Operation and Maintenance Manual With Illustrated Parts List For GPU-600 3-Phase Solid State Transformer-Rectifiers
Operation and Maintenance Manual With Illustrated Parts List For GPU-600 3-Phase Solid State Transformer-Rectifiers
Series 500082-6xx
28.5 Volts, 600 Amps
OM 2244
12/15/2014 Rev A
OM-2244 / Operation and Maintenance Manual
DCS- 600/ Series 500082 / Solid State Transformer-Rectifiers
Introduction
This manual contains operation and maintenance information for “GPU-600” solid-state Transformer-
Rectifiers manufactured by ITW GSE, Troy, Ohio 45373.
This manual is not intended to be a textbook on electricity or electronics. Its primary purpose is to provide
information and instructions to experienced operators, electricians, and mechanics who have never operated
this equipment. It is the intent of this manual to guide and assist operators and maintenance people in the
proper use and care of the equipment.
Use of the manual should not be put off until a trouble or need for help develops. Read the instructions
before starting the unit. Learn to use the manual and to locate information contained in it. Its style and
arrangement are very similar to commercial aircraft manuals.
The manual is divided into five chapters plus an appendix. Each chapter is divided into as many sections as
required. Each new section starts with page 1. Each page is identified by chapter, section and page number,
which are located in the lower, outside corner. When information located in another portion of the manual is
referred to, its location is identified by a chapter, section, paragraph or figure number.
For example: “(see Section 2-3, Paragraph 1.a.)” refers to information located in Chapter 2, Section 3,
Paragraph 1.a. If a chapter and section are not indicated in a reference, the referenced material is located in
the same section as the reference, for example: “(see Paragraph 1.a.).”
The Appendix is the last section. Its contains a list of available options that may be purchased with that unit.
Items on the list with check marks next to them have been added to the standard unit per the customer’s
order. Literature for each option follows. The Appendix will help control the information in the manual:
making it unique to the unit purchased.
In addition to operation and maintenance instructions, the manual contains an illustrated parts list in Chapter
4, and a collection of manufacturer’s literature and supplemental information in Chapter 5.
Chapter 1. Description/Operation
Chapter 2. Servicing/Troubleshooting
Appendix A Options
If you have any questions concerning your ITW GSE equipment, immediately contact our Service Department
by mail, telephone, FAX, or E-Mail.
E-Mail: [email protected]
WARNING
ELECTRIC SHOCK can KILL. Do not touch live electrical parts.
ELECTRIC ARC FLASH can injure eyes, burn skin, cause equipment damage, and
ignite combustible material. DO NOT use power cables to break load. Prevent tools
from causing short circuits.
IMPORTANT Protect all operating personnel. Read, understand, and follow all instructions in the
Operating/Instruction Manual before installing, operating, or servicing the equipment.
Keep the manual available for future use by all operators.
1) General
Equipment that supplies electrical power can cause serious injury or death, or damage to other equipment or
property. The operator must strictly observe all safety rules and take precautionary actions. Safe practices
have been developed from past experience in the use of power source equipment. While certain practices
below apply only to electrically-powered equipment, other practices apply to engine-driven equipment, and
some practices to both.
2) Shock Prevention
Bare conductors, terminals in the output circuit, or ungrounded, electrically-live equipment can fatally shock a
person. Have a certified electrician verify that the equipment is adequately grounded and learn what terminals
and parts are electrically HOT. Avoid hot spots on machine. Use proper safety clothing, procedures, and test
equipment. The electrical resistance of the body is decreased when wet, permitting dangerous currents to
flow through it. When inspecting or servicing equipment, do not work in damp areas. Stand on a dry rubber
mat or dry wood, and use insulating gloves when dampness or sweat cannot be avoided. Keep clothing dry,
and never work alone.
This equipment must be installed and maintained in accordance with the National Electrical Code,
ANSI/NFPA 70, or other applicable codes. A power disconnect switch or circuit breaker must be
located at the equipment. Check the nameplate for voltage, frequency, and phase requirements. If
only 3-phase power is available, connect any single-phase rated equipment to only two wires of the 3-
phase line. DO NOT CONNECT the equipment grounding conductor (lead) to the third live wire of the
3-phase line, as this makes the equipment frame electrically HOT, which can cause a fatal shock.
Always connect the grounding lead, if supplied in a power line cable, to the grounded switch box or
building ground. If not provided, use a separate grounding lead. Ensure that the current (amperage)
capacity of the grounding lead will be adequate for the worst fault current situation. Refer to the
National Electrical Code ANSI/NFPA 70 for details. Do not remove plug ground prongs. Use correctly
mating receptacles.
Inspect cables frequently for damage to the insulation and the connectors. Replace or repair cracked
or worn cables immediately. Do not overload cables. Do not touch output terminals while equipment
is energized.
a) Please lock-out and Tag procedure, Shut off all power at the disconnecting switch or line breaker
before inspecting or servicing the equipment.
b) Lock switch OPEN (or remove line fuses) so that power cannot be turned on accidentally.
d) If troubleshooting must be done with the unit energized, have another person present who is trained
in turning off the equipment and providing or calling for first aid.
EMERGENCY
FIRST AID CALL EMERGENCY RESCUE SQUAD IMMEDIATEL. Seek additional assistance. Use
First Aid techniques recommended by American Red Cross until medical help arrives.
IF BREATHING IS DIFFICULT, give oxygen, if available, and have victim lie down.
FOR ELECTRICAL SHOCK, turn off power. Remove victim; if not breathing, begin
artificial respiration, preferably mouth-to-mouth. If no detectable pulse, begin external
heart massage.
Inspect all precautionary labels on the equipment monthly. Order and replace all labels that cannot be
easily read.
Table of Contents
Appendix A
Chapter 1 Description/Operation
Section 1 Description
1) General
The GPU-600 Solid State Transformer-Rectifiers covered by this manual are manufactured by ITW GSE,
Troy, Ohio 45373. These Transformer Rectifiers (GPUs) are designed to provide ground power for
maintenance and startup of aircraft having 28-VDC electrical systems.
The number 500082 identifies the “model or series” of the GPU. The part number is followed by a
different dash number, which separates the basic units available. The criteria for input voltages, Amps,
and frequencies change with each dash number. Figure 1 uses the part number to identify the variations
possible covered by this manual.
3) Orientation
To avoid confusion in the location of components, the control panel is considered to be the front of the
unit. Left and right are determined by looking at the unit from the front.
