The document provides installation instructions for the iPASOLINK VR 2 Indoor Unit (IDU), detailing the typical installation flow, configurations, and component compositions. It includes sections on unpacking, mounting, connecting cables, and starting up the unit. The installation is intended for skilled personnel and emphasizes compliance with safety standards.

Uploaded by

klaus.csalmeida
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
50 views46 pages

Ipaso vr2 03 GGS-000402-14E Idu

The document provides installation instructions for the iPASOLINK VR 2 Indoor Unit (IDU), detailing the typical installation flow, configurations, and component compositions. It includes sections on unpacking, mounting, connecting cables, and starting up the unit. The installation is intended for skilled personnel and emphasizes compliance with safety standards.

Uploaded by

klaus.csalmeida
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 46

GGS-000402-14E

July 2023

iPASOLINK VR 2
INDOOR UNIT (IDU)
INSTALLATION

NEC Corporation
7-1, Shiba 5-Chome, Minato-Ku, Tokyo 108-8001, Japan
GGS-000402-14E

© 2015 – 2023 by NEC Corporation

GGS-000402-14E
Printed in Japan
CONTENTS –i–

iPASOLINK VR 2
INDOOR UNIT (IDU) INSTALLATION

CONTENTS

1. OVERVIEW 1-1

1.1 Typical Installation Flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1

1.2 iPASOLINK VR 2 Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2


1.2.1 Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2.1.1 One MODEM Port Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2.1.2 Two MODEM Ports Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.2.2 iPASOLINK VR 2 1+0 System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.2.3 iPASOLINK VR 2 1+1 System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.2.4 iPASOLINK VR 2 1+0 XPIC System . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5

2. COMPOSITIONS 2-1

2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1


2.1.1 Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.1.2 iPASOLINK VR 2 Chassis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2

2.2 iPASOLINK VR 2 IDU Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3


2.2.1 MC-SV (Main Card). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.2.2 MC-SVE (Main Card) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2.2.3 Optional Card (Factory Assembled) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
2.2.3.1 CLK-CV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8

3. UNPACK IDU 3-1

4. MOUNT IDU 4-1

4.1 Mount IDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1


4.1.1 Recommended Rack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2

IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


July 2023
– ii/END – CONTENTS

4.1.2 Mount IDU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3

4.2 Replace Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5

4.3 Mount SFP Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5


4.3.1 SFP Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.3.2 Mount SFP Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6

5. CONNECT CABLES 5-1

5.1 Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1


5.1.1 Connector Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1.2 Connect Interface Cable with L-Shaped Plug to IDU . . . . . . . . . . . . . . . 5-2

5.2 Grounding Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5

5.3 Route Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9


5.3.1 Grounding Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
5.3.2 IF Cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
5.3.3 Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
5.3.4 16E1 and GbE Signal Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
5.3.5 XIF Coaxial Cables (XPIC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10

5.4 Connector Pin Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11


5.4.1 Power Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
5.4.2 2M IN/OUT Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-12
5.4.3 CLK-CV Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
5.4.4 (Debug Terminal). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15

6. START UP AND SHUT DOWN 6-1

6.1 Start Up iPASOLINK VR 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1


6.1.1 Basic Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1.2 Start Up Equipment Using USB Memory Device . . . . . . . . . . . . . . . . . . 6-2
6.1.2.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.1.2.2 Start-Up Process Using USB Memory Device . . . . . . . . . . . . . . . 6-3

6.2 Shut Down iPASOLINK VR 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3

GGS-000402-14E iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


OVERVIEW 1-1

1. OVERVIEW

1.1 Typical Installation Flow


The standard installation of Indoor Unit (IDU) is summarized in this section.
Followings shows the typical installation work flow and guides:

 This product is a part of the radio link system, and is intended to be connected
with ODU.

 This product should be installed and operated by skilled personnel.

 After the installation, the system should be ensured to comply with the relevant
limits for general public exposure specified as basic restrictions or reference
levels in the council Recommendation 1999/519/EC.

Figure 1-1 Typical Installation Flow Diagram

Unpacking IDU Unpacking ODU


(see Section 3.) (see Annex)

Mounting IDU Mounting ODU


(see Section 4.) (see Annex)

Assemble Cables
(see Annex)

Wiring and Forming


(see Section 5.)

Grounding
the Frame
(see Section 5.)

Waterproofing
(see Annex)

Orienting Antenna
(see Annex)

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


1-2 OVERVIEW

1.2 iPASOLINK VR 2 Configurations

1.2.1 Reference

1.2.1.1 One MODEM Port Type


NOTE: iPASOLINK VR 2 does not provide the MC-SVE One MODEM Port
type.

