-H1 inverter is
able to continuously operate without disconnection.

U (pu)

PA1 PA2 Zone B

1.1
PA3
1.0
PB6
0.9
Zone A
PB5
tfmin1

PB3 PB4
Zone B

PB1 PB2

0.0 t

Figure 8: Voltage Fault Ride Through Curve.

2023-3-30 Huawei confidential information


FusionSolar Smart PV Solution - Technical Specifications Huawei Confidential

In case of a voltage drop, the inverter injects the reactive current into the grid for voltage
compensation. Under this condition, the inverter reactive current injection follows a
drop characteristic (Figure 9) and has a higher priority than the active current. It is
necessary to limit the total output current not exceeding the maximum current.
Therefore, the inverter active current may be limited if necessary.

Iq (pu)

Imax

drooplv

0 vlv 1 U (pu)

Figure 9: Iq-U Characteristic in LVRT Mode.