7
11
12
6
10
1
2
3
ELECTRICAL DATA
MODEL 6T28-600CL 5T28-600CL 6T28-600CL
DCS600T60208 DCS600T50380 DCS600T6O575
SPECIFICATION NUMBER DCS600S60208 DCS600T50380CE DCS600B60380
DCS600B60208 DCS600S50380CE DCS600S50380
INPUT
Voltage 208 / 230 / 460 220 / 380 230 / 460 / 575
Amps 86 / 78 / 39 82 / 47 79 / 39 / 32
Frequency 60 50 60
Phase 3 3 3
Convenience Receptacle 10A / 115V / 60 Hz 10A / 220V / 50 Hz 10A / 115V / 60 Hz
For ground cable size See Section 2, Figure 1
OUTPUT
D.C. Voltage 28.5 28.5 28.5
Amps 600 600 600
Duty Cycle 100% 100% 100%
Kilowatts 17.1 17.1 17.1
PHYSICAL / DIMENSIONS
Model Length Width Width Height Weight
(overall) (case) (overall) (w/o cable basket) (overall)
Trailer 45.7 inches 24.1 inches 33 inches 35 inches 650 lbs.
(116.1 cm) (61.3 cm) (83.8 cm) (88.8 cm) (295 kg)
Stationary 35.1 inches 24.1 inches 33 inches 29.3 inches 600 lbs.
(89.2 cm) (61.3 cm) (83.8 cm) (74.5 cm) (272 kg)
Bridge 36 inches 24.1 inches 34.4 inches 59.8 inches
(91 cm) (61.3 cm) (87.3 cm) (151.9 cm)
See Sub-section 7, “Detailed Description of GPU-600 Components”, for details on the types and levels of
protection provided by the control system.
6) Theory of Operation
The GPU provides regulated 28.5V DC. Power to the GPU is provided from the local utility company,
through the input contactor. The output contactor, controlled by the Output Switch, connects DC power to
the load.
The 28V DC power supply consists of a simple and reliable step-down transformer (1, Figure 5) whose
output is rectified by six silicon-controlled rectifiers (SCRs) (3, Figure 7) in a full-wave, center tapped
configuration. A filter consisting of an inductor and capacitors produces a low ripple DC voltage.
The printed circuit board (PC Board) (9, Figure 5) regulates the output voltage by controlling the SCR
turn-on. It does this via the phase control method; which uses the SCRs to select the desired portion of
the voltage that has been stepped down by the main transformer to produce the DC voltage. The PC
Board also provides current limiting, over-voltage and overload protection for loads connected to the DC
output. This output is floating (isolated from chassis ground), eliminating any grounding problems
between the load and the chassis ground.
CAUTION
Capacitor charge can injure! Allow capacitors to discharge fully and verify capacitor
discharge with voltmeter before touching the capacitor circuitry.
(5) DC Voltmeter
The M2 output voltmeter ( Figure 4 Item 5) measures the DC output voltage across the main filter
capacitors. The scale has a 50 V DC maximum reading.
1 3 6 5
8 10
4
9 11
2 7
(12) Emergency Stop Switch (CE certified units only – not shown)
This switch is located in the lower right corner. Press to shut off the GPU.
The control board mounts inside the GPU, on a steel panel behind the left side panel. This circuit
board controls for the following functions:
The control board turns off the power supply and turns on the DS2 red overload trip light on the
front panel if more than 31.5 V DC or 2125 A overload exists. To reset, correct the cause of the
condition and then turn the input switch off and back on.
The starting current or output surge current is selected by adjusting R13 starting current control
on the front panel from the minimum 200 A DC to the maximum 2000 A DC.
CAUTION Excess starting current may cause damage to load, blow fuses or damage the power
supply. Contact the factory if you require a current limit lower than the 150 A DC
standard minimum limit.
The voltage value is continuously compared to the actual output. If adequate input voltage exists,
deviation from the desired voltage output is corrected by the change in SCR conduction time set
by the printed circuit board firing pulse output. This corrective action is done quickly because the
control is done electronically with only limited stored energy in the circuitry. Typical response time
is about 25 milliseconds.
The main power transformer is a forced air-cooled, core-type, three-phase unit that reduces the rated
input voltage or voltages to a voltage somewhat higher than the maximum rated output voltage. The
extra voltage for the output provides a reserve capability to compensate for under voltage on the input
circuit, for the higher IR voltage drop found as the transformer, cables and other components heat up
with load and ambient temperature rises.
The main transformer in the GPU supplies power for the DC output and powers the auxiliary output
receptacle and the fan. The main transformers for the 60 Hz. units have windings to provide 115 VAC
for the auxiliary power receptacle and fan motor. The main transformers for the 50 Hz. units have
windings to provide 220 VAC winding for its auxiliary power receptacle and a 110 VAC winding for the
fan motor.
The main transformer has a center tapped coil on each phase that provides six fused (F2-F7) sensing
or synchronizing voltage signals to the solid state printed circuit control board ( Figure 5 Item 9). Be
certain to follow the changeover diagram for both the main transformer and the control transformer (
Figure 5 Item 6) for the input voltage you have available.
CAUTION Improper connections will cause damage. Contact factory if your equipment
specification information and/or voltage changeover diagram does not agree with your
rated three-phase input voltage.
9 8 10 15 13
12
17
11
5 14
20 19
3 18
2 1 7 6 16
1. Power Transformer (T1) 11. Front Panel
2. Capacitors (C15, C16, C17) 12. Voltage Changeover Board
3. 28.5 VDC Output Contactor (K2) 13. SCR Heat Sink Assembly
4. Pre-load Resistor Assembly (R2, R3, R4) 14. Fan Blade
5. Choke (L1) 15. Fan Motor (B1)
6. Control Transformer (T2) 16. Feedback Shunt (R12)
7. Interior Panel 17. Fan Turn-on Thermostat (S4)
8. Fuse Block (F2 through F7) 18. Overload Thermostat (S5)
9. Printed Circuit Board (A1) 19. Fan Fuse (F1)
10. Line Contactor (K1) 20. Ammeter Shunt (R11)
Figure 5 Internal Components of GPU-600
22 23 24 7 8 9 10 11
2
12
1
25
3 6
4 14
5
21 26
20 15
13 19 18 17 16
1. TP1 SCR Gate Pulse from R10 Adjustment 14. R60 Overload Limit (TP20)
2. TP2 SCR Gate Pulse from R9 Adjustment 15. R109 28 V DC Output Calibration (TP13)
3. R9 Balance Adjustment Phase 2 (TP2) 16. R101 5 V Reference Volt Adjustment (TP19)
4. R10 Balance Adjustment Phase 3 (TP1) 17. R102 Voltage Slope Adjustment (TP17)
5. TP8 Balance SCR Gate Pulse Phase1 18. TP19 Reference Volt Test Point (R101)
6. R38 No Load Amp Off Set Null (TP14)* 19. TP17 Voltage Slope Test Point (R102)
7. R37 Over-voltage Trip Point 20. TP15 Common, PC Board Volts
8. TP3 PC Board Common 21. TPF SCR Gate Pulse Timer
9. TP4 +9.1 VDC Timer Voltage 22. TPE Gate Timer Output Phase 2
10. TP5 +15 V Regulated Voltage 23. TPD Gate Timer Output Phase 3
11 TP6 –15 V Regulated Voltage 24. TP13 Actual Output Volt (28.5 or 14.25)
12. TP7 +24 V Non regulated Voltage 25. TP20 Overload Limit (R60) Adjustment
13. TP14 Null at 0 A DC TP (R38)* 26. TPL Overload Trip Summing Point
* Note TP14 provides amplified load amp reading for comparison with overload limit (TP20) and starting
amperage limit (TP21) set by R13 control on front panel.
