w488 Gx-Series Ethercat® Slave Units Users Manual en
w488 Gx-Series Ethercat® Slave Units Users Manual en
GX-series
EtherCAT Slave Units
®
User’s Manual
GX-ID@@@@
GX-OD@@@@
GX-OC@@@@
GX-MD@@@@
GX-AD@@@@
GX-DA@@@@
GX-EC@@@@
GX-ILM @@@
XWT-ID@@
XWT-OD@@
Digital I/O Units
Analog I/O Units
Encoder Input Units
IO-Link Master Unit
W488-E1-05
© OMRON, 2010
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is
constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.
Trademarks
• EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
• ODVA, CIP, CompoNet, DeviceNet, and EtherNet/IP are trademarks of ODVA.
• Windows is a registered trademark of Microsoft Corporation in the USA.
• Sysmac and SYSMAC are trademarks or registered trademarks of OMRON Corporation in Japan and other
countries for OMRON factory automation products.
Other company names and product names that appear in this manual are the trademarks or registered trade-
marks of the relevant companies.
GX-series
EtherCAT Slave Units
User’s Manual
Revised July 2016
Introduction
Thank you for purchasing a GX-series EtherCAT Slave Unit.
This manual contains information you need to know to use the EtherCAT Slave Unit.
Before use, please make sure that you thoroughly read the manual and have a full understanding of the
products functions and performance.
After you finished reading this manual, please keep it in a convenient place.
Intended Readers
This manual is intended for the following individuals.
Those having electrical knowledge (certified electricians or individuals having equivalent knowledge)
and also being qualified for one of the following:
• Introducing FA equipment
• Designing FA systems
• Managing FA sites
Page Structure
This manual's page structure consists of the following.
Section title 1 Mount the following crimp terminal to the signal line of the cable.
procedure number Tighten the terminal block screws to the appropriate tightening torque of 0.5 N • m.
The terminal block is removable; remove the left and right screws if it is necessary to remove
Indicates operation procedure. the terminal block to connect the signal line.
37104-3101-000FL Red
AWG26 (0.14mm2) to AWG24 (0.2mm2) of the current page.
Sheath diameter: 0.8 to 1.0 mm
AWG26 (0.14mm2) to AWG24 (0.2mm2)
37104-3122-000FL Yellow
Sheath diameter: 1.0 to 1.2 mm
AWG26 (0.14mm2) to AWG24 (0.2mm2)
Section title
37104-3163-000FL Orange
Sheath diameter: 1.2 to 1.6 mm Indicates the section title
AWG22 (0.3mm2) to AWG20 (0.5mm2)
37104-2124-000FL Green
Sheath diameter: 1.0 to 1.2 mm
2)
of the current page.
AWG22 (0.3mm to AWG20 (0.5mm2)
37104-2165-000FL Blue
Sheath diameter: 1.2 to 1.6 mm
AWG22 (0.3mm2) to AWG20 (0.5mm2)
37104-2206-000FL Gray
Sheath diameter: 1.6 to 2.0 mm
OMRON connectors
Model Specification Applicable wire range
Spring AWG28 (0.08mm2) to AWG20 (0.5mm2)
XN2A-1430
clamp type Sheath diameter: 1.5 mm max.
Reference
This explains useful tips and reference information when using the product.
Chapters Contents
Explains about the EtherCAT features and the network
Chapter 1 EtherCAT Network
configuration.
Overviews the GX-series EtherCAT Slave Unit and its
Chapter 2 EtherCAT Slave Unit
various types.
Explains the setup method and usage procedures by using
Chapter 3 Basic Usage Procedures
simple system setup examples.
Explains how to install Slave Units, and how to connect and
Chapter 4 Installation and Wiring
wire the EtherCAT network and power supply.
Chapter 5 EtherCAT Communications Explains the details of EtherCAT communications.
Chapter 6 Basic Specifications of Slave Units Explains the common specifications for all Slave Units.
Gives an overview about the Digital I/O Slave Unit and
explains names and functions of components consisting
Chapter 7 Digital I/O Slave Unit
the Slave Unit. It also contains internal circuit diagrams,
wiring diagrams and mounting dimensions.
Gives an overview about the Analog I/O Slave Unit and
explains names and functions of components consisting
Chapter 8 Analog I/O Slave Unit
the Slave Unit. It also contains internal circuit diagrams,
wiring diagrams and mounting dimensions.
Gives an overview about the Encoder Input Slave Unit and
explains names and functions of components consisting
Chapter 9 Encoder Input Slave Unit
the Slave Unit. It also contains internal circuit diagrams,
wiring diagrams and mounting dimensions.
Gives an overview of the IO-Link Master Unit and explains
the names and functions of the components of the IO-Link
Chapter 10 IO-Link Master Unit
Master Unit. It also contains wiring diagrams, and mounting
dimensions.
Gives an overview about the Expansion Unit and explains
names and functions of components consisting the
Chapter 11 Expansion Unit
Expansion Unit. It also contains wiring diagrams and
mounting dimensions.
This contains troubleshooting and inspection methods
Chapter 12 Troubleshooting and Maintenance intended for individuals to handle abnormalities and
conduct regular inspections.
Appendix Appendix Contains the object overview and explains the precautions.
Warranties
z Exclusive Warranty
Omron’s exclusive warranty is that the Products will be free from defects in materials and
workmanship for a period of twelve months from the date of sale by Omron (or such other period
expressed in writing by Omron). Omron disclaims all other warranties, express or implied.
z Limitations
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF
THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based
on infringement by the Products or otherwise of any intellectual property right.
z Buyer Remedy
Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally
shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an
amount equal to the purchase price of the non-complying Product; provided that in no event shall
Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the
Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before
shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from
the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or
information given orally or in writing, are not to be construed as an amendment or addition to the
above warranty.
Application Considerations
Suitability of Use
Omron Companies shall not be responsible for conformity with any standards, codes or regulations
which apply to the combination of the Product in the Buyer’s application or use of the Product. At
Buyer’s request, Omron will provide applicable third party certification documents identifying ratings
and limitations of use which apply to the Product. This information by itself is not sufficient for a
complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness
of the particular Product with respect to Buyer’s application, product or system. Buyer shall take
application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Programmable Products
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or
any consequence thereof.
Disclaimers
Performance Data
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for
the user in determining suitability and does not constitute a warranty. It may represent the result of
Omron’s test conditions, and the user must correlate it to actual application requirements. Actual
performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications
Product specifications and accessories may be changed at any time based on improvements and other
reasons. It is our practice to change part numbers when published ratings or features are changed, or
when significant construction changes are made. However, some specifications of the Product may be
changed without any notice. When in doubt, special part numbers may be assigned to fix or establish
key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
To ensure safe usage of the EtherCAT Slave Unit, the precautions in this manual are displayed with the
following labels and symbols.
The precautions explained in this section describe important information regarding safety. These
precautions must be followed without fail.
Symbols
This symbol indicates a prohibited item (an item you must not
do).
Do not input voltages or currents exceeding the rated range to the Unit.
Using voltages or currents exceeding the rated range may cause Unit failure or fire.
Provide safety measures in external circuits (i.e., not in the Units), including the
following items, to ensure safety in the system if an abnormality occurs due to
malfunction of the PLC or another external factor affecting the PLC operation.
("PLC" includes CPU Units, other Units mounted in the PLC, and Remote I/O
Terminals.)
Not doing so may result in serious accidents.
Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures
must be provided in external control circuits, not in the Units.
The PLC will turn OFF all outputs when its self-diagnosis function detects any error
or when a severe failure alarm (FALS) instruction is executed. As a countermeasure
for such problems, external safety measures must be provided to ensure safety in
the system.
The Slave Unit outputs may remain ON or OFF due to deposits on or burning of the
output relays, or destruction of the output transistors. As a countermeasure for such
problems, external safety measures must be provided to ensure safety in the
system.
When the 24-VDC output (service power supply) is overloaded or short-circuited,
the voltage may drop and result in the outputs being turned OFF. As a
countermeasure for such problems, external safety measures must be provided to
ensure safety in the system.
Implement proper measures as part of your communications system or in your
program to ensure safety in the system even when a communications error or
malfunction occurs during remote I/O communication.
Fail-safe measures must be taken by the customer to ensure safety in the event of
incorrect, missing, or abnormal signals caused by broken signal lines, momentary
power interruptions, or other causes. Not doing so may result in serious accidents.
z Power Supply
• Always use the power supply voltage specified in this manual. An incorrect voltage may result in
malfunction or burning.
• Take appropriate measures to ensure that the specified power with the rated voltage and
frequency is supplied. Be particularly careful in places where the power supply is unstable. An
incorrect power supply may result in malfunction.
• Always turn OFF the power supply to the PLC, Slave Units and other Units before attempting any
of the following. Not turning OFF the power supply may result in malfunction or electric shock.
• Assembling any Units (Expansion Units).
• Removing or attaching the terminal blocks or connectors to Slave Unit.
• Replacing parts (e.g., relays).
• Setting the DIP switch or the node address switches
• Connecting cables or wiring the system.
z Installation
• Before touching a Unit, be sure to first touch a grounded metallic object in order to discharge any
static build-up. Not doing so may result in malfunction or damage.
• Make sure that the terminal blocks, communications cables, and other items with locking devices
are properly locked into place. Improver locking may result in malfunction.
• Mount the Units securely using DIN track.
• Make sure that all Slave Unit mounting screws, cable connector screws, and switch cover screws
are tightened to the torque specified in this manuals. Incorrect tightening torque may result in
malfunction.
• Make sure that all terminal block screws are tightened to the torque specified in this manuals.
Incorrect tightening torque may result in fire, malfunction, or failure.
• Always use the specified communications cables and connectors.
• Do not exceed the ranges that are given in the specifications for the communications distance and
number of connected Units.
• When there are multiple systems, keep the cables unbundled and separated by at least 5 mm to
prevent unstable operation due to interference.
z Wiring
• Turn the power on after checking that the wiring and switch settings are correct.
• Use the correct wire tools to wire the Unit.
• Confirm the polarity of all terminals before wiring them.
• Do not allow foreign matter to enter the Units when wiring and installing the Units.
• Observe the following precautions when wiring the communications cable.
• Separate the communications cables from the power lines or high-tension lines.
• Do not bend the communications cables past their natural bending radius.
• Do not pull on the communications cables.
• Do not place heavy objects on top of the communications cables.
• Always lay communications cable inside ducts.
• Connect both ends of communications cable shielded wires to the connector hoods.
• Turn OFF the power of PLC and all the Slave Units before wiring the communication cables.
z Handling
• When transporting the product, use special packing boxes, and protect it from being exposed to
excessive vibration or impact during transportation.
• Do not bend cables past their natural bending radius or pull on cables.
• Do not place heavy objects on top of the cables.
• After replacing Units, resume operation only after transferring to the new CPU Unit and/or Special
I/O Units the contents of the DM Area, HR Area, and other data required for resuming operation.
Not doing so may result in unexpected operation.
• Check the user program for proper execution before actually running it on the Unit. Not checking
the program may result in unexpected operation.
• When replacing relays or other parts, be sure to confirm that the ratings of the new part are
correct. Not doing so may result in malfunction or burning.
• Confirm that no adverse effect will occur in the system before attempting any of the following.
• Changing the operating mode of the CPU Unit (including changing the setting of the
Operating Mode at Startup)
• Changing the user program or settings
• Changing set values or present values
• Forced refreshing
• Always sufficiently check the safety at the connected devices before you change the settings of a
slave or Unit.
• Do not use thinner when cleaning. Use commercially available alcohol.
• Do not use high-pressure cleaning.
• EtherCAT communications are not always established immediately after the power supply is
turned ON. Use the system variables in the user program to confirm that communications are
established before attempting control operations.
z External Circuits
• Install external breakers and take other safety measures against short-circuiting in external wiring.
• EMC Directives
• Low Voltage Directive
Concepts
z EMC Directives
The OMRON products described in this manual are designed so that they individually comply with
the related EMC Directives so that they can be more easily built into other devices or the overall
machine. The actual products have been checked for conformity to EMC Directives (See note)*.
Whether the products conform to the standards in the system used by the customer, however,
cannot be checked by OMRON and must be checked by the customer. EMC-related performance of
the OMRON devices that comply with EU Directives will vary depending on the configuration, wiring,
and other conditions of the equipment or control panel on which the OMRON devices are installed.
The customer must, therefore, perform the final check to confirm that devices and the overall
machine conform to EMC standards.
Conformance to EU Directives
The OMRON products described in this manual comply with the related EU Directives. To ensure that
the machine or device in which the products are used complies with EU Directives, the products must
be installed as follows:
* Note: Conformance with the EMC Directive was confirmed when using the recommended power supply.
Chapter A Appendix............................................................................A-1
A-1 Object Dictionary...................................................................................................................A-2
A-1-1 Object Dictionary Area ................................................................................................A-2
A-1-2 Data Types ..................................................................................................................A-2
A-1-3 Object Description Format...........................................................................................A-3
A-1-4 Communication Objects ..............................................................................................A-4
A-1-5 PDO Mapping Object ..................................................................................................A-8
A-1-6 Sync Manager Communication Object......................................................................A-24
A-1-7 Manufacturer Specific Objects...................................................................................A-29
A-2 Current Consumption Summary ........................................................................................A-62
A-2-1 Digital I/O Slave Unit .................................................................................................A-62
A-2-2 Analog I/O Slave Unit ................................................................................................A-62
A-2-3 Encoder Input Slave Unit...........................................................................................A-62
A-2-4 IO-Link Master Unit ...................................................................................................A-63
INDEX
EtherCAT Network
This chapter explains the overview of EtherCAT network.
Ethernet frame
Networks
When an Ethernet frame is compared to a "train", an EtherCAT datagram can be considered as "railway
car."
Ethernet frame 1
EtherCAT Master Unit Slave Unit Slave Unit Slave Unit Slave Unit
Ethernet frame
Data a
.
.
.
Data b
Data c
.
.
.
Networks
EtherCAT Master Unit
ID211
0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15
0
AD042
RUN
ERC
ERH
B1 A1
1
1
2
3 MACH 78
456
901
No.
4 x10 1 23
5
78
6
456
901
x10 0
DC24V
7mA
Servo Drive
ADR ADR
ADR
Servomotor
Inverter
IO-Link device
IO-Link
PC ID211
0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15
AD042
RUN
ERC
ERH
(Configuration Tool)
B1 A1
0
1
2
3 MACH 78
456
901
No.
4 x10 1 23
5
78
6
456
901
x10 0 23
7
8
9
10
11
12
13
14
15
COM
DC24V
7mA
Communications cable
ADR ADR
ADR
EtherCAT Network
The overview of each configuration device is as follows:
Communications Unit
By mounting to an inverter and other devices, it is possible to serve as a Slave Unit in the EtherCAT
network.
Configuration Tool
It is a PC software for making setting of the EtherCAT network and each Slave Unit.
It can be used either by connecting to the EtherCAT Master Unit or as a substitute of the EtherCAT
Master Unit.
Communications cable
Uses cables of Ethernet category 5 (100BASE-TX) or higher, with double-shield (aluminum tape and
braided shielding), which are connected straight.
z Expansion Unit
Mounted on a Digital I/O Slave Unit in order to expand the number of I/O points.
Note, however, Expansion Units can only be mounted on Digital I/O Slave Units with 2-tier terminal
block and 16 points.
2
Expansion Unit
2-2-2 Installation, I/O Connection, and Power Supply Methods for Each
Slave Unit
2
IO-Link Master Unit
Expansion Unit
XWT-ID08 (−1)
Varies depending
on the type of
XWT-OD08 (−1) M3 screw Shared with mounted Digital I/O
Models with 2-tier
DIN track terminal unit power Slave Unit
terminal block
XWT-ID16 (−1) block supply (Refer to "11-1-2
I/O Power Supply"
in Page 11 - 3.)
XWT-OD16 (−1)
Although it is not shown in the figure above, supply the unit power and the I/O power separately.
Reference
Start
3
End
*1 If you use an IO-Link Master Unit, refer to the IO-Link System User’s Manual (W570) for IO-Link communications settings
and for information on starting IO-Link communications.
z Mounting
"4-1 Mounting Slave Units" in page 4 - 2
z Setting
Pages in Chapter 6 to Chapter 11 which explain the general specification and details of each type of
Slave Units.
LED State
PWR ON
L/A IN Flickering
L/A OUT Flickering (turned OFF for the terminal Slave Unit only)
RUN ON
ERR OFF
Vertical direction
1 Hook the top side of groove on backside of the Slave Unit to the top side of the DIN
track, lower the DIN track mounting hook, engage the Slave Unit to the track, and press
up the mounting hook to fix it.
(2)
DIN track
2 Hook the bottom side of the end plate to the bottom side of the DIN track and then hook
4
the top side.
Attach an end plate on each side of the Unit.
(1)
End plate
Reference
We recommend cables with double, aluminum tape and braded shielding, taking noise
resistance into consideration.
1 White-Green White-Green 1
2 Green Green 2
3 White-Orange White-Orange 3
4 Blue Blue 4
5 White-Blue White-Blue 5
6 Orange Orange 6
7 White-Brown White-Brown 7
8 Brown Brown 8
Connector Connector
hood Shielded cable * Shielded cable* hood
Reference
There are 2 types of wiring standards for Ethernet cables : "T568A" and "T568B."
The figure above shows a wiring method conforming to the standard "T568A". The wiring
method conforming to the standard "T568B" can also be used.
Connect the communications cable from the EtherCAT Master Unit to the [CN IN] connector of the
4
Communications cable
L2
Slave Unit
Ln
• Unit power supply: For communication and internal operation of Slave Units.
• I/O power supply: For input/output operation of external I/O devices of each Slave Unit.
This section explains how to supply the unit power supply and I/O power supply.
z Supplying unit power supply and I/O power supply from multiple sources
When the unit power and I/O power are supplied from multiple power supplies instead of from one power
supply, the line current, voltage drop, and cable size can be reduced. Moreover, it is effective to secure
safety of the system at power supply errors.
Item Specification
Output voltage 24 VDC ± 10%
Output ripple 600 mVp-p
Has the capacity to supply power more than the total current
Output current
consumption of each Slave Unit
Between output and AC power supply as well as between output and
Isolation
chassis ground
We recommend S8JX series power supplies made by OMRON for the unit power supply for Slave
Units.
Digital I/O Slave Units, Analog I/O Slave Units, and Encoder Input
Slave Units
To 24-VDC unit
power supply
Unit power
supply cable
Pin terminal
+V −V
terminal terminal
Mount a pin terminal, or equivalent to the unit power supply cable so that it will not be displaced.
z Recommended product
The following pin terminals are recommended for the unit power supply cables.
An M12 connector (A-coding, male) is used for the power supply connector.
GX-ILM08C
Digital I/O Slave Units, Analog I/O Slave Units, and Encoder Input
Slave Units
z Units with screw terminal blocks
It supplies the 24-VDC I/O power to the I/O power supply terminal on each Slave Unit.
For the locations of I/O power supply terminals, see the terminal layout diagrams for each Slave Unit
or wiring diagrams in Chapter 7 to Chapter 10.
Moreover, for how to connect power supplies to terminals, refer to "4-4-1 Connecting to a Screw
Terminal Block" in Page 4 - 13.
+ V terminal
24-VDC
power supply
− G terminal
Mount a pin terminal, or equivalent to the power supply cable so that it will not be displaced.
z Recommended product
The following pin terminals are recommended for the unit power supply cables.
Applicable wire
Model Crimping tool Manufacturer
size
CRIMPFOX UD6
(Product No. 1204436) Phoenix Contact
AI0,5-10WH 0.5 mm/AWG20
or CRIMPFOX ZA3 Co., Ltd.
series
Crimper PZ1.5
H0.5/16 orange 0.5 mm/AWG20 Weidmueller Japan Co., Ltd.
(Product No. 900599)
Model Manufacturer
XW4Z-00C OMRON
GX-ILM08C
1 Mount the following crimp terminal to the signal line of the cable.
z Sumitomo 3M connectors
Model Housing color Applicable wire range
AWG26 (0.14mm to AWG24 (0.2mm2)
2)
37104-3101-000FL Red
Sheath diameter: 0.8 to 1.0 mm
AWG26 (0.14mm2) to AWG24 (0.2mm2)
37104-3122-000FL Yellow
Sheath diameter: 1.0 to 1.2 mm
AWG26 (0.14mm2) to AWG24 (0.2mm2)
37104-3163-000FL Orange
Sheath diameter: 1.2 to 1.6 mm
AWG22 (0.3mm2) to AWG20 (0.5mm2)
37104-2124-000FL Green
Sheath diameter: 1.0 to 1.2 mm
AWG22 (0.3mm2) to AWG20 (0.5mm2)
37104-2165-000FL Blue
Sheath diameter: 1.2 to 1.6 mm
AWG22 (0.3mm2) to AWG20 (0.5mm2)
37104-2206-000FL Gray
Sheath diameter: 1.6 to 2.0 mm
z OMRON connectors
Model Specification Applicable wire range
Spring AWG28 (0.08mm2 ) to AWG20 (0.5mm2)
XN2A-1470
clamp type Sheath diameter: 1.5 mm max.
When the cables are prepared this way, an e-CON connector cannot be attached. First cut the end
and remove the cable sheath as shown in the following diagram. (Do not strip the sheaths of the
core wires.)
20 mm min.
4
7 to 8 mm
1 Insert the wire all the way to the wire insertion opening on the cover of the cable
connector.
2 Use a pliers, or equivalent to press the cover into the body. At this point, press the cover
straight in such that the cover is horizontal to the body.
1 Use a flat-blade screwdriver to push the operation lever inside the connector's operation
opening until it locks, as shown in the following diagram.