Figure 1-2 iPASOLINK VR 2 Chassis Layout 1

(MAIN CARD: MC-SV)


[On-Board MODEM 1]

PWR1 PWR2

ODU
GROUNDING PORT (FG)

TNCP CONNECTOR

MC-SV

GGS-000402-14E iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


OVERVIEW 1-3

1.2.1.2 Two MODEM Ports Type

Figure 1-3 iPASOLINK VR 2 Chassis Layout 2

[On-Board MODEM 1] (MAIN CARD: MC-SV)

[On-Board MODEM 2] PWR1 PWR2

ODU ODU
GROUNDING PORT (FG)

TNCP CONNECTOR

TNCP CONNECTOR

MC-SV

ODU ODU
GROUNDING PORT (FG)

TNCP CONNECTOR

TNCP CONNECTOR

MC-SVE

 Reference for Available Configurations


 iPASOLINK VR 2 1+0 System
 iPASOLINK VR 2 1+1 System
 iPASOLINK VR 2 1+0 XPIC System

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


1-4 OVERVIEW

1.2.2 iPASOLINK VR 2 1+0 System

GROUNDING PORT (FG)


ODU

TNCP CONNECTOR

MC-SV

NOTE: iPASOLINK VR 2 does not provide the MC-SVE One MODEM Port
type.

1.2.3 iPASOLINK VR 2 1+1 System


ODU ODU
GROUNDING PORT (FG)

TNCP CONNECTOR

TNCP CONNECTOR

MC-SV

ODU ODU
GROUNDING PORT (FG)

TNCP CONNECTOR

TNCP CONNECTOR

MC-SVE

GGS-000402-14E iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


OVERVIEW 1-5

1.2.4 iPASOLINK VR 2 1+0 XPIC System

On-Board MODEMs can configure one 1+0 XPIC:

MASTER

XPIC GRP MC-SV


SLAVE

MASTER

XPIC GRP SLAVE MC-SVE

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


1-6/END OVERVIEW

This page is intentionally left blank.

GGS-000402-14E iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


COMPOSITIONS 2-1

2. COMPOSITIONS

2.1 Overview

2.1.1 Contents

iPASOLINK VR 2 Indoor Unit (IDU) comprises of the followings:

Figure 2-1 Contents of Cards


1

MC-SV

MC-SVE

No. Description

1 Power Connector [Housing (AMP: 1-178288-4 (x1 ea)) or DK-3100S-04R (x1 ea) and
Socket Contacts (AMP: 1-175218-2 (x4 ea))]

2 MDP-1200MB-1A (IDU) MC-SV: NWA-096363-0**/3**/6**, supporting the ports to


interface with both TDM and ETH.

MC-SVE: NWA-096363-5**; supporting the ports to


interface with ETH only.

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


2-2 COMPOSITIONS

2.1.2 iPASOLINK VR 2 Chassis

[On-Board MODEM 1]

[On-Board MODEM 2] PWR1 PWR2

(MAIN CARD: MC-SV)

 Components
 MC-SV (Main Card)
 MC-SVE (Main Card)
 Optional Card (Factory Assembled)

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


COMPOSITIONS 2-3

2.2 iPASOLINK VR 2 IDU Components

2.2.1 MC-SV (Main Card)

NOTES:
1. MC-SV Card (NWA-096363-0**/3**/6**) supports the ports to interface with both
TDM and ETH.

2. MC-SV Card requires CLK-CV Card optionally to support advanced CLK and CLK
Terminal function. Refer to 2.2.3.1 CLK-CV for details.

   15 16 18 20 21 22

    11 12 13 14
17 19 23

Ref. # Indication Element Description

 Grounding Screw Grounding terminal; screw shaft diameter is 4 mm.

 IF1 TNC Connector IF Terminal connecting to the Outdoor Unit (ODU); SYS1

IF2 TNC Connector IF Terminal connecting to the Outdoor Unit (ODU); SYS2

 CALL Push Button (Optional) Press the button to call the opposite site by OW.
NOTE: This function is supported on CLK-CV[001] and
CLK-CV[002].

 EOW Pin Jack (Optional) Connecting terminal for OW Headset.


NOTE: This function is supported on CLK-CV[001] and
CLK-CV[002].

 CLK D-Sub Connector (Optional) Terminal for Clock Signal input/output. (15 pins)
NOTE: This function is supported on CLK-CV[001] and
CLK-CV[002].
See 2.2.3 Optional Card (Factory Assembled).

 TX 1, TX 2 LED Off State of radio transmission output. (TX Mute On)


(Green)
On State of radio transmission output. (TX Mute Off)

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


2-4 COMPOSITIONS

Ref. # Indication Element Description

 RX1, RX 2 LED Off Not selected for receiving the radio signals.
(Green)
On Selected for receiving the radio signals.

 ODU PWR IF1 Rocker Switch Switch to supply/shut-down power to ODU 1 (using IF1).