Figure 6 Solid State Printed Circuit Control Board Test Points of GPU-600
The 1 amp, F2 through F7 fuses (8, Figure 5) are located near the control board behind the left side
panel. These fuses are accessible by removing the top panel.
The small control transformer located on the interior panel (7, Figure 5) provides 115 V AC to the K1
(10, Figure 5) input contactor coil, input contactor light A (12, Figure 4), and S1 (10, Figure 4) input
contactor switch via the half amp F8 contactor fuse (located on the control transformer). This
transformer does not provide the 10A, 115 VAC auxiliary power.
WARNING Electric shock can kill! Disconnect input power at the source to remove voltage to the
control transformer, input fuses and contactor.
The single-phase auxiliary power receptacle ( Figure 4 Item 5) has the same frequency as the
primary input voltage. It is protected by the F9 fuse ( Figure 4 Item 11), located on the front panel,
typically 10 Amperes. The auxiliary power circuitry is turned off whenever the primary contactor is
open or off. The auxiliary power winding is typically located on the middle leg (B phase) of the main
transformer. It provides power to the receptacle (5, Figure 4) and to the fan motor via the S4 fan turn-
on thermostat. The fan thermostat saves energy and reduces internal dust accumulation by allowing
the fan to run only when necessary to prevent overheating.
A “MOV” voltage surge suppressor, RV1 (6, Figure 4), is installed across the receptacle terminals to
reduce voltage surge problems to the load equipment and the power source.
Output contactor K2 ( Figure 5 Item 3) is operated by the output contactor ON-OFF switch S2 ( Figure
4 Item 11). Placing this switch momentarily in the TOP (spring-loaded) position turns the output
contactor ON, and placing it in the DOWN position turns the output contactor OFF.
The positive output lead is to be connected to the positive output terminal of the K2 contactor. The
negative output lead is to be connected to the R11 ammeter shunt. A small notch has been made in
the bottom of the right and left side panels to allow the output cable assembly to pass out either side.
The S5 normally-closed overload thermostat (18, Fig. 5) mounted on the main SCR rectifier heat sink
is designed to remove the output command signal whenever the heat sink temperature rise becomes
too high from overload, loss of cooling air flow, etc. The thermostat automatically resets on cool
down.
The DC output voltage is smoothed (filtered) by an L-C filter made up of L1 iron core reactor (4,
Figure 5) carrying the output current to the load and the ripple current to the C15, C16, C17
capacitors (2, Figure 5) in parallel with the load terminals. The R2, R3, R4 bypass resistors (4, Figure
5) provide both a pre-load to the SCR devices and a safety discharge circuit for quickly discharging
the filter capacitors whenever the power supply is turned off.
CAUTION Capacitor charge can injure. Be sure capacitors are discharged before touching.
The CR7 flyback diode (9, Figure 7) acts to facilitate discharge of the output filter circuitry as well as
to protect the main SCR rectifier assembly from damaging reverse voltage spikes.
The main SCR heat sink assembly is mounted on the front of the rear panel. It surrounds the 115 V
AC cooling fan assembly for optimum cooling efficiency. The SCR heat sink consists of a formed
aluminum heat sink with 6 “hockey puck” silicon controlled rectifiers (3, Figure 7) held by 6 insulated
compression spring assemblies (2, Figure 7), held against it by 12 U-shaped aluminum heat sinks (4,
Figure 7) for the “SCR” device cooling. There are two snubber pc board assemblies for SCR gate
signal control and protection (10, Figure 7), and the associated insulators, thermostats and hardware.
The solid-state printed circuit board (9, Figure 5) provides a properly timed and sequenced turn on
signal to the silicon controlled rectifiers that must be conducted to provide the desired output.
If the output voltage is too high or if the output current is above the limit set by controls such as the
R13 starting potentiometer, the control board delays the SCR turn-on signal to allow less SCR device
conduction time for a corresponded lower output. Conversely, if the output voltage is too low, the
SCR turn-on signal is delivered earlier in the possible conduction time for each SCR; thereby,
allowing more power to be supplied because of the longer conduction time. Proper operation of the
SCR devices requires phase sequence and presence of all 6 voltage sensing signals, proper phase
sequence and presence of the output voltage to the SCR devices, and the proper magnitude and
sequence of the SCR turn-on signal to the SCR gate leads.
The 115 V AC fan motor ( Figure 5 Item 15) does not run until the SCR heat sink gets hot enough to
turn on the S4 thermostat ( Figure 7 Item 6). This feature can reduce the need for internal power
supply cleaning and the use of electricity.
6 2 5
2 2
10 4
7 7
8
9 1
3,11
a) Visually inspect the shipping crate for damage. If any damage is detected, request that the carrier
agent inspect the shipment and note the damage on the delivery receipt. This is for your protection.
b) If there is no obvious damage to the shipping crate, unpack the unit as follows:
b) Visually inspect the unit for evidence of external damage such as damaged sheet metal, scratches,
dents, etc. Check also for loose connections and components. If the equipment has been damaged
in transit, file a claim for damage at once. If you require assistance with a damage claim, furnish ITW
GSE with full information about the claim.
NOTE: Save the shipping container until the unit has been put into service and determined to be
operating correctly.
Adequate air circulation is needed at all times in order to assure proper operation. Provide a minimum of
12 inches (305mm) of free air space at both the front and rear of the unit. Make sure that the ventilator
openings are not obstructed. The unit should not be installed on a grade greater than 10°.
The GPU has a large inrush current when it is first turned on, much like a large electric motor. Therefore,
to avoid falsely tripping the supply line circuit breaker or fuse, the circuit breaker or fuse should be the
type used with electric motors.
* Conductor sizes listed are for 30 feet or less of each conductor in conduit and for copper conductors having
90º C insulation, such as type FEB, FEPB, RHH, and THHN as based on an ambient temperature of 50° C.
For conductors having other insulation, or for conductors longer than 30 feet, consult local electrical code for
the required conductor size.
** Conductor sizes listed are for 30 feet or less of each conductor in conduit and for copper conductors having
90º C insulation, such as type W, SC, SCE, SCT, PPE, G, and G-GC as based on an ambient temperature of
50° C. For conductors having other insulation, or for conductors longer than 30 feet, consult local electrical
code for the required conductor size.