Flat-blade
Screwdriver
Operation opening
2 Insert the wire all the way to the back of the wire insertion opening.
Check that the sheath of the wire is inserted into the wire insertion opening, and that the end of
the conductor has passed through the connection part.
The figure below shows the structure of CoE in GX-series EtherCAT Slave Units.
Object dictionary
SyncManager FMMU
CAN application protocol has two types of object dictionaries, PDO (Process Data Object) and SDO
(Service Data Object) .
PDO is composed of object dictionaries that can be mapped. The process data is defined by PDO
mapping.
PDO is primarily used in PDO communications for regularly exchanging process data.
Moreover, SDO is able to read and write all object dictionaries and is used in non-fixed-cycle type SDO
(event type messages) communications.
By using the CoE interface to set object SDO and PDO dictionaries, EtherCAT can provide EtherCAT
devices with the same device profile as CAN application protocol.
ESI
files
The following figure shows the communications state transitions from power ON.
Power ON
Initialization
Pre-Operational
Safe-Operational
Operational
SDO PDO
PDO
State communi transmiss Contents
reception
cations ion
Not Not Not Communications are being initialized.
Initialization (Init)
possible. possible. possible. Communications are not possible.
SDO (message) communications are
possible in this state.
Pre-Operational Not Not
Possible This state is entered after initialization has
(Pre-Op) possible. possible.
been completed. It is used to initialize
network settings.
In this state, PDO transmissions are possible
in addition to SDO (message)
Safe-Operational Not communications.
Possible Possible
(Safe-Op) possible. PDO sendings can be used to send
information such as status from the Slave
Unit.
Normal communication state
Operational (Op) Possible Possible Possible PDO communications can be used to control
the I/O data.
5-4-1 Overview
The process data objects (PDO) are used for real-time data transfer via cyclic communications.
There are two types in PDO: RxPDO that receives data from the EtherCAT Master Unit and TxPDO that
sends the present value from a EtherCAT Slave Unit to the EtherCAT Master Unit.
It is possible to hold multiple objects in the EtherCAT application layer so that various process data of
EtherCAT Slave Units can be transferred. The details of process data are described in PDO Mapping
Objects and Sync Manager PDO Assignment Objects. 5
GX-series EtherCAT Slave Units support PDO mapping for I/O control.
5-4-1 Overview
5-4-2 PDO Mapping Settings
The PDO mapping indicates the mapping for application objects (realtime process data) between the
object dictionary and PDO.
The number of mapped objects is described in sub-index 0 of the mapping table. In this mapping table,
indexes 1600 hex to 17FF hex are used for RxPDO and 1A00 hex to 1BFF hex are used for TxPDO.
Object dictionary
Mapping objects
PDO-Length : 32 Bit
PDO_1 Object A Object B Object D
512th transmit
PDO Mapping Sysmac errors Sysmac Error (2002 hex)
(1BFF hex)
Reference
You cannot assign 1700 hex and 1701 hex or 1B00 hex and 1B01 hex at the same time.
257th receive
PDO Mapping Write analog output 16-bit (6411 hex) *1
(1700 hex)
257th transmit
PDO Mapping Read analog input 16-bit (6401 hex) *2
(1B00 hex)
512th transmit
PDO Mapping Sysmac Error (2002 hex)
(1BFF hex)
*1 Analog Output Slave Unit only.
*2 Analog Input Slave Unit only.
257th receive
PDO Mapping Instruction Bits (4020 hex)
(1700 hex)
258th receive
PDO Mapping Preset Value (4011 hex)
(1701 hex)
259th receive
PDO Mapping Instruction Flag (4021 hex)
(1702 hex)
257th transmit
PDO Mapping Position Value (4010 hex)
(1B00 hex)
258th transmit
PDO Mapping Latch Value A (4012 hex)
(1B01 hex)
259th transmit
PDO Mapping Latch Value B (4013 hex)
(1B02 hex)
260th transmit
PDO Mapping Status Bits (4030 hex)
(1B03 hex)
261th transmit
PDO Mapping Status Flag (4031 hex)
(1B04 hex)
512th transmit
PDO Mapping Sysmac Error (2002 hex)
(1BFF hex)
Reference
You cannot assign 1700 hex and 1702 hex or 1B03 hex and 1B04 hex at the same time.
5-5-1 Overview
GX-series EtherCAT Slave Units support the SDO communications.
The EtherCAT Master Unit is able to make parameter settings and monitor status by reading and writing
data from and to entries in object dictionaries via the SDO communications.
Code Meaning
05030000 hex Toggle bit not changed
05040000 hex SDO protocol timeout
05040001 hex Client/Server command specifier not valid or unknown
05040005 hex Out of memory
06010000 hex Unsupported access to an object
06010001 hex Attempt to read a write only object
06010002 hex Attempt to write to a read only object
06020000 hex The object does not exist in the object directory.
06040041 hex The object cannot be mapped into the PDO.
06040042 hex The number and length of the objects to be mapped would exceed the PDO length.
06040043 hex General parameter incompatibility reason
06040047 hex General internal incompatibility in the device.
06060000 hex Access failed due to a hardware error.
06070010 hex Data type does not match, length of service parameter does not match.
06070012 hex Data type does not match, length of service parameter too high.
06070013 hex Data type does not match, length of service parameter too low.
06090011 hex Sub-index does not exist.
06090030 hex Value range of parameter exceeded (only for write access)
06090031 hex Value of parameter written too high
06090032 hex Value of parameter written too low
06090036 hex Maximum value is less than minimum value.
08000000 hex General error
08000020 hex Data cannot be transferred or stored to the application.
08000021 hex Data cannot be transferred or stored to the application because of local control.*1
Data cannot be transferred or stored to the application because of the present device
08000022 hex
state.
08000023 hex Object dictionary dynamic generation fails or no object dictionary is present.
*1 In this status, the Slave Unit operates locally and the EtherCAT Master Unit is unable to control it.
To calculate the input and output response time* of the entire system, refer to the relevant values in the
manual of the host system (EtherCAT Master or CPU Unit) to be used.
* This is the time which takes for an input signal from an Input Slave Unit to be processed by the PLC of the Master
Unit and output to an Output Slave Unit.
5
5-6-2 DC Mode
A mechanism called distributed clock (DC), where the EtherCAT Master Unit and Slave Units share the
same clock, is used for synchronization.
Each of DC mode-ready Slave Units connected to EtherCAT shares the clock information.
By generating interrupt signals and executing input/output processing inside each Slave Unit according
to the clock, it becomes possible to synchronize the input/output timing with other Slave Units.
Set common clock information among the EtherCAT Master Unit and Slave Units
to match the time mutually.
EtherCAT
Master Unit Slave Unit
z Communications cycle
The communications cycle is determined by setting output frequency of Sync0 signal (interrupt
signal in DC mode 1).
The settings are performed on the EtherCAT Master Unit side. For the setting method, refer to the
manual of the EtherCAT Master Unit to be used.
When the power to it is turned on, a Slave Unit always starts up in the "Not notify" setting. If you want to
use a Slave Unit in the "Notify" setting, set it to "Notify" each time you turn on the power.
Note that an emergency message cannot be sent during an EtherCAT communications errors are
5
occurring.
Byte 0 1 2 3 4 5 6 7
Emergency Error register
Contents Reserved. Sysmac error status code
error code (Object 1001 hex)
For contents of emergency message, refer to "12-1-5 Emergency Error Code" in page 12 - 19.
For contents of Sysmac error status codes, refer to "12-1-4 Sysmac Error Status Codes" in page 12 -
14.
Diagnosis history is stored from Diagnosis message 1. If 8 errors are stored in order up to Diagnosis
message 8, the 9th error onward are saved from Diagnosis message 1 again.
The GX-ILM08C can save a maximum of 64 error records in the error history. For details, refer to the
IO-Link System User’s Manual (Cat. No. W570).
History is saved even if emergency messages cannot be sent to the EtherCAT Master Unit due to
EtherCAT communications errors or emergency messages are set to "Not notify."
Errors that occur for non-volatile memory are not saved in the diagnosis history.
• Software setting
The software setting that is set in the SII (slave information interface) in non-volatile memory in the
Slave Unit is used as the node address.
Reference
This helps prevent forgetting to set the parameters because a slave device that was replaced is
detected.
Item Specification
Communication protocol Dedicated protocol for EtherCAT
Modulation Base band
Baud rate 100 Mbps
Physical layer 100BASE-TX (IEEE802.3)
RJ45 × 2 (Shielded)
Connectors CN IN: EtherCAT input
CN OUT: EtherCAT output
Topology Daisy chain
Category 5 or higher (cable with double, aluminum tape and braided shielding is
Communications media
recommended.)
Communications distance Distance between nodes (Slave Units): 100 m max.
Noise immunity Conforms to IEC 61000-4-4, 1 kV or higher
Node address setting
Set on decimal node address switches or with a Configuration Tool.
method
1 to 99: Node address switch setting
Node address range
1 to 65535: Set with Configuration Tool
PWR × 1
L/A IN (Link/Activity IN) × 1
Indicator L/A OUT (Link/Activity OUT) × 1
RUN × 1
ERR × 1
Process data Fixed PDO mapping
PDO size/node 2 bit to 256 byte
Mailbox Emergency messages, SDO requests, SDO responses, and SDO information
SYNCHRONIZATION Digital I/O Slave Unit and Analog I/O Slave Unit: Free Run mode (asynchronous)
mode Encoder Input Slave Unit: DC mode 1
Item Specification
Unit power supply voltage 20.4 to 26.4 VDC (24 VDC −15% to +10%)
I/O power supply voltage 20.4 to 26.4 VDC (24 VDC −15% to +10%)
Noise immunity Conforms to IEC 61000-4-4, 2 kV (power line).
Malfunction 10 to 60 Hz with amplitude of 0.7 mm, 60 to 150Hz and 50 m/s2 in each
of X, Y, and Z directions for 80 minutes
Vibration resistance
<GX-OC1601 Relay Output Unit only>
10 to 55 Hz with double-amplitude of 0.7 mm
150 m/s2 with amplitude of 0.7 mm
PWR
L/A IN
L/A OUT
RUN
ERR
[PWR] indicator
Indicates the unit power supply state.
[RUN] indicator
It indicates the operation state.
[ERR] indicator
6
Reference
on
Flickering
off
on
Blinking
200 ms 200 ms
off
on
1000 ms
Single flash
200 ms 200 ms
off
on
1000 ms
Double flash
200 ms 200 ms 200 ms
off
Digital I/O Slave Units, Analog I/O Slave Units, and Encoder Input
Slave Units
These switches are used to set node addresses of Slave Units in the EtherCAT network (decimal).
Set the tens digit of the node address on the left switch and the ones digit on the right switch.
Setting range is 00 to 99. (Default setting: 00)
90 1 90 1
7 8
7 8
2 3
2 3
4 5 6 4 5 6
Note that the node address set values vary as shown below when the EtherCAT Master Unit is made by
OMRON or by other manufacturers.
The node address setting switches are used to set node address of the Slave Unit in the EtherCAT
network as a hexadecimal value.
Set the hexadecimal value of the EtherCAT node address of the IO-Link Master Unit on the rotary
switches in the following order starting from the rightmost switch: rightmost digit (x1), middle digit (x16),
and leftmost digit (x256).
The setting range is from 000 to FFF hex (0 to 4,095 decimal). (Default setting: 000)
GX-ILM08C
BCDE
BCDE
3456
3456
3456
789A 789A 789A
Digital I/O Slave Units, Analog I/O Slave Units, and Encoder Input
Slave Units
RJ45 connectors are used for the communications connectors as shown below.
CN1 1
8
CN2
M12 connectors (D-coding, female) are used for the communications connectors as shown below.
GX-ILM08C
6
The specifications are given below.
• Electrical specifications: Conform to IEEE 802.3 standards.
(2) Type
T: Ethernet (mating section: M12, D coding)
(7) Connectors
0: M12 plug on one end
1: M12 socket on one end and M12 plug on the other end
2: M12 plugs on both ends
C: M12 plug on one end and RJ45 plug on the other end
D: RJ45 plugs on both ends
E: M12 socket on one end and RJ45 plug on the other end
(8) Cable
K: Standard cable
KR: Flexible cable
Digital I/O Slave Units, Analog I/O Slave Units, and Encoder Input
Slave Units
Fixing screw
For types of recommended pin terminals, refer to "4-3-3 Connecting the Unit Power Supply" in page 4 -
9. 6
Supply the Unit power supply and the I/O power supply through the same power supply connector.
(Notes) Supply the Unit power supply and the I/O power supply from separate sources.
An M12 connector (A-coding, male) is used for the power supply connector.
GX-ILM08C
Digital I/O Slave Units, Analog I/O Slave Units, and Encoder Input
Slave Units
The I/O power supply connector is mounted on the following type of Slave Unit with e-CON connector
and output contacts.
GX-OD1618/OD1628/MD1618/MD1628/OD3218/OD3228/MD3218/MD3228
I/O power is supplied through the power supply connector. Refer to "6-3-4 Unit Power Supply
Connector" in page 6 - 11.
For the detailed explanation of allocation method, refer to the manual of EtherCAT Master Unit to be
connected.
Offset
(byte) 7 bit 0 bit
+1 Reserved
Offset
(byte) 7 bit 0 bit
Offset
(byte) 7 bit 0 bit
+1 Reserved
Offset
(byte) 7 bit 0 bit
Offset
(byte) 7 bit 0 bit
+3 Reserved
Offset
(byte) 7 bit 0 bit
Offset
(byte) 7 bit 0 bit
z 16-point Input Slave Unit, 16-point Expansion Unit, and Sysmac error status
Offset
(byte) 7 bit 0 bit
Offset
(byte) 7 bit 0 bit
+1 Reserved
Offset
(byte) 7 bit 0 bit
Offset
(byte) 7 bit 0 bit
+1 Reserved
Offset
(byte) 7 bit 0 bit
Offset
(byte) 7 bit 0 bit
+3 Reserved
Offset
(byte) 7 bit 0 bit
Overview of functions
z Purpose
This function prevents data changes and unstable data, which may be caused by fluctuation of input
data and unstable contact state due to chattering and noise.
z Details of functions
This function reads inputs (ON/OFF) within a certain set time and turn ON the inputs if they are all
same (all ON or all OFF), and turn them OFF if not.
Note that this function works for all inputs of Slave Units and Expansion Units at the same time.
When the input shifts from OFF to ON (or ON to OFF), it is read 4 times from that point at an interval
of 1/4 of the set time. When all read results are ON (or OFF), the input is turned ON (or OFF).
1 2 3 4 1 2 3 4
7
ON ON
ON OFF OFF ON ON ON ON ON
Input data is OFF because all data Input data is ON because all data
is not ON during 4 readings. is ON during 4 readings.
ON
ON
OFF OFF
ON delay time
The settable time of reading is 0 ms, 0.5 ms, 1 ms (default set value), 2 ms, 4 ms, 8 ms, 16 ms, or 32
ms.
Note that when this function is used, the timing when the contact actually turns ON (or OFF) is
delayed for the set time (ON delay time).
The ON delay time is expressed by "input delay time (time required to read input) + input filter time."
Moreover, if the input filter is used for the Expansion Units as well, the ON delay time becomes
longer because the input delay time is longer than when only Slave Unit is used.
Setting method
The settings are made using the SDO communication.
The target index is 3000 hex.
For the set values, refer to the information in the corresponding index of "Appendix A-1 Object
Dictionary" in Page A - 31.
Overview of functions
z Purpose
This function provides selection whether to hold or clear the outputs if signals from the EtherCAT
Master Unit cannot be received any longer due to communications errors.
z Details of functions
Sets whether to hold or clear the output at communications errors.
It is possible to make setting for each contact. (Default setting: Clear all outputs)
Setting method
The settings are made using the SDO communication.
The target index is set as follows according to the number of outputs of a single Slave Unit (including
Expansion Units mounted).
Total
Output Unit Expansion Unit
output Applicable index
capacity Output capacity
capacity
8 points −
8 points
− 8 points
6306 hex
16 points −
16 points
− 16 points
24 points 16 points 8 points
16 points 16 points 6326 hex
32 points
32 points −
For the set value, refer to the information of the corresponding index of "Appendix A-1 Object
Dictionary" in Page A - 37.
Reference page
Internal
Type Model Names and Wiring
Specification circuits
functions diagram
diagram
GX-ID1611
7-10 7-11 7-12 7-13
GX-ID1621
GX-OD1611
2-tier terminal 7-14 7-15 7-16 7-17
GX-OD1621
block type
GX-OC1601 7-18 7-19 7-21 7-21
Specification
Specification
Item
GX-ID1611 GX-ID1621
Input capacity 16 points
Internal I/O common NPN PNP
15 VDC min. (between each input 15 VDC min. (between each input
ON voltage
terminal and the V terminal) terminal and the G terminal)
5 VDC max. (between each input 5 VDC max. (between each input
OFF voltage
terminal and the V terminal) terminal and the G terminal)
OFF current 1.0 mA max.
6.0 mA max./input (at 24-VDC)
Input current
3.0 mA max./input (at 17-VDC)
ON delay 0.1 ms max.
OFF delay 0.2 ms max.
Without filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms
Input filter value
(Default setting: 1 ms)
Number of circuits per
16 inputs/common
common
Input indicators LED display (yellow)
Isolation method Photocoupler isolation
I/O power supply method Supply by I/O power supply
Unit power supply current
90 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
I/O power supply current
10 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
Weight 180 g max.
Expansion functions Enabled
Short-circuit protection
No
function
Notes For the I/O power supply current value to V and G terminals, refer to "A-5 I/O Power Supply Current" in
Page A - 67.
(1)
(2)
(7) (6)
10 to 18 V 1 3 5 7 9 11 13 15
1 to 9 G 0 2 4 6 8 10 12 14
7-4-1 2-tier Terminal Block Type 16-point Input Slave Unit GX-ID1611/ID1621
Indicates the state of an input contact (ON/OFF).
(5) Input indicators (0 to 15) Not lit: Contact OFF (input OFF state)
Lit in yellow: Contact ON (input ON state)
Connects external devices and the I/O power supply.
(6) Terminal block V, G: I/O power supply terminals
0 to 15: Input terminals
(7) DIN track mounting hook Fixes a Slave Unit to a DIN track.
CN IN
TX+
TX− Photocoupler
RX+ V 24 VDC
RX−
0
Physical 1
• •
layer
• •
CN OUT
Internal circuits
Photocoupler • •
TX+
• •
TX−
• •
RX+
• •
RX−
• •
• •
•
• •
•
•
G
UNIT PS
DC-DC
+V converter
−V
(No-isolation
type)
z GX-ID1621 (PNP)
CN IN
TX+ V 24 VDC
TX− Photocoupler
RX+ 0
RX−
1
• •
Physical • •
layer • •
Internal circuits
CN OUT Photocoupler • •
TX+ • •
TX− • •
RX+ • •
RX− G
•
UNIT PS
DC-DC
+V converter
−V (No-isolation
type)
Wiring diagram
z GX-ID1611 (NPN)
V 1 3 5 7 9 11 13 15
G 0 2 4 6 8 10 12 14
Blue (black)
Black (white)
Brown (red)
Brown (white)
z GX-ID1621 (PNP)
7-4-1 2-tier Terminal Block Type 16-point Input Slave Unit GX-ID1611/ID1621
V 1 3 5 7 9 11 13 15
G 0 2 4 6 8 10 12 14
Black (white)
Brown (white)
Blue (black)
Blue (black)
Brown (red)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors. The colors in parentheses are the wire colors prior to the revisions.
Specification
Specification
Item
GX-OD1611 GX-OD1621
Output capacity 16 points
Rated current
0.5 A/output, 4.0 A/common
(ON current)
Internal I/O common NPN PNP
1.2 V max. 1.2 V max.
Residual voltage (0.5 ADC, between each output terminal (0.5 ADC, between each output terminal
and the G terminal) and the V terminal)
Leakage current 0.1 mA max.
ON delay 0.5 ms max.
OFF delay 1.5 ms max.
Number of circuits per
16 points/common
common
Output indicators LED display (yellow)
Isolation method Photocoupler isolation
I/O power supply method Supply by I/O power supply
Unit power supply current
90 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
I/O power supply current
10 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
Weight 180 g max.
Expansion functions Enabled
Error Mode Output Select either hold or clear.
Short-circuit protection
No
function
Notes For the I/O power supply current value to V and G terminals, refer to "A-5 I/O Power Supply Current" in
Page A - 67.
(1)
(2)
(7) (6)
10 to 18 V 1 3 5 7 9 11 13 15
1 to 9 G 0 2 4 6 8 10 12 14
7-4-2 2-tier Terminal Block Type 16-point Output Slave Unit GX-OD1611/OD1621
Indicates the state of an output contact (ON/OFF).
(5) Output indicators (0 to 15) Not lit: Contact OFF (output OFF state)
Lit in yellow: Contact ON (output ON state)
Connects external devices and the I/O power supply.
(6) Terminal block V, G: I/O power supply terminals
0 to 15: Output terminals
(7) DIN track mounting hook Fixes a Slave Unit to a DIN track.
