COMM DRG EE 0004 - DD0 Typical PV String Configuration
COMM DRG EE 0004 - DD0 Typical PV String Configuration
EARTH CABLE
CABLE TIE
1 7 2
- - -
PV STRING 3 PV STRING 4 NOTES
1. THIS DRAWING INDICATES THE TYPICAL PV STRING INTERCONNECTION IMPLEMENTED ACROSS THE GREAT NOLIGWA, NOLIGWA GOLD AND MOAB
KHOTSONG PV PLANT.
2. THIS DRAWING IS A CONCEPT AND NOT FOR CONSTRUCTION. FINAL STRING INTERCONNECTION DESIGNS WILL BE SUPPLIED BY STI NORLAND.
4. AT THE LAST STRUCTURAL SUPPORT OF EACH PV TABLE, THE PV STRING CABLES WILL ENTER AN UNDERGROUND CONDUIT AND BE ROUTED
TOWARDS THE STRING INVERTER.
5. SUITABLE CONNECTORS SHALL BE USED FOR ALL PV STRING OR PV MODULE INTERCONNECTIONS TO MATCH THE CONNECTORS ON THE PV MODULE
6
5 3 4 LEADS.
-
- - A1 -
6. SUITABLE CABLE TIES SHALL BE USED TO TIE THE PV STRING CABLES TO THE PV MODULE LEADS AND TO SECURE THE CABLES TO THE PV TABLE
- STRUCTURE OR TORQUE TUBE WHERE NEEDED. CABLE CLIPS ATTACHED TO THE PV MODULE SHALL BE USED WHERE NEEDED TO PREVENT CABLES
-
FROM HANGING LOOSELY.
7. ALL CABLES SHALL BE ROUTED AS CLOSELY TOGETHER AS REASONABLY POSSIBLE TO REDUCE THE CABLE AREA LOOPS WITHIN A PV STRING.
PV TABLE WITH 4 PV STRINGS
8. A SUITABLE POLYPROPYLENE FLEXIBLE CONDUIT OR SOLID BLACK UV STABILISED PVC CONDUIT SHALL BE USED AS MECHANICAL PROTECTION FOR
THE PV STRING CABLES CROSSING THE CENTRAL TRACKER MOTOR GAP WITHIN A PV TABLE. ALL CONDUITS ARE TO BE MEDIUM DUTY AS A MINIMUM.
9. CONDUITS TRANSITIONING FROM ABOVE GROUND TO BELOW GROUND AT THE END OF THE PV TABLE SHALL BE A FLEXIBLE POLYPROPYLENE TYPE
CONDUIT AND SEALED FOR VERMIN PROTECTION.
10. STRING CABLES TO BE ROUTED OVER U-BRACKET WHERE BEARINGS ARE LOCATED.
REFERENCES
MOAB KHOTSONG
PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 PV STRING 1 1. 1002373-MOAB-DRG-JJ-0001 PV FIELD GENERAL ARRANGEMENT
MODULE 01 MODULE 02 MODULE 03 MODULE 04 MODULE 05 MODULE 06 MODULE 07 MODULE 08 MODULE 09 MODULE 10 MODULE 11 MODULE 12 MODULE 13 MODULE 14 MODULE 15 MODULE 16 MODULE 17 MODULE18 MODULE 19 MODULE 20 MODULE 21 MODULE 22 MODULE 23 MODULE 24 MODULE 25 MODULE 26 MODULE 27 2. 1002373-MOAB-DRG-EE-0003 STRING INVERTER GROUPING
3. 1002373-MOAB-DRG-EE-0005 DC & LV AC CABLE ROUTES
Filename: C:\USERS\AYESHA.JACOBS\ZUTARI\1002373 - PRELIMINARY DESIGN FOR HARMONY MINE 5X PV SITES - DOCUMENTS\05 DELIVER\DD\MOAB\506 DRAWINGS\EE\1002373-MOAB-DRG-EE-0004_A - TYPICAL PV STRING CONFIGURATION.DWG
GREAT NOLIGWA
8. 1002373-GRNO-DRG-JJ-0001 PV FIELD GENERAL ARRANGEMENT