WARNING
The method of installation, conductor size, and over-current protection shall conform
to the requirements of the local electrical code, the national electrical code, or other
national codes, as applicable. Qualified persons shall do all installation wiring and
machine reconnection.
WARNING
Electric shock can kill! Open the disconnect switch, or breaker, and determine that no
voltage is present before removing top canopy and connecting wires between the
input service and power supply or working on the power supply.
Please contact the Service Department if you have any problem with this
December 15, 2014 Chapter 1-2
Page 2
OM-2244 / Operation and Maintenance Manual
DCS-600/ Series 500082/ Solid State Transformer-Rectifiers
On the left is Voltage Changeover Panel, which sets the input voltage for the main transformer. On
the right is the control transformer, which has different taps for the various input voltages.
(1) Make sure the GPU is not connected to the electrical service.
(2) Remove the top cover.
(3) Locate the items pictures in Figure 2.
(4) Refer to Sheet 6 of the schematic diagram, which is located in Chapter 5 of this manual.
(5) Verify that the configuration matches the appropriate diagram on the schematic.
CAUTION
Reconnection of control transformer as well as main input connection panel must be
made when changing rated input voltage. See changeover diagram.
Changing the voltage configuration requires changes to main transformer T1 configuration on the
Changeover Board and changes to control transformer T2 by moving a yellow wire to a different tap
on the right side of the transformer. (See Figure 2)
(1) On the T1 Changeover Board, move the jumper links as shown on the diagram for your voltage
requirement.
(2) On the right side of control transformer, move the yellow wire to the tap specified in the diagram.
(1) Route the cable through the hole provided in the rear panel.
(2) Connect the three-phase line leads to input terminals on line contactor, which is located on the
interior panel inside the power supply cabinet.
(3) Be certain that the cable will not contact the fan or hot parts on the SCR heat sink assembly.
(4) Attach the equipment ground conductor to the stud provided adjacent to the contactor.
WARNING
To help protect against electrical shock from line voltage or static discharge, make
sure the GPU is grounded.
NOTE: After connecting the input cables, it is recommended that ITW GSE # 904021 urethane coating
be sprayed on the connections at the contactor to protect these connections from corrosion,
fungus, and contamination. Spraying these connections will also reduce the potential for arcing
from dirt and condensation.
A no-load check should be made before the GPU is connected to an aircraft. Proceed as follows.
(1) Replace the top panel.
(2) Apply input power to the GPU from the input power source.
(3) On the front panel of the GPU, turn on the input power switch.
(4) Verify that the amber input power light turns on.
(5) Hold the output contactor switch up in the “Close” position until the green output contactor light
turns on.
(6) Release the output contactor switch to the middle “On” position.
(7) Verify that the voltmeter shows the proper voltage.
December 15, 2014 Chapter 1-2
Page 5
OM-2244 / Operation and Maintenance Manual
DCS-600/ Series 500082/ Solid State Transformer-Rectifiers
(8) Using a handheld voltmeter, verify that voltage is present at the aircraft connector.
(9) Turn off the GPU.
(1) The unit should be prepared for storage as soon as possible after being removed from service.
(2) The unit should be stored in a building which is dry and which may be heated during winter
months. The unit shall be stored on a grade no greater than 10°.
(3) Moisture absorbing chemicals are available for use where excessive dampness is a problem.
However, the unit must be completely packaged and sealed if moisture-absorbing chemicals are
to be effective.
b) Temporary Storage
(1) Use moisture-absorbing chemicals where excessive dampness is a problem. However, the unit
must be completely packaged and sealed if moisture-absorbing chemicals are to be effective.
Seal all openings. Use a waterproof, vapor proof material that is strong enough to resist puncture
damage.
(2) Store the unit in a building which is dry and which may be heated during winter months.
(1) To protect the GPU’s components, the complete unit should be packaged, using moisture proof
packaging and sealing material. Place containers of moisture-absorbing chemicals, such as silica
gel, in the unit before packaging.
(2) Store the unit in a building which is dry and which may be heated during winter months.
Section 3 Operation
IMPORTANT
Before attempting to operate the converter, read this entire section to become fully
familiar with how the converter operates.
1) General
This section contains information for safe and efficient operation of the equipment. Operating instructions
are presented in step-by-step sequence of procedures to be followed in supplying 28 V DC to an aircraft
or similar load.
WARNING Electric shock and fire can kill! Read and understand all operating instructions before
attempting to operate the equipment. Operation attempts by untrained personnel can
endanger people, this equipment, and the load. Do not attempt to operate the
equipment for uses not approved by the manufacturer, or at input and output ratings
not listed in the specification table located in 1-1, Figure 3.
The repeated opening of input fuses or repeated functioning of the overload trip circuitry indicates a
misapplication, a faulty main component, or an improper connection or load. Correct the problem by
following the instructions in Chapter 2 before attempting to operate the power supply. Be certain that a
input disconnect means is readily accessible between the power input source and this DC power supply.
You may need to quickly isolate the DC power source from all power during an emergency, fire, or
equipment malfunction.
(2) Verify that the supply-input connections agree with the input voltage available by comparison to
the voltage changeover diagram.
(3) Connect output cable between load and the proper connection points in the DC power supply.
(4) When all covers or panels are in place, turn on the source of input power.
(5) Set R13 start level control knob (1-1, 8, Figure 4) to the output surge limit required for your load.
b) Bridge Preparation
(2) Place S1 Input Contactor Switch in ON position (1-1, 10, Figure 4).
3) Operation Procedure
a) Input Control Functions
(2) Verify that only the amber input power light (1-1, 12, Figure 4) glows. If the light glows, no
(1) Hold the S2 output contactor switch (1-1, 11, Figure 4) in the up “CLOSE” position long enough
for the green output contactor light (1-1, 13, Figure 4) to glow.
(3) Verify that M1 DC ammeter (1-1, 2, Figure 4) does not read excessive amperage.
(4) The DC power supply should continue to deliver power until the S2 switch is placed in the down
“OFF” position or one of the other control functions turn the unit “OFF”.
4) Voltmeter
a) Verify on the M2 DC voltmeter (1-1, 3, Figure 4) that the DC output voltage level is correct. If not, turn
off power supply, disconnect your load, and refer to Service, Chapter 2 for instructions.
b) If R13 has no effect or if the output current cannot be decreased to about 200 A DC at the R13
minimum position, a faulty SCR device or control circuit malfunction is indicated requiring power
supply repair. Refer to Chapter 2 for service instructions.
Calibration, service, and repair are to be done by ITW GSE Service Department personnel, authorized
distributors of ITW GSE equipment, or trained qualified electronic technicians.
If you have any questions concerning your ITW GSE equipment, immediately contact our Service Department
by mail, telephone, FAX, or E-Mail.
