In House Verification - Oil BDV

The document details the in-house verification of an Oil Breakdown Tester (Model OTS 100AF) with a specified range of 0-100kV and accuracy of 0.1. Verification results indicate that the Rate of Rise of Voltage meets the acceptance criteria of 1.8 kV/s to 2.2 kV/s across multiple tests. The equipment is subject to quarterly verification and must maintain valid calibration.

Uploaded by

Venkatesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
76 views1 page

In House Verification - Oil BDV

The document details the in-house verification of an Oil Breakdown Tester (Model OTS 100AF) with a specified range of 0-100kV and accuracy of 0.1. Verification results indicate that the Rate of Rise of Voltage meets the acceptance criteria of 1.8 kV/s to 2.2 kV/s across multiple tests. The equipment is subject to quarterly verification and must maintain valid calibration.

Uploaded by

Venkatesh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

TRANSFORMER TESTING LAB

IN HOUSE VERIFICATION
UNIQUE IDENTIFICATION
EQUIPMENT EQUIPMENT S.NO DATE
NUMBER
Oil Breakdown Tester 101099441 MTD/LAB/EQ/037

1. DESCRIPTION & IDENTIFICATION OF ITEM


Name : Oil Breakdown Tester
Make : Megger
Model : OTS 100AF
Range : 0-100kV
Accuracy : 0.1
S.No : 101099441
Resolution : 0.1
2. Ambient Temperature :
Relative Humidity :
3. MAJOR EQUIPMENTS USED FOR VERIFICATION
Name: Stop Watch (Shhors)
ID.No : MTD/LAB/EQ/023
4. Results:

Verification of Rate of Rise of Voltage for Oil Breakdown Tester as per IS 6792
Value of each Indi-
Acceptance Criteria
WOI vidual Voltage Time (Sec) Voltage/Time(kV/s)
(2kV/s±0.2kV/s)
Breakdown(kV rms)
1. 1.8 kV/s to 2.2 kV/s
2. 1.8 kV/s to 2.2 kV/s
3. 1.8 kV/s to 2.2 kV/s
4. 1.8 kV/s to 2.2 kV/s
5. 1.8 kV/s to 2.2 kV/s
6. 1.8 kV/s to 2.2 kV/s
Mean: 1.8 kV/s to 2.2 kV/s

Tested By : Reviewed By: Approved By:

Note:
1. Ensure the Oil Breakdown Tester & Stop Watch has valid calibration
2.Verification of Rate of Rise of Voltage for Oil Breakdown Tester is to be done at quarterly frequency

Date of Issue: 12.12.2024 Retention: 2 Years F No: MTD/TTL/F/6.4.13/01 Rev 0