9. 1002373-GRNO-DRG-EE-0003 STRING INVERTER GROUPING
3. 1002373-GRNO-DRG-EE-0005 DC & LV AC CABLE ROUTES
4. 1002373-GRNO-DRG-EE-0006 PV FIELD CABLE TRENCH LAYOUT
5. 1002373-GRNO-DRG-EE-0013 MV AC CABLE ROUTES
6. 1002373-GRNO-DRG-EE-0014 MV AC CABLE TRENCH CROSS SECTION
7. 1002373-GRNO-DRG-EE-0015 PV FIELD EARTHING GENERAL LAYOUT
NOLIGWA GOLD
8. 1002373-NOGD-DRG-JJ-0001 PV FIELD GENERAL ARRANGEMENT
9. 1002373-NOGD-DRG-EE-0003 STRING INVERTER GROUPING
DETAIL 1 [PLAN VIEW]: 3. 1002373-NOGD-DRG-EE-0005 DC & LV AC CABLE ROUTES
4. 1002373-NOGD-DRG-EE-0006 PV FIELD CABLE TRENCH LAYOUT
PV STRING 1 MOUNTED ON 4-STRING PV TABLE 5. 1002373-NOGD-DRG-EE-0013 MV AC CABLE ROUTES
6. 1002373-NOGD-DRG-EE-0014 MV AC CABLE TRENCH CROSS SECTION
7. 1002373-NOGD-DRG-EE-0015 PV FIELD EARTHING GENERAL LAYOUT
ALL SITES
8. 1002373-COMM-DRG-EE-0026 EARTHING & LP EQUIPMENT AND STRUCTURE DRAWINGS
9. 1002373-COMM-DRG-EE-0007 PV FIELD CABLE TRENCH CROSS SECTIONS
PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2 PV STRING 2
MODULE 01 MODULE 02 MODULE 03 MODULE 04 MODULE 05 MODULE 06 MODULE 07 MODULE 08 MODULE 09 MODULE 10 MODULE 11 MODULE 12 MODULE 13 MODULE 14 MODULE 15 MODULE 16 MODULE 17 MODULE18 MODULE 19 MODULE 20 MODULE 21 MODULE 22 MODULE 23 MODULE 24 MODULE 25 MODULE 26 MODULE 27
PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3 PV STRING 3
MODULE 01 MODULE 02 MODULE 03 MODULE 04 MODULE 05 MODULE 06 MODULE 07 MODULE 08 MODULE 09 MODULE 10 MODULE 11 MODULE 12 MODULE 13 MODULE 14 MODULE 15 MODULE 16 MODULE 17 MODULE18 MODULE 19 MODULE 20 MODULE 21 MODULE 22 MODULE 23 MODULE 24 MODULE 25 MODULE 26 MODULE 27
Office: ZACPT
A2
-
-
Plot Date: 5/4/2024 2:46:49 pm
PV STRING BOUNDARY
CABLE TIE
NOTES
1. THIS DRAWING INDICATES THE TYPICAL PV STRING INTERCONNECTION IMPLEMENTED ACROSS THE GREAT NOLIGWA, NOLIGWA GOLD AND MOAB
KHOTSONG PV PLANT.
2. THIS DRAWING IS A CONCEPT AND NOT FOR CONSTRUCTION. FINAL STRING INTERCONNECTION DESIGNS WILL BE SUPPLIED BY STI NORLAND.
5. SUITABLE CONNECTORS SHALL BE USED FOR ALL PV STRING OR PV MODULE INTERCONNECTIONS TO MATCH THE CONNECTORS ON THE PV MODULE
LEADS.
6. SUITABLE CABLE TIES SHALL BE USED TO TIE THE PV STRING CABLES TO THE PV MODULE LEADS AND TO SECURE THE CABLES TO THE PV TABLE
STRUCTURE OR TORQUE TUBE WHERE NEEDED. CABLE CLIPS ATTACHED TO THE PV MODULE SHALL BE USED WHERE NEEDED TO PREVENT CABLES
FROM HANGING LOOSELY.
7. ALL CABLES SHALL BE ROUTED AS CLOSELY TOGETHER AS REASONABLY POSSIBLE TO REDUCE THE CABLE AREA LOOPS WITHIN A PV STRING.