E-Mail: [email protected]
2) Troubleshooting
a) Description
The troubleshooting chart is designed to provide maintenance and repair personnel with a timesaving
guide for locating the source of trouble.
(1) Terminal points (reference applicable schematic and connection diagrams) provide easily
accessible and identifiable test points for checking circuits and electrical components.
(2) Test points are located throughout the circuitry in such a manner that input and output power may
be used for test purposes. Because of these test points and their location, a complete check of
circuitry may be completed very quickly. Therefore, “probable causes” and “remedies” are listed
in a step-by-step sequence which will insure power for testing in all instances where input or
output power may be used with proper safety practices, test equipment, and training experience.
(3) Printed circuit board output troubles should be pinpointed only to determine if the problem is a
board calibration problem or a PC board failure problem. Failure of PC board requires
replacement of the board. Field repair attempts are not recommended.
(4) Always check circuit fuses, circuit breakers and the position of switches first in troubleshooting.
The incorrect positioning of a switch may cause a condition that could be misinterpreted as a
fault.
(5) Electrical component reference designators (such as S1, K2, R10) may be used in the
troubleshooting chart (in parentheses after the item name) to help maintenance personnel identify
parts on the schematic diagrams.
WARNING
High voltage - electric shock and fire can kill! Exercise extreme care to avoid contact
with high voltage leads and components that could cause serious shock and injury if
touched when troubleshooting or operating the equipment. Stay clear of moving
parts. Locate equipment in a safe environment. Have proper safety equipment
available. Do not attempt operation or repair without adequate training.
4) Voltages of Interest
a) Across the secondary on all 3 phases - 66 VAC ± 10% *
* The ± 10% refers to the possibility of input voltage being out of balance or not at the nominal value.
c) Across the 115 VAC receptacle - 115 VAC (230 VAC on 50hz units) ± 10% *
A control board malfunction will probably result in one or more of the following symptoms:
loss of output voltage
inability to produce full load current
output voltage too high or too low
Section 2-2 shows the circuit board test points and provides standard voltages at those points.
NOTE: The circuit board potentiometers are preset at the factory and should not have to be reset in
the field. If a need arises that would indicate the need for field adjustments, please contact the
factory. The only exception is R109, which adjusts the 28 V output level. If necessary, use this control
to increase the output voltage slightly to compensate for the voltage drop in a long output cable.
SCR failure is not common. When they do fail, they generally do so either by shorting or by failing to
turn on.
Shorted SCRs will generally result in tripping the circuit breaker at the power source. However, a
shorted fly-back diode (on the filter choke input or across the output contactor coil) may also trip
the breaker. This is a severe malfunction.
If an SCR does not turn on, it may be because it is open or because the gate signal from the
control board is not reaching the SCR.
o If one SCR does not turn on, a very small change will occur at the output, which will be
difficult to notice. The ripple voltage at the output will increase.
o If two SCR’s do not turn on, the ripple current will increase and can cause other problems.
(consult troubleshooting procedure).
WARNING
Electric shock and fire can kill!
Do not touch energized parts. Always turn off utility power to the unit before
touching anything inside.
Do not leave the GPU on long enough to overheat or fail in the faulty condition.
(1) Turn off the unit and turn off the input power at the utility source.
(2) Disconnect the leads from the transformer to the heat sink assembly.
(3) Wrap each disconnected transformer lead with electrical tape. Mark each lead to identify it so it
can be reconnected to its proper location.
(4) Check the SCRs and fly-back diodes with the ohmmeter to located shorted devices.
(5) With the SCRs and fly-back diodes disconnected, apply power to the unit. Make sure that the
other components are not the cause of the tripped breaker.
(6) If no problems have been found, check for a device that only breaks down to a shorted condition
when voltage is applied by reconnecting one device at a time.
c) Troubleshooting Excessive Output Ripple
An open gate or an open SCR cannot be checked with a VOM. If an SCR is not firing, the AC ripple
current will increase across the filter capacitors, but that will not blow fuses.
Follow these steps to locate a bad SCR:
(1) Connect an oscilloscope across the unfiltered output:
Connect the probe of an oscilloscope to the heat
sink
Connect the isolated neutral of the oscilloscope to
the braid of the fly-back diode.
The output should appear as six evenly spaced pulses
of about the same height. If an SCR is not firing, one of
the pulses will be missing.
Note: if every third pulse is low or missing, check the
balance adjustments, R9 and R10, before attributing
the problem to faulty components.
(2) Disconnect the gate lead for one SCR from the
applicable suppressor board. If the lead disconnection
does not affect the output waveform, that is probably
the bad SCR.
(3) If that SCR was not the source of the problem,
reconnect the gate lead.
Figure 1 Gate Lead Connections
(4) Repeat for other SCRs, one at a time, until the
defective device is located.
If no Oscilloscope is available: Remove all six service fuses next to the A1 PC board. Keep in mind during
this test only one fuse at a time will be placed in the holder with the with fuses other removed.
CAUTION
The input power switch should be off whilst removing and installing
each fuse for this Test
Systematically put only one fuse in it’s holder at a time and turn the input power switch on and see if 28.5VDC
Is indicated on the Ground Power Unit Voltmeter. If voltage is present at the voltmeter then that particular
SCR(Diode) is good. Continue putting one Fuse at a time in it’s holder to check if the 28.5 VDC is present at
the voltmeter , do this until all six fuse holders (SCR) have been checked. If a particular fuse placed in its
holder (again no other fuses installed) does not indicate 28.5 VDC the SCR or that circuit has failed.
6) Troubleshooting Tables
1. Machine will not start a. The input power is turned OFF Turn the power ON at remote
at remote disconnect switch disconnect switch.
b. Blown fuse in remote disconnect Replace blown fuse. If fuse blows
switch frequently, determine and remedy
the cause.
c. Incorrect input power Check input power connections
connections at machine against appropriate connection
diagram in Chapter 5.
d. Incorrect power input (frequency Check that voltage and frequency
and voltage) of power input for this ground
power unit, according to the rating
on its nameplate.
e. Broken input cable Repair cable as necessary.
2. Line contactor fails to close a. Line contactor fuse F8 blown Replace fuse. Check for cause if
fuse blows frequently.
b. Mechanical obstruction on Remove obstruction.
contactor
c. Defective line contactor switch Replace line contactor switch.
d. Defective coil in line contactor Replace contactor if coil is open or
shorted.
e. Cable broken at line contactor Repair broken cable as necessary.
3. Line contactor chatters a. Input cables too small or too Use input cables of sufficient
long capability for proper operation of
the machine. Refer to Section 1-2,
Figure 1 for proper cable size to be
used.
b. Faulty contactor coil Check coil voltage. If correct,
replace contactor.
c. Low line voltage Check line voltage. Correct
problem as necessary.