CN IN
TX+
Photocoupler
Voltage
TX−
drop
RX+
V 24 VDC
RX− 0
1
Physical • •
layer Internal circuits • •
CN OUT • •
TX+ • •
TX− Photocoupler • •
RX+
• •
RX−
• •
• •
• •
• •
• •
UNIT PS
DC-DC
+V converter G
-V (No-isolation •
type) •
z GX-OD1621 (PNP)
CN IN
TX+
TX−
RX+ V 24 VDC
RX− Photocoupler 0
Physical 1
• •
layer
• •
Internal circuits
CN OUT
• •
TX+
• •
TX−
• •
RX+
• •
RX−
Photocoupler • •
• •
Voltage
• •
drop
G
UNIT PS •
DC-DC •
+V converter •
−V (No-isolation
type)
Wiring diagram
z GX-OD1611 (NPN)
V 1 3 5 7 9 11 13 15
G 0 2 4 6 8 10 12 14
z GX-OD1621 (PNP)
7-4-2 2-tier Terminal Block Type 16-point Output Slave Unit GX-OD1611/OD1621
V 1 3 5 7 9 11 13 15
G 0 2 4 6 8 10 12 14
7-4-3 2-tier Terminal Block Relay Type 16-point Output Slave Unit
GX-OC1601
Specification
Item Specification
Output capacity 16 points
Mounted relays NY-5W-K-IE (Fujitsu Component) *
Resistance load
Rated load 250 VAC 2 A/output, common 8 A
30 VDC 2 A/output, common 8 A
Rated ON current 3 A/output
Maximum contact voltage 250 VAC, 125 VDC
Maximum contact current 3 A/output
Maximum switching
750 VAAC, 90 WDC
capacity
Minimum applicable load
5 VDC 1mA
(reference value)
Mechanical service life 20,000,000 operations min.
Electrical service life 100,000 operations min.
Number of circuits per
8 points/common
common
Output indicators LED display (yellow)
Isolation method Relay isolation
The relay drive power is supplied from the unit power
I/O power supply method
supply.
Unit power supply current 210 mA max. (for 20.4 to 26.4-VDC power supply
consumption voltage)
Weight 290 g max.
Expansion functions Enabled
Error Mode Output Select either hold or clear.
Short-circuit protection
No
function
* For the specification of individual relay, refer to the data sheet disclosed by manufacturers.
(1)
(2)
10 to 18 1 3 5 7 8 10 12 14 COM1
1 to 9 0 2 4 6 COM0 9 11 13 15
7-4-3 2-tier Terminal Block Relay Type 16-point Output Slave Unit GX-OC1601
Indicates the state of an output contact (ON/OFF).
(5) Output indicators (0 to 15) Not lit: Contact OFF (output OFF state)
Lit in yellow: Contact ON (output ON state)
(6) Output relay Switches a contact.
Connects external devices and the I/O power supply.
(7) Terminal block COM0, COM1: Common terminals
0 to 15: Output terminals
(8) DIN track mounting hook Fixes a Slave Unit to a DIN track.
Reference
Replacing relays
To replace output section relays, first remove the cover using the following procedure.
(1)
(2)
(3)
Reference
500
5
300 120-VAC resistance load
30 VDC, t = 7ms
4
4 200
240 VAC, COSφ = 0.4
3
100 120 VAC, COSφ = 0.4
2 30 VDC/240 VAC
50 Resistance load
1 AC resistance load 30
20
0.5
10
0.4
DC resistance load 5
0.3 3 30 VDC, t = 40ms
2
0.2
100 to 200 VDC
t = 7 to 40ms
0.1
10 20 30 50 100 200 300 500 1000 0.1 0.2 0.3 0.5 1 3 4 5
NY-5W-K-IE
Photocoupler 5 VDC
CN IN 0
TX+
TX−
RX+
RX− 1
•
Physical •
layer •
Internal circuits
Photocoupler
CN OUT •
•
TX+ • •
TX− •
•
RX+ COM0
RX−
NY-5W-K-IE
Photocoupler 5 VDC
8
Photocoupler •
•
•
•
•
•
•
•
•
•
COM1
DC-DC converter
for relay drive
(No-isolation type)
7
Wiring diagram
7-4-3 2-tier Terminal Block Relay Type 16-point Output Slave Unit GX-OC1601
1 3 5 7 8 10 12 14 COM1
0 2 4 6 COM0 9 11 13 15
7-4-4 2-tier Terminal Block Type 8-point Input and 8-point Output Slave Unit
GX-MD1611/MD1621
Specification
Specification
Item
GX-MD1611 GX-MD1621
Internal I/O common NPN PNP
I/O indicators LED display (yellow)
Unit power supply current
80 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
Weight 190 g max.
Expansion functions No
Short-circuit protection
No
function
z Input section
Specification
Item
GX-MD1611 GX-MD1621
Input capacity 8 points
15 VDC min. (between each input 15 VDC min. (between each input
ON voltage
terminal and the V terminal) terminal and the G terminal)
5 VDC max. (between each input 5 VDC max. (between each input
OFF voltage
terminal and the V terminal) terminal and the G terminal)
OFF current 1.0 mA max.
6.0 mA max./input (at 24-VDC)
Input current
3.0 mA max./input (at 17-VDC)
ON delay 0.1 ms max.
OFF delay 0.2 ms max.
Without filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms
Input filter value
(Default setting: 1 ms)
Number of circuits per
8 points/common
common
Isolation method Photocoupler isolation
I/O power supply method Supply by I/O power supply
I/O power supply current
10 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
z Output section
Specification
Item
GX-MD1611 GX-MD1621
Output capacity 8 points
Rated output current 0.5 A/output, 2.0 A/common
1.2 V max. 1.2 V max.
Residual voltage (0.5 ADC, between each output terminal (0.5 ADC, between each output terminal
and the G terminal) and the V terminal)
Leakage current 0.1 mA max.
ON delay 0.5 ms max.
OFF delay 1.5 ms max.
Number of circuits per
8 points/common
common
Isolation method Photocoupler isolation
I/O power supply method Supply by I/O power supply
GX-MD1611/MD1621
7-4-4 2-tier Terminal Block Type 8-point Input and 8-point Output Slave Unit
(1)
(2)
(8) (7)
12 to 22 V1 1 3 5 7 V2 1 3 5 7 NC
1 to 11 G1 0 2 4 6 G2 0 2 4 6 NC
CN IN
TX+ Photocoupler
TX− V1 24 VDC
RX+ 0
RX− 1
• •
Physical Photocoupler • •
layer • •
TX+ G1
TX−
RX+ Photocoupler
Voltage
drop
RX− V2 24 VDC
0
1
• •
UNIT PS • •
DC-DC Photocoupler • •
+V converter
• •
−V (No-isolation • •
type) • •
• •
G2
z GX-MD1621 (PNP)
CN IN
V1 24 VDC
TX+ Photocoupler
0
TX−
RX+ 1 7
RX− • •
• •
Physical Photocoupler • •
GX-MD1611/MD1621
7-4-4 2-tier Terminal Block Type 8-point Input and 8-point Output Slave Unit
• •
layer • •
Internal circuits
CN OUT
G1
TX+
TX−
RX+ V2 24 VDC
RX− Photocoupler 0
1
• •
• •
• •
UNIT PS
DC-DC • •
+V converter Photocoupler • •
−V (No-isolation • •
Voltage
drop
type) G2
Wiring diagram
z GX-MD1611 (NPN)
V1 1 3 5 7 V2 1 3 5 7 NC
G1 0 2 4 6 G2 0 2 4 6 NC
Black (white)
Brown (white)
Blue (black)
Blue (black)
Brown (red)
z GX-MD1621 (PNP)
V1 1 3 5 7 V2 1 3 5 7 NC
G1 0 2 4 6 G2 0 2 4 6 NC
Black (white)
Brown (white)
Blue (black)
Blue (black)
Brown (red)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors. The colors in parentheses are the wire colors prior to the revisions.
GX-MD1611/MD1621
7-4-4 2-tier Terminal Block Type 8-point Input and 8-point Output Slave Unit
Specification
Specification
Item
GX-ID1612 GX-ID1622
Input capacity 16 points
Internal I/O common NPN PNP
15 VDC min. (between each input 15 VDC min. (between each input
ON voltage
terminal and the V terminal) terminal and the G terminal)
5 VDC max. (between each input 5 VDC max. (between each input
OFF voltage
terminal and the V terminal) terminal and the G terminal)
OFF current 1.0 mA max.
6.0 mA max./input (at 24-VDC)
Input current
3.0 mA max./input (at 17-VDC)
ON delay 0.1 ms max.
OFF delay 0.2 ms max.
Without filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms
Input filter value
(Default setting: 1 ms)
Number of circuits per
8 points/common
common
Input indicators LED display (yellow)
Isolation method Photocoupler isolation
I/O power supply method Supply by I/O power supply
Input device supply
100 mA/point
current
Unit power supply current
90 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
I/O power supply current
10 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
Weight 370 g max.
Expansion functions No
Short-circuit protection
No
function
Notes For the I/O power supply current value to V and G terminals ,refer to "A-5 I/O Power Supply Current" in
Page A - 67.
(1)
(2)
(7) (6)
1 to 9 NC 0 1 2 3 4 5 6 7 NC 8 9 10 11 12 13 14 15
10 to 18 V1 V1 V1 V1 V1 V1 V1 V1 V1 V2 V2 V2 V2 V2 V2 V2 V2 V2
19 to 27 G1 G1 G1 G1 G1 G1 G1 G1 G1 G2 G2 G2 G2 G2 G2 G2 G2 G2
7-4-5 3-tier Terminal Block Type 16-point Input Slave Unit GX-ID1612/ID1622
(4) Node Address setting Switches
Indicates the state of an input contact (ON/OFF).
(5) Input indicators (0 to 15) Not lit: Contact OFF (input OFF state)
Lit in yellow: Contact ON (input ON state)
Connects external devices and the I/O power supply.
<Left side>
V1, G1: I/O power supply terminals
(6) Terminal block 0 to 7: Input terminals
<Right side>
V2, G2: I/O power supply terminals
8 to 15: Input terminals
(7) DIN track mounting hook Fixes a Slave Unit to a DIN track.
CN IN
TX+ V1 24 VDC
TX−
RX+ G1
Input circuit
RX− Photocoupler
V1
Physical
0 to 7
layer
CN OUT G1
TX+
Internal •
•
•
•
TX− circuits • •
V2 24 VDC
RX+
RX− G2
Input circuit
Photocoupler
V2
8 to 15
UNIT PS
DC-DC
+V converter • • G2
• •
• •
−V (No-isolation
type)
z GX-ID1622 (PNP)
CN IN
TX+ G1
TX−
RX+ V1 24 VDC
Input circuit
RX- Photocoupler
G1
Physical
layer 0 to 7
CN OUT Internal V1
• •
TX+ circuits •
•
•
•
TX− G2
RX+
RX− V2 24 VDC
Input circuit
Photocoupler
G2
8 to 15
UNIT PS
DC-DC
+V V2
converter •
•
•
•
• •
−V (No-isolation
type)
Wiring diagram
z GX-ID1612 (NPN)
NC 0 1 2 3 4 5 6 7 NC 8 9 10 11 12 13 14 15
V1 V1 V1 V1 V1 V1 V1 V1 V1 V2 V2 V2 V2 V2 V2 V2 V2 V2
G1 G1 G1 G1 G1 G1 G1 G1 G1 G2 G2 G2 G2 G2 G2 G2 G2 G2
Blue (black)
Blue (black)
Brown (red)
(24 VDC)
z GX-ID1622 (PNP)
7-4-5 3-tier Terminal Block Type 16-point Input Slave Unit GX-ID1612/ID1622
NC 0 1 2 3 4 5 6 7 NC 8 9 10 11 12 13 14 15
V1 V1 V1 V1 V1 V1 V1 V1 V1 V2 V2 V2 V2 V2 V2 V2 V2 V2
G1 G1 G1 G1 G1 G1 G1 G1 G1 G2 G2 G2 G2 G2 G2 G2 G2 G2
Black (white)
Blue (black)
Blue (black)
Brown (red)
(24 VDC)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors. The colors in parentheses are the wire colors prior to the revisions.
Specification
Specification
Item
GX-OD1612 GX-OD1622
Output capacity 16 points
Rated current (ON
0.5 A/output, 4.0 A/common
current)
Internal I/O common NPN PNP
1.2 V max. 1.2 V max.
Residual voltage (0.5 ADC, between each output terminal (0.5 ADC, between each output terminal
7-4-6 3-tier Terminal Block Type 16-point Output Slave Unit GX-OD1612/OD1622
Expansion functions No
Error Mode Output Select either hold or clear.
Short-circuit protection
No
function
Notes For the I/O power supply current value to V and G terminals ,refer to "A-5 I/O Power Supply Current" in
Page A - 67.
(1)
(2)
(7) (6)
1 to 9 NC 0 1 2 3 4 5 6 7 NC 8 9 10 11 12 13 14 15
10 to 18 V1 V1 V1 V1 V1 V1 V1 V1 V1 V2 V2 V2 V2 V2 V2 V2 V2 V2
19 to 27 G1 G1 G1 G1 G1 G1 G1 G1 G1 G2 G2 G2 G2 G2 G2 G2 G2 G2
Voltage
CN IN
drop
V1 24 VDC
TX+
TX− G1
RX+
RX−
V1
Physical
layer Output (0 to 7)
CN OUT Photocoupler
TX+ Internal
TX− G1
circuits • •
RX+ • •
• •
Voltage
RX−
drop
V2 24 VDC
G2
z GX-OD1622 (PNP)
CN IN V1 24 VDC
Voltage
TX+
7
drop
TX−
G1
RX+
RX− V1
7-4-6 3-tier Terminal Block Type 16-point Output Slave Unit GX-OD1612/OD1622
Physical Output (0 to 7)
layer
CN OUT G1
TX+ Internal •
•
•
•
• •
TX− circuits Photocoupler
RX+
V2 24 VDC
RX−
Voltage
drop
G2
V2
UNIT PS
DC-DC
+V converter Output (8 to 15)
−V (No-isolation G2
type) •
•
•
•
• •
Photocoupler
Wiring diagram
z GX-OD1612 (NPN)
NC 0 1 2 3 4 5 6 7 NC 8 9 10 11 12 13 14 15
V1 V1 V1 V1 V1 V1 V1 V1 V1 V2 V2 V2 V2 V2 V2 V2 V2 V2
G1 G1 G1 G1 G1 G1 G1 G1 G1 G2 G2 G2 G2 G2 G2 G2 G2 G2
Blue (black)
Pink (white)
(24 VDC)
z GX-OD1622 (PNP)
NC 0 1 2 3 4 5 6 7 NC 8 9 10 11 12 13 14 15
V1 V1 V1 V1 V1 V1 V1 V1 V1 V2 V2 V2 V2 V2 V2 V2 V2 V2
G1 G1 G1 G1 G1 G1 G1 G1 G1 G2 G2 G2 G2 G2 G2 G2 G2 G2
Blue (black)
Pink (white)
(24 VDC)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors. The colors in parentheses are the wire colors prior to the revisions.
7-4-6 3-tier Terminal Block Type 16-point Output Slave Unit GX-OD1612/OD1622
7-4-7 3-tier Terminal Block Type 8-point Input and 8-point Output Slave Unit
GX-MD1612/MD1622
Specification
Specification
Item
GX-MD1612 GX-MD1622
Internal I/O common NPN PNP
I/O indicators LED display (yellow)
Unit power supply current
90 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
Weight 370 g max.
Expansion functions No
Short-circuit protection
No
function
z Input section
Specification
Item
GX-MD1612 GX-MD1622
Input capacity 8 points
15 VDC min. (between each input 15 VDC min. (between each input
ON voltage
terminal and the V terminal) terminal and the G terminal)
5 VDC max. (between each input 5 VDC max. (between each input
OFF voltage
terminal and the V terminal) terminal and the G terminal)
OFF current 1.0 mA max./input
6.0 mA max./input (at 24-VDC)
Input current
3.0 mA max./input (at 17-VDC)
ON delay 0.1 ms max.
OFF delay 0.2 ms max.
Without filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms
Input filter value
(Default setting: 1 ms)
Number of circuits per
8 points/common
common
Isolation method Photocoupler isolation
I/O power supply method Supply by I/O power supply
Input device supply
100 mA/point
current
I/O power supply current
10 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
z Output section
Specification
Item
GX-MD1612 GX-MD1622
Output capacity 8 points
Rated output current 0.5 A/output, 2.0 A/common
1.2 V max. 1.2 V max.
Residual voltage (0.5 ADC, between each output terminal (0.5 ADC, between each output terminal
and the G terminal) and the V terminal)
Leakage current 0.1 mA max.
ON delay 0.5 ms max.
OFF delay 1.5 ms max.
Number of circuits per
8 points/common
common
Isolation method Photocoupler isolation
I/O power supply method Supply by I/O power supply
GX-MD1612/MD1622
7-4-7 3-tier Terminal Block Type 8-point Input and 8-point Output Slave Unit
(1)
(2)
(8) (7)
1 to 9 NC 0 1 2 3 4 5 6 7 NC 0 1 2 3 4 5 6 7
10 to 18 V1 V1 V1 V1 V1 V1 V1 V1 V1 V2 V2 V2 V2 V2 V2 V2 V2 V2
19 to 27 G1 G1 G1 G1 G1 G1 G1 G1 G1 G2 G2 G2 G2 G2 G2 G2 G2 G2
CN IN
TX+ V1 24 VDC
TX− Photocoupler
RX+ G1
Input circuit
RX−
V1
Physical
layer 0 to 7
CN OUT G1
Internal •
TX+ •
TX−
circuits •
•
•
•
Voltage
drop
RX+ V2 24 VDC
RX−
G2
UNIT PS 0 to 7
DC-DC
+V converter Photocoupler
−V (No-isolation G2
•
type) •
•
•
• •
z GX-MD1622 (PNP)
CN IN
V1 24 VDC
TX+
TX− G1
RX+
RX− Photocoupler V1 7
Input circuit
Physical 0 to 7
layer
GX-MD1612/MD1622
7-4-7 3-tier Terminal Block Type 8-point Input and 8-point Output Slave Unit
CN OUT G1
TX+ Internal • •
• •
TX− circuits • •
RX+ V2 24 VDC
RX−
Voltage
drop
G2
V2
UNIT PS
DC-DC 0 to 7
+V converter
−V (No-isolation G2
type) Photocoupler •
•
•
•
• •
Wiring diagram
z GX-MD1612 (NPN)
NC 0 1 2 3 4 5 6 7 NC 0 1 2 3 4 5 6 7
V1 V1 V1 V1 V1 V1 V1 V1 V1 V2 V2 V2 V2 V2 V2 V2 V2 V2
G1 G1 G1 G1 G1 G1 G1 G1 G1 G2 G2 G2 G2 G2 G2 G2 G2 G2
I/O power
Blue (black)
Blue (black)
Blue (black)
Brown (white)
Brown (red)
Brown (red)
Pink (white)
(24 VDC) supply
(24 VDC)
2-wire sensor NPN output 3-wire Solenoid valve, etc. NPN input 3-wire
(Limit switch, etc.) sensor external device
(Photoelectric sensor, (Emitter of
proximity sensor) photoelectric sensor)
z GX-MD1622 (PNP)
NC 0 1 2 3 4 5 6 7 NC 0 1 2 3 4 5 6 7
V1 V1 V1 V1 V1 V1 V1 V1 V1 V2 V2 V2 V2 V2 V2 V2 V2 V2
G1 G1 G1 G1 G1 G1 G1 G1 G1 G2 G2 G2 G2 G2 G2 G2 G2 G2
I/O power
Brown (red)
Blue (black)
Black (white)
Brown (red)
Pink (white)
2-wire sensor PNP output 3-wire Solenoid valve, etc. PNP input 3-wire
(Limit switch, etc.) sensor external device
(Photoelectric sensor, (Emitter of
proximity sensor) photoelectric sensor)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors. The colors in parentheses are the wire colors prior to the revisions.
GX-MD1612/MD1622
7-4-7 3-tier Terminal Block Type 8-point Input and 8-point Output Slave Unit
Specification
Specification
Item
GX-ID1618 GX-ID1628
Input capacity 16 points
Internal I/O common NPN PNP
15 VDC min. (between each input 15 VDC min. (between each input
ON voltage
terminal and the V terminal) terminal and the G terminal)
5 VDC max. (between each input 5 VDC max. (between each input
OFF voltage
terminal and the V terminal) terminal and the G terminal)
OFF current 1.0 mA max.
6.0 mA max./input (at 24-VDC)
Input current
3.0 mA max./input (at 17-VDC)
ON delay 0.1 ms max.
OFF delay 0.2 ms max.
Without filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms
Input filter value
(Default setting: 1 ms)
Number of circuits per
16 points/common
common
Input indicators LED display (yellow)
Isolation method No isolation
I/O power supply method Supplied from unit power supply
Input device supply
100 mA/point
current
Unit power supply current
150 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
e-CON connector
50 times
insertion durability
Weight 140 g max.
Expansion functions No
Short-circuit protection
Available (Operates at 50 mA/point min.)
function
Notes For the I/O power supply current value to V and G terminals ,refer to "A-5 I/O Power Supply Current" in
Page A - 67.
