One、Product Specifcation Three、(V-A) Property test
Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0
No.: 233130859 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.3 199.5 199.9 205.1 207.8
Rated frequency: 50 Hz Four、Error test
Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.20 +7.9
polar Minus lndoor 1S1.1S2 5% -0.14 +5.8
5VA
600/1 A 20% -0.07 +4.5
Two、Test Result COSΦ= 0.8
100% -0.06 +3.4
0.2S Class
1.Measuring of insulation resistance 120% -0.03 +2.7
Secondary winding to ground≥ 1000 MΩ 3.75 VA
100% -0.02 +2.9
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.18 +8.4
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /
Test date 2023-08-03
One、Product Specifcation Three、(V-A) Property test
Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0
No.: 233130860 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.4 199.5 199.9 205.0 207.9
Rated frequency: 50 Hz Four、Error test
Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.18 +7.4
polar Minus lndoor 1S1.1S2 5% -0.14 +5.6
5VA
600/1 A 20% -0.09 +4.1
Two、Test Result COSΦ= 0.8
100% -0.05 +3.4
0.2S Class
1.Measuring of insulation resistance 120% -0.03 +2.0
Secondary winding to ground≥ 1000 MΩ 3.75 VA
100% -0.02 +2.5
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.18 +6.0
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /
Test date 2023-08-03
One、Product Specifcation Three、(V-A) Property test
Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0
No.: 233130861 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.4 199.5 200.1 204.9 208.2
Rated frequency: 50 Hz Four、Error test
Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.19 +8.5
polar Minus lndoor 1S1.1S2 5% -0.13 +5.4
5VA
600/1 A 20% -0.09 +4.1
Two、Test Result COSΦ= 0.8
100% -0.05 +3.1
0.2S Class
1.Measuring of insulation resistance 120% -0.02 +2.6
Secondary winding to ground≥ 1000 MΩ 3.75 VA
100% -0.03 +2.4
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.18 +9.0
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /
Test date 2023-08-03
One、Product Specifcation Three、(V-A) Property test
Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0
No.: 233130862 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.3 199.4 199.9 204.8 208.0
Rated frequency: 50 Hz Four、Error test
Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.18 +7.8
polar Minus lndoor 1S1.1S2 5% -0.14 +5.3
5VA
600/1 A 20% -0.08 +4.4
Two、Test Result COSΦ= 0.8
100% -0.05 +3.8
0.2S Class
1.Measuring of insulation resistance 120% -0.02 +2.5
Secondary winding to ground≥ 1000 MΩ 3.75 VA
100% -0.02 +2.7
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.19 +9.1
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /
Test date 2023-08-03
One、Product Specifcation Three、(V-A) Property test
Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0
No.: 233130863 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.3 199.6 200.1 204.9 207.8
Rated frequency: 50 Hz Four、Error test
Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.18 +9.0
polar Minus lndoor 1S1.1S2 5% -0.13 +5.4
5VA
600/1 A 20% -0.08 +4.7
Two、Test Result COSΦ= 0.8
100% -0.05 +3.9
0.2S Class
1.Measuring of insulation resistance 120% -0.02 +3.0
Secondary winding to ground≥ 1000 MΩ 3.75 VA
100% -0.03 +3.0
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.20 +6.1
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /
Test date 2023-08-03
One、Product Specifcation Three、(V-A) Property test
Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0
No.: 233130864 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.3 199.6 200.0 204.9 208.1
Rated frequency: 50 Hz Four、Error test
Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.19 +8.3
polar Minus lndoor 1S1.1S2 5% -0.14 +5.3
5VA
600/1 A 20% -0.07 +4.7
Two、Test Result COSΦ= 0.8
100% -0.04 +3.3
0.2S Class
1.Measuring of insulation resistance 120% -0.02 +2.5
Secondary winding to ground≥ 1000 MΩ 3.75 VA
100% -0.02 +2.5
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.16 +7.2
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /
Test date 2023-08-03