4. Contactor operates and trips a. Wrong line voltage Check nameplate of machine for
power source circuit breaker or line voltage to be used. Then
blows fuses measure line voltage. If line voltage
is of improper value, correct this
condition as is necessary to
provide proper voltage input to the
machine.
b. Breaker incorrect size or type or Refer to Section 1-2, Figure 1 for
fuse input current requirements. Make
sure the breaker is appropriate for
a high inrush current – use a
breaker designed for motor starting
applications.
c. Links on voltage changeover Check appropriate voltage
board incorrectly connected changeover diagram in Chapter 5
for proper link positions. Make
correction as necessary.
d. SCR failure or shorted fly-back Refer to detail troubleshooting
diode instructions.
e. Short circuit in primary Remove short circuit.
connections
1. Unit delivers power but soon a. Power supply overloaded Reduce load, overload can be
shuts down (Thermal overload, carried only for a short time.
electronic overload or over- b. Duty cycle too high Do not operate continually at
voltage circuit trips) overload currents.
1. Operator gets shock when a. Case of machine not grounded Ground machine case to an earth-
machine case is touched type ground if utility ground is
already connected. Connect the
normal safety ground and recheck
if “utility” ground had not been
connected.
1. Abnormal current fluctuation, a. Loose cable connections at Check for overheated connections
voltage nearly constant output and tighten.
No Voltage Output
1. Unit on, but no output voltage a. Protective circuit tripped Determine and correct cause of
trip. Then reset and restart unit.
b. Component failure in protective Find the defective component and
circuit replace it.
c. Control circuit board failure Check control board per Section 2-
2 and replace it if faulty.
1. Output contactor will not close. a. Defective output switch (S2) With the unit turned off, place a
jumper between terminals 2 and 4 on
S2. Turn S1 on. If output contactor
closes, S2 is defective. Replace.
b. Defective input contactor With the unit turned off, place a
auxiliary contacts (K1) jumper between terminals NO 1 and
COM 3 on input contactor. Turn S1
on, and place S2 in Close position.
If output contactor closes, K1 is
defective. Replace.
c. Defective output voltage select With the unit turned off, place a
switch (S103) (if applicable) jumper between terminals 4 and 5 on
S103. Turn S1 on, and place S2 in
Close position. If Output contactor
closes, S103 is defective. Replace.
IMPORTANT
Before attempting to make tests and adjustments on the GPU, READ THIS ENTIRE
SECTION to become familiar with the proper procedures.
1) General
This section describes the test points, test values, and adjustment locations for testing and adjusting the
printed circuit board that controls the GPU. The control board is mounted on a hinged panel. To access
the board for measurements and adjustments, open the panel so that the board is accessible from the
front of the GPU and you do not have to work next to hazardous voltages.
Use the Test Procedure (Part 3 of this section) to determine if the circuit board is operating properly. ITW
GSE recommends calibration of the PC board at the factory, but the calibration procedure is included in
this section (Part 4) in case field calibration is necessary. Faulty control boards should be returned to the
manufacturer for repair.
WARNING
Electric shock and arcs can kill or injure! Use caution to inspect or test the printed
circuit control board while the equipment is running. The voltages on the printed
circuit board are safe; however, removing the top panel exposes people to
dangerous voltages. When working with the circuit board, rotate the panel out to
move the board away from internal parts.
3) Test Procedure
Follow the table steps in this section to verify that the PC board is functioning properly. If the voltage
readings to the PC board common are not within specification, attempt to correct the reading by adjusting
the applicable control. Be certain the operating conditions are exactly as stated in the table.
If the board does not adjust, check the leads, fuses (F2-F7), and connectors. If no external problems are
found, the PC control board is faulty. Replace it with a known good board.
After replacing the board, recheck the voltages. In some cases, minor adjustments may be required for
optimum calibration. If the replacement board shows the same magnitude of error and lack of adjustment
control, it is possible that the control board is not at fault. The voltages in the following table are all
referenced to pc board common, which is Test Point 3 (TP3) and Test Point 15 (TP15). Connect the
negative voltmeter lead to either of those test points.
Also, if your GPU is set up for bridge interlock and remote connection option, you will need to add
switches:
Connect normally open "Start" switch between TB101-1 and TB101-2.
Connect normally closed "Stop" switch between TB101-2 and TB101-3.
Calibration Procedure
(3) Turn the power switch on. The amber “Power On” light should be on.
(5) Close the output contactor. Make sure the green “Contactor Closed” light turns on.
2) Maintenance Schedule
WARNING
High voltage may be present inside the GPU cabinet, even when the unit is off.
Exercise extreme caution or FATAL SHOCK may result.
WARNING HIGH VOLTAGE - electric shock can kill! Be certain the input power source is turned
off before opening the cabinet. Stop operation immediately if a possible dangerous
fault is discovered. The front panel input contactor switch does not remove input
power from all components. Be sure capacitors are discharged before you touch.
b) Observe the front panel voltmeter and make sure the voltage is zero. If the voltage is not zero, the
capacitors still hold a charge, indicating a problem with the connection to the preload resistors.
c) Observe general condition of power-input cables and equipment output cables. Inspect for cuts and
abrasions in the insulation that could cause a short circuit. Visually inspect the output cable plug
connector for physical damage and evidence of overheating.
d) Remove the top cover.
5) Internal Inspection
a) Using compressed air or a soft brush, clean any dirt and debris from the interior.
b) Inspect terminal blocks for evidence of overheating due to loose electrical connections.
c) Inspect electrical and mechanical connections for tightness.
d) Remove the front panel screw that holds the circuit board panel. Swing the circuit board panel out to
the side.
e) Inspect the circuit board for evidence of overheating, such as burned components.
f) Inspect the hinge for the circuit board panel. If this hinge sticks or is difficult to operate, spray the
hinge with a silicone spray lubricant.
g) Inspect all wiring, leads, and cables. Inspect for cuts, abrasions, and signs of deterioration and
overheating. Inspect the leads for broken strands and terminals.
h) Inspect the output contactor. If the contacts are badly burned, the contactor should be replaced as
soon as possible. Slightly pitted and burned contacts can be cleaned up with a commercial contact
cleaner and very fine-grained emery cloth or equivalent.
i) Turn the fan blade by hand to make sure that it turns freely.
j) If required, lubricate the fan (refer to the next section for the lubrication schedule).
k) When finished with inspections:
Return the circuit board panel to its closed position and secure with the screw.
Replace the top cover.
Turn on power at the source and check for normal operation.
6) Lubrication
No lubrication is required, except for the fan motor. The fan motor incorporates a sleeve bearing, and
therefore requires periodic lubrication.
a) Lubrication Schedule
The following table shows the fan motor manufacturer’s recommendations for lubricating the motor.
c) Quantity
Use 10 – 15 drops per end (approximately 1.0 cc or 1/8 teaspoon). Do not over oil.
d) Oil Locations
The figure below shows a tube extending upward from the rear bearing. The front bearing has a
similar tube. Use these tubes to oil the bearings.