ODU PWR IF2 Rocker Switch Switch to supply/shut-down power to ODU 2 (using IF2).

 MEM USB Type-A Connecting terminal for USB memory device. (Supporting
a memory device only.)

 2M IN/OUT MDR Connector E1 Traffic Signal Input/Output

11 LCT RJ-45 Connector Ethernet port for connecting WebLCT. (Supporting 10/
100BASE-TX; Auto-Negotiation, Auto-MDI/MDIX.)

12 NMS RJ-45 Connector Terminal for connecting to DCN Network upstream.


(Supporting 10/100BASE-TX; Auto-Negotiation,
Auto-MDI/MDIX)
13 NE/1 RJ-45 Connector Two-Way Use: Terminal for connecting DCN Network
downstream., or traffic Ethernet signal input/output Port 1.
(Supporting 10/100/1000BASE-TX; Auto-Negotiation,
Auto-MDI/MDIX)
14 2 RJ-45 Connector Traffic Ethernet signal input/output Port 2 to Port 4.
(Supporting 10/100/1000BASE-TX; Auto-Negotiation,
15 3 Auto-MDI/MDIX)
16 4
17 1, 2, 3, 4 LED Off State of indicated # of Traffic Ethernet Port: Link Down

On State of indicated # of Traffic Ethernet Port: Link Up

Blinking State of indicated # Traffic Ethernet Port: TX/RX Activity

18 5, 6 SFP Module Port Traffic Ethernet Signal 1000BASE-SX/LX

19 5, 6 LED Off State of indicated # of Traffic Ethernet Port: Link Down

On State of indicated # of Traffic Ethernet Port: Link Up

Blinking State of indicated # of Traffic Ethernet Port: TX/RX Activity


20 MAINT LED Off IDU is in the normal condition.
(Amber) On IDU is in the maintenance mode, or downloading to the
USB Memory is completed (when using PROTECT
switch).

Blink • Once — CPU is starting up.


• Fast — Downloading data to the external storage.
• Slow — Uploading data is completed.
21 ALM LED Off The Card is in the normal condition.
(Red) On A failure is detected in the Card.

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


COMPOSITIONS 2-5

Ref. # Indication Element Description


22 SELV PWR 1/ DK3100 Power Input Terminal for IDU. SELV, –48 V DC. PWR 2 is
2 an optional.
23 PWR 1 LED Off Power is off, or the card is in alarmed condition.
PWR 2 (Red) On The Card is in the normal condition.

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


2-6 COMPOSITIONS

2.2.2 MC-SVE (Main Card)

NOTES:
1. MC-SVE (NWA-096363-5**) does not support the ports to interface with TDM.

2. NWA-096363-5*B/5*C supports the advanced CLK, such as BC (IEEE 1588V2


Boundary Clock) and SOOC (Slave Only Ordinary Clock) without using the
optional CLK-CV Card.

     12 13 15 19

   11 14 16 17 18 20

Ref. # Indication Element Description

 Grounding Screw Grounding terminal; screw shaft diameter is 4 mm.

 IF1 TNC Connector IF Terminal connecting to the Outdoor Unit (ODU); SYS1

IF2 TNC Connector IF Terminal connecting to the Outdoor Unit (ODU); SYS2

 TX 1, TX 2 LED Off State of radio transmission output. (TX Mute On)


(Green)
On State of radio transmission output. (TX Mute Off)

 RX1, RX 2 LED Off Not selected for receiving the radio signals.
(Green)
On Selected for receiving the radio signals.

 ODU PWR 1 LED Off Power to ODU 1 (using IF1) is shut-down.


(Green)
On Power to ODU 1 (using IF1) is supplied.

ODU PWR 2 LED Off Power to ODU 2 (using IF2) is shut-down.


(Green)
On Power to ODU 2 (using IF2) is supplied.

 MEM USB Type-A Connecting terminal for USB memory device. (Supporting
a memory device only.)

 —— D-Sub Connector Debug Terminal (15 pins). For factory test only.

 LCT RJ-45 Connector Ethernet port for connecting WebLCT. (Supporting 10/
100BASE-TX; Auto-Negotiation, Auto-MDI/MDIX.)

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


COMPOSITIONS 2-7

Ref. # Indication Element Description

 NMS RJ-45 Connector Terminal for connecting to DCN Network upstream.