(1)
(2)
(7) (6)
1 V V V V V V V V 1 V0 V1 V2 V3 V4 V5 V6 V7
2 NC NC NC NC NC NC NC NC 2 NC NC NC NC NC NC NC NC
3 G0 G1 G2 G3 G4 G5 G6 G7 3 G G G G G G G G
4 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 4 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7
8 9 10 11 12 13 14 15 8 9 10 11 12 13 14 15
7
1 V V V V V V V V 1 V8 V9 V10 V11 V12 V13 V14 V15
2 NC NC NC NC NC NC NC NC 2 NC NC NC NC NC NC NC NC
4 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15 4 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15
CN IN
TX+
TX−
RX+
RX− Photocoupler
V
Input circuit
NC
Physical Short-circuit
protection element G0
layer
IN0
Internal circuits
CN OUT
TX+
TX−
RX+
RX− Photocoupler
V
Input circuit
•
•
NC
Short-circuit •
protection element G1
IN1
UNIT PS
DC-DC
+V converter
−V (No-isolation
type)
z GX-ID1628 (PNP)
CN IN
TX+ Short-circuit V0
TX−
protection element
RX+ NC
RX− G
Photocoupler
IN0
Input circuit
Physical
layer
Internal circuits
CN OUT
TX+ Short-circuit
TX− protection element V1
RX+ NC
RX− G
Photocoupler
IN1
Input circuit
UNIT PS
DC-DC
+V converter
−V (No-isolation
type)
• •
• •
• •
Wiring diagram
z GX-ID1618 (NPN)
V V V V V V V V
NC NC NC NC NC NC NC NC
G0 G1 G2 G3 G4 G5 G6 G7
V V V V V V V V
NC NC NC NC NC NC NC NC
Blue (black)
Brown (red)
Black (white)
Blue (black)
Brown (white)
z GX-ID1628 (PNP)
NC NC NC NC NC NC NC NC
G G G G G G G G
NC NC NC NC NC NC NC NC
G G G G G G G G
Blue (black)
Brown (red)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors. The colors in parentheses are the wire colors prior to the revisions.
Specification
Specification
Item
GX-OD1618 GX-OD1628
Output capacity 16 points
Rated current (ON
0.5 A/output, 4.0 A/common
current)
Internal I/O common NPN PNP
1.2 V max. 1.2 V max.
Residual voltage (0.5 ADC, between each output terminal (0.5 ADC, between each output terminal
and the G terminal) and the V terminal)
Leakage current 0.1 mA max.
ON delay 0.5 ms max.
OFF delay 1.5 ms max.
Number of circuits per
16 points/common
common
Output indicators LED display (yellow)
Isolation method Photocoupler isolation
I/O power supply method Supply by I/O power supply
Output device supply
100 mA/point
current
Unit power supply current
80 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
Current consumption from
10 mA max. (for power supply voltage of 20.4 to 26.4 VDC)
I/O power supply
e-CON connector
50 times
insertion durability
Weight 130 g max.
Expansion functions No
Error Mode Output Select either hold or clear.
Short-circuit protection
No
function
Notes For the I/O power supply current value to V and G terminals ,refer to "A-5 I/O Power Supply Current" in
Page A - 67.
(1)
(2)
0 1 2 3 4 5 6 7
1 V V V V V V V V
2 NC NC NC NC NC NC NC NC
3 G G G G G G G G
OUT OUT OUT OUT OUT OUT OUT OUT
4 0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15
7
1 V V V V V V V V
2 NC NC NC NC NC NC NC NC
V
V
G
CN IN G
TX+
TX−
Voltage
drop
RX+ V
RX− NC
Photocoupler G
Physical OUT0
layer
CN OUT
Internal circuits
TX+
TX−
RX+
RX−
Voltage
drop
V
•
•
NC
UNIT PS Photocoupler •
G
DC-DC
+V OUT1
converter
−V (No-isolation
type)
•
•
•
z GX-OD1628 (PNP)
V
V
CN IN G
TX+ G
TX−
RX+
V
RX−
NC
Photocoupler
G
Physical
layer OUT0
Internal circuits
Voltage
CN OUT
drop
TX+
TX−
RX+
RX−
V
•
•
NC
•
G
UNIT PS OUT1
DC-DC
+V converter Photocoupler
−V (No-isolation
type)
Voltage
drop
•
•
•
Wiring diagram
z GX-OD1618 (NPN)
V V V V V V V V
NC NC NC NC NC NC NC NC
G G G G G G G G
V
OUT OUT OUT OUT OUT OUT OUT OUT
V 0 1 2 3 4 5 6 7
G
V V V V V V V V
G
NC NC NC NC NC NC NC NC
G G G G G G G G
Pink (white)
Blue (black)
Brown (red)
I/O power supply
(24 VDC)
z GX-OD1628 (PNP)
NC NC NC NC NC NC NC NC
G G G G G G G G
V
OUT OUT OUT OUT OUT OUT OUT OUT
V 0 1 2 3 4 5 6 7
G
V V V V V V V V
G
NC NC NC NC NC NC NC NC
G G G G G G G G
OUT OUT OUT OUT OUT OUT OUT OUT
8 9 10 11 12 13 14 15
Blue (black)
Brown (red)
Pink (white)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors. The colors in parentheses are the wire colors prior to the revisions.
7-4-10 e-CON Connector Type 8-point Input and 8-point Output Slave Unit
GX-MD1618/MD1628
Specification
Specification
Item
GX-MD1618 GX-MD1628
Internal I/O common NPN PNP
I/O indicators LED display (yellow)
Unit power supply current
120 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
e-CON connector
z Input section
Specification
Item
GX-MD1618 GX-MD1628
Input capacity 8 points
15 VDC min. (between each input 15 VDC min. (between each input
ON voltage
terminal and the V terminal) terminal and the G terminal) 7
5 VDC max. (between each input 5 VDC max. (between each input
OFF voltage
terminal and the V terminal) terminal and the G terminal)
GX-MD1618/MD1628
7-4-10 e-CON Connector Type 8-point Input and 8-point Output Slave Unit
OFF current 1.0 mA max.
6.0 mA max./input (at 24-VDC)
Input current
3.0 mA max./input (at 17-VDC)
ON delay 0.1 ms max.
OFF delay 0.2 ms max.
Without filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms
Input filter value
(Default setting: 1 ms)
Number of circuits per
8 points/common
common
Isolation method No-isolation
I/O power supply method Supplied from unit power supply
Input device supply
100 mA/point
current
I/O power supply current
10 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
z Output section
Specification
Item
GX-MD1618 GX-MD1628
Output capacity 8 points
Rated output current 0.5 A/output, 2.0 A/common
1.2 V max. 1.2 V max.
Residual voltage (0.5 ADC, between each output terminal (0.5 ADC, between each output terminal
and the G terminal) and the V terminal)
Leakage current 0.1 mA max.
ON delay 0.5 ms max.
OFF delay 1.5 ms max.
Number of circuits per
8 points/common
common
Isolation method Photocoupler isolation
I/O power supply method Supply by I/O power supply
Output device supply
100 mA/point
current
I/O power supply current
10 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
Error Mode Output Select either hold or clear.
Notes For the I/O power supply current value to V and G terminals ,refer to "A-5 I/O Power Supply Current" in
Page A - 67.
(3) (4)
(5)
(6)
(1)
(2)
GX-MD1618 GX-MD1628
Top side: input Bottom side: output Top side: input Bottom side: output
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
1 V1 V1 V1 V1 V1 V1 V1 V1 1 V0 V1 V2 V3 V4 V5 V6 V7
2 NC NC NC NC NC NC NC NC 2 NC NC NC NC NC NC NC NC
3 G0 G1 G2 G3 G4 G5 G6 G7 3 G1 G1 G1 G1 G1 G1 G1 G1
4 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 4 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7
8 9 10 11 12 13 14 15 8 9 10 11 12 13 14 15
7
1 V V V V V V V V 1 V ● V V V V V V V
GX-MD1618/MD1628
7-4-10 e-CON Connector Type 8-point Input and 8-point Output Slave Unit
2 NC NC NC NC NC NC NC NC 2 NC NC NC NC NC NC NC NC
3 G G G G G G G G 3 G G G G G G G G
OUT OUT OUT OUT OUT OUT OUT OUT 4 OUT OUT OUT OUT OUT OUT OUT OUT
4 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
CN IN
TX+ Photocoupler
V1
Input circuit
TX−
RX+ • NC
RX−
Short-circuit •
•
G0
protection element
IN0
•
Physical •
•
layer Internal circuits
CN OUT
TX+
TX−
RX+
RX−
Voltage
drop
V
NC
Photocoupler G
OUT0
UNIT PS
DC-DC
+V converter
−V (No-isolation V
type) V
G
G
z GX-MD1628 (PNP)
CN IN
TX+ Photocoupler
Input circuit
TX−
RX+
RX−
Short-circuit V0
protection element
•
•
NC
Physical
•
G1
layer IN0
•
CN OUT
Internal circuits
•
•
TX+
V
TX−
RX+ V
RX− G
G
V
•
NC
UNIT PS Photocoupler •
•
DC-DC G
+V converter OUT0
Voltage
−V (No-isolation
drop
type)
•
•
•
Wiring diagram
z GX-MD1618 (NPN)
V1 V1 V1 V1 V1 V1 V1 V1
NC NC NC NC NC NC NC NC
G0 G1 G2 G3 G4 G5 G6 G7
V
IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7
V
G
V V V V V V V V
I/O power supply G
(24 VDC) NC NC NC NC NC NC NC NC
G G G G G G G G
Black (white)
Blue (black)
Pink (white)
Blue (black)
Brown (white)
Blue (black)
Brown (red)
Brown (red)
2-wire sensor Solenoid valve, etc. NPN input 3-wire NPN output 3-wire
(Limit switch, etc.) external device sensor
(Emitter of (Photoelectric sensor,
photoelectric sensor) proximity sensor)
z GX-MD1628 (PNP)
7
GX-MD1618/MD1628
7-4-10 e-CON Connector Type 8-point Input and 8-point Output Slave Unit
V0 V1 V2 V3 V4 V5 V6 V7
NC NC NC NC NC NC NC NC
G1 G1 G1 G1 G1 G1 G1 G1
V
IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7
V
G
V V V V V V V V
I/O power supply G
(24 VDC) NC NC NC NC NC NC NC NC
G G G G G G G G
OUT OUT OUT OUT OUT OUT OUT OUT
0 1 2 3 4 5 6 7
Blue (black)
Pink (white)
Blue (black)
Blue (black)
Black (white)
Brown (red)
Brown (white)
Brown (red)
2-wire sensor Solenoid valve, etc. PNP input 3-wire PNP output 3-wire
(Limit switch, etc.) external device sensor
(Emitter of (Photoelectric sensor,
photoelectric sensor) proximity sensor)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors. The colors in parentheses are the wire colors prior to the revisions.
Specification
Specification
Item
GX-ID3218 GX-ID3228
Input capacity 32 points
Internal I/O common NPN PNP
15 VDC min. (between each input 15 VDC min. (between each input
ON voltage
terminal and the V terminal) terminal and the G terminal)
5 VDC max. (between each input 5 VDC max. (between each input
OFF voltage
terminal and the V terminal) terminal and the G terminal)
(1)
(2)
(7) (6)
1 V V V V V V V V 1 V V V V V V V V
2 NC NC NC NC NC NC NC NC 2 NC NC NC NC NC NC NC NC
3 G0 G1 G2 G3 G4 G5 G6 G7 3 G0 G1 G2 G3 G4 G5 G6 G7
4 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 4 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7
8 9 10 11 12 13 14 15 8 9 10 11 12 13 14 15
1 V V V V V V V V 1 V V V V V V V V
2 NC NC NC NC NC NC NC NC 2 NC NC NC NC NC NC NC NC
3 G8 G9 G10 G11 G12 G13 G14 G15 3 G8 G9 G10 G11 G12 G13 G14 G15
4 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15 4 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15
• GX-ID3228
IN1 IN2
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
1 V0 V1 V2 V3 V4 V5 V6 V7 1 V0 V1 V2 V3 V4 V5 V6 V7
2 NC NC NC NC NC NC NC NC 2 NC NC NC NC NC NC NC NC
3 G G G G G G G G 3 G G G G G G G G
4 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 4 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7
8 9 10 11 12 13 14 15 8 9 10 11 12 13 14 15
1 V8 V9 V10 V11 V12 V13 V14 V15 1 V8 V9 V10 V11 V12 V13 V14 V15
2 NC NC NC NC NC NC NC NC 2 NC NC NC NC NC NC NC NC
3 G G G G G G G G 3 G G G G G G G G
4 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15 4 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15
CN IN
TX+
TX−
RX+
RX− Photocoupler
V
Input circuit
NC
Physical Short-circuit
protection element G0
layer
IN0
Internal circuits
CN OUT
TX+
TX−
RX+
RX− Photocoupler
V
Input circuit
•
• NC
Short-circuit •
protection element G1
IN1
UNIT PS
DC-DC
+V converter
−V (No-isolation
type)
z GX-ID3228 (PNP)
CN IN
TX+ Short-circuit V0
TX−
protection element
RX+ NC
RX− G
Photocoupler
IN0
Input circuit
Physical
layer
CN OUT
Internal circuits
TX+ Short-circuit
TX− protection element V1
RX+ NC
RX− G
Photocoupler
IN1
Input circuit
UNIT PS
DC-DC
+V converter
−V (No-isolation
type)
• •
• •
• •
Wiring diagram
z GX-ID3218 (NPN)
V V V V V V V V V V V V V V V V
NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC
G0 G1 G2 G3 G4 G5 G6 G7 G0 G1 G2 G3 G4 G5 G6 G7
IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7
V V V V V V V V V V V V V V V V
NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC
G8 G9 G10 G11 G12 G13 G14 G15 G8 G9 G10 G11 G12 G13 G14 G15
Black (white)
Blue (black)
Brown (white)
Blue (black)
Brown (red)
z GX-ID3228 (PNP)
NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC
G G G G G G G G G G G G G G G G
IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7
V8 V9 V10 V11 V12 V13 V14 V15 V8 V9 V10 V11 V12 V13 V14 V15
NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC
G G G G G G G G G G G G G G G G
IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15
Blue (black)
Brown (white)
Black (white)
Blue (black)
Brown (red)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors. The colors in parentheses are the wire colors prior to the revisions.
Specification
Specification
Item
GX-OD3218 GX-OD3228
Output capacity 32 points
Rated current (ON
0.5 A/output, 4.0 A/common
current)
Internal I/O common NPN PNP
1.2 V max. 1.2 V max.
Residual voltage (0.5 ADC, between each output terminal (0.5 ADC, between each output terminal
and the G terminal) and the V terminal)
Leakage current 0.1 mA max.
ON delay 0.5 ms max.
OFF delay 1.5 ms max.
Number of circuits per
16 points/common
common
Output indicators LED display (yellow)
Isolation method Photocoupler isolation
I/O power supply method Supply by I/O power supply
Output device supply
100 mA/point
current
Unit power supply current
100 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
Current consumption from
10 mA max. (for power supply voltage of 20.4 to 26.4 VDC)
I/O power supply
e-CON connector
50 times
insertion durability
Weight 210 g max.
Expansion functions No
Error Mode Output Select either hold or clear.
Short-circuit protection
No
function
Notes For the I/O power supply current value to V and G terminals ,refer to "A-5 I/O Power Supply Current" in
Page A - 67.
(1)
(2)
OUT1 OUT2
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
1 V V V V V V V V 1 V V V V V V V V
2 NC NC NC NC NC NC NC NC 2 NC NC NC NC NC NC NC NC
3 G G G G G G G G 3 G G G G G G G G
OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT
4 0 1 2 3 4 5 6 7 4 0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15 8 9 10 11 12 13 14 15 7
1 V V V V V V V V 1 V V V V V V V V
2 NC NC NC NC NC NC NC NC
3 G G G G G G G G 3 G G G G G G G G
4 OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT
8 9 10 11 12 13 14 15 4 8 9 10 11 12 13 14 15
V
V
G
G
Voltage
CN IN
drop
V
TX+ NC
TX− Photocoupler Left side
G
RX+
RX−
OUT0
•
•
•
Physical
layer
Internal circuits
CN OUT
•
TX+ •
•
TX−
RX+
RX−
V
V
G
G
Voltage
UNIT PS
drop
DC-DC V
+V converter NC Right side
−V (No-isolation Photocoupler G
type) OUT0
•
•
•
•
•
•
z GX-OD3228 (PNP)
V
V
CN IN G
G
TX+
TX−
RX+ V Left side
RX− Photocoupler • NC
•
• G
OUT0
Physical
Voltage
drop
layer
Internal circuits
CN OUT •
•
TX+ •
TX−
RX+
RX− V
V
G
G
•
•
•
Wiring diagram
z GX-OD3218 (NPN)
V V V V V V V V V V V V V V V V
NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC
G G G G G G G G G G G G G G G G
V V
OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT
V 0 1 2 3 4 5 6 7 V 0 1 2 3 4 5 6 7
G G
V V V V V V V V V V V V V V V V
G G
NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC
G G G G G G G G G G G G G G G G
Blue (black)
Brown (red)
Pink (white)
I/O power supply
(24 VDC)
z GX-OD3228 (PNP)
V V V V V V V V V V V V V V V V
G G G G G G G G G G G G G G G G
V V
OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT
V 0 1 2 3 4 5 6 7 V 0 1 2 3 4 5 6 7
G G
V V V V V V V V V V V V V V V V
G G
NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC
G G G G G G G G G G G G G G G G
OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT
8 9 10 11 12 13 14 15 8 9 10 11 12 13 14 15
Pink (white)
Blue (black)
Brown (red)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors. The colors in parentheses are the wire colors prior to the revisions.
7-4-13 e-CON Connector Type 16-point Input and 16-point Output Slave Unit
GX-MD3218/MD3228
Specification
Specification
Item
GX-MD3218 GX-MD3228
Internal I/O common NPN PNP
I/O indicators LED display (yellow)
Unit power supply current
150 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
e-CON connector
z Input section
Specification
Item
GX-MD3218 GX-MD3228
Input capacity 16 points
15 VDC min. (between each input 15 VDC min. (between each input
ON voltage
terminal and the V terminal) terminal and the G terminal) 7
5 VDC max. (between each input 5 VDC max. (between each input
OFF voltage
terminal and the V terminal) terminal and the G terminal)
GX-MD3218/MD3228
7-4-13 e-CON Connector Type 16-point Input and 16-point Output Slave Unit
OFF current 1.0 mA max.
6.0 mA max./input (at 24-VDC)
Input current
3.0 mA max./input (at 17-VDC)
ON delay 0.1 ms max.
OFF delay 0.2 ms max.
Without filter, 0.5 ms, 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms
Input filter value
(Default setting: 1 ms)
Number of circuits per
16 points/common
common
Isolation method No-isolation
I/O power supply method Supplied from unit power supply
Input device supply
100 mA/point
current
I/O power supply current
10 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
z Output section
Specification
Item
GX-MD3218 GX-MD3228
Output capacity 16 points
Rated output current 0.5 A/output, 2.0 A/common
1.2 V max. 1.2 V max.
Residual voltage (0.5 ADC, between each output terminal (0.5 ADC, between each output terminal
and the G terminal) and the V terminal)
Leakage current 0.1 mA max.
ON delay 0.5 ms max.
OFF delay 1.5 ms max.
Number of circuits per
16 points/common
common
Isolation method Photocoupler isolation
I/O power supply method Supply by I/O power supply
Output device supply
100 mA/point
current
I/O power supply current
10 mA max. (for 20.4 to 26.4-VDC power supply voltage)
consumption
Error Mode Output Select either hold or clear.
Notes For the I/O power supply current value to V and G terminals ,refer to "A-5 I/O Power Supply Current" in
Page A - 67.
(1)
(2)
1 V V V V V V V V 1 V V V V V V V V
2 NC NC NC NC NC NC NC NC 2 NC NC NC NC NC NC NC NC
3 G0 G1 G2 G3 G4 G5 G6 G7 3 G G G G G G G G
4 IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 4 OUT OUT OUT OUT OUT OUT OUT OUT
0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15 8 9 10 11 12 13 14 15 7
1 V V V V V V V V 1 V V V V V V V V
GX-MD3218/MD3228
7-4-13 e-CON Connector Type 16-point Input and 16-point Output Slave Unit
2 NC NC NC NC NC NC NC NC 2 NC NC NC NC NC NC NC NC
4 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15 4 OUT OUT OUT OUT OUT OUT OUT OUT
8 9 10 11 12 13 14 15
CN IN
TX+ Left side
TX− Photocoupler
V
Input circuit
RX+
RX− NC
Short-circuit
protection element G0
IN0
Physical
layer Internal circuits
CN OUT
TX+ •
•
TX− •
Voltage
drop
RX+
V
RX− •
•
• NC
Photocoupler G
OUT0
Right side
UNIT PS
DC-DC V
+V converter V
−V (No-isolation G
type) G
z GX-MD3228 (PNP)
CN IN
TX+
Photocoupler
Input circuit
TX−
RX+ Left side
RX− Short-circuit
protection element V0
• NC
•
Physical • G
layer IN0
•
Internal circuits
CN OUT •
•
TX+
TX−
RX+
RX− V
V
G
G
UNIT PS V
DC-DC •
NC Right side
+V Photocoupler •
converter •
G
−V (No-isolation OUT0
Voltage
type)
drop
•
•
•
Wiring diagram
z GX-MD3218 (NPN)
V V V V V V V V V V V V V V V V
NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC
G0 G1 G2 G3 G4 G5 G6 G7 G G G G G G G G
V
OUT OUT OUT OUT OUT OUT OUT OUT
IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 0 1 2 3 4 5 6 7
V
G
V V V V V V V V V V V V V V V V
G
NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC
Blue (black)
Brown (white)
Brown (red)
Blue (black)
z GX-MD3228 (PNP)
NC
V
NC
V
NC
V
NC
V
NC
V
NC
V
NC
V
NC
V
NC
V
NC
V
NC
V
NC
V
NC
V
NC
V
NC
V
NC
7
G0 G1 G2 G3 G4 G5 G6 G7 G G G G G G G G
V
OUT OUT OUT OUT OUT OUT OUT OUT
IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 0 1 2 3 4 5 6 7
GX-MD3218/MD3228
7-4-13 e-CON Connector Type 16-point Input and 16-point Output Slave Unit
V
G
V V V V V V V V V V V V V V V V
G
NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC NC
Blue (black)
Brown (white)
Brown (red)
Blue (black)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors. The colors in parentheses are the wire colors prior to the revisions.
z GX-ID1611/ID1621/OD1611/OD1621
135
52
50
73.9
57.1
(mm) 7
z GX-OC1601
50
3.14
74.4
57.6
(mm)
z GX-MD1611/MD1621
135
52
50
3.14
73.9
57.1
(mm)
200
52
50
3.14
93.5
68.9
10.1 (mm)
115
52
50
3.14
43.85
z GX-OD1618/OD1628/MD1618/MD1628
115
50
3.14
49.8
(mm)
z GX-ID3218/ID3228
180
52
50
3.14
43.85
(mm)
z GX-OD3218/OD3228
180
52
50
3.14
49.8
(mm)
z GX-MD3218/MD3228
52 180
50
3.14
49.8
(mm)
Converted data
Hexadecimal (decimal)
20D0 (8400)
1F40 (8000)
8
0000 (0)
z Input range 1 to 5 V
Voltage of 1 to 5 V is converted to data from 0000 to 1F40 hex (0 to 8000). The input data range for
which conversion is possible is 0.8 to 5.2 V and here the output data is FE70 to 20D0 hex (−400 to
+8400). If the input voltage drops below the input range to lower than 0.3 V due to disconnection
and so on, the disconnected line detection is activated and the data is set to 7FFF hex.
