Schedule of Loads: For Main Service Entrance

The document outlines the schedule of electrical loads for a five-unit two-storey house, detailing the number of outlets, voltage, amperage, VA ratings, circuit breaker ratings, wire sizes, and conduit specifications for various electrical appliances and lighting layouts. It calculates the total current requirements for the main service entrance and the main circuit breaker, resulting in a total of 262.55 A and 352.55 A respectively. The document is part of an electrical plan for a project by students from Pangasinan State University.

Uploaded by

Sakura Blossoms
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
386 views1 page

Schedule of Loads: For Main Service Entrance

The document outlines the schedule of electrical loads for a five-unit two-storey house, detailing the number of outlets, voltage, amperage, VA ratings, circuit breaker ratings, wire sizes, and conduit specifications for various electrical appliances and lighting layouts. It calculates the total current requirements for the main service entrance and the main circuit breaker, resulting in a total of 262.55 A and 352.55 A respectively. The document is part of an electrical plan for a project by students from Pangasinan State University.

Uploaded by

Sakura Blossoms
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SCHEDULE OF LOADS

NO. DESCRIPTION OF LOADS # OF OUTLETS VOLTAGE AMPERE VA RATING CB RATING WIRE SIZE CONDUIT
1 LIGHTING LAYOUT 6 230 2.61 600 15 AT 2- 2.0mm2 THWN 1/2 " DIAM. PVC CONDUCTOR
2
2 LIGHTING LAYOUT 3 230 1.30 300 15 AT 2- 2.0mm THWN 1/2 " DIAM. PVC CONDUCTOR
3 LIGHTING LAYOUT 6 230 2.61 600 15AT 2- 3.5mm2 THWN 1/2 " DIAM. PVC CONDUCTOR
4 CONVENIENCE LAYOUT 4 230 3.13 720 20 AT 2- 3.5mm2 THWN 1/2 " DIAM. PVC CONDUCTOR
5 CONVENIENCE LAYOUT 4 230 3.13 720 20 AT 2- 5.5mm2 THWN 1/2 " DIAM. PVC CONDUCTOR
6 REFRIGERATOR 1 230 4.34 1000 30 AT 2- 5.5mm2 THWN 1/2 " DIAM. PVC CONDUCTOR
7 ELECTRIC RANGE 1 230 17.39 4000 30 AT 2- 5.5mm2 THWN 1/2 " DIAM. PVC CONDUCTOR

8 1 HP ACU 1 230 8 1840 20 AT 2- 5.5mm2 THWN 1/2 " DIAM. PVC CONDUCTOR
9 1 HP ACU 1 230 8 1840 20 AT 2- 5.5mm2 THWN 1/2 " DIAM. PVC CONDUCTOR
10 SPARE

FOR MAIN SERVICE ENTRANCE


Total I PER UNIT = 2.61 + 1.30 + 2.61+ 3.13 + 3.13 + 4.34 + 17.39 + 8 + 8 --- 50.51
Total I = 50.51 + (25%x8)
Total I = 52.51 x 5 units
Total I = 262.55 A
*USE: 150mm^2 THWN CU. CONDUCTOR

FOR MAIN CIRCUIT BREAKER


Icb = Total I + 250% of 8
Total I = 2.61 + 1.30 + 2.61+ 3.13 + 3.13 + 4.34 + 17.39 + 8 + 8 --- 50.51
Icb= 50.51 + (250% x 8)
Icb = 70.51 A x 5 units
Icb = 352.55 A

*PROVIDE: 1- 400 AT, 230 V, 1Ø, 60 Hz CIRCUIT BREAKER

STUDENT : PROJECT TITLE : FACULTY : SHEET CONTENT : PLATE NO :

ALEGRE, JUNALIZA MAE P. ENGR. MARK AQUINO OVERALL


ELECTRICAL PLAN OF A
SALES, JASMINE AIRA SCHEDULE OF LOADS
5 UNIT TWO - STOREY HOUSE
COURSE : BS CIVIL ENGINEERING
ELECTRICAL ENGINEERING DEPARTMENT
PANGASINAN STATE UNIVERSITY SHEET NO.
6
YEAR & SECTION : 2E LOCATION : URDANETA CITY, PANGASINAN URDANETA CITY CAMPUS 7