(Supporting 10/100BASE-TX; Auto-Negotiation,
Auto-MDI/MDIX)

 NE/1 RJ-45 Connector Two-Way Use: Terminal for connecting DCN Network
downstream., or traffic Ethernet signal input/output Port 1.
(Supporting 10/100/1000BASE-TX; Auto-Negotiation,
Auto-MDI/MDIX)
11 2 RJ-45 Connector Traffic Ethernet signal input/output Port 2 to Port 4.
(Supporting 10/100/1000BASE-TX; Auto-Negotiation,
12 3 Auto-MDI/MDIX)
13 4
14 1, 2, 3, 4 LED Off State of indicated # of Traffic Ethernet Port: Link Down

On State of indicated # of Traffic Ethernet Port: Link Up

Blinking State of indicated # Traffic Ethernet Port: TX/RX Activity


15 5, 6 SFP Module Port Traffic Ethernet Signal 1000BASE-X
16 5, 6 LED Off State of indicated # of Traffic Ethernet Port: Link Down

On State of indicated # of Traffic Ethernet Port: Link Up

Blinking State of indicated # of Traffic Ethernet Port: TX/RX Activity


17 MAINT LED Off IDU is in the normal condition.
(Amber) On IDU is in the maintenance mode, or downloading to the
USB Memory is completed (when using PROTECT
switch).

Blink • Once — CPU is starting up.


• Fast — Downloading data to the external storage.
• Slow — Uploading data is completed.
18 ALM LED Off The Card is in the normal condition.
(Red) On A failure is detected in the Card.
19 SELV PWR 1/ DK3100 Power Input Terminal for IDU. SELV, –48 V DC. PWR 2 is
2 an optional.
20 PWR 1 LED Off Power is off, or the card is in alarmed condition.
PWR 2 (Red) On The Card is in the normal condition.

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


2-8/END COMPOSITIONS

2.2.3 Optional Card (Factory Assembled)

2.2.3.1 CLK-CV

PCB

CLK-CV is to be mounted directly on the MC-SV (Main Card) and which provide the
following functions.
 Advanced clock function such as [IEEE 1588v2 Boundary Clock (BC) and Slave Only
Ordinary Clock (SOOC)].
 CLK Terminal (for inputs/outputs of the clock signals) by the High-Density D-Sub 15-Pin
connector.

Advanced Clock function CLK Terminal

CLK-CV[001]  
CLK-CV[002] 
CLK-CV[003] 

NOTE: iPASOLINK VR 2 equipped with MC-SVE (NWA-096363-5**) for its Main


Card can support the advanced CLK without using optional CLK-CV Card.

GGS-000402-14E iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


UNPACK IDU 3-1

3. UNPACK IDU

NOTE: Please keep the packing materials. In case that the equipment needs
to be transported, use the original packing materials to prevent the
equipment from damages.

Procedure 3-1 Unpack IDU

1. Open the container box by lifting its top cover.

Shipping Tag / Packing Slip


(with a bar-code and
the information of importer)

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


3-2/END UNPACK IDU

2. Unbox the contents. The contents are boxed as shown below:

Flap
Attachment
Desiccant

Flap

Pad on Top

Polyethylene Sheet

(IDU)

Pad on Bottom

Inner Packing Box

3. Remove the polyethylene sheet from IDU.

4. Check the appearance of IDU for any damage.

GGS-000402-14E iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


MOUNT IDU 4-1

4. MOUNT IDU

4.1 Mount IDU


IMPORTANT: Make sure the power line and supply the electricity after properly
mounting the equipment on 19-inch Rack. Do not grab or push near the center
of the equipment while the power is on.

Do not grab or push

Do not grab or push

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


4-2 MOUNT IDU

4.1.1 Recommended Rack


iPASOLINK VR 2 should be mounted on the19-inch Rack whose two post frames,
square U-shaped or channel, face their channel sides to make the air duct rooms.
iPASOLINK VR 2 provides the air outlets on its both sides, which requires rooms on
its both sides to avoid rise in temperature.

Example below uses EIA 310-D [IEC-60297] Rack:

Figure 4-1 Recommended 19-inch Rack

19-INCH RACK
facing channel sides to make rooms
POST FRAME

19-INCH RACK POST FRAME

channel faces outward

channel faces
outward

19-INCH RACK
POST FRAMES

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


MOUNT IDU 4-3

4.1.2 Mount IDU

Procedure 4-1 Procedure of Mounting IDU

1. Supporting brackets are attached on the front of IDU.

(Front) (Rear)

2. Place and adjust the IDU into the mounting position of 19-Inch Rack.

Spring Washer

Screw Flat Washer

Spring Washer

Screw Flat Washer

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


4-4 MOUNT IDU

3. Secure both ends of the IDU to the 19-Inch Rack using four screws.

IDU

Even in the 19-Inch Rack, this IDU needs the following spaces to avoid rise in
temperature:

 Keep at least 200 mm (approx. 7.9 inches) of clearance behind.


 Interspace at least one rack unit* above and below the IDU when multiple
IDUs are mounted in the same rack.

