Lect. 6 protection 2022
Lect. 6 protection 2022
Lecture 6
Presented by:
Professor Dr. Saady Abd-El hamid
Definition
14
A- Operation during ( Normal &External Fault)
V N1N2= 0,
B- Operation during (Internal Fault), Case 1 RF= 0, Grid
C- Operation during (Internal Fault), Case 2 RF= 0, single source
D- Operation during (Internal Fault), Case 3 high fault impedance
E- Operation during (Internal Fault), Case 4, False detection internal
series fault
2- Principles of Differential Relaying
Current Balance High Impedance
21
Current Balance High Impedance- Unbiased Differential
• With these schemes a certain degree of CT saturation is possible
under heavy fault conditions. This leads to false operation of the
relay.
• Stabilization is achieved by means of a stabilizing
resistor, RS, intended to raise the operating voltage of the system.
• Fault current through RS could lead to dangerous over voltages
voltage limiters are required.
• Relatively easy to set but it requires identical CT s (identical
magnetization characteristics) in order to minimize the spill
current with normal load.
- Alternatively the operating point of the system is increased by the
use of a stabilizing resistor (unbiased/high impedance diff. protection.
Behavior of differential current relay during external Fault
with saturation of C.T.2
2-b Principles of Differential Relaying
Current Balance High Impedance For REF
• REF is fast and sensitive (more so than biased
differential protection)
• Applied to transformer windings especially ones
which have been impedance earthed.
• Also bus-zones and generators.
• Typically only used for EF schemes (transformers)
but could be triplicated to offer phase fault
protection as well generator, motor, bus-zone.
26
Proactive frequency control for high renewables penetrated power systems 27
3-
𝑰𝟏 + 𝑰𝟐
𝑵𝒐 𝑰𝟏 − 𝑰𝟐 > 𝑵𝒓
𝟐
𝑵𝒓 𝑰𝟏 + 𝑰𝟐
𝑰𝟏 − 𝑰𝟐 >
𝑵𝒐 𝟐
𝑰𝒅 > 𝑲𝑰𝒓
Percentage or Biased Differential Relay