Converted data
Hexadecimal (decimal)
20D0 (8400)
1F40 (8000)
7FFF
0.3 V
(Disconnection in case it is less than 0.3 V)
z Input range 0 to 10 V
Voltage of 0 to 10 V is converted to data from 0000 to 1F40 hex (0 to 8000). The input data range for
which conversion is possible is −0.5 to 10.5 V and here the output data is FE70 to 20D0 hex (−400
to +8400). When input data is a negative voltage, it is expressed as the two's complement
(hexadecimal) and the output data for a disconnected line is the same as for an input of 0 V (0000
hex).
Converted data
Hexadecimal (decimal)
20D0 (8400)
1F40 (8000)
0000 (0)
−0.5 V
Voltage
0V 10 V 10.5 V
FE70 (−400)
Converted data
Hexadecimal (decimal)
1130 (4400)
0FA0 (4000)
F060 (−4000)
EED0 (−4400)
Converted data
Hexadecimal (decimal)
20D0 (8400)
1F40 (8000)
1.2 mA
(Disconnection in case it is less than 1.2 mA)
For how to set with the input range switch, refer to "Names and functions" in Page 8 - 20.
Offset
(byte) 7 bit 0 bit
0
Analog input data for CH1
+1
+2
Analog input data for CH2
+3
+4
Analog input data for CH3
+5
+6
Analog input data for CH4
+7
Offset
(byte) 7 bit 0 bit
0
Analog input data for CH1
+1
+2
Analog input data for CH2
+3
+4
Analog input data for CH3
+5
+6
Analog input data for CH4
+7
Overview of functions
z Purpose
This function sets to skip processing unused points, and enhances the speed of refresh cycles of
analog input.
Whether AD conversion is enabled or disabled is settable for each point. (Default setting: Enable for
all channels)
Notes Regardless of this setting, an Analog Input Slave Unit uses four points of data allocation
area.
Setting method
8
Set by SDO communications.
The target index is 3100 hex.
The table below shows the analog conversion time by the number of AD conversion available points.
Enabled
Conversion time [μs]
channel
1 point 500
2 points 1000
3 points 1500
4 points 2000
Overview of functions
z Purpose
The function averages the inputs if they fluctuates minutely due to noise and so on as shown in the
figure below, and obtains smooth input values.
Analog
input value
Actual input
Input after averaging processing
Time
z Details of functions
This function is used to calculate the average value of analog inputs during a period of up to 64 ms,
and generate it as converted data.
The setting is made with the Analogue Input Moving Average object. You can use the following
formula to calculate the sampling count from the setting of the Analogue Input Moving Average
object and the number of AD conversion available points. Digits below the decimal point are
rounded up.
Sampling count = Setting of the Analogue Input Moving Average [μs]/(Number of AD conversion
available points × 500 μs)
The processing that is performed inside the Unit is shown below for when the sampling count is 4.
At the initial calculation, the initial data is stored in all processing buffers to perform the moving
average processing.
D3 D5
D2
D1
Time [ms]
Moving average 5th time 2nd time 3rd time 4th time
Moving average value = (D2 + D3 + D4 + D5) /4
calculation (5th) data data data data
Internal buffer
Setting method
Set by SDO communication.
The target index is 3132 hex. 8
For the details, refer to the information in the corresponding index of "Appendix A-1 Object Dictionary"
in Page A - 42.
Overview of functions
z Purpose
The function detects a disconnection of analog input signal line.
Note that this function is valid only when the input range is "1 to 5 V" or "4 to 20 mA."
z Details of functions
If any analog input signal line (voltage/current inputs) of the points that are enabled by the "AD
Conversion Available Point Setting" is disconnected, the disconnected line detection flag of that
point (target index: 3136 hex) is turned ON.
If the moving average is enabled, the function works to detect a disconnected line in moving
average processing results.
The AD converted data at disconnected line detection is 7FFF hex.
If the input returns to the convertible range again, this function is automatically cancelled and normal
conversion data is input.
The table below shows details of the disconnected line detection flag.
Bits State
0 1: CH1 disconnected / 0: CH1 normal
1 1: CH2 disconnected / 0: CH2 normal
2 1: CH3 disconnected / 0: CH3 normal
3 1: CH4 disconnected / 0: CH4 normal
4 to 15 Reserved
Overview of functions
z Purpose
If final input voltage and current deviates due to characteristics of input devices and methods of
connection, correct the "deviation" and adjust inputs.
z Details of functions
This function corrects conversion values of input voltages and currents at 2 points, 0% and 100%,
as shown in the figure below.
Converted data
After correction
Before correction
0%
100% Voltage/current
The correctable range is from −5% to +5% each of the minimum and maximum input values.
The correctable range for each input range is as follows.
Setting method
Set by SDO communication.
The target indexes are as follows.
• Upper limit correction: 3112 hex Analogue Input Adjustment High Execute (user adjustment 8
execution (upper limit))
• Lower limit correction: 3115 hex Analogue Input Adjustment Low Execute (user adjustment execution
For the correction procedure, refer to the information in the corresponding index of "Appendix A-1
Object Dictionary" in Page A - 41.
z Output range 0 to 5 V
Data from 0000 to 1F40 hex (0 to 8000) is converted to voltage from 0 to 5 V and output.
The output data range for which conversion is possible is FE70 to 20D0 hex (−400 to +8400) and
here the output data is −0.25 to +5.25 V.
Voltage
5.25 V
5V
0V
8000 FE70 (−400) Converted data
1F40 20D0 7FFF Hexadecimal (decimal)
−0.25 V 0000 (0) (8000) (8400)
z Output range 1 to 5 V
Data from 0000 to 1F40 hex (0 to 8000) is converted to voltage from 1 to 5 V and output.
The output data range for which conversion is possible is FE70 to 20D0 hex (−400 to +8400) and
here the output data is 0.8 to 5.2 V.
Voltage
5.2 V
5V
1V
0.8 V
0V Converted data
8000 FE70 0000 (0) 1F40 20D0 7FFF Hexadecimal (decimal)
(−400) (8000) (8400)
z Output range 0 to 10 V
Data from 0000 to 1F40 hex (0 to 8000) is converted to voltage from 0 to 10 V and output.
The output data range for which conversion is possible is FE70 to 20D0 hex (−400 to +8400) and
here the output data is −0.5 to +10.5 V.
Voltage
10.5 V
10 V
0V
FE70
8000 (−400) Converted data
1F40 20D0 7FFF Hexadecimal (decimal)
−0.5 V 0000 (0)
(8000) (8400)
Voltage
11 V
10 V
EED0 F060
8000 (−4400) (−4000) 0000 (0) Converted data
0V 0FA0 1130 7FFF Hexadecimal (decimal)
(4000) (4400)
-10 V
-11 V 8
Current
20.8 mA
20 mA
4 mA
3.2mA
0 mA Converted data
8000 FE70 0000 (0) 1F40 20D0 7FFF Hexadecimal (decimal)
(−400) (8000) (8400)
For how to set with the output range switch, refer to "Names and functions" in Page 8 - 23.
Offset
(byte) 7 bit 0 bit
0
Analog output data for CH1
+1
+2
Analog output data for CH2
+3
Offset
(byte) 7 bit 0 bit
Overview of functions
z Purpose
This function sets to skip processing unused points, and enhances the speed of refresh cycles of
z Details of functions
Normally in this Unit, the values for two input points are converted in sequence. The setting can be
changed, so that unused points are not converted.
By reducing the number of conversion points, the conversion cycle speed is increased.
Whether DA conversion is enabled or disabled is settable for each point. (Default setting: Enable all
channels)
Notes Regardless of this setting, an Analog Output Slave Unit uses two points of data allocation area.
Setting method
Set by SDO communications. 8
The target index is 3200 hex.
For the set values, refer to the information in the corresponding index of "Appendix A-1 Object
The table below shows the analog conversion time by the number of DA conversion available points.
Enabled
Conversion time [μs]
channel
1 point 500
2 points 1000
Overview of functions
z Purpose
This function outputs set values if a communications error occurs.
z Details of functions
It is possible to set a value to be output when a communications error occurs for each point.
Select an output value from the following 5 patterns.
Setting method
Set by SDO communications.
The target index is 3240 hex.
For the set values, refer to the information in the corresponding index of "Appendix A-1 Object
Dictionary" in Page A - 45.
Overview of functions
z Purpose
If final output voltage and current deviates due to characteristics of output devices and methods of
connection, correct the "deviation" and adjust outputs.
z Details of functions
This function corrects conversion values of output voltages and currents at 2 points, 0% and 100%,
as shown in the figure below.
Converted data
After correction
0%
100 % Voltage/current
The correctable range is from −5% to +5% each of the minimum and maximum values of outputs.
The correctable range for each output range is as follows.
8
Output range Low limit High limit
0 to 5 V −0.25 to +0.25 V 4.75 to 5.25 V
Setting method
Set by SDO communications.
The target indexes are as follows.
• Upper limit correction: 3212 hex Analogue Output Adjustment High Execute (user adjustment
execution (upper limit))
• Lower limit correction: 3215 hex Analogue Output Adjustment Low Execute (user adjustment
execution (lower limit))
For the correction procedure, refer to the information in the corresponding index of "Appendix A-1
Object Dictionary" in page A-44.
Reference page
Internal
Type Model Names and Wiring
Specification circuits
functions diagram
diagram
4-point Input Slave
GX-AD0471 8-19 8-20 8-22 8-22
Unit
2-point Output
GX-DA0271 8-23 8-23 8-25 8-26
Slave Unit
Specification
Specification
Item
Voltage input Current input
Input capacity 4 points (possible to set number of enabled points)
0 to 5 V
1 to 5 V
Input range 4 to 20 mA
0 to 10 V
−10 to +10 V
Input range setting Input range switch: Common to input CH1/CH2, common to input CH3/CH4
method SDO communications: Possible to set input CH1 to CH4 separately
Maximum signal input ±15 V ±30 mA
Input impedance 1 MΩ min. Approx. 250 Ω
Resolution 1/8000 (full scale)
(1)
(2)
(7) (6)
V1 I1 V2 I2 V3 I3 V4 I4
NC
+ + + + + + + +
AG V1 AG V2 AG V3 AG V4 NC
− − − −
V+
510 kΩ
I+
250 Ω
V−
510 kΩ
AG
Analog GND
Wiring diagram
Short-circuit *
Voltage input 0V
0V Current input
Specification
Specification
Item
Voltage output Current output
Output capacity 2 points (possible to set number of enabled points)
0 to 5 V
1 to 5 V
Output range 4 to 20 mA
0 to 10 V
−10 to +10 V
Output range setting Output range switch, SDO communications:
method Possible to set outputs CH1 and CH2 separately.
External output allowable
5 kΩ min. 600 Ω max.
load resistance
Resolution 1/8000 (full scale)
8
Names and functions
(1)
(2)
(7) (6)
V1 I1 V2 I2 NC
+ + + + NC NC NC NC
NC 1 NC 2 NC NC NC NC NC
− −
I+
V+
−*
Analog GND
* Negative terminals of output CH1 and output CH2 are internally connected. 8
Wiring diagram
NC 1− NC 2− NC NC NC NC NC
Output 1:
At voltage output
Output 2:
External At current output
device
External
device
135
52
50
3.14
73.9
57.1
z Counter status + counter present value data + external latch A data + external
latch B data (size = 26 bytes)
Offset
(byte) D07 D06 D05 D04 D03 D02 D01 D00
+2 (LL)
+3 (LH)
CH1 Present value data
+4 (HL)
+5 (HH)
+6 (LL)
+7 (LH)
CH2 Present value data
+8 (HL)
+9 (HH)
+10 (LL)
+11 (LH)
CH1 Latch A data
+12 (HL)
+13 (HH)
+14 (LL)
+15 (LH)
CH2 Latch A data
+16 (HL)
+17 (HH)
+18 (LL)
+19 (LH)
CH1 Latch B data
+20 (HL)
+21 (HH)
+22 (LL)
+23 (LH)
CH2 Latch B data
+24 (HL)
+25 (HH)
z Counter status + counter present value data + external latch A data + external
latch B data + Sysmac error status (size = 27 bytes)
Offset
(byte) D07 D06 D05 D04 D03 D02 D01 D00
+2 (LL)
+3 (LH)
CH1 Present value data
+4 (HL)
+5 (HH)
+6 (LL)
+7 (LH)
CH2 Present value data
+8 (HL)
+9 (HH)
+10 (LL)
+11 (LH)
CH1 Latch A data
+12 (HL)
+13 (HH)
+14 (LL)
+15 (LH)
CH2 Latch A data
+16 (HL)
+17 (HH)
+19 (LH)
CH1 Latch B data
+20 (HL)
+21 (HH)
+22 (LL)
+23 (LH)
CH2 Latch B data
+24 (HL)
+25 (HH) 9
+26 Sysmac error status 9-2-1 Input Data Allocation
Abbreviations used for the counter status information description have the following meanings.
Offset
(byte) D07 D06 D05 D04 D03 D02 D01 D00
+4 (LL)
+6 (HL)
+7 (HH)
+8 (LL)
+10 (HL)
+11 (HH)
Abbreviati
Status name Operation Detection
on
0: Disabled
1: Enabled
EXLBEn External latch B enabled Level
0: Disabled
Clear present value
EXRESCn external reset generation 0→1: Clear flag Edge
flag
Clear external latch A
EXLACn 0→1: Clear flag Edge
generation flag
Clear external latch B
EXLBCn 0→1: Clear flag Edge
generation flag
Count continuously
counter value
If the counter value exceeds the maximum value, the counter value returns to 0 to continue count
operation.
If the counter value becomes less than 0, the counter value returns to the maximum value to continue
count operation.
Setting method
The settings are made using the SDO communications.
The target index is 4003 hex.
For the details, refer to the information in the corresponding index of "Appendix A-1 Object Dictionary"
in Page A - 47.
Note that SDO communications are used for setting an input method. (Default setting: Phase A/B
phase difference pulse input (Multiplication × 4))
The target index is 4002 hex.
For the set values, refer to the information in the corresponding index of "Appendix A-1 Object
Dictionary" in Page A - 47.
Phase B
Multiplication x 1 0 1 2 3 2 1
Multiplication x 4 0 1 2 3 4 5 6 7 8 9 10 11 12 11 10 9 8 7 6 5 4 3 2 1
When phase A/B phase difference pulse is input, the connection with external input devices
becomes as follows.
Input A
A
Encoder Input B
B
Input Z
Z
(Reset Input)
Counter value 0 1 2 3 4 5 6 7 8 7 6 5 4 3 2 1 0
When code and pulses are input, the connection with external input devices becomes as follows.
Encoder or other
Input A
pulse generators Count pulse
Input B
Sensor or
Input Z
switch Count direction
control
Input A
Input B
Counter value 0 1 2 3 4 5 6 7 8 7 6 5 4 3 2 1 0
When incremental/decremental pulses are input, the connection with external input devices
becomes as follows.
Encoder or other
Input A
pulse generators Incremental
pulse
Input B
Encoder or other
Input Z
pulse generators Decremental
pulse
CW CCW
Note that SDO communications are used to set encoder direction. (Default setting: Forward direction at
9-3-4 Encoder Direction Setting
CW)
The target index is 4001 hex.
For the set values, refer to the information in the corresponding index of "Appendix A-1 Object
Dictionary" in Page A - 46.
If the counter value is reset via input of the present value external reset or phase Z, the "external reset
generation flag" is turned ON. By changing "clear present value external reset generation flag" from 0 to
1, "external reset generation flag" is cleared, enabling the next reset reception.
Preset value
internal reset execution
[soft switch]
For both latch A and B inputs, when latch is generated via latch input, the "external latch generation
flag" changes from 0 to 1 and the counter value is stored in objects (latch value A/latch value B) as
latch A/latch B data.
By changing "clear external latch generation flag" from 0 to 1, it is possible to clear the "external
latch generation flag."
When the "external latch generation flag" is cleared, the next latch input becomes enabled. 9
If it is desired to use latched counter values (latch values) in a ladder program, select PDO mapping
9-3-6 Counter Preset
* To use SDO communications, acquire/store the present counter value at the rise of latch A/B of external
control input, regardless of the status of the soft switch "external latch A/B enabled."
Reference page
Internal
Type Model Names and Wiring
Specification circuits
functions diagram
diagram
Open collector
GX-EC0211 9-15 9-17 9-20 9-21
input type
Line driver
GX-EC0241 9-23 9-25 9-28 9-29
Input type
Specification
Item Specification
Counter point 2 points
Counter phase A
Counter phase B
Input signal Counter phase Z
Latch input (A/B)
Counter reset input
Counter enabled status
LED display (green)
display
Input indicators LED display (yellow)
Unit power supply current
130 mA max. (for 20.4 to 26.4 VDC power supply voltage)
consumption
Weight 390 g max.
Specification
Item
Counter phase A/B Counter phase Z
20.4 to 26.4 VDC 20.4 to 26.4 VDC
4.5 to 5.5 VDC 4.5 to 5.5 VDC
Input voltage (24 VDC −15 to (24 VDC −15 to
(5 VDC ± 5%) (5 VDC ± 5%)
+10%) +10%)
8.4 mA 8.6 mA 8.4 mA 8.6 mA
Input current
(at 24 VDC) (at 5 VDC) (at 24 VDC) (at 5 VDC)
ON voltage 19.6 V min. 4.5 V min. 18.6 V min. 4.5 V min.
OFF voltage 4 V max. 1.5 V max. 4 V max. 1.5 V max.
Input restriction resistance 2.7 kΩ 430 Ω 2.7 kΩ 430 Ω
Maximum response Single phase 500 kHz (phase difference
125 kHz 9
frequency Multiplication × 4, 125 kHz)
Filter switching NA NA 9-4-1 Open collector input type GX-EC0211
B B G
ON
voltage
Terminal Terminal
input input OFF
OFF
voltage voltage
A A A A
ON
voltage
Phase A
OFF
voltage
A A
Terminal F F F F
input
E
ON
voltage
Phase B
OFF
voltage
A A
Timing condition
A B C D E F G
<0.3 μs >1 μs >2 μs >4 μs >8 μs >2 μs >4 μs
Specification
Item
Latch input (A/B) Reset input
Internal I/O common NPN
Input voltage 20.4 to 26.4 VDC (24 VDC −15 to +10%) 20.4 to 26.4 VDC (24 VDC −15 to +10%)
Input impedance 4.0 kΩ 3.3 kΩ
Input current 5.5 mA (at 24 VDC) 7 mA (at 24 VDC)
ON voltage/ON current 17.4 VDC min./3 mA min. 14.4 VDC min./3 mA min.
OFF voltage/OFF current 5 VDC max./1 mA max. 5 VDC max./1 mA max.
ON response time 3 μs max. 15 μs max.
OFF response time 3 μs max. 90 μs max.
(1)
(7) (6)
CH1 CH2
1 to 9 RSV RSV V1 V1 V1 RSV LA1 LB1 RST1 RSV RSV V1 V1 V1 RSV LA2 LB2 RST2
9
10 to 18 V1 V1 A24 B24 Z24 V2 V2 V2 V2 V1 V1 A24 B24 Z24 V2 V2 V2 V2
9-4-1 Open collector input type GX-EC0211
19 to 27 G1 G1 A5 B5 Z5 G2 G2 G2 G2 G1 G1 A5 B5 Z5 G2 G2 G2 G2
• Input indicators
CH1 CH2
Name State Contents Name State Contents
Lit green. Counter operating Lit green. Counter operating
CH1 CH2
OFF Counter stopped OFF Counter stopped
Input A (phase A signal/count Input A (phase A signal/count
Lit Lit
pulse signal/incremental count pulse signal/incremental count
yellow. yellow.
signal) available signal) available
A1 A2
Input A (phase A signal/count Input A (phase A signal/count
OFF pulse signal/incremental count OFF pulse signal/incremental count
signal) not available signal) not available
Input B (phase B signal/count Input B (phase B signal/count
Lit direction control Lit direction control
yellow. signal/decremental count signal) yellow. signal/decremental count signal)
available available
B1 B2
Input B (phase B signal/count Input B (phase B signal/count
direction control direction control
OFF OFF
signal/decremental count signal) signal/decremental count signal)
not available not available
Lit Lit
Phase Z input available Phase Z input available
Z1 yellow. Z2 yellow.
OFF Phase Z input not available OFF Phase Z input not available
Lit Lit
External latch input A available External latch input A available
yellow. yellow.
LA1 LA2
External latch input A not External latch input A not
OFF OFF
available available
Lit Lit
External latch input B available External latch input B available
yellow. yellow.