ONE RACK UNIT or MORE 200 mm (7.9 inches)


or more

 (FRONT) (REAR) 
ONE RACK UNIT or MORE

WALL

*: One rack unit = 1.75 inches (approx. 45 mm)

NOTE: The bottom of IDU is heated up while in service.

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


MOUNT IDU 4-5

4.2 Replace Fuse


Fuses on the IDU cannot be replaced at the customer site. If the IDU does not turn on
even though the power is supplied, contact NEC.

4.3 Mount SFP Module

ATTENTION!
It is recommended to use the designated SFPs supplied by NEC for use in
iPASOLINK VR 2. NEC does not guarantee the performances of iPASOLINK if
other vendors’ SFP modules are installed.

SFP MODULE PORT

(Main Card above uses MC-SV as an example.)

4.3.1 SFP Module


The Small Form-factor Pluggable (SFP) is a compact and hot-pluggable transceiver
designed to support Gigabit Ethernet (GbE) interface in the iPASOLINK.
iPASOLINK offers the following five options for SFP modules:

1) Single Mode Fiber (SMF): This SFP complies with 1000BASE-LX Ethernet
Interface. The SFP operates with the 1310 nm laser transmitter and has a
duplex LC connector.

2) Multi Mode Fiber (MMF): This SFP complies with 1000 BASE-SX Ethernet
Interface. The SFP operates with the 850 nm laser transmitter and has a duplex
LC connector.

3) Electrical SFP (RJ45): This SFP complies with 10/100/1000 BASE-T copper
interface.

NOTE: SyncE function is not supported by Electrical SFP.

4) Electrical SFP (DIN 1.0/2.3): This SFP complies with STM-1e SDH interface.

The SFP modules also accept LC fiber connectors with Polished Connector (LC-PC)
or Ultra Polished Connector (LC-UPC).

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


4-6/END MOUNT IDU

4.3.2 Mount SFP Module

1. Mount an SFP module into the SFP port until it clicks and is completely
seated.

ATTENTION!
SIDE VIEW

Keep the SFP module in horizontal position.

GGS-000402-14E iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


CONNECT CABLES 5-1

5. CONNECT CABLES

5.1 Precautions

5.1.1 Connector Types

STRAIGHT PLUG
CAUTION:
Tighten the TNC-Male Connector of IF
IDU Cable on the IDU IF Port with fingers. To
tighten the connection, hold the plug head
while holding the cable by the other hand.
IF cable

Hold the plug head for the L-Shape plug as


NOTE
L-SHAPE PLUG well.
Tightening Torque:
0.3 to 0.5 N•m (3 to 5 kgf•cm)
IDU

IF CABLE

NOTE
L-SHAPE PLUG
Holding a wrong part of the L-Shape plug (as
shown left) may damage the connector.
IDU

IF cable

NOTE: For the use of the L-Shape Plug, following precautions should be read and be
fully understood to prevent connectors from being damaged.

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


5-2 CONNECT CABLES

5.1.2 Connect Interface Cable with L-Shaped Plug to IDU

(1) Protect the joint of plug and cable by wrapping the vinyl tape around:
It is strongly recommended to wrap vinyl tape around the joint of the plug and cable for
the IF Cable terminated with the L-Shaped Plug. See below:

PLUG BODY 1. Wrap the tape for one to 1.5 times carefully around
the joint from the starting point as shown at the left
start here photograph.
NOTE: Ensure not to twist the cable against the plug
while wrapping the joint.

CABLE

20 mm wide tape
is recommended.
2. Keep wrapping till the tape reaches midway up the
middle of the plug. See Step 4. below for the
measurements.

3. Tightly wrap the tape around the joint for more than
four or five times pressing the tape by fingers.

4. Referring to the example shown left, check if the


tape is appropriately wrapped.

slightly
above L
L/2

20 mm

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


CONNECT CABLES 5-3

(2) Ensure the facing angles of plug and port:


Align the IF Cable Plug to the IF Port on the IDU. Check their heads are in the
appropriate angle to each other.

IF PORT
(Interfacing point
Interface point of on IDU)
IDU side connector

Do not attempt to rotate L-Shape plug


by holding the cable, which may give
IF PLUG too much stress or cause damages to
(Interfacing point of plug) the IF Cable, IF Plug and IF Port.
Interface point of

CAUTION: Ensure that the power to MODEM is off before proceeding to


the next step.

 For iPASOLINK VR 2 using MC-SV: Set the MD/ODU PWR rocker


switch to OFF position.

 For iPASOLINK VR 2 using MC-SVE: Disable the power to MODEM


using WebLCT:
 Menu Path:
Maintenance Control  ODU PS Control
[ODU PS Control option window; select Shutdown]

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


5-4 CONNECT CABLES

(3) Face IF Plug of IF Cable and IF Port on IDU.