7) Inspection Records
Since the fan lubrication is so infrequently, you should keep track of the lubrications using the chart below
or some similar record.
When ordering parts from your ITW GSE Distributor, be sure to include all pertinent information from the
unit’s identification plate: Specification No., Model No., and unit rating.
WARNING
High voltages may be present inside the cabinet, even when the unit is off. Exercise
extreme caution or FATAL SHOCK may result.
a) Turn off the input power at the source. Make sure that the power cannot be inadvertently turned back
on.
b) Remove the top cover.
c) Disconnect the three AC input leads at the terminals on the input contactor and the grounding wire at
the grounding lug.
d) Loosen the cable clamp on the rear of the GPU and remove the input cable from the clamp.
e) Disconnect the output cable from the output contactor (+) and the ammeter shunt (-).
f) Loosen the cable clamp at the base and remove the output cable from the GPU.
g) If the unit is a bridge mount unit, also disconnect and remove the remote control cables.
h) If the unit is bridge mount or fixed mount, attach a lifting hoist or forklift to the bottom of the GPU and
remove the mounting screws or bolts that attach the GPU to its mounting.
i) Carefully remove the GPU.
j) Move the GPU to a clear working area where it can be placed on a solid supporting structure.
k) Re-install the GPU in the reverse order of removal. See Section 1-2 for additional information on
installing the GPU.
WARNING
To avoid the danger of electric shock, always make sure that the input power is turned
off at the source and cannot be inadvertently turned back on before working inside the
GPU.
a) Lights
The light bulbs are accessible from the front by unscrewing the lens.
b) Circuit Board
Chapter 4-3, Figure 2 gives the location and part number of the circuit board. To replace the circuit
board, unplug the connectors and remove the six screws.
c) Fuses
The following table provides the locations and functions of the fuses. If a fuse has blown, check the
related circuitry. Always replace the fuses with similar fuses having the same type and rating.
d) Thermostat Switches
December 15, 2014 Chapter 3-1
Page 2
OM-2244 / Operation and Maintenance Manual
DCS-600/ Series 500082 / Solid State Transformer-Rectifiers
Two thermostat switches mount to the top of the heat sink assembly. Refer to Chapter 4-3, Figure 7.
The switch on the left side controls the fan. The switch on the right side shuts down the GPU when an
overload occurs.
The fan thermostat is normally open. If this switch fails in the open position, the fan will never turn on
and the unit will eventually shut off with an overload indication. If the fan thermostat fails in the closed
position, the fan will run continuously, even when the unit is cold. This switch turns on when the
temperature reaches 100° ± 8° F and turns off when the temperature falls back down to 80° ± 5° F.
The overload thermostat is normally closed. If this switch fails in the open position, the GPU will not
produce any output voltage. If this switch fails in the closed position, the GPU will not shut down if the
heat sink gets too hot. This switch opens when the temperature reaches 190° ± 5° F and closes when
the temperature falls back down to 172° ± 8° F.
Both of these switches can be tested using an ohmmeter and a heat gun. To replace a thermostat,
unplug the wires and then remove the two screws that hold it. Reconnect the wires to the new
thermostat.
e) Fly-back Diode
The fly-back diode, CR7, is located on the left side of the heat sink assembly near the base. Failure is
not common, but if fails in a shorted condition, it can cause high input current. Refer to Chapter 2-1
for troubleshooting information.
Chapter 4-3, Figure 7 gives the part number for the diode.
(1) Buff the heat sink in the area where the diode attaches to remove any oxidation.
(2) Smear a thin film of Burndy Penetrox “A” (or similar oxide-inhibiting electrical joint compound) in
the area where the diode attaches to the heat sink.
(3) When replacing the diode, torque the nut to 4.2 to 5.2 ft-lb. (5.7 to 7.05 N-m).
f) SCR Diodes
The six SCR diodes mount to the heat sink. If an SCR fails to conduct, it can cause excessive ripple
in the output. If an SCR fails by shorting, the unit can draw excessive input current. SCR replacement
is somewhat complicated, so be sure that a failed SCR is the cause of the problem before replacing.
Refer to Chapter 2-1 for troubleshooting information.
If you plan to replace an SCR, you will need a 903878 Force Indicator Gauge. This gauge, shown in
Figure 1, measures the deflection of the flat spring on top of the SCR as the screws are tightened.
The gauge consists of two metal plates that are free to rotate about a common point where they are
fastened together.
When this gauge is placed on a flat surface so that it makes three-point contact, the sheet metal
plates rotate so that the left edge of the rear plate aligns with the right edge of the front piece at
the calibration notch.
When this gauge is placed on a properly-adjusted SCR spring, the left edge of the rear plate
aligns with the right edge of the front plate at the top notch (marked VE3000/VE2500).
Chapter 4-3, Figure 7 gives the part number for the diode.
(1) Disconnect and remove the failed SCR diode noting how the pieces are assembled. Figure 2
shows a cross section.
(2) Buff the heat sink in the area where the diode attaches to remove any oxidation.
(3) Smear a thin film of Burndy Penetrox “A” (or similar oxide-inhibiting electrical joint compound) in
the area where the diode attaches to the heat sink.
(4) Tighten the nuts evenly until they are finger tight.
(5) Tighten each screw in 1/4 turn increments using the correct size hex key.
(6) Place the Force Indicator Gauge firmly against the top spring as shown in Figure 3. Be sure both
ends and the center are in firm contact with the spring.
(7) Tighten the screws in 1/4 turn increments until the gauge shows correct alignment between the
left edge of the rear gauge plate and the right edge of the top notch (VE3000/VE2500) on the
front gauge plate.
(8) If you have tightened the screws too much, loosen both nuts and start over. Never adjust the
force by backing off the nuts. Friction will always produce a false reading.
2) Purpose
The purpose of this list is to provide parts identification and descriptive information to maintenance and
provisioning personnel for use in provisioning, requisitioning, purchasing, storing, and issuing of spare parts.
3) Arrangement
Chapter 4 is arranged as follows:
Section 1 - Introduction
Section 2 - Manufacturer’s Codes
Section 3 - Illustrated Parts List
The parts list contains a breakdown of the equipment into assemblies, subassemblies, and detail
parts. All parts of the equipment are listed except:
(1) Standard hardware items (attaching parts) such as nuts, screws, washers, etc., which are
available commercially.
(2) Bulk items such as wire, cable, sleeving, tubing, etc., which are also commercially available.
(3) Permanently attached parts, which lose their identity by being welded, soldered, riveted, etc., to
other parts, weldments, or assemblies.
