0% found this document useful (0 votes)
0 views

ConnectionPrintPDF (89)

The MT-1 Checking Report details the periodic check of a net meter for a school in Ambala Cantt, conducted on March 21, 2025. The report includes consumer information, meter readings, and observations, confirming the meter's accuracy and proper functioning within limits. All seals were found intact, and the meter's multiplying factor was noted as RX20.

Uploaded by

RAJESH KUMAR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
0 views

ConnectionPrintPDF (89)

The MT-1 Checking Report details the periodic check of a net meter for a school in Ambala Cantt, conducted on March 21, 2025. The report includes consumer information, meter readings, and observations, confirming the meter's accuracy and proper functioning within limits. All seals were found intact, and the meter's multiplying factor was noted as RX20.

Uploaded by

RAJESH KUMAR
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

MT-1 Checking Report

MT-1 No :- MT1A14-0325-161966-1801 Date of Checkings :- 21/03/2025 Checking For :- Periodical


Date of Last Checking :- 21/03/2025 Main Meter/Check Meter :- Consumer-End Type of Meter : Net Meter
Meter Location :- Not near the main gate
(A) Consumer Basic Information as per billing database :-
1. Name of Circle :- Ambala 2. Name of Division : - Amabala Cantt 3. Name of sub-division :- A14
(BABYAL)
4. Name of consumer :- PRINCIPAL 5. Address :- MODEL SCHOOL, KISMAT 6. Tariff Category : - NDS
D.C. NAGAR, Ambala Cantt., HR, IND

7. Connected load (KW) :- 48.00 8. Contract Demand (KVA) : 53.33 9. New Load (KW / KVA) :- /
10. Meter Make : AVON 11. Meter Serial Number : 1327803 12. Account Number : 2100500000
13. Billing Month : Feb 2025 14. CCB MF : 20.00 15. CCB Mobile No.: 9992599275
(B) Master Information found at Site
Sr. No. General Information Value Sr. No. Metering details Value
1. Meter Type DLMS 1. Modem Connected[Y/N]
2. Voltage LT 2. Meter CT Ratio -/5A
3 Feeder category Urban 3. Meter PT Ratio 3X240V/
4 Seasonal / Non-seasonal Non-Seasonal 4. Meter MF 01
5 Product/ Service School 5. CT Ratio 100/5A
6. Meter Make Secure Meter Ltd. 6. PT Ratio 3X240V/
7. Meter Serial No HRT78770 7. Revs /Pulse 8000
8. Modem Make
8. Multiplying Factor R x 20
9. Modem Serial Number :

(C) Readings in Meter at time of checking


Parameter Reading
T Real Time 21/03/25 12:09
Actual Date/Time 21/03/2025 12:09
n (MD reset count) 94
n (MD reset count) After
U (Import-Kwh) 19403.95 u (Export-Kwh) 625.95
Net (KWH) 18778.0
r (KVArh-Lag) 3791.11 r (KVArh-Lag Export) 536.43
r (KVArh-Lead) 2641.86 r (KVArh-Lead Export) 111.38
A (KVAh) 20226.72 A (KVAh Export) 1103.46
C (Cum Demand) Kw 142.174 C (Cum Demand Export) Kw 25.590
C (Cum Demand) After Kw C (Cum Demand Export) After Kw
C (Cum Demand) Kva 143.660 C (Cum Demand Export) Kva 30.832
C (Cum Demand) After Kva C (Cum Demand Export) After Kva
MDI (kw) 1.116 MDI Export (kw) 0.002
MDI After (kw) MDI Export After (kw)
MDI (kva) 1.116 MDI Export (kva) 0
MDI (kva) After MDI Export After (kva)
H (Power on Hour)

AC-TOD Import KWH Export KWH Import KVAH Export KVAH


1. 2814.27 0 2920.55 0
2. 1438.28 0.78 1665.97 6.34
3. 13232.05 623.19 13578.29 1081.47
4. 152.72 1.82 172.24 14.42
5. 175.34 0.13 191.14 1.13
6. 193.80 0.02 206.74 0.09
7. 924.73 0.01 986.61 0.01
8. 472.83 0 505.26 0

Sr. No. Tampers on Display of Meter Sr. No. Tampers on Display of Meter
1 TMC 4685 6 Lrc----b--, 20.3.25/15:00
2 PPT-----
7 CVR 00
3 PCT---o-u-,
8 CKT GOOD
4 POT---
5 LOC---O---, 20.3.25/17:05 9

Page 1/2
(D) Position of Seals
Seals of Before Checking After Checking
MCB E5522705+06
BP
OP
TTB
MDI_KW M5274560 M5274560
TC M5274558+59 M5274558+59
Combined CT/PT F3108585+86 F3108585+86
Company Seals 5776273+74 5776273+74
Meter Cover Seals M4876156+55 M4876156+55

Accucheck Parameter : Accucheck Parameter After :


Serial Number of Accucheck : Serial Number of Accucheck :
P1 235 C1 41.8 PF KW 27.0 P1 C1 PF KW
P2 237 C2 29.9 0.99 KVA 27.3 P2 C2 KVA
P3 237 C3 40.5 KVAR P3 C3 KVAR
Load in KW Load in KVA

Meter Display Parameters Meter Display Parameters after


U1 236 L1 2.10 PF KW 1.36 U1 L1 PF KW
U2 238 L2 1.50 0.9 KVA 1.37 U2 L2 KVA
U3 237 L3 2.08 KVAR U3 L3 KVAR
Results of accuracy of meter :
Meter (MRI-CMRI) Accucheck Difference % age error
KWH W/L
KVARH
KVAH
Dial Test OK
Results of accuracy of meter after :
Meter (MRI-CMRI) Accucheck Difference % age error
KWH
KVARH
KVAH
Dial Test
Load in KW
Load in KVA
Details of CT/PT in case of new connection or change of CT/PT

Equipment Make Serail No. Ratio Burdon Accuracy Class Detail of M&T Lab
& Firm Seals existing
on the equipments
CT Existing
PT

(E) Observations :
Visited the site for periodical checking. Accuracy of meter checked and found working within limits. MF be read as RX20(Twenty). MCB resealed properly.

LOR Case : NO
LOR Case Reason :

Designation / Signature Designation / Signature Designation / Signature Designation / Signature

AE M&P /Sunil Kumar JE/ALMs M&P ALM OP / Subash Estate Officer / Rajesh Kumar
/Sachin/Sunil, Ashok

Account Number : 2100500000 MT-1 No :- MT1A14-0325-161966-1801 Page 2/2