IF PORT on IDU

IF PLUG of IF Cable

(4) Secure the joint of IF Plug and IF Port:


Do not forcibly rotate the plug. Rotate it gently using both hands.

This step ends the procedure.

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


CONNECT CABLES 5-5

5.2 Grounding Cables


Installed IDU should be grounded. The locations of the grounding terminals are
shown below.

Grounding Terminal on IDU

Using MC-SV Card

Ground Terminal on IDU Flange


(for test/maintenance use only)

Grounding Terminal on IDU

Using MC-SVE Card

Ground Terminal on IDU Flange


(for test/maintenance use only)

NOTES:

1. Connect the Grounding Terminal on the IDU to the ground using the
earth cable. Refer to Figure 5-1, Figure 5-2.

2. Screw torque should be within 1.3 ±0.2 N•m (13 ±2 kgf•cm).

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


5-6 CONNECT CABLES

Figure 5-1 Grounding Procedure (Example – 1/2)

LIGHTNING ROD
PROTECTED AREA

OUTDOOR GROUNDING TERMINAL 30°


30°
(On-Site Facility)

COAXIAL CABLE
GROUNDING ODU
WIRE

INDOOR GROUNDING TERMINAL


(On-Site Facility) RACK
Use a copper grounding conductor
IDU
to ground the equipment.
EARTH LINE

This is the buried grounding wire. (Grounding Resistance:


This type of wire should be naked less than 10 ohms)
(not insulated), which is recommended.

GROUND LEVEL

(Grounding resistance should be


less than 10 Ohms.)

CAUTIONS:
1. Ensure to install ODU(s) within the area protected by lightning rod.
2. To avoid surge currents caused by lightning circulating in the equipment
earth system, connect the equipment earth system (frame ground) to the
ground of the lightning rod at the ground level.

NOTES:

1. Frame Ground terminal of the IDU [5 mm square cable, which means


more than 2.5 mm diameter cable (10 AWG) is recommended to apply
for the earth grounding. The proper press fix terminal tool shall be
used.]
2. Screw torque should be within 1.3 ±0.2 N•m (13 ±2 kgf•cm).

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


CONNECT CABLES 5-7

Figure 5-2 Grounding Procedure (Example – 2/2)


TOWER (Overhead View)

LIGHTNING ROD

Let cables go through the center of


tower as much as possible.
ODU
GROUNDING WIRE
COAXIAL CABLE

FG
GROUNDING WIRE**
Grounding Wire for ODU should be
(away from tower) connected to the nearest EP of the tower.
(Grounding Resistance should EP
be less than 10 Ohms) GROUNDING WIRE*1
(Grounding-resistance:
less than 10 ohms)

Let the coaxial cable run through inside of the steel tower.
Let the grounding wire between ODU and IDU run through
(Grounding Resistance should inside of the steel tower.
be less than 10 ohms)
Use a copper grounding conductor to ground the rack.
The grounding conductor to the CO GND should be
COAXIAL CABLE connected to the rack.

INDOOR EARTH LINE

IDU

This is the buried grounding


wire. This type of wire should
be naked (not insulated). which
is recommended.

GROUNDING LEVEL

NOTES:

*: NEC recommends that frame ground of ODU should be connected to


earth line as NEC’s standard installation.

**: If grounding resistance of tower is low enough (less than 10 ohms),


grounding wire of lightning rod is unnecessary.

EP: Earth Ground Point of tower

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


5-8 CONNECT CABLES

FG Frame Ground terminal. [5 mm square cable, which means that a greater


than 2.5 mm diameter cable (10 AWG) is recommended to apply for the
earth grounding. The proper press fix terminal tool shall be used.]

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


CONNECT CABLES 5-9

5.3 Route Cables

5.3.1 Grounding Cables


The IDU of iPASOLINK VR 2 provides one Grounding Terminal on its On-Board
MODEM. The illustration below uses the Main Card whose card type is MC-SV as an
example.
The connected Grounding Cable should be routed to/from the left-side of the IDU, then
to/from the rack top.

NOTE: Screw torque should be within 1.3 ±0.2 N•m (13 ±2 kgf•cm)

5.3.2 IF Cables
Up to tow IF Ports are provided on the IDU of iPASOLINK VR 2. The illustration below
uses the Main Card whose card type is MC-SV as an example.
IF Cable(s) should be routed to/from the left side of the IDU, then to/from the rack top.

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


5-10 CONNECT CABLES

5.3.3 Power Cables


Two Power Terminals are provided on the IDU. The Power Cables should be routed to/
from the right-side of the IDU, then to/from the rack top. The illustration below uses the
Main Card whose card type is MC-SV as an example.

CAUTION:
Use four 16-20 AWG twisted pair wires to assemble the Power
Supply Cable. The plugging slots of the PWR Terminal (Power Input
Connector) should be fully used by the Power Supply Cable’s plug
pins. Leaving (a) vacant plugging slot(s) may damage the PWR
Terminal due to the overcurrent.

5.3.4 16E1 and GbE Signal Cables


 One 16E1 Port is provided on MC-SV (Main Card).
 Ports #1 to #4 on the MC-SV (Main Card) are the RF-45 Terminals providing the
10/100/1000BASE-TX Signals.
 Ports #5 and #6 on the MC-SV (Main Card) are the SFP Ports providing the
1000BASE-SX/LX Signals.
Connected cables should be routed to/from the nearest side, then to/from the rack top.
The illustration below uses the Main Card whose card type is MC-SV as an example.

5.3.5 XIF Coaxial Cables (XPIC)


iPASOLINK VR 2 equipped with two On-Board MODEMs can configure one 1+0 XPIC
without using the external connections.

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


CONNECT CABLES 5-11

5.4 Connector Pin Assignments


Followings show the pin assignments of connectors. Alignments in the illustrations here
are those of terminals on IDU side.

5.4.1 Power Terminal

 Designation: PWR 1 / PWR 2


 Connector Type: Tyco D-3100S Series Connector (4-Pin)

CAUTION:
Use four 16-20 AWG twisted pair wires to assemble the Power
Supply Cable. The plugging slots of the PWR Terminal (Power Input
Connector) should be fully used by the Power Supply Cable’s plug
pins. Leaving (a) vacant plugging slot(s) may damage the PWR
Terminal due to the overcurrent.

PWR 1 PWR 2

MC-SV

PWR 1 PWR 2

MC-SVE

Table 5-1 Pin Assignment for PWR 1/2 Terminal Connector

Tyco D-3100S 4-Pin Pin Assignment

1 2 3 4

PIN# ASSIGNMENT PIN# ASSIGNMENT

1 –48 V 3 GND

2 –48 V 4 GND

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


5-12 CONNECT CABLES

5.4.2 2M IN/OUT Terminal


 Designation: 2M IN/OUT
 Connector Type: MDR-68

NOTE: MC-SVE Card (NWA-096363-5**) does not provide this terminal.


2M IN/OUT Terminal

Table 5-2 Pin Assignment for 2M IN/OUT Terminal Connector


MDR-68 Pin Assignment
34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35

PIN# ASSIGNMENT PIN# ASSIGNMENT


1 GND 35 GND
2 CH16_IN (+) 36 CH16_IN (–)
3 CH16_OUT (+) 37 CH16_OUT (–)
4 CH15_IN (+) 38 CH15_IN (–)
5 CH15_OUT (+) 39 CH15_OUT (–)
6 CH14_IN (+) 40 CH14_IN (–)
7 CH14_OUT (+) 41 CH14_OUT (–)
8 CH13_IN (+) 42 CH13_IN (–)
9 CH13_OUT (+) 43 CH13_OUT (–)
10 CH12_IN (+) 44 CH12_IN (–)
11 CH12_OUT (+) 45 CH12_OUT (–)
12 CH11_IN (+) 46 CH11_IN (–)
13 CH11_OUT (+) 47 CH11_OUT (–)
14 CH10_IN (+) 48 CH10_IN (–)
15 CH10_OUT (+) 49 CH10_OUT (–)
16 CH9_IN (+) 50 CH9_IN (–)
17 CH9_OUT (+) 51 CH9_OUT (–)
18 CH8_IN (+) 52 CH8_IN (–)
19 CH8_OUT (+) 53 CH8_OUT (–)
20 CH7_IN (+) 54 CH7_IN (–)
21 CH7_OUT (+) 55 CH7_OUT (–)
22 CH6_IN (+) 56 CH6_IN (–)
23 CH6_OUT (+) 57 CH6_OUT (–)
24 CH5_IN (+) 58 CH5_IN (–)
25 CH5_OUT (+) 59 CH5_OUT (–)
26 CH4_IN (+) 60 CH4_IN (–)
27 CH4_OUT (+) 61 CH4_OUT (–)
28 CH3_IN (+) 62 CH3_IN (–)
29 CH3_OUT (+) 63 CH3_OUT (–)
30 CH2_IN (+) 64 CH2_IN (–)
31 CH2_OUT (+) 65 CH2_OUT (–)
32 CH1_IN (+) 66 CH1_IN (–)
33 CH1_OUT (+) 67 CH1_OUT (–)
34 GND 68 GND

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


CONNECT CABLES 5-13

5.4.3 CLK-CV Card

 Designation: CLK
 Connector Type: High Density D-SUB 15

NOTES:
1. MC-SVE (NWA-096363-5**) does not use this card.

2. This connector is supported on CLK-CV[001] and CLK-CV[002].

CLK Terminal

Table 5-3 Pin Assignment for CLK Terminal Connector

D-SUB 15 Pin Assignment

11 12 13 14 15
6 7 8 9 10
1 2 3 4 5

PIN# ASSIGNMENT PIN# ASSIGNMENT PIN# ASSIGNMENT

1 ——— 6 CLK_EXT_IN_P 11 ———

2 ——— 7 CLK_EXT_IN_N 12 ———

3 CLK_EXT_ONT_N 8 CLK_EXT_OUT_P 13 ———

4 ——— 9 ——— 14 ———

5 GND 10 GND 15 ———

NOTE: Pins that have no assignments should be kept open.

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


5-14 CONNECT CABLES

 Designation: EOW
 Connector Type: 3.5mm headset jack

NOTES:
1. MC-SVE (NWA-096363-5**) does not use this card.

2. This connector is supported on CLK-CV[001] and CLK-CV[002].

EOW Terminal

Table 5-4 Pin Assignment for EOW Terminal Connector

EOW Terminal Connector Pin Assignment

1 3 2

PIN# ASSIGNMENT

1 Sleeve: GND

2 tip: MIC-in

3 ring: Audio-out

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


CONNECT CABLES 5-15

5.4.4 (Debug Terminal)

 Designation: (For Factory Test Only)


 Connector Type: High Density D-SUB 15

NOTE: This terminal is on MC-SVE Card (NWA-096363-5**).

(Debug Terminal)

Table 5-5 Pin Assignment for Debug Terminal Connector

D-SUB 15 Pin Assignment

5 4 3 2 1
10 9 8 7 6
15 14 13 12 11

PIN# ASSIGNMENT PIN# ASSIGNMENT PIN# ASSIGNMENT

1 ——— 6 ——— 11 ———

2 ——— 7 ——— 12 ———

3 ——— 8 ——— 13 ———

4 ——— 9 ——— 14 ———

5 ——— 10 ——— 15 ———

NOTE: All pins should be kept opened.

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


5-16/END CONNECT CABLES

This page is intentionally left blank.

GGS-000402-14E iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


START UP AND SHUT DOWN 6-1

6. START UP AND SHUT DOWN

6.1 Start Up iPASOLINK VR 2

6.1.1 Basic Operation

1. Confirm that the power cable is properly connected:


 Power Cable (SELV) should be connected at DC –48V Port.
2. MAINT LED (Amber) starts blinking by turning on the equipment.
3. When the start-up process is completed, the MAINT LED (Amber) will
turn off.
4. For the first time only, the equipment starts up disabling the radio output.

WARNING:
Do not turn off the power until the start-up process is complete.
Repeated turning the power on and off within a short interval may
cause the equipment failure.

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


6-2 START UP AND SHUT DOWN

6.1.2 Start Up Equipment Using USB Memory Device

iPASOLINK VR 2 provides a function to start up the equipment using the configuration


information data stored in the USB memory device.

6.1.2.1 Preparation

Followings should be considered for the data to be used for this function:

 NE Names should be identical. This means that if an NE Name is registered to the


equipment, the stored data should have the same NE Name, and also that if the
equipment has no NE Name, then the stored data should not have the NE Name
either.

 The Configuration file with no NE Name can be applied for either system with or
without an NE Name.

 If Configuration data of multiple NEs are stored in the USB memory device, the
data with the identical NE Name (including no name) to that of the connected
equipment will be uploaded.

 Followings show their file paths when the storage is USB memory device:

Table 6-1 Designated File Path

File Type NE Name File Path File Name

Equipment Configuration Data Registered /config/ <NE Name>-evo-equip.cfg

evo-equip.cfg
No Name /config/ evo-equip.cfg
Network Configuration Data Registered /config/ <NE Name>-evo-network.cfg

evo-network.cfg
No Name /config/ evo-network.cfg
User Configuration Data Registered /config/ <NE Name>-evo-user.cfg

evo-user.cfg
No Name /config/ evo-user.cfg

GGS-000402-14E IPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION


START UP AND SHUT DOWN 6-3

6.1.2.2 Start-Up Process Using USB Memory Device

1. Referring to 6.1.2.1 Preparation, confirm the data stored in the USB


memory device.

2. Confirm that the power is not supplied to the equipment.

3. Plug in the USB memory device to the USB Port on the equipment.

4. Supply the power to the equipment.


NOTE: If the valid data are not found in the plugged USB memory device,
the equipment starts up using its configuration data stored in its own.

6.2 Shut Down iPASOLINK VR 2

1. Powering off the power unit or power injector shuts down iPASOLINK VR.

iPASOLINK VR 2: INDOOR UNIT (IDU) INSTALLATION GGS-000402-14E


6-4/END START UP AND SHUT DOWN

This page is intentionally left blank.