LB1 LB2
External latch input B not External latch input B not
OFF OFF
available available
Lit Lit
External reset input available External reset input available
RST1 yellow. RST2 yellow.
OFF External reset input not available OFF External reset input not available
• Terminal block
Terminal
CH block Terminal name Contents
number
1 RSV -
2 RSV -
Encoder power supply input (power supply input at twisted-pair
3 V1
wiring)
Encoder power supply input (power supply input at twisted-pair
4 V1
wiring)
Encoder power supply input (power supply input at twisted-pair
5 V1
wiring)
6 RSV -
7 LA1/LA2 Latch A input
8 LB1/LB2 Latch B input
9 RST1/RST2 Reset input
10 V1 Encoder power supply input
11 V1 Encoder power supply output
CH1 12 A24 Phase A input (24 V)
CH2 13 B24 Phase B input (24 V)
14 Z24 Phase Z input (24 V)
15 V2 Sensor power supply input
16 V2 Sensor power supply output
9
9-4-1 Open collector input type GX-EC0211
CN IN
V1
TX+
TX−
RX+ G1
RX− Photocoupler
V1
circuits
Input
Physical
layer A24
CN OUT 1.2 kΩ 1.5 kΩ
TX+
A5
TX−
RX+
430 Ω
RX− G1
Photocoupler
V1
circuits
Input
B24
UNIT PS
DC-DC 1.2 kΩ 1.5 kΩ
+V converter B5
−V
(No-isolation 430 Ω
type)
Internal circuits
Photocoupler
V1
circuits
Input
Z24
1.2 kΩ 1.5 kΩ
Z5
430 Ω
V2
G2
Photocoupler
V2
circuits
Input
LA/LB
2 kΩ 2 kΩ
G2
Photocoupler
V2
circuits
Input
RST
3.3 kΩ
G2
Wiring diagram
RSV RSV V1 V1 V1 RSV LA1 LB1 RST1 RSV RSV V1 V1 V1 RSV LA2 LB2 RST2
G1 G1 A5 B5 Z5 G2 G2 G2 G2 G1 G1 A5 B5 Z5 G2 G2 G2 G2
White: White:
Phase B Phase B
Black: Black:
Phase A Phase A
Orange: Orange:
Blue: Blue:
Blue
Brown
Black
Blue
Black
Blue
Brown
Black
Blue
Black
0V 0V
Blue
Brown
Black
Encoder Latch Encoder Latch
(NPN open collector (NPN open collector
output type) Output output type) NPN output
2-wire sensor 3-wire sensor
9
9-4-1 Open collector input type GX-EC0211
RSV RSV V1 V1 V1 RSV LA1 LB1 RST1 RSV RSV V1 V1 V1 RSV LA2 LB2 RST2
G1 G1 A5 B5 Z5 G2 G2 G2 G2 G1 G1 A5 B5 Z5 G2 G2 G2 G2
Blue
Black
Blue
Black
Blue
Brown
Black
Blue
Brown
Black
Black: Phase A Latch Reset
White: Phase B Phase Phase Phase
A B Z
Latch Reset
Blue
Black
Orange: Phase Z
Brown: Vcc
Blue
Brown
Black
Blue: 0V Latch
Encoder Output
2-wire sensor Latch
(NPN open collector
output type) NPN output
Encoder power supply 3-wire sensor
(24 VDC or 5 VDC)
Encoder
(NPN open collector
output type)
Specification
Item Specification
Counter point 2 points
Counter phase A
Counter phase B
Input signal Counter phase Z
Latch input (A/B)
Counter reset input
Counter enabled status
LED display (green)
display
Input indicators LED display (yellow)
Unit power supply current
100 mA max. (for 20.4 to 26.4 VDC power supply voltage)
consumption
Weight 390 g max.
Specification
Item
Counter phase A/B Counter phase Z
Input voltage EIA standard RS-422-A line driver level
Input impedance 120 Ω ±5%
gH level input voltage 0.1 V
gL level input voltage -0.1 V
Hysteresis voltage 60 mV
Maximum response Single phase 4 MHz (phase difference
1 MHz
frequency Multiplication × 4, 1 MHz)
Filter switching NA
9
9-4-2 Line Driver Input Type GX-EC0241
E
D
ON ON
voltage
A (+)
OFF
Phase A OFF voltage
ON
A (−)
OFF
A A
F F F F
Terminal
input
E
D
ON ON
voltage
B(+)
OFF
OFF voltage
Phase B ON
B (−)
OFF
A A
Timing condition
A B C D E F G
<25 ns >125 ns >250 ns >0.5 μs >1 μs >0.25 μs >0.5 μs
Specification
Item
Latch input (A/B) Reset input
Internal I/O common PNP
Input voltage 20.4 to 26.4 VDC (24 VDC −15 to +10%) 20.4 to 26.4 VDC (24 VDC −15 to +10%)
Input impedance 4.0 kΩ 3.3 kΩ
Input current 5.5 mA (at 24 VDC) 7 mA (at 24 VDC)
ON voltage/ON current 17.4 VDC min./3 mA min. 14.4 VDC min./3 mA min.
OFF voltage/OFF current 5 VDC max./1 mA max. 5 VDC max./1 mA max.
ON response time 3 μs max. 15 μs max.
OFF response time 3 μs max. 90 μs max.
(1)
(7) (6)
CH1 CH2
9
1 to 9 RSV RSV RSV RSV RSV RSV LA1 LB1 RST1 RSV RSV RSV RSV RSV RSV LA2 LB2 RST2
10 to 18 V1 V1 A+ B+ Z+ V1 V1 V1 V1 V1 V1 A+ B+ Z+ V1 V1 V1 V1
9-4-2 Line Driver Input Type GX-EC0241
19 to 27 G1 G1 A− B− Z− G1 G1 G1 G1 G1 G1 A− B− Z− G1 G1 G1 G1
• Input indicators
CH1 CH2
Name State Contents Name State Contents
Lit green. Counter operating Lit green. Counter operating
CH1 CH2
OFF Counter stopped OFF Counter stopped
Input A (phase A signal/count Input A (phase A signal/count
Lit Lit
pulse signal/incremental count pulse signal/incremental count
yellow. yellow.
signal) available signal) available
A1 A2
Input A (phase A signal/count Input A (phase A signal/count
OFF pulse signal/incremental count OFF pulse signal/incremental count
signal) not available signal) not available
Input B (phase B signal/count Input B (phase B signal/count
Lit direction control Lit direction control
yellow. signal/decremental count signal) yellow. signal/decremental count signal)
available available
B1 B2
Input B (phase B signal/count Input B (phase B signal/count
direction control direction control
OFF OFF
signal/decremental count signal) signal/decremental count signal)
not available not available
Lit Lit
Phase Z input available Phase Z input available
Z1 yellow. Z2 yellow.
OFF Phase Z input not available OFF Phase Z input not available
Lit Lit
External latch input A available External latch input A available
yellow. yellow.
LA1 LA2
External latch input A not External latch input A not
OFF OFF
available available
Lit Lit
External latch input B available External latch input B available
yellow. yellow.
LB1 LB2
External latch input B not External latch input B not
OFF OFF
available available
Lit Lit
External reset input available External reset input available
RST1 yellow. RST2 yellow.
OFF External reset input not available OFF External reset input not available
• Terminal block
Terminal
CH block Terminal name Contents
number
1 RSV -
2 RSV -
3 RSV -
4 RSV -
5 RSV -
6 RSV -
7 LA1/LA2 Latch A input
8 LB1/LB2 Latch B input
9 RST1/RST2 Reset input
10 V1 Internal circuit/sensor power supply input
11 V1 (Spare)
12 A+ Phase A input (+)
13 B+ Phase B input (+)
CH1
14 Z+ Phase Z input (+)
CH2
15 V1 (Spare)
16 V1 Sensor power supply output
17 V1 Sensor power supply output
18 V1 Sensor power supply output
9
9-4-2 Line Driver Input Type GX-EC0241
CN IN
TX+
TX− DC-DC
converter V1
RX+
RX− (No-isolation G1
Line type)
receiver
Physical
layer
A−
CN OUT
4.7 kΩ
TX+
TX− A+
RX+ 4.7 kΩ
RX−
B−
4.7 kΩ
B+
4.7 kΩ
UNIT PS
DC-DC Z−
Internal circuits
+V converter 4.7 kΩ
−V
(No-isolation
type) Z+
4.7 kΩ .
.
.
.
Photocoupler
G1
circuits
Input
LA/LB
2 kΩ 2 kΩ
V1
Photocoupler
G1
circuits
Input
RST
3.3 kΩ
V1
Wiring diagram
Internal circuit /
sensor power supply
(24 VDC)
RSV RSV RSV RSV RSV RSV LA1 LB1 RST1 RSV RSV RSV RSV RSV RSV LA2 LB2 RST2
V1 V1 A+ B+ Z+ V1 V1 V1 V1 V1 V1 A+ B+ Z+ V1 V1 V1 V1
G1 G1 A− B− Z− G1 G1 G1 G1 G1 G1 A− B− Z− G1 G1 G1 G1
Blue: 0V
Blue
Brown
Black
Blue
Brown
Black
Black
Blue
Black
Blue
Blue
Brown
Black
Black
Latch Latch
Encoder
(Line driver Output NPN output
output type) 2-wire sensor 3-wire sensor
9
9-4-2 Line Driver Input Type GX-EC0241
Encoder
(Line driver
output type)
215
52
50
3.14
93.5
68.9
10.1 [mm]
10-1-1 Introduction
An IO-Link Master Unit is a slave that has I/O processing functions for IO-Link communications with
IO-Link devices and I/O processing functions for digital I/O data (ON/OFF signals) with non-IO_Link
devices.
For an IO-Link Master Unit, processing functions can be assigned for each port to combine different
types of I/O processing functions.
Also, with IO-Link devices that support digital inputs with pin 2, the IO-Link Master Unit can
simultaneously perform both IO-Link communications and receive digital inputs.
EtherCAT EtherCAT
M12 M12
GX-series IO-Link Master Unit
Mapping
The data in the IO-Link Master Unit is allocated in the OUT and IN areas in the I/O memory of the
EtherCAT Master Unit.
Also, the Sysmac error status is allocated to the IN area of I/O memory of the EtherCAT Master Unit.
Refer to the manual of the EtherCAT Master Unit for allocation methods.
10
Precautions for Correct Use
Allocate the input and output data for IO-Link devices consecutively starting from data 01. A
Default I/O
Data name Size Details
allocation
I/O Port Status 2 bytes Yes Indicates whether input data (IO-Link input data, digital inputs from
pin 2, and digital input data) is enabled or disabled for each port.
Also indicates the status of the I/O power supply to the IO-Link
Master Unit.
I/O Port Error Status 8 bytes Yes Indicates the following errors for each port:
IO-Link communications error, short-circuit in I/O cable, device
configuration verification error, device I/O size error, PDO mapping
error, error-level device event, and information-level device event
Digital Input Data 2 bytes No Digital inputs with pin 2 in IO-Link Mode, or digital input data in SI
Mode.
Port 1 IO-Link Input Data 32 words × Yes (2 bytes This is the input data from IO-Link devices such as sensors that are
8 ports per port) connected to port 1 in IO-Link Mode.
· ·
· ·
· ·
Port 8 IO-Link Input Data This is the input data from IO-Link devices such as sensors that are
connected to port 8 in IO-Link Mode.
Sysmac Error Status 1 byte Yes Contains status flags that are used to check errors that occur and
confirm when they have been eliminated.
Input offset D15 D14 D13 D12 D11 D10 D09 D08 D07 D06 D05 D04 D03 D02 D01 D00
(words)
0 Not used. Sysmac Error Status
+1 D15: I/O Power ON Flag, D14: IO-Link Communications Input Data Enabled Flags
Module Processing Error, D08 to D13: Not used.
+2 Error Status for Port 2 Error Status for Port 1
+3 Error Status for Port 4 Error Status for Port 3
+4 Error Status for Port 6 Error Status for Port 5
+5 Error Status for Port 8 Error Status for Port 7
+6 Port 1 IO-Link Input Data 01 Upper Byte Port 1 IO-Link Input Data 01 Lower Byte
+7 Port 2 IO-Link Input Data 01 Upper Byte Port 2 IO-Link Input Data 01 Lower Byte
· · ·
· · ·
· · ·
+13 Port 8 IO-Link Input Data 01 Upper Byte Port 8 IO-Link Input Data 01 Lower Byte
Default I/O
Data name Size Details
allocation
Digital Output Data 2 bytes No This is the digital output data in SO Mode.
Port 1 IO-Link Output Data 32 words × 8 Yes (2 bytes per This is the output data from IO-Link devices such as
ports port) actuators that are connected to port 1 in IO-Link Mode.
· ·
· ·
· ·
Port 8 IO-Link Output Data This is the output data from IO-Link devices such as
actuators that are connected to port 8 in IO-Link Mode.
Output offset D15 D14 D13 D12 D11 D10 D09 D08 D07 D06 D05 D04 D03 D02 D01 D00
(words)
0 Port 1 IO-Link Output Data 01 Upper Byte Port 1 IO-Link Output Data 01 Lower Byte
+1 Port 2 IO-Link Output Data 01 Upper Byte Port 2 IO-Link Output Data 01 Lower Byte
· · ·
· · ·
· · ·
+7 Port 8 IO-Link Output Data 01 Upper Byte Port 8 IO-Link Output Data 01 Lower Byte
Master Unit
10-3-1 Basic Functions of IO-Link Master Units
The following are the basic functions of OMRON's IO-Link Master Units.
For details, refer to the IO-Link System User’s Manual (W570).
10
Function name Description
I/O data (process data) in the IO-Link devices is cyclically shared with
Cyclic communications
Application Examples
Cyclic communications can be used to check the amount of detection
performance deterioration in devices, and to check changes in usage
conditions (e.g., amount of incident light for photoelectric sensors,
stability detection margins, and excessive proximity for proximity
sensors).
The host communications master can send messages (commands) to
Communic
the IO-Link Master Unit and receive the response from the IO-Link
ations
Master Unit.
The IO-Link Master Unit can also function as a gateway to send
messages (commands and responses) between the host
communications master and the IO-Link devices.
Refer to 6-3 Message Communications in the IO-Link System User’s
Message
Manual (Cat. No. W568).
communications
Application Examples
• During operation, you can change and adjust device parameters
(e.g., threshold settings, tuning execution, and ON-delay time
changes) from a program.
• During operation, you can check the internal status, such as the
operating times of devices.
You can select any of the following modes for each port:
IO-Link Mode, SIO (DI) Mode, SIO (DO) Mode, and Disable Port. This
Communications mode settings
allows you to combine IO-Link communications and digital I/O in a
single terminal or unit.
In IO-Link Mode, you can perform digital input with pin 2 while
Digital inputs for pin 2
performing IO-Link communications.
The IO-Link Master Unit automatically matches the specific baud rates
(COM1, COM2, or COM3) of the IO-Link devices to communicate with
Automatic baud rate setting for IO-Link
the IO-Link devices.
communications
Therefore, it is not necessary to set the baud rate of the connected
device for each port.
This function is used to verify the configuration of IO-Link devices that
are registered for connection to the IO-Link Master Unit (as set in the
Connected device verification IO-Link Device Configuration Settings or the IO-Link Device Information
Area) when the power supply is turned ON .
The user can enable or disable connected device verification.
This function detects IO-Link cable breaks, disconnections from IO-Link
IO-Link communications error
device ports, error-level device events, device configuration verification
detection
errors, and IO-Link device malfunctions.
Detection of short-circuits in I/O cables This function detects short-circuits in device cables.
10-4 Specifications
10-4 Specifications
This section gives the specifications and part names of the IO-Link Master Unit, describes its functions,
and provides wiring diagrams.
10-4-1 Specifications 10
z Communications Specifications
10-4-1 Specifications
The following table gives the EtherCAT communications specifications of the GX-ILM08C.
Item Specification
Communications
EtherCAT protocol
protocol
Modulation Baseband
Baud rate 100 Mbps
Physical layer 100BASE-TX (IEEE 802.3)
M12 (D-coding, female) × 2 (shielded)
Connectors CN IN: EtherCAT input
CN OUT: EtherCAT output
Category 5 or higher (cable with double, aluminum tape and braided shielding is
Communications media
recommended.)
Communications
Distance between nodes (Slave Units): 100 m max.
distance
Noise resistance Conforms to IEC 61000-4-4, 1 kV or higher.
Node address setting
Set on hexadecimal node address switches or with a Configuration Tool.
method
000 to FFF hex (0 to 4,095 decimal): Set on node address switches or with a
Node address range
Configuration Tool.
UNIT PWR × 1
IO PWR × 1
L/A IN (Link/Activity IN) × 1
Indicators
L/A OUT (Link/Activity OUT) × 1
RUN × 1
ERR × 1
Process data Variable PDO mapping
PDO size/node 2 to 270 bytes
Mailbox Emergency messages, SDO requests, SDO responses, and SDO information
Synchronization mode Free Run Mode (asynchronous)
z General Specifications
The following table gives the general specifications of the GX-ILM08C.
Item Specification
Unit power supply
20.4 to 26.4 VDC (24 VDC −15%/+10%)
voltage
I/O power supply 20.4 to 26.4 VDC (24 VDC −15%/+10%)
Noise resistance Conforms to IEC 61000-4-4, 2 kV (power line).
Malfunction: 10 to 60 Hz with amplitude of 0.7 mm, 60 to 150 Hz and 50 m/s2 for 80
Vibration resistance
minutes each in X, Y, and Z directions
Shock resistance 150 m/s2 with amplitude of 0.7 mm
Dielectric strength 600 VAC (between isolated circuits)
Insulation resistance 20 MΩ min. (between isolated circuits)
Ambient operating
−10 to 55°C
temperature
Ambient operating
25% to 85% (with no condensation)
humidity
Ambient operating
No corrosive gases
atmosphere
Storage temperature −25 to 65°C
Storage humidity 25% to 85% (with no condensation)
Degree of protection IP67
Mounting M5 screw mounting
Mounting strength 100 N
Communications
30 N
connector strength
Connectors for EtherCAT communications: M12 (D-coding, female) × 2
Connector types Power supply connector: M12 (A-coding, male) × 1
I/O connectors: M12 (A-coding, female)*1 × 8
Round connectors (communications connector, power supply, and I/O): 0.39 to 0.49
Screw tightening N·m
torque*2 M5 (Unit mounted from the front):1.47 to 1.96 N·m
Cover for node address setting switches: 0.4 to 0.6 N·m
Applicable standards EU: EN 61131-2, RCM, KC, and IO-Link conformance
*1 Confirms to Class A when used as an IO-Link connector.
*2 For SmartClick Connectors, insert the Connector all the way and turn it approx. 1/8 of a turn. Torque
management is not required.
z Unit Specifications
10-4 Specifications
The specifications for the GX-ILM08C are given below.
Item Specification
Unit name IO-Link Master Unit
Model GX-ILM08C
Number of IO-Link ports 8
COM1: 4.8 kbps
Communications
Baud rate COM2: 38.4 kbps
specifications
COM3: 230.4 kbps
10
Rated voltage 24 VDC (20.4 to 26.4 VDC)
Device power
Maximum load
10-4-1 Specifications
supply*1 in IO-Link 0.2 A/port
current
Mode or SIO (DI)
Short-circuit
Mode Yes
protection
Internal I/O common PNP
Rated voltage 24 VDC (20.4 to 26.4 VDC)
Input current 5 mA typical (at 24 VDC)
Digital inputs (in SIO ON voltage/ON
15 VDC min., 5 mA min.
(DI) Mode) current
OFF voltage 5 VDC max.
No filter, 0.25 ms, 0.5 ms, 1 ms (default), 2 ms, 4 ms, 8 ms, 16
Input filter time
ms, 32 ms, 64 ms, 128 ms, or 256 ms
Internal I/O common PNP
Output type Push-pull
Rated voltage 24 VDC (20.4 to 26.4 VDC)
Maximum load
Digital outputs (in 0.3 A/port
current
SIO (DIO) Mode)
Short-circuit
Provided.
protection
Leakage current 0.1 mA max.
Residual voltage 1.5 V max.
Internal I/O common PNP
Rated voltage 24 VDC (20.4 to 26.4 VDC)
Input current 2 mA (24 VDC)
Digital inputs for pin ON voltage/ON
15 VDC min., 2 mA min.
2 (in IO-Link Mode) current
OFF voltage 5 VDC max.
No filter, 0.25 ms, 0.5 ms, 1 ms (default), 2 ms, 4 ms, 8 ms, 16
Input filter time
ms, 32 ms, 64 ms, 128 ms, or 256 ms
Cable type Unshielded
Cable length 20 m max.
Electrostatic
Cable specifications
capacity between 3 nF max.
lines
Loop resistance 6 Ω max.
175 × 33 × 60 mm (W×H×D) (The height is 43 mm when the
Dimensions
connectors are included.)
Isolation method Photocoupler isolation
I/O power supply method Supplied from the power supply connector.
Unit power supply current consumption 60 mA
I/O power supply current consumption 100 mA
Weight 430 g
Item Specification
IN communications L+
connector Internal Isolation
C/Q I/O
circuits circuit
OUT communications DI connector
connector 1
L-
IO-Link
Non- circuits
Unit power supply isolated
24 V power L+
supply
Circuit layout Unit power supply circuits
C/Q I/O
0V DI connector
Power L- 8
supply
connector
I/O power
supply 24 V Non-isolated
power supply
I/O power circuits
supply 0 V
10-4 Specifications
10-4-2 Part Names and Functions
(8)
(1) (2)
(5)
(3) (6)
10
(7)
(8)
Status Indicators
z L/A IN Indicator
This indicator shows the input communications status.
For the indicator specifications, refer to "6-3-1 Status Indicators" in Page 6 - 4.
z RUN Indicator
This indicator shows the operating status of EtherCAT communications.
For the indicator specifications, refer to "6-3-1 Status Indicators" in Page 6 - 4.
z ERR Indicator
This indicator provides information on errors.
For the indicator specifications, refer to "6-3-1 Status Indicators" in Page 6 - 4.
z IO PWR Indicator
This indicator shows the I/O power supply status.
10-4 Specifications
I/O Indicators
10
z C/Q Indicator
These indicator show the digital I/O status.
I/O Connectors
Port 1 Port 2
Port 3 Port 4
Port 5 Port 6
Port 7 Port 8
I/O Connectors
z GX-ILM08C
60
10
175
(mm)
The I/O response time is the time required for the following processing: The CPU Unit processes an
external signal input to one EtherCAT slave, and another EtherCAT (CoE) slave outputs the processed
result as an external signal.
For the timing charts and calculation methods for EtherCAT slaves, refer to System Response Time in
Process Data Communications in the NJ/NX-series CPU Unit Built-in EtherCAT Port User’s Manual
(Cat. No. W505).
The following EtherCAT slave parameters are necessary to calculate I/O response times.
• Slave input response time: Specific input response time for EtherCAT slave
• Slave output response time: Specific output response time for EtherCAT slave
The parameter values and calculation methods for the GX-series IO-Link Master Unit are given below.
z Input Data
I/O data type IO-Link input data from
Digital input data for pin 2 Digital input data in SIO
IO-Link communications
Parameter in IO-Link Mode (DI) Mode
in IO-Link Mode
0.134 × Pin_size*1
+ 0.012 × (Total size (in 0.134 × Pin_size*1
bytes) of IO-Link input data
+ 0.012 × (Total size (in bytes) of IO-Link input data from
from IO-Link
IO-Link communications from port 1 to port 8) + 5.02 +
communications from port 1
Input filter time [ms]
to port 8) + 5.02+ IO-Link
communications cycle*2 [ms]
Example: When the IO-Link
input data sizes of the
Example: When the IO-Link
IO-Link devices (sensors)
input data sizes of the Example: When port 1
Slave input for port 1 through port 4 are
IO-Link devices (sensors) through port 7 are used by
response time all 2 bytes, the IO-Link input
for port 1 through port 4 are IO-Link devices with an
data sizes of the IO-Link
all 2 bytes, the IO-Link input IO-Link input data size of 2
devices (sensors) for port 5
data sizes of the IO-Link bytes and port 8 is used by a
through port 8 are all 4
devices (sensors) for port 5 non-IO-Link device (sensor)
bytes, and the IO-Link
through port 8 are all 4 with no input filter: 0.134 ×
communications cycle for
bytes, and no input filter is 2 bytes × 4 devices + 0.012
those IO-Link devices
used: 0.134 × 4 bytes × 4
(sensors) is 2.1 [ms]: 0.134 × Total of 14 bytes + 5.02 =
× 4 bytes × 4 devices + devices + 0.012 × Total of 6.26 [ms]
24 bytes + 5.02 = 7.452 [ms]
0.012 × Total of 24 bytes +
5.02 + 2.1 = 9.552 [ms]
*1 Pin_size: The larger of the total IO-Link input data sizes for IO-Link communications between ports 1 and 4 and
ports 5 and 8.
10-6 Communications
*2 For information on how to determine the IO-Link communications cycle, refer to "10-6-2 Determining the
IO-Link Communications Cycle" in Page 10 - 18Determining the IO-Link Communications Cycle.
Performance
z Output Data
I/O data type IO-Link output data from IO-Link
Digital output data in SIO (DO) Mode
Parameter communications in IO-Link Mode
0.091 × Pout_size*1 + 0.001 × (Total size (in 0.091 × Pout_size*1 + 0.001 × (Total size (in
bytes) of IO-Link output data from IO-Link bytes) of IO-Link output data from IO-Link 10
communications from port 1 to port 8) + communications from port 1 to port 8) +
3.04 + IO-Link communications cycle*2 [ms] 3.04 [ms]
When the IO-Link Device Baud Rate IO-Link Device Is COM2 (38.4
kbps) or COM1 (4.8 kbps)
The IO-Link communications cycle will be as described below.
The IO-Link communications cycle = (Minimum cycle time of the IO-Link devices*) [ms]
* You can check the minimum cycle times for the IO-Link devices in the instruction manuals for the IO-Link
devices.
Or, you can place the CX-ConfiguratorFDT online and check the cycle time in Read Device Configuration in the
Diagnosis Tab Page for the IO-Link Master Unit, as shown in the following screen capture.
1 Remove the cover from the right side of the Digital I/O Slave Unit.
(1) Depress the catch and remove one side of the cover.
(2) Pull out the cover to remove it entirely.
(1) (2)
Reference page
Internal
Model Names and Wiring
Specification circuits
functions diagram
diagram
XWT-ID08
11-5 11-5 11-6 11-7
XWT-ID08-1
XWT-OD08
11-8 11-8 11-9 11-10
XWT-OD08-1
XWT-ID16
11-11 11-11 11-12 11-13
XWT-ID16-1
XWT-OD16
11-14 11-14 11-15 11-16
XWT-OD16-1
Specification
Specification
Item
XWT-ID08 XWT-ID08-1
Internal I/O common NPN PNP
I/O capacity 8 inputs 11
15 VDC min. (between each input 15 VDC min. (between each input
ON voltage
terminal and the V terminal) terminal and the G terminal)
(1)
IN
(2)
(4) (3)
6 to 10 V 1 3 5 7
1 to 5 G 0 2 4 6
Photocoupler
V 24 VDC
0
1
Internal circuits
• •
Photocoupler • •
• •
• •
• •
• •
• •
• •
• •
•
G
•
z XWT-ID08-1 (PNP)
V 24 VDC
Photocoupler
0
1
• •
• •
Internal circuits
• •
• •
Photocoupler
• •
• •
• •
G
•
V 1 3 5 7
G 0 2 4 6
11
Blue (black)
Brown (red)
Brown (white)
z XWT-ID08-1 (PNP)
V 1 3 5 7
G 0 2 4 6
Black (white)
Brown (white)
Blue (black)
Blue (black)
Brown (red)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors.
The colors in parentheses are the wire colors prior to the revisions.
Specification
Specification
Item
XWT-OD08 XWT-OD08-1
Internal I/O common NPN PNP
I/O capacity 8 outputs
Rated output current 0.5 A/output, 2.0 A/common
1.2 V max. 1.2 V max.
Residual voltage (0.5 ADC, between each output terminal (0.5 ADC, between each output terminal
and the G terminal) and the V terminal)
Leakage current 0.1 mA max.
ON delay time 0.5 ms max.
OFF delay time 1.5 ms max.
Number of circuits per
8 inputs/common
common
Isolation method Photocoupler isolation
Output indicators LED display (yellow)
Error Mode Output Select either hold or clear.
Weight 80g max.
(1)
0UT
(2)
(4) (3)
6 to 10 V 1 3 5 7
1 to 5 G 0 2 4 6
z XWT-OD08 (NPN)
Photocoupler
V 24 VDC
0
1
Internal circuits
• •
• •
• •
• •
Photocoupler • •
• •
• •
• •
• •
• •
• •
G
•
z XWT-OD08-1 (PNP)
V 24 VDC
Photocoupler 0
1
• •
Internal circuits
• •
• •
• •
• •
• •
Photocoupler
• •
• •
Voltage
drop
G
•
Wiring diagram
z XWT-OD08 (NPN)
V 1 3 5 7
G 0 2 4 6
z XWT-OD08-1 (PNP)
V 1 3 5 7
G 0 2 4 6
Specification
Specification
Item
XWT-ID16 XWT-ID16-1
Internal I/O common NPN PNP
I/O capacity 16 inputs 11
15 VDC min. (between each input 15 VDC min. (between each input
ON voltage
terminal and the V terminal) terminal and the G terminal)
(1)
IN
(2)
(4) (3)
10 to 18 V 1 3 5 7 9 11 13 15
1 to 9 G 0 2 4 6 8 10 12 14
Photocoupler
V 24 VDC
0
1
Internal circuits
• •
• •
Photocoupler
• •
• •
• •
• •
• •
• •
•
• •
•
•
G
z XWT-ID16-1 (PNP)
V 24 VDC
Photocoupler
0
1
• •
• •
Internal circuits
• •
• •
Photocoupler
• •
• •
• •
G
•
V 1 3 5 7 9 11 13 15
G 0 2 4 6 8 10 12 14
11
Brown (white)
Blue (black)
Blue (black)
Brown (red)
z XWT-ID16-1 (PNP)
V 1 3 5 7 9 11 13 15
G 0 2 4 6 8 10 12 14
Black (white)
Brown (white)
Blue (black)
Blue (black)
Brown (red)
Reference
Wire colors have been changed according to revisions in the JIS standards for photoelectric and
proximity sensors.
The colors in parentheses are the wire colors prior to the revisions.
Specification
Specification
Item
XWT-OD16 XWT-OD16-1
Internal I/O common NPN PNP
I/O capacity 16 outputs
Rated output current 0.5 A/output, 4.0 A/common
1.2 V max. 1.2 V max.
Residual voltage (0.5 ADC, between each output terminal (0.5 ADC, between each output terminal
and the G terminal) and the V terminal)
Leakage current 0.1 mA max.
ON delay time 0.5 ms max.
OFF delay time 1.5 ms max.
Number of circuits per
16 inputs/common
common
Isolation method Photocoupler isolation
Output indicators LED display (yellow)
Error Mode Output Select either hold or clear.
Weight 120g max.
(1)
OUT
(2)
(4) (3)
10 to 18 V 1 3 5 7 9 11 13 15
1 to 9 G 0 2 4 6 8 10 12 14
z XWT-OD16 (NPN)
V 24 VDC
0
1
Internal circuits
• •
• •
• •
• •
Photocoupler
• •
• •
• •
• •
• •
• •
• •
G
•
z XWT-OD16-1 (PNP)
V 24 VDC
Photocoupler
0
1
• •
Internal circuits
• •
• •
• •
• •
• •
Photocoupler • •
• •
Voltage
• •
drop
G
•
Wiring diagram
z XWT-OD16 (NPN)
V 1 3 5 7 9 11 13 15
G 0 2 4 6 8 10 12 14
z XWT-OD16-1 (PNP)
V 1 3 5 7 9 11 13 15
G 0 2 4 6 8 10 12 14
z XWT-ID08/ID08-1/OD08/OD08-1
13 66 43.9
11
50
29.9
3.1
49.7 (mm)
z XWT-ID16/ID16-1/OD16/OD16-1
12 94 43.9
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
50
29.9
3.1
49.7 (mm)
12-1 Troubleshooting
12-1-1 Errors that Can be Checked with Status Indicator and Actions to
Take
In this section, the states of status indicator are indicated using the following abbreviations.
Abbreviation Definition
On ON
Off OFF
F Flickering (ON (50 ms) - OFF (50 ms) flashing)
B Blinking (ON (200 ms) - OFF (200 ms) flashing)
SF Single flash (ON (200 ms) - OFF (1000 ms) flashing)
DF Double flash (ON (200 ms) - OFF (200 ms) - ON (200 ms) - OFF (1000 ms) flashing)
− Unknown
For details on definition of each state, refer to "6-3-1 Status Indicators" in page 6 - 4.
[L/A IN]
[PWR] [RUN] [ERR]
[L/A OUT] Description Cause Actions
indicator indicator indicator
LED
PDO communications
EtherCAT EtherCAT or both PDO and SDO
On F On Off communication communication is communications are
is in progress. being executed. being executed.
State is normal.
After removing the
following factors of
power supply shutdown,
restart the Slave Unit
according to the
specification of
connected EtherCAT
Master Unit.
• Are the power supply
The power is not
Power supply cables wired
Off Off Off Off properly supplied
error correctly?
to the Slave Unit.
• Are the power supply
cables disconnected?
• Is the power supply
voltage within the
specification range?
• Is the power supply
capacity sufficient?
• Is the power supply
malfunctioning?
[L/A IN]
[PWR] [RUN] [ERR]
[L/A OUT] Description Cause Actions
indicator indicator indicator
LED
On If the error does not
clear even after the
A hardware failure power is turned ON
F occurred. again, the Slave Unit
On − Off Hardware error hardware is damaged.
12-1 Troubleshooting
Replace the Slave Unit.
The Expansion
Check the Expansion
B Unit is
Unit connection.
disconnected.
Check the switch
A range setting settings then restart the
Illegal switch switch or other Slave Unit according to
setting switch setting is the specification of
illegal. connected EtherCAT 12
Master Unit.
Use the Configuration
12-1-1 Errors that Can be Checked with Status Indicator and Actions to Take
Tool or SDO
communications to
Non-volatile A non-volatile restore the default data
memory data memory data error and restart the Slave
error occurred. Unit according to the
On − − B specification of
connected EtherCAT
Master Unit.
Sync manager The sync manager Change to the correct
setting error setting is illegal. settings.
If the problem is not
resolved even after the
measures described
A hardware failure above are taken, the
Hardware error
occurred. Slave Unit hardware
may be damaged.
Replace the applicable
Slave Unit.
[L/A IN]
[PWR] [RUN] [ERR]
[L/A OUT] Description Cause Actions
indicator indicator indicator
LED
Operation standby
Link
status after
On On − − established in −
establishing link in
physical layer
physical layer.
After checking the
following items, restart
the Slave Unit according
to the specification of
connected EtherCAT
Master Unit.
• Is the
communications
cable wired correctly?
A link in physical • Are any cables
layer has not been disconnected or loose
established. in the part that
connects to the
connector?
• Is the cable length
appropriate?
• Is the
communications
cable of the
recommended
Link not
specification?
On Off − − established in
Check that EtherCAT
physical layer
Master Unit is operating
correctly. If using an
OMRON EtherCAT
Master Unit, check the
The host master EtherCAT Master Unit
has not been mode and Slave Unit
started. node addresses. If
using EtherCAT Master
Unit from another
manufacturer, refer to
the user's manual for
that Master Unit.
If the problem is not
resolved even after the
measures described
A hardware failure above are taken, the
occurred. Slave Unit hardware
may be damaged.
Replace the applicable
Slave Unit.
[L/A IN]
[PWR] [RUN] [ERR]
[L/A OUT] Description Cause Actions
indicator indicator indicator
LED
After checking the
following items, restart
the Slave Unit according
to the specification of
connected EtherCAT
12-1 Troubleshooting
Master Unit.
[Item about
communication cable]
• Is the
communications
cable wired correctly?
• Are any cables
disconnected or loose
in the part that 12
A communications connects to the
error occurred. connector?
12-1-1 Errors that Can be Checked with Status Indicator and Actions to Take
• Is the cable length
appropriate?
• Is the
communications
cable of the
recommended
specification?
[Item about power
Process data
supply]
communica-
• Is the power supply
tions timeout *
voltage within the
On − − DF specification range?
• Is the power supply
capacity sufficient?
• If there are devices in
the vicinity that
generate noise, take
necessary measures
against the noise to
protect the EtherCAT
Master Unit and Slave
Units and the
communications
Malfunction due to cable.
noise • The noise resistance
deteriorates if a cable
other than those of
the recommended
specification is used.
Use the
communications
cable of the
recommended
specification.
Check to see if the
Communications
cable is disconnected or
Link in physical cable
loose in the part that
later OFF disconnection
connects to the
occurred.
connector.
[L/A IN]
[PWR] [RUN] [ERR]
[L/A OUT] Description Cause Actions
indicator indicator indicator
LED
It is commanded
from the EtherCAT
Safe-
Master Unit to shift
On − SF − Operational
to the
state
Safe-Operational
state.
If the trouble occurred
It is commanded
during operating the
from the EtherCAT
Pre- system, check the state
Master Unit to shift
On − B − Operational of the connected
to the
state EtherCAT Master Unit.
Pre-Operational
state.
It is commanded
from the EtherCAT
On − Off − Init state
Master Unit to shift
to the Init state.
* Due to the EtherCAT specification, a communication timeout does not occur with those Slave Units that only
handle input data.
The GX-series Slaves that have only input data are listed below.
• GX-AD0471
• GX-ID1611
• GX-ID1611+XWT-ID08
• GX-ID1611+XWT-ID16
• GX-ID1611+XWT-ID08-1
• GX-ID1611+XWT-ID16-1
• GX-ID1621
• GX-ID1621+XWT-ID08
• GX-ID1621+XWT-ID16
• GX-ID1621+XWT-ID08-1
• GX-ID1621+XWT-ID16-1
• GX-ID1612
• GX-ID1622
• GX-ID1618
• GX-ID1628
• GX-ID3218
• GX-ID3228
[L/A IN]
[PWR] [RUN] [ERR]
[L/A OUT] Description Actions
indicator indicator indicator
LED
After checking the following items,
restart the Slave Unit according to
Synchronization
the specification of connected
On − B B frequency (Sync0
EtherCAT Master Unit.
frequency) setting error
• Set the correct synchronization
frequency.
[L/A IN]
[PWR] [RUN] [ERR]
[L/A OUT] Description Actions
indicator indicator indicator
LED
After checking the following items,
restart the Slave Unit according to
the specification of connected
EtherCAT Master Unit.
• Is the communications cable
12-1 Troubleshooting
Synchronization error (at
On − B SF wired correctly?
synchronization start)
• Is the communications cable
exposed to excessive noise?
• Review set time of Sync Not
Received Timeout Setting
(synchronization error setting).
After checking the following items,
restart the Slave Unit according to
the specification of connected 12
EtherCAT Master Unit.
Communications • Is the communications cable
On − SF SF
12-1 Troubleshooting
the output indicator is Terminal block screws are
Check if terminal block
turned ON. loosened. (Terminal block
screws are loosened.
type only)
A connected device is Check the wiring with the
disconnected. connected device.
Slave Units with digital
A connected device is Replace the connected
outputs
defective. device.
Although the output is ON,
nothing is output and Check if a
12
A communications error
Slave Unit's output communications error
occurred.
indicator does not turn ON occurred.
12-1 Troubleshooting
detected. A connected device is Check the wiring with the
disconnected. connected device.
A connected device is Replace the connected
defective. device.
Set the correct counter
The setting of counter
input method and restart
input method is wrong.
the Slave Unit.
The pulse frequency
exceeds the maximum
Set the pulse frequency 12
frequency of the Slave
within the Slave Unit
Unit specification.
specification or the mode
The pulse is not counted Or, the frequency exceeds
ID211
0 1 2 3 4 5 6 7
AD042
RUN
8 9 10 11 12 13 14 15 ERC
ERH
B1 A1
0
1
2
3 MACH 78
456
9 01
No.
4
12-1 Troubleshooting
x10 1
23
5
78
6
456
9 01
x10 0
23
7
8
9
10
11
12
13
14
15
COM
DC24V
7mA
Master notified.
Error notification
Description Notification method Page
type
Notification is provided when an error is "12-1-4
Error status is received by the
Sysmac error detected in the application. These errors Sysmac Error
TxPDO and the master is
status are displayed only on the OMRON Status Codes"
notified of errors every cycle.
Sysmac Studio Support Software. in page 12 - 14
Notification is provided of
"12-1-5
application-level errors. Either
Emergency The slave notifies the master Emergency
CiA-defined error codes are used or
messages when an error occurs. Error Code" in
error codes are added to vendor-specific
page 12 - 19
areas.
"12-1-6
Notification is provided of errors in
The master is notified by writing Application
Application layer EtherCAT communications. The error
to the application layer status Layer Status
status notification method and error codes that
register when an error occurs. Codes" in
are defined by ETG are used.
page 12 - 21
Error List
The errors (i.e., events) that can occur in the GX-series EtherCAT Slave Unit are given on
the following pages. Event levels are given as following in the tables:
Maj: Major fault level
Prt: Partial fault level
Min: Minor fault level
Obs: Observation
Info: Information
Refer to the NJ-series Troubleshooting Manual (Cat. No. W503) for all of the event codes that may
occur in an NJ-series Controller.
Level
Event code Event name Meaning Assumed cause Reference
Maj Prt Min Obs Info
04A00000 hex Expansion An Expansion Unit • The Expansion Unit is √ 12-16
Unit Hardware was disconnected disconnected.
Error during operation or • The Expansion Unit is faulty.
a signal between
the Slave Unit and
Expansion Unit was
broken.
04A20000 hex Slave A hardware error • The Slave Unit is faulty. √ 12-16
Hardware occurred in the
Error Slave Unit.
14A00000 hex Non-volatile An error occurred in • Noise √ 12-17
Memory the control
Checksum parameters.
Error
24610000 hex Switch Setting The setting switch • The analog range that is set on √ 12-17
Error is set out of range. the switch is outside the setting
range.
64CC0000 hex I/O An I/O signal line is • I/O signal wiring is √ 12-18
Disconnection disconnected. disconnected or has a faulty
Detected connection.
• An I/O signal line is
disconnected.
84A00000 hex Slave Unit A verification error • An error occurred in the control √ 12-18
Verification occurred for the SII. board.
Error
04A10000 hex Non-volatile An error occurred in • Non-volatile memory is faulty. √ 12-19
Memory non-volatile
Hardware memory.
Error
Error Descriptions
This section describes the information that is given for individual errors.
12-1 Troubleshooting
Event name Gives the name of the error. Event code Gives the code of the error.
Meaning Gives a short description of the error.
Source Gives the source of the error. Source details Gives details on Detection timing Tells when the
the source of the error is detected.
error.
Error attributes Level Tells the level of Recovery Gives the Log category Tells which log
influence on recovery the error is saved
control.*1 method.*2 in.*3 12
Effects User program Tells what will Operation Provides special information on the operation that results
happen to from the error.
execution of the
z Error Descriptions
Event name Expansion Unit Hardware Error Event code 04A00000 hex
Meaning An Expansion Unit was disconnected during operation or a signal between the Slave Unit and Expansion Unit was
broken.
Source EtherCAT Master Function Module Source details Slave Detection Continuously
timing
Error attributes Level Minor fault Recovery Error reset (after Log category System
cycling Slave Unit
power)
Effects User program Continues Operation The Slave Unit where the error occurred performs the
error output operation (fail-safe).
LED EtherCAT NET RUN EtherCAT NET ERR EtherCAT LINK/ACT
--- --- ---
System-defined Variable Data type Name
variables
None --- ---
Cause and Assumed cause Correction Prevention
correction The Expansion Unit was Turn OFF the power supply, mount Do not allow the Expansion Unit to be
disconnected during operation. the Expansion Unit, and turn the disconnected during operation.
power supply back ON.
A signal between the Slave Unit and Turn OFF the power supply, mount None
Expansion Unit was broken. the Expansion Unit, and turn the
power supply back ON.
If cycling the power supply does not
correct the problem, replace the
Expansion Unit.
Attached None
information
Precautions/ The emergency error code is 5020 hex.
Remarks
Event name Non-volatile Memory Checksum Error Event code 14A00000 hex
Meaning An error occurred in the control parameters.
Source EtherCAT Master Function Module Source details Slave Detection When
timing establishing
communications
after turning ON
power to the
Slave Unit
12-1 Troubleshooting
Error attributes Level Minor fault Recovery Error reset (after Log category System
cycling Slave Unit
power)
Effects User program Continues Operation The Slave Unit’s I/O communications stop and the outputs
turn OFF.
LED EtherCAT NET RUN EtherCAT NET ERR EtherCAT LINK/ACT
--- Flashes at 1-s intervals. ---
System-defined Variable Data type Name
variables
None --- --- 12
Cause and Assumed cause Correction Prevention
correction Noise Return the control parameters to their Implement noise countermeasures.
Event name Slave Unit Verification Error Event code 84A00000 hex
Meaning A verification error occurred for the SII.
Source EtherCAT Master Function Module Source details Slave Detection When
timing establishing
communications
after turning ON
power to the
Slave Unit
Error attributes Level Minor fault Recovery Error reset (after Log category System
cycling Slave Unit
power)
Effects User program Continues Operation The Slave Unit where the error occurred does not go to
Pre-operational state.
LED EtherCAT NET RUN EtherCAT NET ERR EtherCAT LINK/ACT
--- --- ---
System-defined Variable Data type Name
variables
None --- ---
Cause and Assumed cause Correction Prevention
correction
An error occurred in the control If cycling the power supply does not None
board. correct the problem, replace the
Slave Unit.
Attached None
information
Precautions/ The emergency error code is 6140 hex.
Remarks
Event name Non-volatile Memory Hardware Error Event code 04A10000 hex
Meaning An error occurred in non-volatile memory.
Source EtherCAT Master Function Module Source details Slave Detection When
timing establishing
communications
after turning ON
power to the
Slave Unit
12-1 Troubleshooting
Error attributes Level Observation Recovery --- Log category System
Effects User program Continues Operation Writing to non-volatile memory is not possible.
LED EtherCAT NET RUN EtherCAT NET ERR EtherCAT LINK/ACT
--- --- ---
System-defined Variable Data type Name
variables
None --- ---
Cause and Assumed cause Correction Prevention
correction Non-volatile memory failure. Replace the EtherCAT Slave Unit. None 12
Attached None
information
Notification to
Error Diagnosis
Name of error Contents EtherCAT Measures
code history
Master Unit
A timeout was
detected when writing
Non-volatile
data to non-volatile Not
5530 hex Memory Can be notified Write the data again.
memory during saved
Hardware Error
EtherCAT
communications.
At turning ON the If the error occurs
power supply, a even after restarting
Slave Unit
verification error Cannot be the power supply, the
6140 hex Verification Saved
occurred on the Slave notified Slave Unit is
Error Unit information stored damaged. Replace the
in the Slave Unit. Slave Unit.
Notification to
Error Diagnosis
Name of error Contents EtherCAT Measures
code history
Master Unit
A non-volatile memory
data error occurred.
Initialize non-volatile
memory from a
Configuration Tool or
Non-volatile
An error occurred in with SDO
Memory
6330 hex non-volatile memory Saved Can be notified communications, and
Checksum
data in the Slave Unit. then restart the Slave
Error
Unit.
(Target indexes: 1011
hex Restore default
parameters
(parameter restore))
If the error occurs
A hardware error even after restarting
Slave occurred in the Cannot be the power supply, the
7030 hex Saved
Hardware Error EtherCAT notified Slave Units is
communications area. damaged. Replace the
Slave Units.
Notification to
Error Diagnosis
Name of error Contents EtherCAT Measures
code history
Master Unit
The Expansion Unit is
disconnected. Check
the Expansion Unit
connection.
Expansion Unit Expansion Unit
5020 hex Saved Cannot be notified If the error is displayed
Hardware Error hardware errors
again, the Expansion
Unit is damaged.
Replace the
Expansion Unit.
Notification to
Error Diagnosis
Name of error Contents EtherCAT Measures
code history
Master Unit
Check the slave
I/O
A broken analog input Not voltage or current input
2130 hex Disconnection Can be notified
line was detected. saved line to see if it is
Detected
broken.
Set the range setting
Switch Setting A range setting switch Not
5600 hex Can be notified switch correctly and
Error setting is illegal. saved
restart the Slave Unit.
Notification to
Error Diagnosis
Name of error Contents EtherCAT Measures
code history
Master Unit
If the error is still
Slave displayed after
Hardware error in the
Hardware Error restarting the power
7100 hex analog conversion Saved Cannot be notified
(analog supply, the Slave Unit
area
hardware error) is damaged. Replace
12-1 Troubleshooting
the Slave Unit.
Notification
AL status Diagnosis
Name of error Contents to EtherCAT Measures
code history
Master Unit
An error was detected in
Check the Sync
TxPDO Setting the TxPDO settings (e.g., Not Can be
001E hex Manager settings in the
Error a logic setting error in the saved notified
Master Unit.
Sync Manager).
PDO WDT An incorrect PDO WDT Not Can be Check the WDT settings
001F hex
Setting Error setting was detected. saved notified in the Master Unit.
An incorrect TxPDO
TxPDO setting was made (e.g., an Check the TxPDO
Not Can be
0024 hex Assignment index, subindex, or size assignment settings in
saved notified
Error that is out of range was the Master Unit.
registered).
An incorrect RxPDO
RxPDO setting was made (e.g., an Check the RxPDO
Not Can be
0025 hex Assignment index, subindex, or size assignment settings in
saved notified
Error that is out of range was the Master Unit.
registered).
Check the
The SYNC0 interrupt
Synchronization Not Can be synchronization settings.
002C hex stopped during operation
Error saved notified (Encoder Input Slave
in Operational state.
Units only)
Check the
No SYNC0 signals have
SYNC Signal Not Can be synchronization settings.
002D hex been received since
Not Received saved notified (Encoder Input Slave
entering DC mode.
Units only)
12-2-1 Cleaning
Perform the following cleaning regularly to ensure the equipment is kept in the best condition possible.
• Wipe the equipment over with a soft, dry cloth when doing daily cleaning.
• If dirt remains even after wiping with a soft, dry cloth, wipe over with a cloth that has been wet with a
sufficiently diluted detergent (2%) and wrung dry.
• Units will become stained if items such as rubber or vinyl products or adhesive tape are left on the
Unit for a long period. Remove such items during regular cleaning. 12
12-2-1 Cleaning
Precautions for Correct Use
Never use benzene, thinners, or other volatile solvents, or chemical cloths.
The unit coating may change if these products are used.
12-2-2 Inspections
Always perform periodic inspections to ensure the equipment is kept in the best possible condition.
Periodic inspections should occur every 6 months to a year.
Periodic inspections should occur more frequently, however, for Units that are used in environments
subject to high temperatures, high humidity, or a lot of dust.
Inspection item
Periodically inspect the following items to ensure that they do not deviate from the criteria.
If the items deviate from the criteria, adjust the environment so the criteria are met or adjust the Unit
itself.
Inspection Inspection
Inspection details Criteria
item method
Are the ambient and in-panel
−10 to 55°C Thermometer
temperatures appropriate?
Environment Is the ambient and in-panel humidity 25 to 85% (with no
Hygrometer
appropriate? condensation)
Has dust collected? No dust Visual inspection
Has the Slave Unit been secured? No looseness Phillips screwdriver
Are the communications cable
No looseness Visual inspection
Installation connectors inserted properly?
Are the external wiring screws loose? No looseness Phillips screwdriver
Are the connection cables damaged? No visible damage Visual inspection
The following values are indicated within the pointed brackets <>.
* The default settings of device type, device name, hardware version, and software version vary by the Slave Unit
Types.
Model Manufacturer Manufacturer
Manufacturer device
DeviceType hardware software
Slave Unit Expansion Unit name
version version
− 00010191 hex GX-ID1611/GX-ID1621
GX-ID1611+ID08(-1)/
XWT-ID08 (−1) 00010191 hex
GX-ID1621+ID08(-1)
GX-ID1611+ID16(-1)/ "V1.00 "
GX-ID1611 XWT-ID16 (−1) 00010191 hex space (20 hex) of
GX-ID1621+ID16(-1) (space (20 hex)
/ID1621 20 characters
GX-ID1611+OD08(-1)/ of 15 characters)
XWT-OD08 (−1) 00030191 hex
GX-ID1621+OD08(-1)
GX-ID1611+OD16(-1)/
XWT-OD16 (−1) 00030191 hex
GX-ID1621+OD16(-1)
MSB LSB
d a o l
64 hex 61 hex 6F hex 6C hex
• The ABORT code is displayed if a value other than the specific is written.
• A value 0000 0001 hex (command valid) is indicated when reading.
• Unit version 1.0 of the GX-series Digital I/O Slaves, Analog I/O Slaves, and Encoder Input Slaves will
always give 00000000 hex as the serial number.
* The table below shows the identity object values by Slave Unit types.
Model Revision Model Revision
Product Product
Type Number Number
Slave Unit Expansion Unit Code (hex) Slave Unit Expansion Unit Code (hex)
(hex) (hex)
− 0000000E 00010000 − 00000017 00010000
XWT-ID08 0000000F 00010000 XWT-ID08 00000018 00010000
XWT-ID08-1 00000013 00010000 XWT-ID08-1 0000001C 00010000
XWT-ID16 00000010 00010000 XWT-ID16 00000019 00010000
GX-ID1611 XWT-ID16-1 00000014 00010000 GX-ID1621 XWT-ID16-1 0000001D 00010000
XWT-OD08 00000011 00010000 XWT-OD08 0000001A 00010000
31 16 15 8 7 0
Sub
Indexes Bit length
Indexes
MSB LSB
The following indexes describes the specific objects by Slave Unit types.
* The default settings of the 257th transmit PDO Mapping and the 257th receive PDO Mapping are given below.
Model 257th Receive PDO Mapping 257th Transmit PDO Mapping
Type Number of Number of
Slave Unit Expansion Unit 1st object 1st object
objects objects
− − − 01 hex 61000110 hex
XWT-ID08 (−1) − − 01 hex 61200120 hex
GX-ID1611/ID1621 XWT-ID16 (−1) − − 01 hex 61200120 hex
XWT-OD08 (−1) 01 hex 63000110 hex 01 hex 61000110 hex
XWT-OD16 (−1) 01 hex 63000110 hex 01 hex 61000110 hex
− 01 hex 63000110 hex − −
XWT-ID08 (−1) 01 hex 63000110 hex 01 hex 61000110 hex
2-tier terminal GX-OD1611/OD1621 XWT-ID16 (−1) 01 hex 63000110 hex 01 hex 61000110 hex
block XWT-OD08 (−1) 01 hex 63200120 hex − −
* The default settings (Number of objects) of the 258th transmit PDO Mapping and the 258th receive PDO
Mapping are given below.
258th Receive PDO 258th Transmit PDO
Model
Type Mapping Mapping
Slave Unit Expansion Unit Number of objects Number of objects
− − 10 hex
XWT-ID08 (−1) − 20 hex
GX-ID1611/ID1621 XWT-ID16 (−1) − 20 hex
XWT-OD08 (−1) 10 hex 10 hex
XWT-OD16 (−1) 10 hex 10 hex
− 10 hex −
XWT-ID08 (−1) 10 hex 10 hex
GX-OD1611/OD1621 XWT-ID16 (−1) 10 hex 10 hex
2-tier terminal block
XWT-OD08 (−1) 20 hex −
XWT-OD16 (−1) 20 hex −
− 10 hex −
XWT-ID08 (−1) 10 hex 10 hex
GX-OC1601 XWT-ID16 (−1) 10 hex 10 hex
XWT-OD08 (−1) 20 hex −
XWT-OD16 (−1) 20 hex −
GX-MD1611/MD1621 − 10 hex 10 hex
GX-ID1612/ID1622 − − 10 hex
3-tier terminal block GX-OD1612/OD1622 − 10 hex −
GX-MD1612/MD1622 − 10 hex 10 hex
GX-ID1618/ID1628 − − 10 hex
GX-OD1618/OD1628 − 10 hex −
e-CON GX-MD1618/MD1628 − 10 hex 10 hex
Connectors GX-ID3218/ID3228 − − 20 hex
GX-OD3218/OD3228 − 20 hex −
GX-MD3218/MD3228 − 10 hex 10 hex
• Mapping for soft switch command from the EtherCAT Master Unit to Slave Units.
* The default settings for Sync Manager 2 PDO Assignment and Sync Manager 3 PDO Assignment are different
for OMRON software and software from other companies. The default settings are given in the following table.
MSB LSB
l c l e
6C hex 63 hex 6C hex 65 hex
Writing values other than this is invalid.
Reference
In the default Sysmac Studio settings, sub-index 1 (Sysmac Error Status) is automatically
mapped to a PDO because 1BFF hex (512th transmit PDO Mapping) is assigned.
Set
Filter set value [ms]
value
00 hex 0
01 hex 0.5
02 hex 1
03 hex 2
04 hex 4
05 hex 8
06 hex 16
07 hex 32
Bits 15 14 • • • • • 1 0
Contents OUT15 OUT14 • • • • • OUT1 OUT0
setting setting setting setting
Bits 31 30 • • • • • 1 0
Contents OUT31 OUT30 • • • • • OUT1 OUT0
setting setting setting setting
Objects of Device Profile areas that are implemented in a Digital I/O Slave Unit is determined by the
number of inputs and/or outputs per Slave Unit and whether or not Expansion Units are connected.
The following table shows the objects of Device Profile area that are implemented in Digital I/O Slave
Unit and the number of sub-indexes.
Set
Range
value
00 hex 10 to +10 V
01 hex 0 to 5 V
02 hex 0 to 10 V
03 hex 4 to 20 mA
07 hex 1 to 5 V
MSB LSB
e v a s
65 hex 76 hex 61 hex 73 hex
t e s r A
74 hex 65 hex 73 hex 72 hex
MSB LSB
e v a s
65 hex 76 hex 61 hex 73 hex
t e s r
74 hex 65 hex 73 hex 72 hex
Bits State
0 1: CH1 disconnected, 0: CH1 normal
1 1: CH2 disconnected, 0: CH2 normal
2 1: CH3 disconnected, 0: CH3 normal
3 1: CH4 disconnected, 0: CH4 normal
4 to 15 Reserved
Set
Range
value
00 hex 4 to 20 mA
01 hex 0 to 10 V
03 hex −10 to +10 V
04 hex 0 to 5 V
06 hex 1 to 5 V
MSB LSB
e v a s
65 hex 76 hex 61 hex 73 hex
t e s r
74 hex 65 hex 73 hex 72 hex
Notes: Always adjust the lower limit first. If the lower limit is adjusted without adjusting the upper limit 100%, the
lower limit adjustment may have an error.
MSB LSB
e v a s
65 hex 76 hex 61 hex 73 hex
t e s r
A
74 hex 65 hex 73 hex 72 hex
Writing values other than the above is invalid.
Set
Range
value
00 hex Hold Last State (Hold and output.)
01 hex Low Limit (Output the lower limit.)
02 hex High Limit (Output the upper limit.)
03 hex User Count (Output a user specified value.)
04 hex Zero Count (Output a value of 0000 hex in the setting range.)
Summary
XWT-OD08 5 mA max. XWT-OD08-1 5 mA max.
XWT-ID16 10 mA max. XWT-ID16-1 10 mA max.
XWT-OD16 10 mA max. XWT-OD16-1 10 mA max.
VCC: I/O power supply voltage (The allowable power supply voltage range is 20.4 to 26.4 V, so 20.4 V will be
used here to allow for the worst possible conditions.)
VON: ON voltage for a Unit with DC inputs
VR: Sensor's output residual voltage
It is sometimes possible to satisfy the above equation by adjusting the I/O power supply voltage (VCC)
to 26.4 V.
2-wire DC input
VR R RIN
sensor type slave
VCC
Connect a bleeder resistor if the sensor's leakage current is greater than the OFF current of a Unit with
DC inputs.
Connecting Two-wire DC
The bleeder resistor constant can be calculated using the following equation.
Output Inductive
transistor load Diode
Output Unit
(with output transistor)
The points to which I/O power must be supplied are divided into small blocks. The I/O power supply
Example:
The following example is for when seven, three-wire sensors with a current consumption of 30 mA
each are connected to the GX-ID1612.
The GX-ID1612 specifications are,
• Input current of 6.0 mA max./point (at 24 VDC)
• I/O power supply current consumption of 10 mA max. (at 20.4 to 26.4 VDC).
Therefore,
I/O power supply current supplied to V and G terminals =10 mA + (6 mA × 7 points) + (30 mA × 7
points) = 262 mA
*1 This value does not apply when two-wire output devices are connected.
Use the following formula when two-wire output devices are connected:
I/O power supply current supplied to V and G terminals = (Current consumption of Output Slave Unit from
I/O power supply) + (Total load current of the
connected loads)
*2 Compare the value from the above formula to the rated current (common) of the Output Slave Unit and use
the smaller value.
Example:
The following example is for when five relays with a load current of 20 mA each are connected to the
GX-OD1612.
The GX-OD1612 specifications are,
A-6 Glossary
Use the following list of EtherCAT terms for reference.
Abbrevia-
Term Description
tion
Status for indicating information on errors that occur in an application
AL status (application layer status) −
on a slave.
CAN application protocol over
CoE A CAN application protocol service implemented on EtherCAT.
EtherCAT
CiA is the international users' and manufacturers' group that
CAN in Automation CiA
A-6 Glossary
develops and supports higher-layer protocols.
Collection of device dependent information and functionality
device profile − providing consistency between similar devices of the same device
type.
Clock distribution mechanism used to synchronize EtherCAT Slave
distributed clocks DC
Units and the EtherCAT Master Units.
EtherCAT slave controller ESC A controller for EtherCAT slave communication. A
An XML file that contains setting information for an EtherCAT Slave
EtherCAT slave information ESI
Unit.
EtherCAT state machine ESM An EtherCAT communication state machine.
The ETG is a global organization in which OEM, End Users and
EtherCAT Technology Group ETG Technology Providers join forces to support and promote the further
technology development.
index − Address of an object within an application process.
The EtherCAT network configuration information held by the
network configuration information −
EtherCAT master.
Abstract representation of a particular component within a device,
object −
which consists of data, parameters, and methods.
Data structure addressed by Index and Sub-index that contains
object dictionary OD description of data type objects, communication objects and
application objects.
A state in EtherCAT communications where SDO communications
operational −
and I/O are possible.
PDO communications − An acronym for process data communications.
A state in EtherCAT communications where only SDO
pre-operational −
communications are possible without being able to perform I/O.
Collection of application objects designated to be downloaded
Process data −
cyclically or acyclically for the purpose of measurement and control.
One type of EtherCAT communications that uses process data
process data communications − objects (PDOs) to exchange information in realtime with a fixed
cycle. This is also called PDO communications.
Structure described by mapping parameters containing one or
Process data object PDO
several process data entities.
Receive PDO RxPDO A process data object received by an EtherCAT Slave Unit.
A state in EtherCAT communications where only SDO
safe operational − communications and reading input data from slaves are possible.
Outputs from slaves are not performed.
One type of EtherCAT communications that uses service data
SDO communications −
objects (SDOs) for communicating information when required.
CoE asynchronous mailbox communications where all objects in the
service data object SDO
object dictionary can be read and written.
Slave Information Interface SII Slave information that is stored in non-volatile memory in the slave.
subindex − Sub-address of an object within the object dictionary.
Abbrevia-
Term Description
tion
Collection of control elements to coordinate access to concurrently
sync manager SM
used objects.
Transmit PDO TxPDO A process data object sent from an EtherCAT Slave Unit.
O U
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the
previous version.
Revision code Date Revised content
01 August 2010 Original production
02 September 2010 Added Encoder Input Slave Units GX-EC02xx.
03 July 2011 Added functions for change to unit version 1.1 and corrected errors.
04 November 2013 Added descriptions and corrected mistakes.
05 July 2016 Added GX-ILM08C IO-Link Master Unit.
OMRON ASIA PACIFIC PTE. LTD. OMRON (CHINA) CO., LTD. © OMRON Corporation 2010-2016 All Rights Reserved.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Room 2211, Bank of China Tower, In the interest of product improvement,
Alexandra Technopark, 200 Yin Cheng Zhong Road, specifications are subject to change without notice.
Singapore 119967 PuDong New Area, Shanghai, 200120, China