This form is divided into six columns. Beginning at the left side of the form and proceeding to the
right, columns are identified as follows:
Numerical Index
6 Explanation of Numerical Index
The purpose of this index is to assist the user in finding the illustration and description of a part when the
part number is known. Part numbers are arranged in alphanumerical sequence.
FIGURE – ITEM NO. ITW GSE PART NO. FIGURE – ITEM NO. ITW GSE PART NO.
FIGURE – ITEM NO. ITW GSE PART NO. FIGURE – ITEM NO. ITW GSE PART NO.
FIGURE – ITEM NO. ITW GSE PART NO. FIGURE – ITEM NO. ITW GSE PART NO.
4-6 83B1101
2- W11166-009
6- W11166-011
3-10 W9760-066
Code Vendor’s Name and Address Code Vendor’s Name and Address
Code Vendor’s Name and Address Code Vendor’s Name and Address
Code Vendor’s Name and Address Code Vendor’s Name and Address
Code Vendor’s Name and Address Code Vendor’s Name and Address
NOTE: An item which does not reflect an index number is an assembly which is not illustrated in its
assembled state, or it is similar (right-hand, left-hand, top, etc.) to an item which is illustrated.
7 3 4
2 6
UNITS
FIGURE ITW GSE
NOMENCLATURE EFF PER
ITEM NO. PART NO.
ASSY.
UNITS
FIGURE ITW GSE
NOMENCLATURE EFF PER
ITEM NO. PART NO.
ASSY.
2- 1 288271 Panel, PC Board 1
2 180294B Board, PC, Control, Ay. 1
404915-001 …Spacer, Pc Board 6
3 180480 Choke Assembly 1
4 180065 Shunt, 2000 Amp, 50 mV (for ammeter) 1
5 Ref. Voltage Changeover Board (see note) Ref.
6 405129-001 Block, Fuse 1
W11166-009 …Fuse, Fast Blow, AGC 1 A, 250 V 6
83A1105 …Label, Fuse 1
7 287637 Motor, Fan 1
8 288305-002 Rectifier, Output, SCR Assembly (See Figure 7) 1
9 406991 Blade, Fan 1
10 201016 Shroud, Fan 1
288322 …Label, Warning, Fan 1
400234-003 …Tag, Instructions 2
201015 …Bracket, Mounting, Fan Shroud 2
11 288303-001 Block, Fuse 1
400647-005 …Fuse, 5 A 1
288363 …Label, Precautionary, Fan Fuse 1
* 12 408567 Relay, 24 VAC, 4PDT (shown on Figure 6) J,K,L 2
* 408352 …Socket, Relay J,K,L 2
* 408585 …Spring, Relay J,K,L 2
* 288366 …Chart, Wire, Bridge Mount Units J,K,L 2
UNITS
FIGURE ITW GSE
NOMENCLATURE EFF PER
ITEM NO. PART NO.
ASSY.
3- 1 Panel, Front, GPU, Ay. (See Figure 5) Ref.
2 405278-007 Capacitor, ALS, 115000 MF, 40 VDC A,C,F,J, 3
(V56289, # 36DX772F200DF2A)
Capacitor, ALS, 115000 MF, 40 VDC B,E,G,H,K 4
* 350488-094 …Insulator, Mylar, .014, 2” Wide A,C,F,J, 3
* …Insulator, Mylar, .014, 2” Wide B,E,G,H,K 4
* 361052-009 …Clamp, Mounting, Capacitor A,C,F,J, 3
* 361052-009 …Clamp, Mounting, Capacitor B,E,G,H,K 4
* 788732 Cover, Capacitors, CE E,H 1
3 286810-001 Output Contactor, 28.5 VDC 1
4 589561 Transformer, Power A,F,J 1
180358 Transformer, Power B,E,G,H,K 1
181565 Transformer, Power C, 1
5 Panel, Interior Assembly (See Figure 6) Ref.
6 280023 Feedback Shunt (See Figure 7) Ref.
7 487050-005 Resistor, Pre-load, Assembly 1
8 489603 Panel, Rear 1
403091-008 …Plug, Hole, Plastic 1
* 9 488819 Cable, 2/0 (#202) 1
* 10 W9760-066 Cable, # 6 (#201) 1
* 11 288731 Cover, Contactor & Transformer E,H 1
* 12 288732 Cover, Capacitors, CE E,H 1
1
8
7
3
4 2 6
UNITS
FIGURE ITW GSE
NOMENCLATURE EFF PER
ITEM NO. PART NO.
ASSY.
4- 288321-001 Base, Ay. A-E 1
288321-002 Base, Ay. F-K 1
1 288262 Base, Mounting, GPU 1
th
2 288282 Support, Caster, 5 Wheel A-E 1
th
288349 …Spacer, 5 Wheel A-E 1
3 288283 Catch, Latch A-E 1
4 288297-001 Kit, Caster A-E 1
th
5 288353 Brake, 5 Wheel A-E 1
6 83B1101 Tire, Symmetrical, Ball Bearing, 10° A-E 2
7 288251 Axle, Mounting, Wheels A-E 1
486143-002 …Spacer, Black, Pipe A-E 2
8 283322 Bracket, Output, Cable 2
489971 …Spacer, Output Cable 4
1
4
7 8 10
9 11
14
G P U 600
UNITS
FIGURE ITW GSE
NOMENCLATURE EFF PER
ITEM NO. PART NO.
ASSY.
5- 288307-003 Panel, Front, GPU, Assembly A,C,F,J,L 1
288307-004 Panel, Front, GPU, Assembly B,G,K 1
288307-006 Panel, Front, GPU, Assembly E,H 1
288307-008 Panel, Front, GPU, Assembly 1
Notes:
A,C,F,J are 60 Hz.
B,E,G,H,K are 50 Hz.
Potentiometer (item 3) is included with wire harness (item 19)
7 2 6
2 2
11
8 8
9
10 4,5 1
3,12
UNITS
FIGURE ITW GSE PART
NOMENCLATURE EFF PER
ITEM NO. NO.
ASSY.
7- 288305-002 Rectifier, Output, SCR Assembly GPU-600 Ref.
Contact ITW GSE if copies of these drawings are not with this manual. Refer to Appendix A for specific
information on GPU-600 Solid State Transformer-Rectifier optional equipment.
The following is a list of options/features available for the 500082, GPU-600 Solid State Transformer-Rectifier.
This chart contains the description, part number, and document number of the option/feature. There is also a
column to identify which option/feature is contained in this Appendix.
Option/Features Available
1) Exposure to:
b) Environments where the accumulation of lint or excessive dirt will interfere with normal ventilation
d) Nuclear radiation
f) Damp or very dry locations, radiant heat, vermin infestation, or atmospheres conducive to fungus
growth
g) Abnormal shock, vibration or mechanical loading from external sources during equipment operation
2) Operation at:
e) Unbalanced voltages
4) Operation with: