CT Test Report 103012747 ASG2806A 233130859

The document provides specifications and test results for the UP-ZC-10 product, including details on rated current, frequency, and accuracy classes. It outlines various property tests and error tests conducted on multiple units, with results indicating insulation resistance and voltage withstand capabilities. The test date for all units is noted as August 3, 2023.

Uploaded by

Mario T
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views6 pages

CT Test Report 103012747 ASG2806A 233130859

The document provides specifications and test results for the UP-ZC-10 product, including details on rated current, frequency, and accuracy classes. It outlines various property tests and error tests conducted on multiple units, with results indicating insulation resistance and voltage withstand capabilities. The test date for all units is noted as August 3, 2023.

Uploaded by

Mario T
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

One、Product Specifcation Three、(V-A) Property test

Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0


No.: 233130859 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.3 199.5 199.9 205.1 207.8

Rated frequency: 50 Hz Four、Error test


Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.20 +7.9

polar Minus lndoor 1S1.1S2 5% -0.14 +5.8


5VA
600/1 A 20% -0.07 +4.5
Two、Test Result COSΦ= 0.8
100% -0.06 +3.4
0.2S Class
1.Measuring of insulation resistance 120% -0.03 +2.7

Secondary winding to ground≥ 1000 MΩ 3.75 VA


100% -0.02 +2.9
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.18 +8.4
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /

Test date 2023-08-03


One、Product Specifcation Three、(V-A) Property test
Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0
No.: 233130860 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.4 199.5 199.9 205.0 207.9

Rated frequency: 50 Hz Four、Error test


Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.18 +7.4

polar Minus lndoor 1S1.1S2 5% -0.14 +5.6


5VA
600/1 A 20% -0.09 +4.1
Two、Test Result COSΦ= 0.8
100% -0.05 +3.4
0.2S Class
1.Measuring of insulation resistance 120% -0.03 +2.0

Secondary winding to ground≥ 1000 MΩ 3.75 VA


100% -0.02 +2.5
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.18 +6.0
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /

Test date 2023-08-03


One、Product Specifcation Three、(V-A) Property test
Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0
No.: 233130861 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.4 199.5 200.1 204.9 208.2

Rated frequency: 50 Hz Four、Error test


Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.19 +8.5

polar Minus lndoor 1S1.1S2 5% -0.13 +5.4


5VA
600/1 A 20% -0.09 +4.1
Two、Test Result COSΦ= 0.8
100% -0.05 +3.1
0.2S Class
1.Measuring of insulation resistance 120% -0.02 +2.6

Secondary winding to ground≥ 1000 MΩ 3.75 VA


100% -0.03 +2.4
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.18 +9.0
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /

Test date 2023-08-03


One、Product Specifcation Three、(V-A) Property test
Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0
No.: 233130862 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.3 199.4 199.9 204.8 208.0

Rated frequency: 50 Hz Four、Error test


Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.18 +7.8

polar Minus lndoor 1S1.1S2 5% -0.14 +5.3


5VA
600/1 A 20% -0.08 +4.4
Two、Test Result COSΦ= 0.8
100% -0.05 +3.8
0.2S Class
1.Measuring of insulation resistance 120% -0.02 +2.5

Secondary winding to ground≥ 1000 MΩ 3.75 VA


100% -0.02 +2.7
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.19 +9.1
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /

Test date 2023-08-03


One、Product Specifcation Three、(V-A) Property test
Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0
No.: 233130863 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.3 199.6 200.1 204.9 207.8

Rated frequency: 50 Hz Four、Error test


Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.18 +9.0

polar Minus lndoor 1S1.1S2 5% -0.13 +5.4


5VA
600/1 A 20% -0.08 +4.7
Two、Test Result COSΦ= 0.8
100% -0.05 +3.9
0.2S Class
1.Measuring of insulation resistance 120% -0.02 +3.0

Secondary winding to ground≥ 1000 MΩ 3.75 VA


100% -0.03 +3.0
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.20 +6.1
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /

Test date 2023-08-03


One、Product Specifcation Three、(V-A) Property test
Type: UP-ZC-10 I(A) 0.5 0.8 1.0 2.0 3.0
No.: 233130864 1S1.1S2 U(V) / / / / /
Rated current ratio: 600/1 A 2S1.2S2 U(V) 196.3 199.6 200.0 204.9 208.1

Rated frequency: 50 Hz Four、Error test


Accuracy class Secondary
Class Test item f(%) δ (')
1S1.1S2: 600/1 A 0.2S Class Rated output 5 VA load
2S1.2S2: 600/1 A 5P20 Class Rated output 5 VA 1% -0.19 +8.3

polar Minus lndoor 1S1.1S2 5% -0.14 +5.3


5VA
600/1 A 20% -0.07 +4.7
Two、Test Result COSΦ= 0.8
100% -0.04 +3.3
0.2S Class
1.Measuring of insulation resistance 120% -0.02 +2.5

Secondary winding to ground≥ 1000 MΩ 3.75 VA


100% -0.02 +2.5
COSΦ= 0.8
Between secondary windings≥ 1000 MΩ
1%
2.Sign inspection of the outlet terminals
2S1.2S2 5%
Minus polar, Correct . 5VA
600/1 A 20%
3.Working-frequency voltage-withstand test COSΦ= 0.8
100% -0.16 +7.2
Secondary winding to ground 3 kV 1 min 5P20 Class
120%
Between secondary windings 3 kV 1 min
/ VA
100%
COSΦ= /

Test date 2023-08-03