8. A SUITABLE POLYPROPYLENE FLEXIBLE CONDUIT OR SOLID BLACK UV STABILISED PVC CONDUIT SHALL BE USED AS MECHANICAL PROTECTION FOR
THE PV STRING CABLES CROSSING THE CENTRAL TRACKER MOTOR GAP WITHIN A PV TABLE. ALL CONDUITS ARE TO BE MEDIUM DUTY AS A MINIMUM.
9. CONDUITS TRANSITIONING FROM ABOVE GROUND TO BELOW GROUND AT THE END OF THE PV TABLE SHALL BE A FLEXIBLE POLYPROPYLENE TYPE
CONDUIT AND SEALED FOR VERMIN PROTECTION.
10. STRING CABLES TO BE ROUTED OVER U-BRACKET WHERE BEARINGS ARE LOCATED.
DRIVE ARMS
11. ALL CONDUITS TO BE SECURED WITH A MINIMUM OF 2 CABLE TIES.
REFERENCES
MOTOR
6 mm2 PV STRING CABLES
4 PV STRING CABLES TO BE ROUTED ALONGSIDE TRACKER MOAB KHOTSONG
PV MODULE LEADS DAISY CHAIN CONNECTION 1. 1002373-MOAB-DRG-JJ-0001 PV FIELD GENERAL ARRANGEMENT
ROUTED TO UNDERGROUND CONDUIT TORQUE TUBE OF PV MODULE LEADS 2. 1002373-MOAB-DRG-EE-0003 STRING INVERTER GROUPING
3. 1002373-MOAB-DRG-EE-0005 DC & LV AC CABLE ROUTES
Filename: C:\USERS\AYESHA.JACOBS\ZUTARI\1002373 - PRELIMINARY DESIGN FOR HARMONY MINE 5X PV SITES - DOCUMENTS\05 DELIVER\DD\MOAB\506 DRAWINGS\EE\1002373-MOAB-DRG-EE-0004_A - TYPICAL PV STRING CONFIGURATION.DWG
GREAT NOLIGWA
8. 1002373-GRNO-DRG-JJ-0001 PV FIELD GENERAL ARRANGEMENT
CABLE TIE SECURING PV MODULE 9. 1002373-GRNO-DRG-EE-0003 STRING INVERTER GROUPING
SEE NOTE 10
LEAD AND STRING CABLES 3. 1002373-GRNO-DRG-EE-0005 DC & LV AC CABLE ROUTES
UP TO 2 CABLES ROUTED
CABLE TIE SECURING STRING 4. 1002373-GRNO-DRG-EE-0006 PV FIELD CABLE TRENCH LAYOUT
THROUGH CONDUIT 5. 1002373-GRNO-DRG-EE-0013 MV AC CABLE ROUTES
CABLES TO U-BRACKET
6. 1002373-GRNO-DRG-EE-0014 MV AC CABLE TRENCH CROSS SECTION
FLEXIBLE POLYPROPYLENE OR
7. 1002373-GRNO-DRG-EE-0015 PV FIELD EARTHING GENERAL LAYOUT
CABLE TIES SECURING CONDUIT SOLID PVC CONDUIT
TO TRACKER PV PANEL NOLIGWA GOLD
DEDICATED PV PANEL 8. 1002373-NOGD-DRG-JJ-0001 PV FIELD GENERAL ARRANGEMENT
9. 1002373-NOGD-DRG-EE-0003 STRING INVERTER GROUPING
3. 1002373-NOGD-DRG-EE-0005 DC & LV AC CABLE ROUTES
4. 1002373-NOGD-DRG-EE-0006 PV FIELD CABLE TRENCH LAYOUT
5. 1002373-NOGD-DRG-EE-0013 MV AC CABLE ROUTES
6. 1002373-NOGD-DRG-EE-0014 MV AC CABLE TRENCH CROSS SECTION
7. 1002373-NOGD-DRG-EE-0015 PV FIELD EARTHING GENERAL LAYOUT
ALL SITES
8. 1002373-COMM-DRG-EE-0026 EARTHING & LP EQUIPMENT AND STRUCTURE DRAWINGS
9. 1002373-COMM-DRG-EE-0007 PV FIELD CABLE TRENCH CROSS SECTIONS
CABLE TIES
INSTALLED
AROUND PILE